    2 Ceiling Cassette(50Hz, R22)

    General Description

    Thank you very much for your special patronage of LG air conditioners.

    LGs "Ceiling Cassette" is a indoor unit which is installed for the significant purpose. The ceiling cassette is

    used for the commercial purposes. It can be installed in various places such as restaurants, hotels, offices and

    meeting rooms.

    This unit has nice outlook and is equipped with many special features. It has four louver for the air circulation in

    all directions which in turn can maintain even and wide cooling. In other side it has facility for high elevation pip-

    ing (30m), built in drain pump (drain throw 70cm),high ceiling operation,others for facilitating its working.

    Noise level of the unit is very low.

    In installation field unit is installed in fall ceiling. It has wide capacity range from 18 to 48 kBtu/h.

    A lot of information regarding the design & installation of this system is provided in this publication. This new

    products series contains data on the same pattern.

    Please utilize all the information for conducting your business efficiently.

    Make sure the specification, dimension or others technical data are same as provided in enginering data bookbefore you start the project.

    We look forward to your continuing support.

    LG Electronics lnc.

    Air Conditioning Division

  • 7/27/2019 Engineering Data Cassette 4 Way

    3/52

    Table of contents

    Table of contents Page

    1. Models List .............................................................................................................................................................. 4

    2. Model Number Nomenclature ....................................................................................................................... 5

    3. Feature & Benefts .............................................................................................................................................. 6

    4. List o Functions ...................................................................................................................................................

    145. Specifcations ........................................................................................................................................................

    186. Dimensional Drawings .....................................................................................................................................

    217. Wiring Diagrams ................................................................................................................................................

    258. Rerigerant Cycle Diagrams ........................................................................................................................

    269. Selection Procedure .........................................................................................................................................

    2710. Perormance Data .............................................................................................................................................

    3311. The Coecient o Capacity Change ....................................................................................................

    3412. Operation range ...................................................................................................................................................

    3513. Air Velocity and Temperature Distributions(Reference Data) .............................................................

    14. Sound Levels ...................................................................................................................................................... 37

    15. Installation ............................................................................................................................................................. 38

    16. Function o Remote Control ....................................................................................................................... 50

    LG Airconditioners Product Data

    32007 Product Data

    12

  • 7/27/2019 Engineering Data Cassette 4 Way

    4/52

    4

    1. Models List

    1.1 Cooling Only

    5.3 18HT-C186HLA1

    HT-C246HLA1

    1, 220-240V, 50Hz

    R22

    Nominal Capacity

    ,V,Hz

    HT-C306HLA030

    HT-C368DLA0

    HT-C488DLA0

    kW kBtu/h Model Name Refrigerant

    3, 380-415V, 50Hz

    8.8

    36

    48

    10.5

    14.0

    7.0 24

    Ceiling Cassette(50Hz,R22)

    HT-C186HLA0

    HT-C246HLA0

    Power SupplyModel

  • 7/27/2019 Engineering Data Cassette 4 Way

    5/52

    2.ModelNumberNomenclature

    H T C 1 8 6 H L

    Development Sequence

    Function

    A : Basic C : Plasma Air Purifying

    E : Elevation Grille F : Elevation Grille + Plasma Air Purifying

    Decoration Panel Information

    L : Basic Panel

    H : TH Chassis D : TD1 Chassis

    Chassis Type

    Electric Standard (Volts / Freq. / Phase)6 : 220-240V, 50Hz, 1 8 : 380-415V, 50Hz, 3

    Nominal Cooling CapacityEx) 18-> 18,000 Btu/h 24-> 24,000 Btu/h

    Model TypeC : Cooling Only

    A 0

    H : Development in Thailand

    T : Cassette Type

    N : Indoor Type , U : Outdoor Type

    2.1ModelNumberNomenclature

    52007 Product Data

  • 7/27/2019 Engineering Data Cassette 4 Way

    6/52

    6 Ceiling Cassette(50Hz,R22)

    3.Features & Benefits

    Energy Saving Gold Fin (Optional)

    Heat Exchanger fins are coated with anticorrosive &

    hydrophilic layers. It prevents the corrosion of heat

    exchanger. Fins remain as new even after long time

    of operation and maintains eff iciency of heat

    exchanger constant. It also saves power & mainte-

    nanceCost.

    Compact Design and EasyInstallation

    Only about 225mm height in the ceiling is sufficient for installationspace.

    Low Noise with 3-dimensionalturbo fanThemostadvancedlow-noisedesign.

    Theadoptionofturbo-fanandroundtypeheat

    exchangerprovidesthe quietest operation.

    Hygienic and Easy-to-Clean Filter

    Washableandanti bacteriafilterisadopted.

    Itiseasytoopengrilleandreplacecleanfilter.

    840mm

    840mm

    225mm

    (For TH Chassis)

  • 7/27/2019 Engineering Data Cassette 4 Way

    7/52

    72007 Product Data

    3.Features & Benefits

    Central Control (Optional)It enables to control 16 x 8 = 128 units with the helpof 8 controllers. All units can be put on and off fromone central room. For setting the temperature, fanspeed and other sub functions, access the sespec-tureLCD wiredremotecontrollerofeachunit.

    Cooling & Fan Operation(for cooling only)

    LG Ceiling Cassette air conditioner provides cooling & fan operation. In the cooling mode, it cools the air withan operation range of 18~30C. In the fan operation mode, only indoor fan at the selected speed will run, out-doorfanandcompressorwill beoff.

    Wired Remote Control (Accessory)

    It can control all the functions of the unit. You cancheck/set temperature, change operation mode, settimer & also diagnose the error of the unit. It alsohastheoptionofweeklyprogram.

    Auto Restart Operation

    When there is electricity failure the unit shuts off and after resumption of the po wer, unit will start in the samemode as prior to the power failure. Memorized condition are on / off condition, operating mode (cooling/heat-ing), set temperature and fan speed.The unit will memorize the above conditions and start with same memo-rizedcondition.

    Two Thermistor Control (Accessory)

    There may be a significant difference between the temperature taken at the installed product and indoor tem-perature. Two thermistor control provides option to control temperature by referring any of the two tempera-tures. With the help of the slide switch at the back of the LCD wired remote controller, selection of the desiredthermistor for controlling the unit can be done. One thermistor is in the Indoor unit & the other one is in theLCD wiredremote.

    Main

    PCB

    Controller# 1

    Controller# 2

    Controller# 8

    M1

    Sub1

    M2

    Sub2

    M16

    Sub16

    M17

    Sub17

    M18

    Sub18

    M128

    Sub128

    Timer

    Program

    Hour

    Cancel 2ndF

    Week Holiday

    Set/Clr

    MinRESET

    PLASMA

    ZONE 1 2 3 4

    Operation unit No Func

    HumidifyJET

    SLo

    AUTO

    AUTO SWING OPERATION FAN SPEED

    Program set

    SUBFUNCTIONSET TEMPRoom Temp

    HI

    MED

    LO

    Heater

    Defrost

    Filter

    Preheat

    Outdoor

    Time

    TimerOn

    S e tn o. Time

    Off

    01 0 3 0 5 07 09 1 1 1 3 15 1 7 1 9 2 1 23

    2ndF

  • 7/27/2019 Engineering Data Cassette 4 Way

    8/52

    8 Ceiling Cassette(50Hz,R22)

    3.Features & Benefits

    CeilingBoardDrainPan

    Maximum 700mm

    DrainPump

    Flexibledrainhose

    Pipefixture

    Slope1/50~1/100

    HardTube(ex.PVC)

    ++

    +

    +PollutedAir PurifiedfreshAir

    +4.8KVdischarge

    Ionizer Photo-CatalystCoatedMesh

    Dustparticles

    Odour

    Dustelectrodedischarge

    Odourmolecule

    Generatingplasma

    Plasma Air Purifying System (Optional)

    The PLASMA Air Purifying Function not only removes micro-scopic contaminants and dust, but also removes housemites, pollen, and pet fur helps to prevent allergic diseases

    likeasthma.

    High Head Drain Pump(700mm)

    Built-inDrainPumpdrainsout waterautomatically.

    Astandarddrain-headheightofupto 700mmispossible,creatingtheidealsolutionforperfect waterdrainage.

    High Ceiling Operation (Accessory)

    According to the height of the installation, it provides vari-

    ability of indoor fan motor rpm. If the height of installation

    is low then you can adjust low rpm of indoor fan motor.

    On the other hand if the height of the installation is high

    you can adjust high rpm of indoor fan motor. Selection of

    speed can be done by slide switch at the back of the LCD

    wiredremote.

    Installation on thenormal-height ceiling

    installation on thehigher ceiling

  • 7/27/2019 Engineering Data Cassette 4 Way

    9/52

    2007 Product Data 9

    Child Lock Function (Accessory)

    It prevents the children or others from tampering

    with the control buttons. Unit can be controlled bythe wireless remote controller. This can be easily setby pressing timer key & Min key simultaneously.

