Page 1: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

ERV D / HRV DERV EC D / HRV EC D

Heat and Energy Recovery Ventilators

Page 2: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

2 AIR HANDLING UNITS |2017-11 |www.blauberg.us

Page 3: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

3www.blauberg-group.com

CONTENT

ERV D(R) 80 6

HRV D / ERV D series overview 4

HRV D(R) 120 / ERV D(R) 120 10

HRV D(R) 150 / ERV D(R) 150 16

ERV EC D(R) 80 22

HRV EC D(R) 120 / ERV EC D(R) 120 26

HRV EC D(R) 150 / ERV EC D(R) 150 32

S50 – 20/40/60 push button timer 38

Page 4: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

4 AIR HANDLING UNITS |2017-11 |www.blauberg.us

HRV D / ERV D series

ERV D 80

ERV DR 80

ERV EC D 80

ERV EC DR 80

ERV D 120

ERV DR 120

ERV EC D 120

ERV EC DR 120

Core

ERV ERV

Motor

Airflow @ 0.1 in. W. G. 74 CFM 88 CFM 136 CFM 176 CFM

Max. CFM/W 0.99 1.72 0.84 2.86

Sensible Recovery Efficiency

at 32°F (0°C)

69 73 63 66

Defrost system Fan defrost Recirculation Fan defrost Recirculation Fan defrost Recirculation Fan defrost Recirculation

Build incontrol

board with independent

fan speed adjustment 0%-

100%

+ + + + + + + +

Slim casing design 8 7/16” 9 1/16”

Page 5: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

5www.blauberg-group.com

HRV D / ERV D series

HRV D 120

HRV DR 120

HRV EC D 120

HRV EC DR 120

ERV D 150

ERV DR 150

ERV EC D 150

ERV ECDR 150

HRV D 150

HRV DR 150

HRV EC D 150

HRV EC DR 150

Core

HRV ERV HRV

Motor

Airflow @ 0.1 in. W. G. 136 CFM 176 CFM 161 CFM 181 CFM 161 CFM 181 CFM

Max. CFM/W 0.84 2.86 1.00 2.56 1.00 2.56

Sensible Recovery Efficiency

at 32°F (0°C)

60 62 67 73 64 69

Defrost system

Fan defrost

Recircula-tion

Fan defrost

Recircula-tion

Fan defrost

Recircula-tion

Fan defrost

Recircula-tion

Fan defrost

Recircula-tion

Fan defrost

Recircula-tion

Build incontrol

board with independent

fan speed adjustment 0%-100%

+ + + + + + + + + + + +

Slim casing design 9 1/16” 9 1/8”

Page 6: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

6 AIR HANDLING UNITS |2017-11 |www.blauberg.us

Energy Recovery Ventilators are the complete whole house ventilation system designed to bring a continuous supply of fresh air into the house while exhausting an equal amount of stale air.

• 74 CFM airflow rate provides effective ventilation in apartment overcoming high pressure in condo tower duct systems.

• Cross flow core ensures up to 69% SRE.• Slim casing design (8 7/16”) is perfect for in-ceiling installation.• Build in control board enables Supply and Exhaust fan inde-

pendent speed adjustment from 0 to 100% right at the job side.• Fast and simple mounting process thanks to brackets system.• Automatic recirculation damper (R option) for effective cold

protection.• No drain needed (ERV).

Steel casing is covered with high-quality multilayer alu-minium and zinc alloy to prevent corrosion. The casing is equipped with a switch to turn the ventilator off when the service panel is opened.

CASING

DESCRIPTION

FILTERWashable MERV 6 air filters in exhaust and supply air streams.Optional supply: anti grease aluminum filter.

Defrost system is activated when the outdoor temperature falls below 23° F (-5° C).Recirculation defrost ERV DR 80.Fan stop defrost ERV D 80.

DEFROST SYSTEM

The unit is equipped with supply and exhaust centrifugal fans with backward curved blades and build-in thermal overheating protection with automatic restart. The electric motors and impellers are dynamically balanced.

FANS

The unit incorporates an integrated automation and control system with following functions: • Operation mode switch.• Airflow balancing enabled by supply and exhaust fan in-

dependent speed adjustment from 0 to 100% (percent-age is displayed on built in screen).

• Automatic recovery core frost protection.• External control device connection (up to 5 at the same

time).

CONTROL

5 year warrantyWARRANTY

ERV D 80 ERV DR 80

Backdraft Dampers ClampsAir disk valve

ACCESSORIES

Timer

Enthalpic core (ERV D(R) 80) provides both heat&humi-dity recovery. For enthalpic core no drain required.

HEAT RECOVERY CORE

Page 7: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

7www.blauberg-group.com

ERV D 80 ERV DR 80

ENERGY RECOVERY VENTILATION

Due to low height of the casing the units offer perfect solution for the false ceiling installation in limited space.Brackets system makes mounting process easy and fast.

MOUNTING

Step 1 Step 2 Step 3

H

H = 8 7/16”

Page 8: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

8 AIR HANDLING UNITS |2017-11 |www.blauberg.us

ERV D 80 ERV DR 80

External Static Pressure Net Supply Air FlowGross Air Flow

PowerSupply Exhaust

Pa in. W.G. L/s CFM L/s CFM L/s CFM Watts25 0.1 35 74 37 78 37 78 7450 0.2 31 66 32 68 33 70 7475 0.3 26 56 27 57 28 59 74

100 0.4 22 46 22 47 23 49 74125 0.5 17 36 17 36 18 38 74150 0.6 11 24 12 25 12 25 73175 0.7 6 12 6 13 6 13 73200 0.8 2 4 1 2 2 4 72

Supply Temperature Net Airflow Average Power (Watts)

SensibleRecovery Efficiency

Apparent Sensible

Effectiveness

NetMoisture Transfer°C °F L/s CFM

Heating

I 0 32 20 42 43 69 82 0.46

II 0 32 25 54 55 66 78 0.46

III 0 32 30 63 67 66 78 0.44

IV

V -25 -13 20 42

Total Recovery Efficiency

Cooling VI 35 95 20 42 42.6 46.1 71.9 0.49

Model Volts Max. Watts Max. Amps

ERV D(R) 80 120V, 60Hz 74 0.6

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

0 10 20 30 40 50 60 70 80 90

Ext.

