estándar de instalación para its1000m - v2.0

Upload: alexander-gomez

Post on 15-Oct-2015

88 views

Category:

Documents


6 download

TRANSCRIPT

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page1, Total17

    Estndar de Instalacin para Minishelter

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page2, Total17

    Control de versiones

    Fecha

    Versin

    revisada Descripcin Autor

    25-Jun-13 V1.0 Draft E. Garca

    22-Ago-13 V2.0 Revisin interna E. Garca

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page3, Total17

    Contenido

    1 Acerca de Este Captulo .................................................................................. 5

    1.1 Propsito ................................................................................................... 5

    1.2 Dirigido ...................................................................................................... 5

    1.3 Organizacin ............................................................................................. 5

    1.4 Referencias ................................................................................................ 5

    2 Distribucin Interna ......................................................................................... 6

    2.1 Acerca de este captulo ............................................................................ 6

    2.2 Apariencia.................................................................................................. 6

    2.3 Dimensiones y Peso ................................................................................. 6

    2.3.1 Dimensiones y Peso .......................................................................... 6

    2.3.2 Parmetros de Energa ...................................................................... 7

    2.3.3 Distribucin Interna ........................................................................... 8

    3 Estndar de Instalacin ITS1000M .................................................................. 9

    3.1 Rectificador ETP48200 .............................................................................. 9

    3.1.1 Apariencia .......................................................................................... 9

    3.1.2 Breaker de entrada de energa AC .................................................... 9

    3.1.3 Aterramiento del ETP48200 ............................................................. 10

    3.1.4 Distribucin de breakers DC en el PDU .......................................... 10

    3.1.5 Breakers para bateras .................................................................... 11

    3.2 BBU3900 .................................................................................................. 11

    3.3 Cableado de Alarmas Internas ............................................................... 11

    3.4 Normas de Cableado .............................................................................. 13

    3.4.1 Cable de energa AC ........................................................................ 13

    3.4.2 Cable de energa DC RRUs ............................................................. 14

    3.4.3 Cable de Energa DC BBU y ATN910 .............................................. 14

    3.4.4 Cables de Transmisin .................................................................... 14

    3.4.5 Cables de Fibra ptica .................................................................... 15

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page4, Total17

    3.4.6 Cable de Aterramiento ..................................................................... 15

    3.4.7 Cables de monitoreo para FAN y TEC ............................................ 15

    3.5 Salida de Cables...................................................................................... 16

    3.6 Anclaje e Instalacin de ITS1000M ........................................................ 17

    3.6.1 Anclaje de la Base ............................................................................ 17

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page5, Total17

    1 Acerca de Este Captulo

    1.1 Propsito

    Este documento presenta los estndares de instalacin para el gabinete

    ITS1000M, describe posiciones del producto, y una gua rpida de

    instalacin.

    1.2 Dirigido

    Este documento est dirigido a:

    Ingenieros de Operacin y Mantenimiento

    Ingenieros de red

    Ingenieros de campo

    Personal de instalacin y supervisin de estaciones base.

    1.3 Organizacin

    Este documento consta de 3 partes las cuales se detallan a continuacin:

    1.4 Referencias

    ITS1000M (Mini-shelter) Product Description (V100R003C00_03)

    ITS1000M (Mini-shelter) Quick Installation Guide (V100R003C00_01)

    Mini-shelter_Standard_Product_Fact_Sheet for TdPx

    Capitulo Titulo Descripcin

    Capitulo 1 Acerca de este documento

    Describe el proposito ,organizacin

    y referencias de la documentacin.

    Capitulo 2

    Distribucin Interna gabinete

    ITS1000M

    Describe la distribucin del gabinete

    ITS1000M, y sus diversos mdulos.

    Capitulo 3

    Estandar de instalacion para

    gabinete ITS1000M

    Describe el estandar de instalacin del

    gabinete ITS1000M.

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page6, Total17

    2 Distribucin Interna

    2.1 Acerca de este captulo

    Este captulo describe las normas de instalacin del gabinete ITS1000M.