    After child lock is set, pressing any key will displayCL on the LCD for 3 seconds and all the keys will beineffective.

    Jet Cool

    In this mode quick and fast cooling is done. Cold

    and high velocity air is supplied to the room till the

    indoortemperaturereaches18C.

    Swirl Swing (Accessory)

    Itisthefunctionforcomfortcooling/heatingoperation.

    Thediagonaltwolouversareopenedthe

    morelargerthantheotherlouvers.Afteroneminute,itisopposite.

    Group Control (Accessory)

    It enables to control up to 16 units with the help of

    one wired remote controller.All the units will follow

    samesettingoftemperature & othersub functions.

    1 2 16........

    ........

    Vane2SwirlSwing(New)4- Open(Conventional)

    SwirlSwing(New)4- Open(Conventional)

    2.4% 4.8%100%Improved

    ComparisonofAirFlow Types

    ComparisonofFloor

    Temp.Distribution(20 C)

    Vane1 Close OpenOpen

    Open

    Open

    Open

    Close CloseOpen

    Vane3 Cl os e O pe n Cl os e Cl os eOpen

    OpenOpen Close CloseOpenVane2

    OpenOpen

    Time

    Close CloseOpenVane4

    Vane1

    Vane3

    Vane2

    Time

    Vane4

    Van

    Vane4

    Vane1

    3.Features & Benefits

    Timer

    Program

    Hour

    Cancel 2ndF

    Week Holiday

    Set/Clr

    MinRESET

    PLASMA

    ZONE 1 2 3 4

    Operation unit No Func

    HumidifyJETSLo

    AUTO

    AUTO SWING OPERATION FAN SPEED

    Program set

    SUB FUNCTIONSET TEMPRoom Temp

    HI

    MEDLO

    Heater

    DefrostFilter

    Preheat

    Out door

    Time

    TimerOn

    Set no. Time

    Off

    01 03 05 07 09 11 13 15 17 19 21 23

    2ndF

    CHILDLOCK Display

    ZONE 1 2 3 4

    Operation unit No Func

    HumidifyJETSLo

    AUTO

    A U TO S W IN G O P ER ATIO N FAN SPEED

    Program set

    SUBFUNCTIONSET TEMPRoomTemp

    HIMED

    LO

    HeaterDefrostFilter

    Preheat

    Outdoor

    Time

    TimerOnS etn o .T im e

    Off0 1 03 0 5 0 7 0 9 1 1 1 3 15 1 7 1 9 2 1 23

    2ndF

    o

  • 7/27/2019 Engineering Data Cassette 4 Way

    10/52

    10 Ceiling Cassette(50Hz,R22)

    3.Features & Benefits

    Space Control (Accessory)

    Vanesanglecan becontrolled bypair,consideringitsinstallationenvironment.

    Forexampledirectdraftscan beannoying,leading

    todiscomfortandreducedproductivityvanecontrolhelpstoeliminatethisproblem.Easilycontrolled by wiredremotecontrol.

    AirFlow can becontrolledeasilyregardinganyspaceenvironment.

    +2C

    +1C

    +0.5CSetting Temp.

    COMP

    Cooling CoolingHeating

    onSet

    ModeSet

    ModeSet

    ModeSet

    ModeLow/Stop

    Low/Stop

    SetMode

    off

    Low Low LowStop

    off off off off off on on on on

    CYCLE

    IndoorFAN

    -0.5C

    -1C

    -2C

    Inside Temp

  • 7/27/2019 Engineering Data Cassette 4 Way

    11/52

    112007 Product Data

    Time Delay Safety Function

    It delays restarting of the compressor by three min-

    utestherebypreventingdamagetothecompressor.

    Long Refrigerant Piping

    LG Ceiling Cassette air conditioners can cover up to

    30m length and 15 m height. It provides flexibility of

    installationand keepthe buildinginagoodoutlook.

    Zero Standby Power Due to SMPS (Switching Modulation PowerSupply)

    technology, there is almost zero power consumptioninthestandbymode.

    15m

    30m

    5~6W

    0.5W

    3.Features & Benefits

  • 7/27/2019 Engineering Data Cassette 4 Way

    12/52

    C a tegory F unc tionHTNC186HL A0 HTNC 246HL A0

    H T NC 3 0 6H LA 0 H T NC 3 6 8D LA 0 H T NC 4 8 8D LA 0

    Air supply outlet 4 4 4 4 4Airflow di rection control(left & right ) - - - - -

    Airflow di rection control(up & down Auto Aut o Auto Aut o Aut oAut o swi ng(left & right) - - - - -

    4 / 5

    - - - - -

    - - - - -

    - - - - -

    - - - - -

    - - - - -

    Wired remote cont roller(for hot el use)

    Wi reless remot e controller(simple)

    General cent ral cont roller (Non LGAP)

    Dry cont act

    Ind ivi dual

    control

    CAC

    network

    functi on

    Special

    funct ion kit

    Air f low

    Air purifying

    Installation

    Reliabilit y

    Conveni ence

    HTNC186HL A1 HTNC246HL A1

    Aut o swi ng(up & down)

    12 Ceiling Cassette (50Hz,R22)

    4.ListofFunctions

    Airflow steps(fan/cool)Chaos windVane ControlJet cool(Power wind )Swirl wind

    Aut o restart operat i on

    Elect ro t hermostatCTIE

    PDI(power distribut ion ind icat or)PI485Zone control

    Simple central control(LGAP)

    Wireless LCD remote cont rol

    Si mple wired remot e controllerDeluxe wired remote cont rollerSt andard wired remot e controllerTwo thermi stor cont rolTimer(weekly)Timer(on/off)Sleep mode

    Group control

    Forced operat i onChi ld lock

    Aut o operation(artificial int elligence)

    Auto cleaning

    Auto changeoverSoft d ry operat i on

    Self diagnosisHot st art

    Deod orizi ng filt erPlasma air purifi er

    Prefilt er(washable / ant i -fungus)Drain pumpE.S.P. cont rolElect ric heat er(op eration)

    High Ceiling Operation

    Accessory Accessory Accessory Accessory Accessory

    Accessory Accessory Accessory Accessory Accessory

    Accessory Accessory Accessory Accessory Accessory

    Others

    Option Option Option Option Option

    Accessory Accessory Accessory Accessory Accessory

    Accessory Accessory Accessory Accessory Accessory

    Zero Stand by Power

    Accessory

    O : Applied, X : Not applied, - : No relation* Option : Model name & price are different according to options, and assembled in factory with main unit* Accessory : Installed at field, ordered and purchased separately by the corresponding model name,

    Note:

    supplied separate package.

    AccessoryAccessoryAccessoryAccessory

    AccessoryAccessoryAccessoryAccessoryAccessory

    AccessoryAccessoryAccessoryAccessoryAccessory

    Option Option Option Option Option

    Option Option Option Option Option

    Option Option Option Option Option

    Accessory Accessory Accessory Accessory Accessory

    ( )3/4 4 / 5( )3/4 4 / 5( )3/4 4/ 5( )3/4 4 / 5( )3/4(wired remote)(auto wind)

  • 7/27/2019 Engineering Data Cassette 4 Way

    13/52

    C a tegory F unc tionHTUC 186HL A0 HTUC246HL A0

    H T UC 3 0 6 HL A0 H T UC 3 6 8 DL A0 H T UC 4 8 8 DL A0

    Defrost/Deicing

    High pressure switch - - - - -

    Phase protection

    - - - - -

    Reliability

    HTUC 186HL A1 HTUC246HL A1

    Restart delay(3-minutes)

    132007 Product Data

    4.ListofFunctions

    Self diagnosisSoft start

    Test function

    Thermistor

    Low ambient operation

    Auto operation(Artificial intelligence)

    Auto restart operation

    Network soluation(LGAP)

    PDI(Power Distribution Indicator)

    PI485

    CAC network

    function

    Convenience

    Special

    function kit

    Others

    Low pressure switch

    - - - - -

    - - - - -

    - - - - -

    - - - - -

    - - - - -

    - - - - -

    - - - - -

    O : Applied, X : Not applied, - : No relation* Option : Model name & price are different according to options, and assembled in factory with main unit* Accessory : Installed at field, ordered and purchased separately by the corresponding model name,

    supplied separate package

    - - - - -

  • 7/27/2019 Engineering Data Cassette 4 Way

    14/52

    14 Ceiling Cassette(50Hz,R22)

    5.Specifications

    / V / Hz 1 / 220 240 / 50

    kW 5.3 5.3 7 7

    B tu/h 18,000 18,000 24,000 24,000

    kW - - - -

    B tu/h - - - -

    Current Nominal R unning C urrent A 0.3

    Induction Induction Induction Induction

    Tu rbo Fan Tur bo Fan Tur bo Fan Tur bo Fan

    100

    CMM 15 / 12 / 10 15 / 12 / 10 17 /15 /13 17 /15 /13

    cfm 350 300 260/ / / / / / / /

    External S ta ti c P re ss u re m mAq - - - -

    Capacitor F / Vac

    Direct Direct Direct Direct

    Coil

    B ody mm(inch)