Di�

eren

tial P

ress

ure

- in.

WG

Gross Airow - CFM

SupplyExhaust

Extract air

Supply airExhaust air

Intake air

PERFORMANCE

Page 9: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

9www.blauberg-group.com

ERV DR 80

ERV D 80

Ø 4 7/8”

Ø 4 7/8”

4 1/16”

4 1/2” 29 13/16”

26”

21 15/16” 8 7/16” 4 7/16”

8 7/16” 4 7/16”

3 7/8 ”

3 7/8 ”

9 1/2 ”

9 1/2 ”

20 3/

16”

20 3/

16”

18 1/16”

9 1/2 ”

17 1/

16”

17 1/

16”

9 1/2 ”

Ø 4 7/8”

Ø 4 7/8”

4 1/16”

4 1/2” 29 13/16”

26”

21 15/16” 8 7/16” 4 7/16”

8 7/16” 4 7/16”

3 7/8 ”

3 7/8 ”

9 1/2 ”

9 1/2 ”

20 3/

16”

20 3/

16”

18 1/16”

9 1/2 ”

17 1/

16”

17 1/

16”

9 1/2 ”

ERV D 80 ERV DR 80

ENERGY RECOVERY VENTILATION

DIMENSIONS

Page 10: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

10 AIR HANDLING UNITS |2017-11 |www.blauberg.us AIR HANDLING UNITS |2017-11 |

Heat and Energy Recovery Ventilators are the complete whole house ventilation system designed to bring a continuous supply of fresh air into the house while exhausting an equal amount of stale air.

• 142 CFM airflow rate provides effective ventilation in apartment overcoming high pressure in condo tower duct systems.

• Cross flow core ensures up to 63% SRE.• Slim casing design (9 1/16”) is perfect for in-ceiling installation.• Build in control board enables Supply and Exhaust fan inde-

pendent speed adjustment from 0 to 100% right at the job side.• Fast and simple mounting process thanks to brackets system.• Automatic recirculation damper (R option) for effective cold

protection.• No drain needed (ERV).

Steel casing is covered with high-quality multilayer alu-minium and zinc alloy to prevent corrosion. The casing is equipped with a switch to turn the ventilator off when the service panel is opened.

CASING

DESCRIPTION

FILTERWashable MERV 6 air filters in exhaust and supply air streams.Optional supply: anti grease aluminum filter.

Defrost system is activated when the outdoor temperature falls below 23° F (-5° C).Recirculation defrost HRV/ERV DR 120.Fan stop defrost HRV/ERV D 120.

DEFROST SYSTEM

The unit is equipped with supply and exhaust centrifugal fans with forward curved blades and build-in thermal over-heating protection with automatic restart. The electric mo-tors and impellers are dynamically balanced.

FANS

The unit incorporates an integrated automation and control system with following functions: • Operation mode switch.• Airflow balancing enabled by supply and exhaust fan inde-

pendent speed adjustment from 0 to 100% (percentage is displayed on built in screen).

• Automatic recovery core frost protection.• External control device connection (up to 5 at the same time).

CONTROL

5 year warrantyWARRANTY

Backdraft Dampers ClampsAir disk valve

ACCESSORIES

Timer

Aluminum cross-flow core (HRV D(R) 120) ensures efficient heat recovery.

Enthalpic core (ERV D(R) 120) provides both heat&humidity recovery. For enthalpic core no drain required.

HEAT RECOVERY CORE

HRV D(R) 120 ERV D(R) 120

Page 11: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

11www.blauberg-group.com

HEAT AND ENERGY RECOVERY VENTILATION

Due to low height of the casing the units offer perfect solution for the false ceiling installation in limited space.Brackets system makes mounting process easy and fast.

MOUNTING

Step 1 Step 2 Step 3

H

H = 9 1/16”

HRV D(R) 120 ERV D(R) 120

Page 12: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

12 AIR HANDLING UNITS |2017-11 |www.blauberg.us AIR HANDLING UNITS |2017-11 |

External Static Pressure Net Supply Air FlowGross Air Flow

PowerSupply Exhaust

Pa in. W.G. L/s CFM L/s CFM L/s CFM Watts25 0.1 63 134 66 140 64 136 15650 0.2 61 130 64 136 62 131 15575 0.3 60 128 63 133 61 129 153

100 0.4 59 124 61 129 58 123 152125 0.5 56 118 58 123 56 119 151150 0.6 53 112 55 117 54 114 149175 0.7 50 106 52 110 52 110 147200 0.8 48 102 50 106 49 104 146225 0.9 46 98 48 102 47 100 145250 1 44 94 46 97 43 91 143275 1.1 39 83 41 87 38 81 140300 1.2 32 67 33 70 31 66 135325 1.3 22 47 23 49 21 44 130350 1.4 13 28 14 30 13 28 127375 1.5 7 14 5 11 7 15 126

Supply Temperature Net Airflow Average Power (Watts)

SensibleRecovery Efficiency

Apparent Sensible

Effectiveness

NetMoisture Transfer°C °F L/s CFM

Heating

I 0 32 30 64 85 63 74 0.42

II 0 32 45 95 114 60 70 0.36

III 0 32 50 106 128 59 69 0.34

IV

V -25 -13 31 65 89 44 48 0.37

Total Recovery Efficiency

Cooling VI 35 95 30 64 85 40 62 0.34

Model Volts Max. Watts Max. Amps

ERV D(R) 120 120V, 60Hz 156 1.3

HRV D(R) 120 ERV D(R) 120

PERFORMANCE ERV D(R) 120

Ext.

Dif

fere

ntia

l Pre

ssur

e -

in. W

G

Gross Airflow - CFM

Ext.