    2.2 Apariencia

    2.3 Dimensiones y Peso

    2.3.1 Dimensiones y Peso

    Parmetro Descripcin

    Internal Dimensions (W x D x H) 800 mm (W) x 800 mm (D) x 1800 mm (H)

    External Dimensions (W x D x H ) 905 mm (W) x 1135 mm (D) x 2110 mm (H)

    Base Dimensions (W x D x H ) 900 mm (W) x 900 mm (D) x 200 mm (H)

    Peso Neto del Gabinete 220Kg

    Protection Level IP55 / IP34

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page7, Total17

    2.3.2 Parmetros de Energa

    Parmetro Descripcin

    AC Input Voltage - Frecuency 220V/380V - 45Hz65Hz

    Power Module Capability 50A

    AC Input Circuit Breaker 110A

    DC Output Circuit Breaker LLVD: 100A x 2, 20A x1; BLVD: 63A x 1,

    32A x 1, 16A x 5

    Battery Breaker 125A x 2

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page8, Total17

    2.3.3 Distribucin Interna

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page9, Total17

    3 Estndar de Instalacin ITS1000M

    3.1 Rectificador ETP48200

    3.1.1 Apariencia

    3.1.2 Breaker de entrada de energa AC

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page10, Total17

    3.1.3 Aterramiento del ETP48200

    El cable de aterramiento del ETP48200 debe llegar hasta la barra del

    Minishelter ubicada a la salida del mismo.

    3.1.4 Distribucin de breakers DC en el PDU

    Para caso 2G+3G

    Para Caso LTE

    FREE FREE FAN RRU 1 RRU 2 RRU 3 RRU 4 RRU 5 RRU 6 BBU BAT 1 BAT 2

    100A 100A 20A 63A 32A 16A 16A 16A 16A 16A 125A 125A

    BAT1 BAT2LLVD BLVD

    FREE FREE FAN FREE TEC RRU 1 RRU 2 RRU 3 ATN910I BBU BAT 1 BAT 2

    100A 100A 20A 63A 32A 16A 16A 16A 16A 16A 125A 125A

    BAT1 BAT2LLVD BLVD

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page11, Total17

    3.1.5 Breakers para bateras

    3.2 BBU3900

    La BBU3900 se anclar debajo del DCDU, de no estar instalado este

    elemento, dejar el espacio de una unidad de rack entre el ETP48200 y la

    BBU3900, como se muestra en la figura.

    3.3 Cableado de Alarmas Internas

    El cableado de los sensores se realizar a los respectivos puertos asignados

    en la tarjeta UIM02C.

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page12, Total17

    Luego de esto se debe colocar el cable de monitoreo desde el puerto

    EXT_ALM 0 de la tarjeta UPEU en la BBU3900 hacia los puertos

    ALM1-ALM8 de la tarjeta UIM02C. Tal como se muestra en la imagen.

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page13, Total17

    3.4 Normas de Cableado

    3.4.1 Cable de energa AC

    El cable que suministra la energa AC, ser conectado al rectificador

    ETP48200, tal como se muestra en la figura. El cable a usar es un

    vulcanizado de 3 hilos de 25mm2.

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page14, Total17

    3.4.2 Cable de energa DC RRUs

    Los cables de energa DC para las RRUs debern ser conectados a los

    breakers BLVD, usando primero los 3 primeros de 16A (Caso LTE) o los

    de 63A, 32A y los 4 siguientes de 16A (Caso 2G+3G).

    3.4.3 Cable de Energa DC BBU y ATN910

    El cable de energa DC de la BBU y ATN910I debern ser colocados en

    los breaker de 16A BLVD (Solo en caso LTE).

    3.4.4 Cables de Transmisin

    El cable de TX, dependiendo de su posicin en la BBU (Cable E1s o

    cable Ethernet) sers peinado y sujetos hacia el lado correspondiente,

    teniendo en cuenta que deben salir por un mismo punto del gabinete

    Minishelter.

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page15, Total17

    3.4.5 Cables de Fibra ptica

    Los cables de FO, dependiendo de su posicin en la BBU (Conectados a

    la GTMU, WBBP o LBBP) sern peinados y sujetos hacia el lado

    correspondiente, teniendo en cuenta que deben salir del gabinete

    agrupados y nunca por la misma salida que cables de TX, energa u

    otros.

    3.4.6 Cable de Aterramiento

    El aterramiento del gabinete se realizar usando la barra de tierra que

    bien ubicada en el lateral del Minishelter.

    3.4.7 Cables de monitoreo para FAN y TEC

    Para los cables de monitoreo del FAN y el TEC, favor utilizar estos

    puertos de la tarjeta UIM02C

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page16, Total17

    3.5 Salida de Cables

    La salida de cables del gabinete Minishelter, se har por las aberturas que tiene

    en la parte baja, se debe respetar el orden indicado y luego de colocados los

    cables correspondientes, estos debern ser sellados correctamente usando

    sikaflex. A continuacin se muestra una imagen con la distribucin de cables.

    Para el caso 2G+3G:

    Para el caso LTE

  • Estndar de Instalacin Minishelter V2.0 Security Level

    2013-08-23 Huawei Proprietary - Restricted Distribution Page17, Total17

    3.6 Anclaje e Instalacin de ITS1000M

    3.6.1 Anclaje de la Base