    Decorative P anel mm(inch)

    Body kg (lbs ) 26(57) 26(57) 26(57) 26(57)

    Decorative Panel kg (lbs )

    LongLifeFilter

    dB (A)+3 32 / 28 / 25 32 / 28 / 25 35 /33 /30 35 /33 /30

    Liquid mm (inch) 6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4)

    Gas mm (inch) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8)

    Drain (ID) mm 32 32 32 32

    l/h 1.9 1.9 2.4 2.4Fus e Fus e Fus e Fus e

    Thermis tor Thermis tor Thermis tor Thermistor

    R 22 R 22 R 22 R 22

    Capillary Tube C apillary Tube Capillary Tube Capillary T ube

    S ingle S ingle S ingle S ingle

    No .mm2 3 x 2.5 (4 0.75) 3 x 2.5 (4 0.75) 3 x 2.5 (4 0.75) 3 x 2.5 (4 0.75)

    CeilingCessetteType

    Air Fi lter

    R eferigerant

    Fa nAir Flow R ate

    (H / M / L )

    Cooling Capacity

    Heating Capacity

    Connectable Outdoor Unit

    Power and Trans mission Interunit Cable

    Sound Level (H / M / L)

    Dehumidification R ateSafety Devices

    Temperature Sensor

    Piping Connections

    R eferigerant Control

    Dimensions (W x H x D)

    Net Weight

    PowerSupply

    Motor Type

    Motor Output(W ) x No. of Unit

    Fan Type

    Drive

    R ow Column FP I

    1 /220 240 /50 1 / 220 240 / 50 1 / 220 240 / 50

    HTNC 186HL A0 HTNC 186HL A1 HT NC 246HL A0 HTNC 246HL A1

    Indoor Unit Type

    Model

    Model No : HTNC186HLA0, HTNC186HLA1, HTNC246HLA0, HTNC246HLA1

    0.3 0.3 0.3

    100 100 100

    Note :

    1. Capacities are based on the following conditions:

    Cooling: - Indoor Temperature 27 (80.6 ) DB/ 19 (66.2 ) WB

    - Outdoor Temperature 35 (95 ) DB/ 24 (75.2 ) WB

    Heating: - Indoor Temperature 20 (68 ) DB/15 (59 ) WB

    - Outdoor Temperature 7 (44.6 ) DB/ 6 (42.8 ) WB

    Piping Length - Interconnecting Piping Length 7.5m

    - Level Difference ofZero

    2. Wiring cable size must comply with the applicable local and national code.

    3. The specification may be subject to change without prior notice for purpose of improvement.

    LongLifeFilter LongLifeFilter LongLifeFilter

    5(11) 5(11) 5(11) 5(11)

    950*950*30(37.4*37.4*1.2)

    840*840*225(33.1*33.1*8.9) 840*840*225(33.1*33.1*8.9) 840*840*225(33.1*33.1*8.9) 840*840*225(33.1*33.1*8.9)

    950*950*30(37.4*37.4*1.2) 950*950*30(37.4*37.4*1.2) 950*950*30(37.4*37.4*1.2)

    350 300 260 390 360 320 390 360 320

    - - - -

    2Rx9Cx18FPI 2Rx9Cx18FPI 2Rx9Cx18FPI 2Rx9Cx18FPI

  • 7/27/2019 Engineering Data Cassette 4 Way

    15/52

    152007 Product Data

    5.Specifications

    HT NC 306HL A0 HT NC 368DL A0 HT NC 488DL A0

    / V / Hz 1 / 220 240 / 50 3 / 380 415 / 50 3 / 380 415 / 50

    kW 8 .8 10 .5 14

    B tu/h 30,000 36,000 48,000

    kW - - -

    B tu/h - - -

    C urre nt Nomina l R unning C urrent A 0 .3 0 .4 0 .4

    Induc tion Induction Induction

    T urbo F a n T ur bo F an T ur bo Fa n

    100 124 124

    C MM 22 / 19 / 16 27 / 22 / 20 35 / 30 / 2 7

    cfm 490 460 420/ / / / / /

    External S ta tic P re s sure m mAq - - -

    Capacitor F / Vac

    Direct D irec t D irect

    Co i l

    B ody mm( inch)

    Decora tive P ane l mm( inch)

    Body kg ( lbs )

    Decorat ive P anel kg ( lbs )

    dB (A) +3 41 / 39 / 37 42 / 37 / 36 48 / 45 / 42

    Liquid mm ( inch)

    Gas mm ( inch)

    Drain (ID) mm 32 32 32

    l/h 3 2 .9 4 .6

    F us e F us e F us e

    T hermis tor T hermis tor T hermis tor

    R 22 R 22 R 22

    S ingle S ingle S ingle

    No . mm2

    Dimensions ( W x H x D)

    Ne t W eight

    P ower S upply

    Motor Type

    Motor Output(W ) x No. of Unit

    Fan T ype

    Drive

    R ow Column F P I

    Connecta ble Outdoor Unit

    P ower and Transmission Interunit Ca ble

    S ound Level (H / M / L )

    Dehumidif ication R a te

    S afety Devices

    Temperature S ensor

    Piping Connect ions

    R efer igerant C ontrol

    Ceiling Cass ette Type

    Ai r F ilt er

    Model

    R efer igerant

    F a n Air Flow R ate (H / M / L )

    Indoor Unit Type

    Cooling Capacity

    Heat ing Capacity

    Model No : HTNC306HLA0,HTNC368DLA0,HTNC488DLA0

    Note :

    1. Capacities are based on the following conditions:

    Cooling: - Indoor Temperature 27 (80.6 ) DB/ 19 (66.2 ) WB

    - Outdoor Temperature 35 (95 ) DB/ 24 (75.2 ) WB

    Heating: - Indoor Temperature 20 (68 ) DB/15 (59 ) WB

    - Outdoor Temperature 7 (44.6 ) DB/ 6 (42.8 ) WB

    Piping Length - Interconnecting Piping Length 7.5m

    - Level Difference ofZero

    2. Wiring cable size must comply with the applicable local and national code.

    3. The specification may be subject to change without prior notice for purpose of improvement.

    840*840*225(33.1*33.1*8.9) 840*840*225(33.1*33.1*8.9) 840*840*225(33.1*33.1*8.9)

    950*950*30(37.4*37.4*1.2) 950*950*30(37.4*37.4*1.2) 950*950*30(37.4*37.4*1.2)

    LongLifeFilter LongLifeFilter LongLifeFilter

    5(11) 5(11) 5(11)

    510 460 420 630 580 500

    - - -

    2Rx9Cx18FPI 2Rx12Cx19FPI 2Rx12Cx19FPI

  • 7/27/2019 Engineering Data Cassette 4 Way

    16/52

    &HLOLQJ&DVVHWWH+]5

    6SHFLILFDWLRQV

    +78& +/ $ +7 8& +/ $ +78& +/ $ +78& +/ $

    N:

    %WXK

    N:

    %WXK & RROLQJ N:

    +HDWLQJ N:

    & RROLQJ $

    +HDWLQJ $

    6 WDUWLQJ & XUUHQW & RROLQJ+HDWLQJ $

    9 +] a a a a

    1RPP [ [ [ [

    3RZHU DQG 7 UDQVPLVVLRQ & DEOH

    2XWGRRU WR ,QGRRU RU 2XWGRRU WR % '

    1R PP

    'LPHQV LRQV : [ + [ ' PPLQFK

    5 RWDU\ 5 RWDU\ 5 RWDU\ 5 RWDU\

    433%$ 4- 3 %$ 43 3$% 433$%

    2QH 3 KDVH 2QH 3 KDVH 2QH 3 KDVH 2QH 3KDVH

    2LO FKDUJH YROXPH FF

    +LJK HIILFLHQF\ +LJK HIILFLHQF\ +LJK HIILFLHQF\ +LJK HIILFLHQF\

    2LO FKDUJH YROXPH FF

    2LO FKDUJH YROXPH FF

    & \FOH $ & KDUJH D W P JR]

    & \FOH % & KDUJH DW P JR]

    5 5 5 5

    & DSLOODU\ 7 XEH & DSLOODU\ 7 XEH & DSLOODU\ 7 XEH & DSLOODU\ 7 XEHJPR]IW

    5 & 5 & 5 & 5 &

    &DSDFLWRU 9DF

    'LUHFW 'LUHFW 'LUHFW 'LUHFW

    6 LGH 6 LGH 6 LGH 6 LGH

    $LU ) ORZ 5 DWH1R RI ) DQ &0 0FIP [ [ [ [

    6 RXQG /HYHO+/ 6 RXQG 3 UHVVXUH G%$

    /LTXLG& \FOH $ PPLQFK

    *DV& \FOH $ PPLQFK

    /LTXLG& \FOH % PPLQFK

    *DV& \FOH % PPLQFK

    +LJK 3UHVVXUH * DV PPLQFK

    7RWDO 3 LSLQJ P

    0DLQ 3 LSLQJ P

    7RWDO %UDQFK 3 LSLQJ P

    ( DFK %UDQFK 3 LSLQJ P

    2XWGRRU 8QLWa,QGRRU 8QLW P

    ,QGRRU 8QLWa,QGRRU 8QLW P

    &RROLQJ R&R) a a a a

    +HDWLQJ R&R)