Dif

fere

ntia

l Pre

ssur

e -

in. W

G

Gross Airflow - CFM

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

0 20 40 60 80 100 120 140 160

SupplyExhaust

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

0 20 40 60 80 100 120 140 160

SupplyExhaust

Extract air

Supply airExhaust air

Intake air

Page 13: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

13www.blauberg-group.com

HRV D(R) 120 ERV D(R) 120

HEAT AND ENERGY RECOVERY VENTILATION

PERFORMANCE HRV D(R) 120

External Static Pressure Net Supply Air FlowGross Air Flow

PowerSupply Exhaust

Pa in. W.G. L/s CFM L/s CFM L/s CFM Watts25 0.1 67 142 69 146 64 136 15850 0.2 65 138 67 142 62 131 15775 0.3 63 134 65 138 60 127 156

100 0.4 62 132 64 136 58 123 155125 0.5 60 127 62 131 56 119 153150 0.6 58 123 60 127 54 114 152175 0.7 56 119 58 123 52 110 151200 0.8 53 113 55 117 50 106 149225 0.9 51 109 53 112 47 100 148250 1 48 101 49 104 44 93 146275 1.1 44 92 45 95 40 85 143300 1.2 40 84 41 87 34 72 141325 1.3 30 64 31 66 26 55 135350 1.4 17 37 18 38 15 32 130375 1.5 10 21 10 21 8 17 128

Supply Temperature Net Airflow Average Power (Watts)

SensibleRecovery Efficiency

Apparent Sensible

Effectiveness

NetMoisture Transfer°C °F L/s CFM

Heating

I 0 32 30 64 86 60 70 0.05

II 0 32 45 95 114 57 67 0.04

III 0 32 50 106 126 55 65 0.04

IV

V -25 -13 31 65 85 60 64 0.03

Total Recovery Efficiency

Cooling VI 35 95 30 64 86 29 61 0.04

Model Volts Max. Watts Max. Amps

HRV D(R) 120 120V, 60Hz 156 1.3

Ext.

Dif

fere

ntia

l Pre

ssur

e -

in. W

G

Gross Airflow - CFM

Ext.

Dif

fere

ntia

l Pre

ssur

e -

in. W

G

Gross Airflow - CFM

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

0 20 40 60 80 100 120 140 160

SupplyExhaust

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

0 20 40 60 80 100 120 140 160

SupplyExhaust

Page 14: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

14 AIR HANDLING UNITS |2017-11 |www.blauberg.us

DIMENSIONS

HRV DR 120 | ERV DR 120

HRV D 120 | ERV D 120

3 3/4” 12 3/

8 ”

5 13/16”

5 13/16” 34 7/8” 30 15/16”

12 3/

8 ”

20 1/

16”

3/4”

20 1/

16”

26 3/8” 22 7/16”

Ø 4 7/8” 1 1/8”

1 7/16” 12 5/

8 ” 23

1/4 ”

9 1/16” 3 9/

16”

3 9/16

” 3 15/16”

9 1/16” 3 15/16”

12 5/

18”

23 1/

4 ”

Ø 4 7/8”

3 3/4” 12 3/

8 ”

5 13/16”

5 13/16” 34 7/8” 30 15/16”

12 3/

8 ”

20 1/

16”

3/4”

20 1/

16”

26 3/8” 22 7/16”

Ø 4 7/8” 1 1/8”

1 7/16” 12 5/

8 ” 23

1/4 ”

9 1/16”

3 9/16

” 3 9/

16”

3 15/16”

9 1/16” 3 15/16”

12 5/

18”

23 1/

4 ”

Ø 4 7/8”

HRV D(R) 120 ERV D(R) 120

Page 15: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

15www.blauberg-group.com

HEAT AND ENERGY RECOVERY VENTILATIONHRV D(R) 120 ERV D(R) 120

Page 16: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

16 AIR HANDLING UNITS |2017-11 |www.blauberg.us AIR HANDLING UNITS |2017-11 |

Heat and Energy Recovery Ventilators are the complete whole house ventilation system designed to bring a continuous supply of fresh air into the house while exhausting an equal amount of stale air.

• 161 CFM airflow rate provides effective ventilation in apartment overcoming high pressure in condo tower duct systems.

• Cross flow core ensures up to 67% SRE.• Slim casing design (9 1/8”) is perfect for in-ceiling installation.• Build in control board enables Supply and Exhaust fan inde-

pendent speed adjustment from 0 to 100% right at the job side.• Fast and simple mounting process thanks to brackets system.• Automatic recirculation damper (R option) for effective cold

protection.• No drain needed (ERV).

Steel casing is covered with high-quality multilayer alu-minium and zinc alloy to prevent corrosion. The casing is equipped with a switch to turn the ventilator off when the service panel is opened.

CASING

DESCRIPTION

FILTERWashable MERV 6 air filters in exhaust and supply air streams.Optional supply: anti grease aluminum filter.

Defrost system is activated when the outdoor temperature falls below 23° F (-5° C).Recirculation defrost HRV/ERV DR 150.Fan stop defrost HRV/ERV D 150.

DEFROST SYSTEM

The unit is equipped with supply and exhaust centrifugal fans with backward curved blades and build-in thermal overheating protection with automatic restart. The electric motors and impellers are dynamically balanced.

FANS

The unit incorporates an integrated automation and control system with following functions:• Operation mode switch.• Airflow balancing enabled by supply and exhaust fan inde-

pendent speed adjustment from 0 to 100% (percentage is displayed on built in screen).

• Automatic recovery core frost protection.• External control device connection (up to 5 at the same time).

CONTROL

5 year warrantyWARRANTY

HRV D(R) 150 ERV D(R) 150

Backdraft Dampers ClampsAir disk valve

ACCESSORIES

Timer

Aluminum cross-flow core (HRV D(R) 150) ensures efficient heat recovery.

Enthalpic core (ERV D(R)150) provides both heat&humidity recovery. For enthalpic core no drain required.`

HEAT RECOVERY CORE

Page 17: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

17www.blauberg-group.com

HRV D(R) 150 ERV D(R) 150

HEAT AND ENERGY RECOVERY VENTILATION

Due to low height of the casing the units offer perfect solution for the false ceiling installation in limited space.Brackets system makes mounting process easy and fast.