    2XWGRRU 8QLW 7\SH &HLOLQJ & DV V HWWH 7\SH

    1R PP ,QFOXGLQJ (DUWK ,QFOXGLQJ (DUWK ,QFOXGLQJ (DUWK ,QFOXGLQJ (DUWK

    3LSLQJ & RQQHFWLRQV

    0D[ ,QWHUXQLW

    3LSLQJ /H QJWK

    0D[ (OHYDWLRQ

    'LIIHUHQFH

    2SHUDWLRQ 5DQJH

    2XWGRRU

    +HDW ( [FKDQJHU5RZV [ &ROXPQ [ )3, 1R

    'HIURVWLQJ 0HWKRG

    )D Q'ULYH

    'LVFKDUJH 'LUHFWLRQ6LGH7RS

    5HIULJHUDQW7\SH

    &RQWURO$GGLWLRQDO 5 HIULJHUD QW & KDUJH

    &RPSUHVVRU

    7\SH

    4W\ [ 0RGHO

    0RWRU W\SH

    2LO W\SH

    &RPSUHVVRU

    7\SH

    4W\ [ 0RGHO

    0RWRU W\SH

    2LO W\SH

    0D[ 1XPEHU RI &RQQHFWDEOH ,QGRRU 8QLWV

    &RPSUHVVRU

    7\SH

    4W\ [ 0RGHO

    0RWRU W\SH

    2LO 7\SH

    3RZHU 6XSSO\ &DEOH2XWGRRU

    3RZHU DQG 7 UDQVPLVVLRQ & DEOH%' WR ,QGRRU

    1HW : HLJKW

    1RPLQDO ,QSXW

    0LQ5DWLQJ0D[

    7HV WLQJ & RPELQDWLRQ

    5XQQLQJ &XUUHQW5DWLQJ

    3RZHU 6XSSO\

    2XWGRRU XQLW

    1RPLQDO &DSDFLW\

    0LQ5DWLQJ0D[

    &RROLQJ

    +HDWLQJ

    0RGHO1R+78&+/$+78&+/$+78&+/$+78&+/$

    1RWH

    &DSDFLWLHV DUH EDVHG RQ WKH IROORZLQJ FRQGLWLRQV

    &RROLQJ ,QGRRU 7HPSHUDWXUH '% :%

    2XWGRRU 7HPSHUDWXUH '% :%

    +HDWLQJ ,QGRRU 7HPSHUDWXUH '% :%

    2XWGRRU 7HPSHUDWXUH '% :%

    3LSLQJ /HQJWK ,QWHUFRQQHFWLQJ 3LSLQJ /HQJWK P

    /HYHO 'LIIHUHQFH RI =HUR

    :LULQJ FDEOH VL]H PXVW FRPSO\ ZLWK WKH DSSOLFDEOH ORFDO DQG QDWLRQDO FRGH

    7KH VSHFLILFDWLRQ PD\ EH VXEMHFW WR FKDQJH ZLWKRXW SULRU QRWLFH IRU SXUSRVH RI LPSURYHPHQW

  • 7/27/2019 Engineering Data Cassette 4 Way

    17/52

    172007 Product Data

    5.Specifications

    HT UC 306HL A0 HT UC 368DL A0 HT UC 488DL A0

    kW 8.8 10.5 14

    B tu/h 30,000 36,000 48,000

    kW - - -B tu/h - - -

    Cooling kW - - -

    Heating kW - - -

    - - -

    C ooling A 15 6 8.5

    Heating A - - -

    S tarting C urrent C ooling/Heating A 68 55 58

    / V / Hz 1/220~240/50 3/380~415/50 3/380~415/50

    No. mm 3 2.5 4 4 4 4

    P ower and Transmission Cable

    (Outdoor to Indoor or Outdoor to BD)

    No. mm - - -

    Dimensions W x H x D mm(inch) 870 * 800 * 320 (34.2*31.4*12.6) 900 * 1160 * 370(35.4*45.7*14.6) 900 * 1160 * 370(35.4*45.7*14.6)

    73(160) 81(179) 87(192)

    1 1 1

    R otary S croll S croll

    NHT52VBAT S Q042YAA S B061YAAOne P has e T hree P has e T hree P hase

    Oil charge volume cc 1300 1300 1,650

    High efficiency High efficiency High efficiency

    - - -

    - - -

    - - -

    Oil charge volume cc - - -

    - - -

    - - -

    - - -

    - - -

    Oil charge volume cc - - -

    - - -

    Cycle A Charge (at 7.5m) g(oz) 2,000(71) 2,000(71) 2,600(92)

    Cycle B Charge (at 7.5m) g(oz) - - -

    R 22 R 22 R 22

    Capillary Tube C apillary T ube C apillary T ube

    g/m(oz/ft) 40(4.62) 40(4.62) 60(6.94)

    (2R 36C 18) 1 (1R 22C 17) 2 (2R 26C 18) 2

    - - -

    Capacitor GG/Vac 6/470 6/400 6/400

    Direct Direct Direct

    S ide S ide S ide

    Air F low R ateNo. of F a n C MM(cfm) 51(1810) x 1 104 (3673) x 2 104 (3673) x 2

    S ound Level(H/L) S ound P res sure dB(A)+3 58/- 67/- 71/-

    Liquid(C ycle A) mm(inch) 6.35(1/4) 6.35(1/4) 9.52(3/8)

    Ga s (C ycle A) mm(inch) 15.88(5/8) 15.88(5/8) 19.05(3/4)

    Liquid(C ycle B ) mm(inch) - - -

    Ga s (C ycle B ) mm(inch) - - -

    H igh P res sure G as mm(inch) - - -

    T otal P iping m 30 30 30

    Main P iping m - - -

    T otal B ranch P iping m - - -

    E ach B ranch P iping m - - -

    Outdoor Unit~Indoor Unit m 7 15 15

    Indoor Unit~Indoor Unit m - - -

    Cooling oC (oF ) -21 GG43(69.8~109.4) -21GG43(69.8~109.4) -21GG43(69.8~109.4)

    Heating oC (oF ) - - -

    4 0.75(Including Ea rth)4 0.75(Including E arth)4 0.75(Including E arth)

    Ceiling Cassette TypeOutdoor Unit Type

    P iping C onnections

    Max . Interunit

    Piping Length

    Max . E levation

    Difference

    Operation R ange

    (Outdoor)

    Heat E xchanger(R ows x Column x FPI) No.

    Defrosting Method

    F anDrive

    Discharge Direction(S ide/Top)

    R efrigerantType

    Control

    Additional R efrigerant Charge

    Compressor(#3)

    Type

    Qty x Model

    Motor type

    Oil type

    Compressor(#2)

    Type

    Qty x Model

    Motor type

    Oil type

    Compressor(#1)

    Type

    Qty x ModelMotor type

    Oil T ype

    P ower and Transmission Cable(BD to Indoor)

    Net W eight

    Max . Number of Connectable Indoor Units

    No. mm

    Testing Combination

    R unning C urrent(R ating)

    P ower S upply

    P ower S upply Cable(Outdoor)

    Nominal Capacity

    (M inGG

    R atingGG

    Max)

    Cooling

    Heating

    Nominal I nput

    (M inGGR atingGGMax)

    Outdoor unit

    Model No : HTUC368DLA0,HTUC488DLA0

    Note :

    1. Capacities are based on the following conditions:

    Cooling: - Indoor Temperature 27 (80.6 ) DB/ 19 (66.2 ) WB

    - Outdoor Temperature 35 (95 ) DB/24 (75.2 ) WB

    Heating: - Indoor Temperature 20 (68 ) DB/15 (59 ) WB

    - Outdoor Temperature 7 (44.6 ) DB/ 6 (42.8 ) WB

    Piping Length - Interconnecting Piping Length 7.5m

    - Level Difference ofZero

    2. Wiring cable size must comply with the applicable local and national code.

    3. The specification may be subject to change without prior notice for purpose of improvement.

  • 7/27/2019 Engineering Data Cassette 4 Way

    18/52

    6.1IndoorUnits

    18 Ceiling Cassette (50Hz,R22)

    6.DimensionalDrawings

    L1

    048

    1L

    3L4

    L

    09

    09

    2L

    03

    587

    840

    678

    40

    110 110

    950

    950

    Unit:mm

    840UnitsizeezistinU048

    )tlob

    gnignaH(

    276

    5.101

    5.101

    )gninepognilieC(578

    875 (Ceilingopening)