MOUNTING

Step 1 Step 2 Step 3

H

H = 9 1/8”

Page 18: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

18 AIR HANDLING UNITS |2017-11 |www.blauberg.us AIR HANDLING UNITS |2017-11 |

External Static Pressure Net Supply Air FlowGross Air Flow

PowerSupply Exhaust

Pa in. W.G. L/s CFM L/s CFM L/s CFM Watts25 0.1 72 152 74 157 70 149 19250 0.2 68 144 70 148 66 140 19275 0.3 65 137 67 141 63 132 191

100 0.4 60 127 62 131 59 125 191125 0.5 56 119 58 123 55 117 190150 0.6 52 111 54 114 51 108 190175 0.7 48 102 50 105 47 100 189200 0.8 44 93 45 96 43 90 188225 0.9 36 77 40 85 38 79 187250 1 32 67 35 74 33 69 185275 1.1 27 57 30 64 28 59 184300 1.2 22 46 25 53 23 48 183325 1.3 17 35 20 42 17 36 181350 1.4 12 24 15 32 12 25 179375 1.5 6 13 10 21 7 14 178400 1.6 1 2 5 10 1 2 176

Supply Temperature Net Airflow Average Power (Watts)

SensibleRecovery Efficiency

Apparent Sensible

Effectiveness

NetMoisture Transfer°C °F L/s CFM

Heating

I 0 32 30 64 67 67 83 0.47

II 0 32 45 94 64 64 78 0.38

III 0 32 50 105 62 62 76 0.36

IV

V -25 -13 31 65 44 44 48 0.37

Total Recovery Efficiency

Cooling VI 35 95 31 65 101 41.5 68 0.42

Model Volts Max. Watts Max. Amps

ERV D(R) 150 120V, 60Hz 192 1.6

PERFORMANCE ERV D(R) 150

Extract air

Supply airExhaust air

Intake air

Ext.

Dif

fere

ntia

l Pre

ssur

e -

in. W

G

Gross Airflow - CFM

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

0 20 40 60 80 100 120 140 160 180

SupplyExhaust

HRV D(R) 150 ERV D(R) 150

Page 19: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

19www.blauberg-group.com

HEAT AND ENERGY RECOVERY VENTILATION

PERFORMANCE HRV D(R) 150

External Static Pressure Net Supply Air FlowGross Air Flow

PowerSupply Exhaust

Pa in. W.G. L/s CFM L/s CFM L/s CFM Watts25 0.1 76 161 79 166 71 149 19250 0.2 73 154 75 159 67 142 19275 0.3 68 145 71 149 64 135 191

100 0.4 65 137 67 141 60 127 191125 0.5 60 127 62 131 56 119 191150 0.6 56 119 58 123 52 110 190175 0.7 52 110 54 113 48 102 189200 0.8 48 101 49 104 44 93 188225 0.9 38 81 44 93 40 84 187250 1 34 72 39 83 35 74 186275 1.1 29 62 34 71 31 65 185300 1.2 25 52 28 59 26 54 183325 1.3 19 41 23 48 20 42 181350 1.4 13 29 18 37 14 30 179375 1.5 8 17 12 25 9 18 177400 1.6 3 6 7 15 3 6 176

Supply Temperature Net Airflow Average Power (Watts)

SensibleRecovery Efficiency

Apparent Sensible

Effectiveness

NetMoisture Transfer°C °F L/s CFM

Heating

I 0 32 31 65 97 64 79 0.05

II 0 32 44 94 124 62 76 0.05

III 0 32 49 104 134 60 74 0.05

IV

V -25 -13 31 65 85 60 64 0.03

Total Recovery Efficiency

Cooling VI 35 95 30 64 97 31.1 64 0.04

Model Volts Max. Watts Max. Amps

HRV D(R) 150 120V, 60Hz 192 1.6

Ext.

Dif

fere

ntia

l Pre

ssur

e -

in. W

G

Gross Airflow - CFM

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

0 20 40 60 80 100 120 140 160 180

SupplyExhaust

HRV D(R) 150 ERV D(R) 150

Page 20: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

20 AIR HANDLING UNITS |2017-11 |www.blauberg.us

DIMENSIONS

HRV DR 150 | ERV DR 150

HRV D 150 | ERV D 150

11 13

/16 ”

21 9/

16”

4 5/8”

4 5/8” 9 1/8”

9 1/8”

11 13

/16 ”

2 9/16

27 3/4” 31 11/16”

36 1/8” 40 ”

11 13

/16 ”

11 13

/16 ”

25 3/

16”

25 3/

16”

4 5/8”

4 5/8”

Ø 4 7/8”

Ø 4 7/8”

11 13

/16 ”

21 9/

16”

4 5/8”

4 5/8” 9 1/8”

9 1/8”

11 13

/16 ”

2 9/16

27 3/4” 31 11/16”

36 1/8” 40 ”

11 13

/16 ”

11 13

/16 ”

25 3/

16”

25 3/

16”

4 5/8”

4 5/8”

Ø 4 7/8”

Ø 4 7/8”

HRV D(R) 150 ERV D(R) 150

Page 21: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

21www.blauberg-group.com

HEAT AND ENERGY RECOVERY VENTILATIONHRV D(R) 150 ERV D(R) 150

Page 22: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

22 AIR HANDLING UNITS |2017-11 |www.blauberg.us AIR HANDLING UNITS |2017-11 |

Energy Recovery Ventilators are the complete whole house ventilation system designed to bring a continuous supply of fresh air into the house while exhausting an equal amount of stale air.

• 81 CFM airflow rate provides effective ventilation in apartment overcoming high pressure in condo tower duct systems.