    785(Hanging bolt) 4545

    41

    2

    3

    950

    059

    6

    03

    5L

    (unit:mm)

    L1 L3L2 L4Dimension

    Model

    HTNC186HLA0

    225

    288

    70.4

    140

    139.8

    210.5

    84

    152

    Number Name

    1 Liquidpipeconnection 6.35

    2 Gaspipeconnection

    HTNC186HLA0,

    HTNC186HLA1

    3 Drainpipeconnection

    4 Powersupplyconnection

    5 Air dischargegrille

    6 Air suctiongrille

    Descripition

    HTNC246HLA0,

    HTNC246HLA1 HTNC306HLA0HTNC368DLA0 HTNC488DLA0

    6.35 6.35 6.35 9.52

    12.70 15.88 15.88 15.88 19.05

    - - - - -

    - - - - -

    - - - - -

    - - - - -

    (unit:mm)

    ModelNo : HTNC186LA0, HTNC186LA1, HTNC246HLA0, HTNC246LA1, HTNC306HLA0

    5

    HTNC186HLA1

    HTNC246HLA0

    HTNC246HLA1

    HTNC306HLA0

    HTNC368DLA0

    HTNC488DLA0

    L5

    47

    52

  • 7/27/2019 Engineering Data Cassette 4 Way

    19/52

    192007 ProductData

    Air discharge grille

    W

    6.2Outdoor Units

    W mmH mmD mmL1 mmL2 mmL3 mmL4 mmL5 mm

    L6 mmL7 mmL8 mmL9 mmL10 mmL11 mm

    mm 6.35mm 15.88

    HTUC306HLA0Model

    Dimensions

    870 870 870655 655 800

    320 320 320370 370 37025 25 25

    340 340 340775 775 77525 25 25

    546 546 546162 162 162162 162 162

    54 54 5474.5 74.5 74.579 79 79

    HTUC186HLA0 HTUC246HLA0

    6.35 6.35 15.88 12.70

    Model No : HTUC186LA0, HTUC186LA1, HTUC246HLA0,

    (30k)

    (18k,24k)

    6. Dimensional Drawings

    HTUC246LA1, HTUC306HLA0

    HTUC186HLA1 HTUC246HLA1

  • 7/27/2019 Engineering Data Cassette 4 Way

    20/52

    20 CeilingCassette(50Hz,R22)

    L6L7 L8 L9

    4L

    H

    11L01L

    5L

    W

    D1

    L

    2L

    3L

    Gas side3-way valve

    Control cover

    Liquid side3-way valve

    4-hole for anchor bolts

    W mm

    H mm

    D mm

    L1 mm

    L2 mm

    L3 mmL4 mm

    L5 mm

    L6 mm

    L7 mm

    L8 mm

    L10 mm

    L11 mm

    mm

    mm

    MdelDimensions HTUC368DLA0 HTUC488DLA0

    9001,165

    370

    46045

    4101,135

    30

    550

    175

    175

    112

    120

    83

    900

    1,165370460

    45

    4101,135

    30

    550

    175175

    112

    120

    83

    6.35 9.52

    15.88 19.05

    6. Dimensional Drawings

    L9 mm

    Model : HTUC368DLA0, HTUC488DLA0

  • 7/27/2019 Engineering Data Cassette 4 Way

    21/52

    212007 Product Data

    7. WiringDiagrams

    Model No : HTNC186HLA0, HTNC186HLA1,

    CONNECTOR NUMBER LOCATION

    CN-POWER AC POWER SUPPLY

    CN-MOTOR BLDC FAN MOTOR OUTPUT

    CN-D/PUMP DRAIN PUMP OUTPUT

    CN-DISP DISPLAY

    CN-FLOAT FLOAT SWITCH INPUT

    CN-REMO REMOTE CONTROL

    CN-GRILLE ELEVATION TWILLE

    CN-CC CENTRAL CONTROL

    CN-PIPE1 DISCHARGE PIPE SENSOR

    CN-ROOM ROOM SENSOR CN-HVB AIR CLEANER

    CN-VANE1 STEP MOTOR

    CN-VANE2 STEP MOTOR

    HTNC306HLA0

    7.1 IndoorWiringDiagrams

    HTNC246HLA0, HTNC246HLA1,

    Option

  • 7/27/2019 Engineering Data Cassette 4 Way

    22/52

    22 Ceiling Cassette(50Hz,R22)

    7. WiringDiagrams

    Model No : HTNC368DLA0, HTNC488DLA0

    CONNECTOR NUMBER LOCATION

    CN-POWER AC POWER SUPPLY

    CN-MOTOR BLDC FAN MOTOR OUTPUT

    CN-D/PUMP DRAIN PUMP OUTPUT

    CN-DISP DISPLAY

    CN-FLOAT FLOAT SWITCH INPUT

    CN-REMO REMOTE CONTROL

    CN-GRILLE ELEVATION TWILLE

    CN-CC CENTRAL CONTROL

    CN-PIPE1 DISCHARGE PIPE SENSOR

    CN-ROOM ROOM SENSOR CN-HVB AIR CLEANER

    CN-VANE1 STEP MOTOR

    CN-VANE2 STEP MOTOR

    Option

  • 7/27/2019 Engineering Data Cassette 4 Way

    23/52

    Notes:

    CM

    BR

    WH

    COMPRESSOR

    BROWN

    WHITE

    BL

    OR

    YL

    BLUE

    ORANGE

    YELLOW

    BK

    RD

    GN/YL

    BLACK

    RED

    GREEN/YELLOW

    7.2 Outdoor Wiring Diagrams

    ModelNo:HTUC186HLA0,HTUC186HLA1,

    ModelNo:HTUC306HLA0

    7. Wiring Diagrams

    HTUC246HLA0,HTUC246HLA1

    232007ProductData

  • 7/27/2019 Engineering Data Cassette 4 Way

    24/52

    Notes:

    CM

    BR

    WH

    COMPRESSOR

    BROWN

    WHITE

    BL

    OR

    YL

    BLUE

    ORANGE

    YELLOW

    BK

    RD

    GN/YL

    BLACK

    RED

    GREEN/YELLOW

    Model No : HTUC368DLA0, HTUC488DLA0

    (U)(V ) (W)

    24

    7. WiringDiagrams

    Ceiling Cassette(50Hz,R22)

  • 7/27/2019 Engineering Data Cassette 4 Way

    25/52

    252007 ProductData

    8. Refrigerant Cycle Diagrams

    INDOOR UNIT OUTDOOR UNIT

    INDOORCOIL

    OUTDOORCOIL

    COMPRESSORGASSIDE

    LIQUIDSIDECAPILLARY TUBE

    ModelNo: HT-C186HLA0, HT-C186HLA1, HT-C246HLA0HT-C368DLA0, HT-C488HLA0

    CAPILLARY TUBE

    COOLING

    15.88

    Field PipingModel Gas(mm)

    Liquid(mm)

    HT-C186HLA0,HT-C186HLA1

    HT-C246HLA0,HT-C246HLA1

    HT-C306HLA0

    HT-C368DLA0

    HT-C488DLA0

    15.88

    15.88

    19.05

    12.70 6.35

    6.35

    6.35

    6.35

    9.52

    Refrigerant pipe connection part diameter

    ,HT-C246DLA1, HT-C306HLA0

  • 7/27/2019 Engineering Data Cassette 4 Way

    26/52

    26 Ceiling Cassette(50Hz,R22)

    Step1. Determinecoolingloadrequirementsatdesignconditions.

    Requiredloadconditions:Requiredcoolingcapacity (TC)..............................21,000Btu/hSensiblecapacity (SHC) ........................................ 17,000Btu/h

    TemperatureairenteringOutdoorUnit ................. 95FTemperatureairenteringIndoorUnit ..................... 80FDB/67F WBDBdry bulb temperatureWBwet bulb temperature

    Step2. Selectunit basedonrequiredcoolingcapacity.

    BasedonTotalCoolingCapacity,choosesuitablemodelfromthespecificationtable.Themodel withnetcoolingcapacityof24,000Btu/hisselected.ThesystemisHT-C246HLA0.Verifytheunitperformanceatthegivenconditionsinaccordance withstep3.

    Step3. Determineifsystemselectedsatisfiescoolingrequirements.

    Entercoolingcapacitiestableonpage31athighspeedand 95Foutdoorenteringairtemperaturewith80FDB/67F WBindoorenteringairtemperature.Totalcoolingcapacity = 23,000Btu/h, Sensiblecapacity=19,300Btu/h

    Tofindcapacityatintermediateconditionsnotinthetable ;Interpolationshould beused whendesignconditionsare betweentwonumbersthatareinthecapacitytable.Extra-polationisnotrecommended.