• Cross flow core ensures up to 73% SRE.• Slim casing design (8 7/16”) is perfect for in-ceiling installation.• Build in control board enables Supply and Exhaust fan inde-

pendent speed adjustment from 0 to 100% right at the job side.• Fast and simple mounting process thanks to brackets system.• Automatic recirculation damper (R option) for effective cold

protection.• No drain needed (ERV).• Up to 1.72 CFM/W (Energy Star requirement — 1.2 CFM/W).

Steel casing is covered with high-quality multilayer alu-minium and zinc alloy to prevent corrosion. The casing is equipped with a switch to turn the ventilator off when the service panel is opened.

CASING

DESCRIPTION

FILTERWashable MERV 6 air filters in exhaust and supply air streams.Optional supply: anti grease aluminum filter.

Defrost system is activated when the outdoor temperature falls below 3° F (-5° C).Recirculation defrost ERV EC D(R) 80.Fan stop defrost ERV EC D80.

DEFROST SYSTEM

High efficient electronically commutated motors with ex-ternal motor and impeller with backward curved blades. EC motors are featured with high performance and total speed controllable range. The electric motors and impellers are dy-namically balanced.

FANS

The unit incorporates an integrated automation and control system with following functions: • Operation mode switch.• Airflow balancing enabled by supply and exhaust fan in-

dependent speed adjustment from 0 to 100% (percent-age is displayed on built in screen).

• Automatic recovery core frost protection.• External control device connection (up to 5 at the same

time).

CONTROL

5 year warrantyWARRANTY

ERV EC D 80ERV EC DR 80

Backdraft Dampers ClampsAir disk valve

ACCESSORIES

Timer

Enthalpic core (ERV EC D(R) 80) provides both heat&humidity recovery. For enthalpic core no drain required.

HEAT RECOVERY CORE

Page 23: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

23www.blauberg-group.com

ERV EC D 80ERV EC DR 80

ENERGY RECOVERY VENTILATION

Due to low height of the casing the units offer perfect solution for the false ceiling installation in limited space.Brackets system makes mounting process easy and fast.

MOUNTING

Step 1 Step 2 Step 3

H

H = 8 7/16”

Page 24: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

24 AIR HANDLING UNITS |2017-11 |www.blauberg.us

PERFORMANCE

External Static Pressure Net Supply Air FlowGross Air Flow

PowerSupply Exhaust

Pa in. W.G. L/s CFM L/s CFM L/s CFM Watts25 0.1 38 81 40 84 42 88 6150 0.2 35 74 36 76 38 81 6175 0.3 32 67 33 69 35 74 61

100 0.4 29 61 30 63 31 65 60125 0.5 26 54 26 56 27 57 61150 0.6 22 46 23 48 22 47 60175 0.7 17 37 18 38 17 36 58200 0.8 12 26 13 27 12 26 59225 0.9 8 16 7 14 8 17 55

Supply Temperature Net Airflow Average Power (Watts)

SensibleRecovery Efficiency

Apparent Sensible

Effectiveness

NetMoisture Transfer°C °F L/s CFM

Heating

I 0 32 20 42 25 73 82 0.46

II 0 32 25 53 38 69 79 0.47

III 0 32 30 63 49 68 78 0.45

IV

V -25 -13 20 42

Total Recovery Efficiency

Cooling VI 35 95 20 42 25 54.5 72 0.49

Model Volts Max. Watts Max. Amps

ERV EC D(R) 80 120V, 60Hz 61 0.9

Extract air

Supply airExhaust air

Intake air

ERV EC D 80ERV EC DR 80

Ext.

Dif

fere

ntia

l Pre

ssur

e -

in. W

G

Gross Airflow - CFM

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

0 10 20 30 40 50 60 70 80 90

SupplyExhaust

Page 25: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

25www.blauberg-group.com

DIMENSIONS

ERV EC DR 80

ERV EC D 80

Ø 4 7/8”

Ø 4 7/8”

4 1/16”

4 1/2” 29 13/16”

26”

21 15/16” 8 7/16” 4 7/16”

8 7/16” 4 7/16”

3 7/8 ”

3 7/8 ”

9 1/2 ”

9 1/2 ”

20 3/

16”

20 3/

16”

18 1/16”

9 1/2 ”

17 1/

16”

17 1/

16”

9 1/2 ”

Ø 4 7/8”

Ø 4 7/8”

4 1/16”

4 1/2” 29 13/16”

26”

21 15/16” 8 7/16” 4 7/16”

8 7/16” 4 7/16”

3 7/8 ”

3 7/8 ”

9 1/2 ”

9 1/2 ”

20 3/

16”

20 3/

16”

18 1/16”

9 1/2 ”

17 1/

16”

17 1/

16”

9 1/2 ”

ERV EC D 80ERV EC DR 80

ENERGY RECOVERY VENTILATION

Page 26: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

26 AIR HANDLING UNITS |2017-11 |www.blauberg.us AIR HANDLING UNITS |2017-11 |

Heat and Energy Recovery Ventilators are the complete whole house ventilation system designed to bring a continuous supply of fresh air into the house while exhausting an equal amount of stale air.

• 176 CFM airflow rate provides effective ventilation in apartment overcoming high pressure in condo tower duct systems.

• Cross flow core ensures up to 66% SRE.• Slim casing design (9 1/16”) is perfect for in-ceiling installation.• Build in control board enables Supply and Exhaust fan inde-

pendent speed adjustment from 0 to 100% right at the job side.• Fast and simple mounting process thanks to brackets system.• Automatic recirculation damper (R option) for effective cold

protection.• No drain needed (ERV).• Up to 2.86 CFM/W (Energy Star requirement – 1.2 CFM/W).

Steel casing is covered with high-quality multilayer alu-minium and zinc alloy to prevent corrosion. The casing is equipped with a switch to turn the ventilator off when the service panel is opened.

CASING

DESCRIPTION

FILTERWashable MERV 6 air filters in exhaust and supply air streams.Optional supply: anti grease aluminum filter.

Defrost system is activated when the outdoor temperature falls below 23° F (-5° C).Recirculation defrost HRV/ERV EC DR 120.Fan stop defrost HRV/ERV EC D 120.