    Iftheinterconnectingpipinglengthismorethan 7.5m ;Findthecapacity(%)atthatparticularinterconnectingpipinglengthfromthecoefficientofcapacitychangegraph,onpage33..

    MultiplycoefficientfactorwithTotalCoolingCapacity & SensibleCapacity.

    Ex:At30minterconnecting pipinglength,fromcoefficientofcapacitychangegraph,coeffienctfactoris0.915.

    TotalCoolingCapacity =Capacity (%)xTotalCoolingCapacity

    =91.5x23,000

    = 21,045Btu/h100 100

    SensibleCapacity =Capacity (%)x SensibleCapacity = 91.5x19,300 = 17,660Btu/h

    100 100

    9.SelectionProcedure

  • 7/27/2019 Engineering Data Cassette 4 Way

    27/52

    272007 ProductData

    10. Performance Data

    Outdoor DB ()

    Indoor WB ()

    I nd oo r DB () TC S HC P I TC SHC P I TC SHC P I TC S HC P I TC SHC P I TC SHC P I TC S HC P I TC S HC P I TC SHC P I

    5.1 4.6 1.53 5.6 3.5 1.58 6.0 1.5 1.61 4.9 4.6 1.69 5.4 3.5 1.74 5.8 1.6 1.78 4.7 4.5 1.81 5.2 3.4 1.87 5.6 1.5 1.90

    5.3 5.2 1.53 5.7 4.3 1.58 6.0 2.8 1.61 5.1 5.1 1.69 5.5 4.4 1.75 5.8 2.9 1.78 4.9 4.9 1.81 5.3 4.3 1.87 5.6 2.8 1.91

    5.5 5.5 1.54 5.8 5.2 1.59 6.0 3.9 1.62 5.3 5.3 1.70 5.6 5.3 1.75 5.8 4.0 1.79 5.1 5.1 1.82 5.4 5.2 1.88 5.6 3.9 1.91

    5.7 5.7 1.54 5.9 5.8 1.59 6.0 4.8 1.62 5.5 5.5 1.70 5.6 5.6 1.76 5.8 4.9 1.79 5.3 5.3 1.82 5.4 5.4 1.88 5.6 4.7 1.92

    16.1 19.4 22 .8 16.1 19.4 22 .8 16.1 19.4 22 .8

    29.4 35.0 40.6

    23.9

    26.7

    29.4

    32.2

    ModelNo: HT-C186HLA0

    TC S HC P I TC S HC P I TC S HC P I TC S HC P I TC S HC P I TC S HC P I

    4.5 4.4 1.9 1 4.9 3.3 1.9 7 5.3 1.5 2.01 4.1 4.1 2.00 4.6 3.2 2.06 4.9 1.4 2.10

    4.6 4.6 1.9 2 5.0 4.2 1.9 8 5.3 2.7 2.01 4.3 4.3 2.00 4.6 4.0 2.07 4.9 2.6 2.114.8 4.8 1.9 2 5.1 5.0 1.9 8 5.3 3.8 2.02 4.5 4.5 2.01 4.7 4.7 2.07 4.9 3.6 2.11

    5.0 5.0 1.9 3 5.1 5.1 1.9 9 5.3 4.6 2.03 4.6 4.6 2.02 4.8 4.8 2.08 4.9 4.4 2.12

    19. 4 22 .816 .1 19. 4 22 .8 16 .1

    51 .746 .1

    ModelNo:

    Outdoor DB ()

    Indoor WB ()

    I ndoo r DB () TC S HC P I TC S HC P I TC S HC PI TC S HC PI TC SHC P I TC S HC PI TC S HC PI TC S HC P I TC SHC P I

    4.8 4.6 1.40 5.4 3.5 1.44 5.8 1.5 1.47 4.7 4.7 1.55 5.2 3.5 1.60 5.6 1.6 1.62 4.5 4.5 1.66 5.0 3.4 1.71 5.4 1.5 1.74

    5.1 5.1 1.40 5.5 4.3 1.45 5.8 2.8 1.47 4.9 4.9 1.55 5.3 4.4 1.60 5.6 2.9 1.63 4.7 4.7 1.66 5.1 4.3 1.71 5.4 2.8 1.74

    5.2 5.2 1.41 5.5 5.2 1.45 5.7 3.9 1.48 5.1 5.1 1.56 5.3 5.3 1.60 5.5 4.0 1.63 4.9 4.9 1.67 5.2 5.2 1.72 5.4 3.9 1.75

    5.4 5.4 1.41 5.6 5.6 1.46 5.7 4.8 1.48 5.2 5.2 1.56 5.4 5.4 1.61 5.5 4.9 1.64 5.0 5.0 1.67 5.2 5.2 1.72 5.3 4.8 1.75

    29.4

    32.2

    29.4 35.0 40.6

    16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8

    23.9

    26.7

    TC S HC P I TC S HC P I TC S HC P I TC S HC P I TC S HC P I TC S HC P I

    4.3 4.3 1.75 4.7 3.3 1.81 5.1 1.5 1.84 3.9 3.9 1.83 4.4 3.2 1.89 4.7 1.4 1.9 2

    4.4 4.4 1.76 4.8 4.2 1.81 5.1 2.7 1.84 4.1 4.1 1.84 4.4 4.0 1.89 4.7 2.6 1.9 3

    4.6 4.6 1.76 4.9 4.9 1.82 5.1 3.8 1.85 4.3 4.3 1.84 4.5 4.5 1.90 4.7 3.6 1.9 3

    4.8 4.8 1.77 4.9 4.9 1.82 5.0 4.6 1.86 4.4 4.4 1.85 4.6 4.6 1.90 4.6 4.4 1.9 4

    46 .1 51 .7

    16 .1 19. 4 22 .8 16 .1 19. 4 22 .8

    ModelNo: HT-C186HLA1

    1. All capacites are net, evaporator fan motor heat is deducted.

    2. DB=Dry Bulb Temperature( C), WB=Wet Bulb Temperature( C)

    )Wk:tinU(yticapactaehelbisneS=CHS.4

    )Wk:tinU(yticapacgnilooclatoT=CT.3

    5. PI=Power Input(Comp.+ indoor fan motor+outdoor fan motor) (kW)

    Notes:

    Cooling Capacity(SI Unit)

  • 7/27/2019 Engineering Data Cassette 4 Way

    28/52

    28 CeilingCassette(50Hz,R22)

    10. Performance Data

    ModelNo: HT-C246HLA1

    ModelNo: HT-C306HLA0

    TC S HC PI TC S HC P I TC S HC PI TC S HC PI TC S HC PI TC S HC PI

    5.5 5.5 2.66 6.0 4.3 2.74 6.5 1.9 2.79 5.1 5.1 2.78 5.6 4.1 2.87 6.0 1.8 2.92

    5.7 5.7 2.67 6.1 5.4 2.75 6.5 3.5 2.80 5.3 5.3 2.79 5.7 5.1 2.88 6.0 3.4 2.93

    5.9 5.9 2.67 6.2 6.2 2.76 6.5 4.9 2.81 5.5 5.5 2.80 5.8 5.8 2.88 6.0 4.6 2.94

    6.1 6.1 2.68 6.3 6.3 2.77 6.4 5.9 2.82 5.7 5.7 2.80 5.8 5.8 2.89 6.0 5.7 2.95

    22.8 16.1 19.4 22.816.1 19.4

    46.1 51.7

    Outdoor DB ()

    Indoor WB ()

    Indoor DB () TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

    6.9 6.2 2.19 7.7 4.7 2.25 8.2 2.1 2.30 6.7 6.3 2.42 7.4 4.8 2.49 8.0 2.1 2.54 6.5 6.1 2.59 7.1 4.6 2.67 7.7 2.0 2.72

    7.2 7.1 2.19 7.8 5.8 2.26 8.3 3.8 2.30 7.0 7.0 2.42 7.5 6.0 2.50 8.0 3.9 2.55 6.7 6.7 2.59 7.3 5.8 2.68 7.7 3.8 2.73

    7.5 7.5 2.20 7.9 7.0 2.27 8.2 5.3 2.31 7.2 7.2 2.43 7.6 7.2 2.51 7.9 5.4 2.55 7.0 7.0 2.60 7.4 7.0 2.68 7.7 5.3 2.73

    7.8 7.8 2.21 8.0 7.8 2.28 8.2 6.4 2.32 7.5 7.5 2.44 7. 7 7. 7 2.52 7.9 6.6 2.56 7.2 7.2 2.61 7.5 7.5 2.69 7.6 6.4 2.74