DEFROST SYSTEM

High efficient electronically commutated motors with ex-ternal motor and impeller with forward curved blades. EC motors are featured with high performance and total speed controllable range. The electric motors and impellers are dy-namically balanced.

FANS

The unit incorporates an integrated automation and control system with following functions: • Operation mode switch.• Airflow balancing enabled by supply and exhaust fan inde-

pendent speed adjustment from 0 to 100% (percentage is displayed on built in screen).

• Automatic recovery core frost protection.• External control device connection (up to 5 at the same time).

CONTROL

5 year warrantyWARRANTY

HRV EC D(R) 120 ERV EC D(R) 120

Backdraft Dampers ClampsAir disk valve

ACCESSORIES

Timer

Aluminum cross-flow core (HRV EC D(R) 120) ensures efficient heat recovery.

Enthalpic core (ERV EC D(R) 120 provides both heat&humidity recovery. For enthalpic core no drain required.

HEAT RECOVERY CORE

Page 27: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

27www.blauberg-group.com

HRV EC D(R) 120 ERV EC D(R) 120

HEAT AND ENERGY RECOVERY VENTILATION

Due to low height of the casing the units offer perfect solution for the false ceiling installation in limited space.Brackets system makes mounting process easy and fast.

MOUNTING

Step 1 Step 2 Step 3

H

H = 9 1/16”

Page 28: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

28 AIR HANDLING UNITS |2017-11 |www.blauberg.us AIR HANDLING UNITS |2017-11 |

External Static Pressure Net Supply Air FlowGross Air Flow

PowerSupply Exhaust

Pa in. W.G. L/s CFM L/s CFM L/s CFM Watts25 0.1 83 176 86 181 81 171 19850 0.2 80 170 83 175 79 167 19775 0.3 78 166 81 171 78 164 195

100 0.4 76 162 79 167 76 162 192125 0.5 74 157 77 162 75 159 191150 0.6 73 156 76 160 74 156 190175 0.7 71 151 74 156 72 153 188200 0.8 70 148 72 152 71 150 186225 0.9 67 141 70 147 69 146 183250 1 64 137 67 142 67 141 181275 1.1 62 132 64 136 64 136 178300 1.2 59 126 61 130 61 129 175325 1.3 56 119 58 122 58 122 171350 1.4 52 110 53 111 53 113 166

375 1.5 45 95 43 91 46 97 157

400 1.6 34 71 23 49 34 72 141425 1.7 17 35 8 17 17 36 128450 1.8 9 20 0 0 9 20 124

Supply Temperature Net Airflow Average Power (Watts)

SensibleRecovery Efficiency

Apparent Sensible

Effectiveness

NetMoisture Transfer°C °F L/s CFM

Heating

I 0 32 31 66 23 66 66 0.42

II 0 32 45 95 50 63 63 0.36

III 0 32 50 106 66 62 62 0.34

IV

V -25 -13

Total Recovery Efficiency

Cooling VI 35 95 31 66 23 50 62 0.34

Model Volts Max. Watts Max. Amps

ERV EC D(R) 120 120V, 60Hz 198 2.5

PERFORMANCE ERV EC D(R) 120

Extract air

Supply airExhaust air

Intake air

Ext.

Dif

fere

ntia

l Pre

ssur

e -

in. W

G

Ext.

Dif

fere

ntia

l Pre

ssur

e -

in. W

G

Gross Airflow - CFM Gross Airflow - CFM

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2

0 20 40 60 80 100 120 140 160 180 2000

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2

0 20 40 60 80 100 120 140 160 180 200

SupplyExhaust

SupplyExhaust

HRV EC D(R) 120 ERV EC D(R) 120

Page 29: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

29www.blauberg-group.com

HEAT AND ENERGY RECOVERY VENTILATION

PERFORMANCE HRV EC D(R) 120

External Static Pressure Net Supply Air FlowGross Air Flow

PowerSupply Exhaust

Pa in. W.G. L/s CFM L/s CFM L/s CFM Watts25 0.1 89 189 92 195 83 175 20450 0.2 87 185 90 190 81 171 20175 0.3 85 180 88 185 79 167 200

100 0.4 82 175 85 180 78 164 198125 0.5 80 169 82 175 76 161 196150 0.6 78 165 80 170 75 159 194175 0.7 76 160 78 165 74 157 193200 0.8 74 156 76 161 73 154 190225 0.9 68 144 74 156 70 149 188250 1 66 140 71 151 68 144 186275 1.1 64 135 69 145 66 139 183300 1.2 61 128 66 140 63 132 180325 1.3 57 121 63 134 59 125 176350 1.4 52 110 60 127 54 114 176375 1.5 43 91 55 117 44 94 164400 1.6 30 64 44 92 31 67 151425 1.7 17 35 18 37 17 36 132450 1.8 8 16 7 14 8 16 128

Supply Temperature Net Airflow Average Power (Watts)

SensibleRecovery Efficiency

Apparent Sensible

Effectiveness

NetMoisture Transfer°C °F L/s CFM

Heating

I 0 32 31 66 23 62 69 0.05

II 0 32 45 95 50 60 67 0.04

III 0 32 50 106 66 58 65 0.04

IV

V -25 -13

Total Recovery Efficiency

Cooling VI 35 95 31 66 23 37 61 0.04

Model Volts Max. Watts Max. Amps

HRV EC D(R) 120 120V, 60Hz 198 2.5

Ext.

Dif

fere

ntia

l Pre

ssur

e -

in. W

G

Ext.