    29.4

    32.2

    23.9

    26.7

    16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8

    29.4 35.0 40.6

    TC S HC P I TC S HC P I TC S HC P I TC S HC P I TC S HC P I TC S HC P I

    6.1 6.0 2.73 6.7 4.5 2.82 7. 2 2.0 2.87 5.6 5.6 2.86 6.2 4.3 2.95 6.7 1.9 3.00

    6.4 6.4 2.74 6.9 5.6 2.83 7. 3 3.7 2.88 5.9 5.9 2.87 6.4 5.4 2.96 6.7 3.5 3.01

    6.6 6.6 2.75 7. 0 6.8 2.84 7. 2 5.1 2.89 6.1 6.1 2.88 6.4 6.4 2.9 7 6.7 4.9 3.02

    6.8 6.8 2.76 7. 0 7. 0 2.85 7. 2 6.2 2.90 6.3 6.3 2.88 6.5 6.5 2.98 6.7 5.9 3.03

    19. 4 22 .816 .1 19. 4 22.8 16 .1

    51 .746 .1

    Ou tdoor DB ()

    Indoor WB ()

    I nd oo r D B () TC S HC P I TC S HC P I TC S HC P I TC S HC P I TC S HC P I TC S HC P I TC S HC P I TC S HC P I TC S HC P I

    6.2 5.9 2.12 6.9 4.4 2.19 7.4 2.0 2.23 6.0 6.0 2.35 6.6 4.5 2.42 7. 1 2.0 2.47 5.8 5.8 2.51 6.4 4.4 2.59 6.9 1.9 2.64

    6.5 6.5 2.13 7. 0 5.6 2.20 7. 4 3.6 2.24 6.3 6.3 2.36 6.7 5.7 2.43 7. 1 3.7 2.48 6.0 6.0 2.52 6.5 5.5 2.60 6.9 3.6 2.65

    6.7 6.7 2.14 7. 1 6.7 2.20 7. 4 5.0 2.25 6.5 6.5 2.36 6.8 6.8 2.44 7. 1 5.1 2.48 6.3 6.3 2.53 6.6 6.6 2.61 6.9 5.0 2.66

    6.9 6.9 2.14 7. 2 7. 2 2.21 7. 3 6.1 2.25 6.7 6.7 2.37 6.9 6.9 2.44 7. 1 6.2 2.49 6.5 6.5 2.54 6.7 6.7 2.62 6.8 6.1 2.67

    23 .9

    26 .7

    29.4

    32 .2

    19. 4 22 .8

    40 .6

    16 .1 19. 4 22 .8 16 .1 19. 4 22 .8 16 .1

    29. 4 35 .0

    Outdoor DB ()

    Indoor WB ()

    Indoor DB () TC SHC P I TC SHC P I TC SHC P I TC SHC P I TC SHC P I TC SHC P I TC SHC P I TC SHC P I TC SHC P I

    8.4 7.0 2.78 9.3 5.3 2.87 10.0 2.3 2.92 8.1 7.2 3.08 9.0 5.4 3.17 9. 7 2.4 3.23 7 .9 7.0 3.29 8.7 5.3 3.40 9.3 2.3 3.468.8 8.1 2.79 9 .5 6.7 2.88 10.0 4.4 2.93 8.5 8.2 3.08 9.2 6.8 3.18 9.7 4.4 3.24 8.2 8.0 3.30 8.8 6.6 3.41 9.4 4.3 3.47

    9.1 8.8 2.80 9.6 8.0 2.89 10.0 6.0 2.94 8.8 8.8 3.09 9.3 8.2 3.19 9. 7 6.1 3.25 8.5 8.5 3.31 9.0 8.0 3.42 9.3 6.0 3.48

    9.4 9.3 2.81 9.7 8.9 2.90 10.0 7.3 2.95 9.1 9.1 3.10 9.4 9.1 3.20 9.6 7.5 3.26 8.8 8.8 3.32 9.1 8.8 3.43 9.3 7.3 3.49

    29.4

    32.2

    23.926.7

    16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8

    29.4 35.0 40.6

    TC S HC P I TC S HC P I TC S HC P I TC S HC P I TC S HC P I TC S HC P I

    7. 4 6.8 3.48 8.2 5.1 3.59 8.8 2.3 3.66 6.9 6.5 3.64 7. 6 4.9 3.7 5 8.2 2.2 3.82

    7.7 7.7 3.49 8.4 6.4 3.60 8.8 4.2 3.67 7. 2 7. 2 3.65 7. 7 6.1 3.7 6 8.2 4.0 3.83

    8.0 8.0 3.50 8.5 7. 8 3.61 8.8 5.8 3.68 7. 4 7. 4 3.66 7. 8 7. 4 3.7 8 8.2 5.6 3.85

    8.3 8.3 3.51 8.6 8.6 3.62 8.7 7.1 3.69 7.7 7.7 3.67 7.9 7.9 3.7 9 8.1 6.8 3.86

    19. 4 22 .816 .1 19. 4 22 .8 16 .1

    51 .746 .1

    ModelNo: HT-C246HLA0

    Cooling Capacity(SI Unit)

  • 7/27/2019 Engineering Data Cassette 4 Way

    29/52

    292007ProductData

    10. Performance Data

    ModelNo: HT-C488DLA0

    ModelNo: HT-C368DLA0

    Outdoor DB ( )

    Indoor WB ()

    I ndoo r DB () TC SHC P I TC SHC P I TC SHC P I TC SHC P I TC SHC PI TC SHC P I TC SHC P I TC SHC P I TC SHC P I9.9 9.1 2.98 10.9 6.9 3.08 11.8 3.0 3.13 9.6 9.2 3.30 10.6 7.0 3.40 11.4 3.1 3.46 9.2 9.0 3.53 10.2 6.8 3.64 11.0 3.0 3.71

    10.3 10.3 2.99 11.1 8.6 3.08 11.8 5.6 3.1 4 10.0 10.0 3.31 10.8 8.8 3.41 1 1.4 5.7 3.47 9.6 9.6 3.54 10.4 8.5 3.65 11.0 5.6 3.72

    10.7 10.7 3.00 11.3 10 .4 3.09 11.7 7.8 3.1 5 10.3 10.3 3.32 10.9 10.6 3.42 11.3 7.9 3.48 10.0 10.0 3.55 10.5 10.3 3.66 10. 9 7. 7 3.73

    11.1 11.1 3.01 11.4 11 .4 3.10 11.7 9.5 3.1 6 10.7 10.7 3.33 11.0 11.0 3.43 1 1.3 9.7 3.49 10 .3 10.3 3.56 10.6 10.6 3.67 10.9 9.4 3.74

    16 .1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22 .8

    23 .9

    26 .7

    29.4

    32 .2

    29.4 35 .0 40 .6

    TC S HC PI TC S HC PI TC S HC PI TC S HC PI TC S HC PI TC S HC PI

    8.7 8.7 3.73 9.6 6.6 3.85 10.3 2.9 3.92 8.1 8.1 3.90 8.9 6.3 4.02 9.6 2.8 4.10

    9.1 9.1 3.74 9.8 8.3 3.86 10.3 5.4 3.93 8.4 8.4 3.91 9.1 7.9 4.03 9.6 5.2 4.11

    9.4 9.4 3.75 9.9 9.9 3.87 10.3 7.5 3.94 8.7 8.7 3.92 9.2 9.2 4.05 9.6 7.2 4.12

    9.7 9.7 3.76 10.0 10.0 3.88 10.3 9.2 3.95 9.0 9.0 3.93 9.3 9.3 4.06 9.5 8.8 4.13

    22.8 16.1

    51.7

    19.4 22.816.1 19.4

    46.1

    Outdoor DB ()

    Indoor WB ()

    Indoor DB () TC SHC PI TC SHC PI TC SHC PI TC SHC P I TC SHC PI TC SHC PI TC SHC PI TC SHC P I TC SHC PI

    13.0 11.2 4.60 14.3 8.5 4.74 15.4 3.7 4.83 12.5 11.4 5.08 1 3.8 8.6 5.24 1 4.9 3.8 5.34 12.1 11.1 5.44 13.3 8.4 5.61 1 4.3 3.7 5.72

    13.5 12.9 4.61 14.6 10.6 4.76 15.4 7.0 4.85 13.0 13.0 5.10 1 4.1 10.8 5.26 1 4.9 7.1 5.36 12.6 12.6 5.46 13.6 10.6 5.63 14.3 6.9 5.73

    14.0 14.0 4.63 14.8 12.8 4.77 15.4 9.6 4.86 13.5 13.5 5.11 1 4.3 13.0 5.28 1 4.8 9.8 5.37 13.1 13.1 5.47 13.8 12.7 5.65 1 4.3 9.6 5.75

    14.5 14.5 4.64 14.9 14.2 4.79 15.3 11.7 4.88 14.0 14.0 5.13 1 4.4 14.4 5.29 14.7 11.9 5.39 13.5 13.5 5.49 13.9 13.9 5.66 1 4.2 11.6 5.77

    26.7

    29.4

    32.2

    23.9

    22.819.4 22.8 16.1 19.416.1 19.4 22.8 16.1

    29.4 35.0 40.6

    TC S HC PI TC S HC PI TC S HC PI TC S HC PI TC S HC PI TC S HC PI

    11.4 10.8 5.75 12.6 8.2 5.93 13.5 3.6 6.05 10.5 10.3 6.02 11.7 7.8 6.20 12.5 3.5 6.32