Dif

fere

ntia

l Pre

ssur

e -

in. W

G

Gross Airflow - CFM Gross Airflow - CFM

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2

0 20 40 60 80 100 120 140 160 180 2000

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2

0 20 40 60 80 100 120 140 160 180 200

SupplyExhaust

SupplyExhaust

HRV EC D(R) 120 ERV EC D(R) 120

Page 30: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

30 AIR HANDLING UNITS |2017-11 |www.blauberg.us

HRV EC D(R) 120 ERV EC D(R) 120

DIMENSIONS

HRV EC DR 120 | ERV EC DR 120

HRV EC D 120 | ERV EC D 120

3 3/4” 12 3/

8 ”

5 13/16”

5 13/16” 34 7/8” 30 15/16”

12 3/

8 ”

20 1/

16”

3/4”

20 1/

16”

26 3/8” 22 7/16”

Ø 4 7/8” 1 1/8”

1 7/16” 12 5/

8 ” 23

1/4 ”

9 1/16” 3 9/

16”

3 9/16

” 3 15/16”

9 1/16” 3 15/16”

12 5/

18”

23 1/

4 ”

Ø 4 7/8”

3 3/4” 12 3/

8 ”

5 13/16”

5 13/16” 34 7/8” 30 15/16”

12 3/

8 ”

20 1/

16”

3/4”

20 1/

16”

26 3/8” 22 7/16”

Ø 4 7/8” 1 1/8”

1 7/16” 12 5/

8 ” 23

1/4 ”

9 1/16”

3 9/16

” 3 9/

16”

3 15/16”

9 1/16” 3 15/16”

12 5/

18”

23 1/

4 ”

Ø 4 7/8”

Page 31: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

31www.blauberg-group.com

HEAT AND ENERGY RECOVERY VENTILATION HRV EC D(R) 120 ERV EC D(R) 120

Page 32: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

32 AIR HANDLING UNITS |2017-11 |www.blauberg.us AIR HANDLING UNITS |2017-11 |

Heat and Energy Recovery Ventilators are the complete whole house ventilation system designed to bring a continuous supply of fresh air into the house while exhausting an equal amount of stale air.

• 181 CFM airflow rate provides effective ventilation in apartment overcoming high pressure in condo tower duct systems.

• Cross flow core ensures up to 73% SRE.• Slim casing design (9 1/8”) is perfect for in-ceiling installation.• Build in control board enables Supply and Exhaust fan inde-

pendent speed adjustment from 0 to 100% right at the job side.• Fast and simple mounting process thanks to brackets system.• Automatic recirculation damper (R option) for effective cold

protection.• No drain needed (ERV).• Up to 2.56 CFM/W (Energy Star requirement – 1.2 CFM/W).

Steel casing is covered with high-quality multilayer alu-minium and zinc alloy to prevent corrosion. The casing is equipped with a switch to turn the ventilator off when the service panel is opened.

CASING

DESCRIPTION

FILTERWashable MERV 6 air filters in exhaust and supply air streams.Optional supply: anti grease aluminum filter.

Defrost system is activated when the outdoor temperature falls below 23° F (-5° C).Recirculation defrost HRV/ERV EC DR 150.Fan stop defrost HRV/ERV EC D 150.

DEFROST SYSTEM

High efficient electronically commutated motors with ex-ternal motor and impeller with backward curved blades. EC motors are featured with high performance and total speed controllable range. The electric motors and impellers are dy-namically balanced.

FANS

The unit incorporates an integrated automation and control system with following functions:• Operation mode switch.• Airflow balancing enabled by supply and exhaust fan inde-

pendent speed adjustment from 0 to 100% (percentage is displayed on built in screen).

• Automatic recovery core frost protection.• External control device connection (up to 5 at the same time).

CONTROL

5 year warrantyWARRANTY

HRV EC D(R) 150 ERV EC D(R) 150

Backdraft Dampers ClampsAir disk valve

ACCESSORIES

Timer

Aluminum cross-flow core (HRV EC D(R) 150) ensures efficient heat recovery.

Enthalpic core (ERV EC D(R) 150) provides both heat&humidity recovery. For enthalpic core no drain required.

HEAT RECOVERY CORE

Page 33: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

33www.blauberg-group.com

HRV EC D(R) 150 ERV EC D(R) 150

HEAT AND ENERGY RECOVERY VENTILATION

Due to low height of the casing the units offer perfect solution for the false ceiling installation in limited space.Brackets system makes mounting process easy and fast.

MOUNTING

Step 1 Step 2 Step 3

H

H = 9 1/8”

Page 34: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

34 AIR HANDLING UNITS |2017-11 |www.blauberg.us AIR HANDLING UNITS |2017-11 |

External Static Pressure Net Supply Air FlowGross Air Flow

PowerSupply Exhaust

Pa in. W.G. L/s CFM L/s CFM L/s CFM Watts25 0.1 85 181 88 186 81 171 18650 0.2 82 175 85 180 78 165 18675 0.3 80 169 82 174 75 159 186

100 0.4 77 162 79 167 72 153 185125 0.5 74 156 76 161 70 147 185150 0.6 70 149 73 154 67 141 184175 0.7 67 142 69 146 64 135 184200 0.8 64 135 66 139 61 128 184225 0.9 55 117 62 131 57 121 183250 1 52 110 58 123 54 114 182275 1.1 49 104 54 115 51 107 181300 1.2 45 96 50 107 47 99 181325 1.3 42 88 46 97 43 91 180350 1.4 38 80 41 88 39 83 178375 1.5 34 73 37 78 36 75 176400 1.6 30 64 32 69 31 66 174425 1.7 26 54 28 58 27 56 172450 1.8 21 45 22 47 22 47 169475 1.9 16 35 17 36 17 36 166500 2 12 24 12 25 12 25 163525 2.1 6 14 7 14 7 14 159550 2.2 2 4 2 3 2 4 156

Supply Temperature Net Airflow Average Power (Watts)

SensibleRecovery Efficiency

Apparent Sensible

Effectiveness

NetMoisture Transfer°C °F L/s CFM

Heating

I 0 32 31 66 26 73 82 0.46

II 0 32 46 97 42 70 78 0.38

III 0 32 50 107 52 68 75 0.36

IV

V -25 -13 31 65 89 63 77 0.37

Total Recovery Efficiency

Cooling VI 35 95 31 66 26 50.1 68 0.42

Model Volts Max. Watts Max. Amps

ERV EC D(R) 150 120V, 60Hz 186 2.5

PERFORMANCE ERV EC D(R) 150

Extract air

Supply airExhaust air

Intake air

Ext.

Dif

fere

ntia

l Pre

ssur

e -

in. W

G

Ext.

Dif

fere

ntia

l Pre

ssur

e -

in. W

G

Gross Airflow - CFM Gross Airflow - CFM

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2

2.2

2.4

0 20 40 60 80 100 120 140 160 180 2000

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2

2.2

2.4

0 20 40 60 80 100 120 140 160 180 200

SupplyExhaust

SupplyExhaust

HRV EC D(R) 150 ERV EC D(R) 150

Page 35: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

35www.blauberg-group.com

HEAT AND ENERGY RECOVERY VENTILATION

PERFORMANCE HRV EC D(R) 150

External Static Pressure Net Supply Air FlowGross Air Flow

PowerSupply Exhaust

Pa in. W.G. L/s CFM L/s CFM L/s CFM Watts25 0.1 85 181 88 186 81 171 18650 0.2 82 175 85 180 78 165 18675 0.3 80 169 82 174 75 159 186

100 0.4 77 162 79 167 72 153 185125 0.5 74 156 76 161 70 147 185150 0.6 70 149 73 154 67 141 184175 0.7 67 142 69 146 64 135 184200 0.8 64 135 66 139 61 128 184225 0.9 55 117 62 131 57 121 183250 1 52 110 58 123 54 114 182275 1.1 49 104 54 115 51 107 181300 1.2 45 96 50 107 47 99 181325 1.3 42 88 46 97 43 91 180350 1.4 38 80 41 88 39 83 178375 1.5 34 73 37 78 36 75 176400 1.6 30 64 32 69 31 66 174425 1.7 26 54 28 58 27 56 172450 1.8 21 45 22 47 22 47 169475 1.9 16 35 17 36 17 36 166500 2 12 24 12 25 12 25 163525 2.1 6 14 7 14 7 14 159550 2.2 2 4 2 3 2 4 156

Supply Temperature Net Airflow Average Power (Watts)

SensibleRecovery Efficiency

Apparent Sensible

Effectiveness

NetMoisture Transfer°C °F L/s CFM

Heating

I 0 32 31 66 26 69 78 0.04

II 0 32 46 97 42 67 74 0.05

III 0 32 50 107 52 65 73 0.05

IV

V -25 -13

Total Recovery Efficiency

Cooling VI 35 95 31 66 25.8 40.2 64 0.04

Model Volts Max. Watts Max. Amps

HRV EC D(R) 150 120V, 60Hz 186 2.5

Ext.

Dif

fere

ntia

l Pre

ssur

e -

in. W

G

Ext.

Dif

fere

ntia

l Pre

ssur

e -

in. W

G

Gross Airflow - CFM Gross Airflow - CFM

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2

2.2

2.4

0 20 40 60 80 100 120 140 160 180 2000

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

1.8

2

2.2

2.4

0 20 40 60 80 100 120 140 160 180 200

SupplyExhaust

SupplyExhaust

HRV EC D(R) 150 ERV EC D(R) 150

Page 36: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

36 AIR HANDLING UNITS |2017-11 |www.blauberg.us

DIMENSIONS

HRV EC DR 150 | ERV EC DR 150

HRV EC D 150 | ERV EC D 150

11 13

/16 ”

21 9/

16”

4 5/8”

4 5/8” 9 1/8”

9 1/8”

11 13

/16 ”

2 9/16

27 3/4” 31 11/16”

36 1/8” 40 ”

11 13

/16 ”

11 13

/16 ”

25 3/

16”

25 3/

16”

4 5/8”

4 5/8”

Ø 4 7/8”

Ø 4 7/8”

11 13

/16 ”

21 9/

16”

4 5/8”

4 5/8” 9 1/8”

9 1/8”

11 13

/16 ”

2 9/16

27 3/4” 31 11/16”

36 1/8” 40 ”

11 13

/16 ”

11 13

/16 ”

25 3/

16”

25 3/

16”

4 5/8”

4 5/8”

Ø 4 7/8”

Ø 4 7/8”

HRV EC D(R) 150 ERV EC D(R) 150

Page 37: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

37www.blauberg-group.com

HEAT AND ENERGY RECOVERY VENTILATIONHRV EC D(R) 150 ERV EC D(R) 150

Page 38: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

38 AIR HANDLING UNITS |2017-11 |www.blauberg.us

S50 20/40/60 PUSH BUTTON TIMER

An electronic wall control timer that is compatible with all HRV  D  /  ERV  D models. This control activates the system on three possible modes of operation.The button activates the system to run in intermittent mode for 20/40/60 minutes, it then returns to the predetermined setting. The light indicator of this wall control shows clearly, in which operating mode the unit is.

• Push once for 20-minute, twice for 40-minute, or three times for 60-minute activation. Indicator lights up and the controlled unit goes to high speed.

• Push once more to stop activation. Unit returns to its pre-vious setting.

CONTROL

DESCRIPTION

ELECTRICAL DIAGRAM

Power supply: 24V AC ±10% or 24V DC ±10%Communication protocol: Normally opened contactUser interface: Push buttonType of indication:• LED 1 = 20 min timer is active;• LED 2 = 40 min timer is active;• LED 3 = 60 min timer is active.Output voltage: 24V AC ±10% or 24V DC ±10%Current Out: 100 mA, max

SPECIFICATION

Button

20 min

24 VACCOMHigh

NO

40 min

60 min

Page 39: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

39www.blauberg-group.com

Page 40: ERV D / HRV D ERV EC D / HRV EC D - Blauberg North America · 2019-08-21 · ERV D series ERV D 80 ERV DR 80 ERV EC D 80 ERV EC DR 80 ERV D 120 ERV DR 120 ERV EC D 120 ERV EC DR 120

11/2017

Technical changes reserved.Illustrations and texts are non-binding.

Blauberg Ventilatoren174 N. 36th Street

Lafayette, IN 47905tel.: +1 765 780 7139

[email protected]

www.blaubergventilatoren.de