    11.9 11.9 5.77 12.8 10.3 5.95 13.5 6.7 6.06 11.0 11.0 6.03 11.9 9.8 6.22 12.5 6.4 6.34

    12.3 12.3 5.79 13.0 12.4 5.9 7 13.5 9.3 6.08 11.4 11.4 6.05 12.0 11 .8 6.24 12.5 8.9 6.36

    12.7 12.7 5.81 13.1 13.1 5.9 9 13.4 11.3 6.10 11.8 11.8 6.07 12 .2 12 .2 6.26 12.4 10 .8 6.38

    16.1 19.4 22 .816.1 19.4 22.8

    46.1 51 .7

    1. All capacites are net, evaporator fan motor heat is deducted.

    2. DB=Dry Bulb Temperature( C), WB=Wet Bulb Temperature( C)

    )Wk:tinU(yticapactaehelbisneS=CHS.4

    )Wk:tinU(yticapacgnilooclatoT=CT.3

    5. PI=Power Input(Comp.+ indoor fan motor+outdoor fan motor) (kW)

    Notes:

    Cooling Capacity(SI Unit)

  • 7/27/2019 Engineering Data Cassette 4 Way

    30/52

    30 Ceiling Cassette(50Hz,R22)

    10. Performance Data

    Cooling Capacity(English Units)

    ModelNo: HT-C186HLA1

    Indoor DB ( F)

    ModelNo: HT-C186HLA0

    Notes: 1. All capacites are net, evaporator fan motor heat is deducted.F ), WB=Wet Bulb Temperature( F)

    3. TC=Total cooling capacity(Unit:1,000Btu/h)

    5. PI=Power Input(Comp.+ indoor fan motor+outdoor fan motor) (kW)4.SHC=Sensible heat capacity(Unit:1,000Btu/h)

    2. DB=Dry Bulb Temperature(

    PI PI PI PI PI PI PI PI PI

    Outdoor DB ( F)

    Indoor WB ( F)

    PI PI PI PI PI PI

    Outdoor DB ( F)

    Indoor WB ( F)

    Indoor DB ( F)

    PI PI PI PI PI PI PI PI PI

    Indoor WB ( F)

    Outdoor DB ( F)

    Indoor DB ( F)

    PI PI PI PI PI PI

    Outdoor DB ( F)

    Indoor WB ( F)

    Indoor DB ( F)

  • 7/27/2019 Engineering Data Cassette 4 Way

    31/52

    312007 Product Data

    10. Performance Data

    ModelNo: HT-C246HLA0

    ModelNo: HT-C246HLA1

    PI PI PI PI PI PI PI PI PI

    Outdoor DB ( F)

    Indoor WB ( F)

    Indoor DB ( F)

    PI PI PI PI PI PI

    Outdoor DB ( F)

    Indoor WB ( F)

    Indoor DB ( F)

    ModelNo: HT-C306HLA0

    PI PI PI PI PI PI PI PI PI

    Outdoor DB ( F)

    Indoor WB ( F)

    Indoor DB ( F)

    PI PI PI PI PI PI

    Outdoor DB ( F)

    Indoor WB ( F)

    Indoor DB ( F)

    PI PI PI PI PI PI PI PI PI

    PI PI PI PI PI PI

    Outdoor DB ( F)

    Outdoor DB ( F)

    Indoor WB ( F)

    Indoor WB ( F)

    Indoor DB ( F)

    Indoor DB ( F)

    Cooling Capacity(English Units)

  • 7/27/2019 Engineering Data Cassette 4 Way

    32/52

    32 CeilingCassette(50Hz,R22)

    10. Performance Data

    ModelNo: HT-C488DLA0

    Notes: 1. All capacites are net, evaporator fan motor heat is deducted.F ), WB=Wet Bulb Temperature( F)

    3. TC=Total cooling capacity(Unit:1,000Btu/h)

    5. PI=Power Input(Comp.+ indoor fan motor+outdoor fan motor) (kW)4.SHC=Sensible heat capacity(Unit:1,000Btu/h)

    2. DB=Dry Bulb Temperature(

    ModelNo: HT-C368DLA0

    PI

    PI

    PI

    PI

    PI

    PI

    PI

    PI

    PI

    PI PI PI PI PI PI

    PI PI PI PI PI PI PI PI PI

    PI PI PI PI PI PI

    Outdoor DB ( F)

    Indoor WB ( F)

    Indoor DB ( F)

    Outdoor DB ( F)

    Indoor WB ( F)

    Indoor DB ( F)

    Outdoor DB ( F)

    Indoor WB ( F)

    Indoor DB ( F)

    Outdoor DB ( F)

    Indoor WB ( F)

    Indoor DB ( F)

    Cooling Capacity(English Units)

  • 7/27/2019 Engineering Data Cassette 4 Way

    33/52

    Model No : HT-C186HLA0, HT-C186HLA1,HT-C246HLA0,HT-C246DLA1,HT-C306HLA0

    Notes:* Equivalentpipelength = Actualpipelength +numberofbend x0.3

    * Refertothespecificationforthemaximumpipelengthofeachmodel.

    Cooling(24k)

    Cooling(18k)

    Models 18k 24k

    25 30AdditionalRefrigerant

    70

    75

    80

    85

    90

    95

    100

    7.5 30

    Total Pipe Length(m )

    yticapaC

    %(

    )

    Cooling(48k)

    Cooling(36k)

    Cooling(30k)

    30k 36k 48k

    40 40 60

    2010

    Cooling Capacity

    (g/m)

    2007 Product Data 33

    11.TheCoefficientofCapacityChange

    HT-C368DLA0,HT-C488DLA0

  • 7/27/2019 Engineering Data Cassette 4 Way

    34/52

    34 Ceiling Cassette (50Hz,R22)

    12. OperationRange

    24(75.2)

  • 7/27/2019 Engineering Data Cassette 4 Way

    35/52

    352007 ProductData

    Discharge angle : 45Air velocity [m/s]

    13. Air Velocity and temperature Distributions(Reference Data)

    Ceiling Cassette 4-way TD1 chassis (36kBtu/h) Models

    2.7m

    2m

    1m

    0m

    4m3m2m1m0m1m2m3m4m

    2.0 2.0

    1.5 1.5

    1.0 1.0

    0.5 0.5

    Air velocity [m/s]

    Discharge angle : 40

    2.7m

    2m

    1m

    0m

    4m3m3m 2m2m 1m0m1m4m

    2.0 2.0

    1.5 1.5

    1.0 1.0

    0.5 0.5

    Ceiling Cassette 4-way TH chassis (18kBtu/h) Models

  • 7/27/2019 Engineering Data Cassette 4 Way

    36/52

    36 CeilingCassette(50Hz,R22)

    13. Air Velocity and temperature Distribution

    Temperature [ C]

    Ceiling Cassette 4-way TH chassis (18kBtu/h) Models

    2.7m

    2m

    1m

    0m

    4m3m3m 2m2m 1m0m1m4m

    18 18

    20 20

    22 22

    24 24

    Discharge angle:45u

    Ceiling Cassette 4-way TD1 chassis (36kBtu/h) Models

    2.7m

    2m

    1m

    0m

    4m3m2m1m0m1m2m3m4m

    20 20

    22 22

    24 24

    Temperature [ C]

    Discharge angle:40u

  • 7/27/2019 Engineering Data Cassette 4 Way

    37/52

    372007 Product Data

    Overall

    SoundPressureLevel

    Notes:

    - Soundmeasuredat1.5mawayfromthecenteroftheunit.

    - Dataisvalidatfreefieldcondition- Dataisvalidatnominaloperationcondition- ReferenceaccousticpressureOdB = 20 Pa- Soundlevel willvarydependingonarangeoffactorssuchas

    theconstruction(acousticabsorptioncoefficient)ofparticular roomin whichtheequipmentisinstalled.

    -Theoperatingconditionsareassumedto bestandard.

    Model

    HT-C186HLA0(1)

    HT-C246HLA0(1)

    SoundLevels(dBA)

    H M L

    32

    35

    28

    33

    25

    30

    1.5m

    Ceiling

    OctaveBandCenterFrequency (Hz)

    02

    er

    Bd(leveL

    erusserP

    dnuoS

    )

    aP

    OctaveBandCenterFrequency (Hz)

    02

    er

    Bd(leveL

    erusserP

    dnuoS

    )

    aP

    10

    20

    30

    40

    50

    60

    70

    80

    90

    63 125 250 500 1000 2000 4000 8000

    NC-15

    NC-70

    NC-65

    NC-60

    NC-55

    NC-50

    NC-45

    NC-40

    NC-35

    NC-30

    NC-25

    NC-20

    10

    20

    30

    40

    50

    60

    70

    80

    90

    63 125 250 500 1000 2000 4000 8000

    NC-15

    NC-70

    NC-65

    NC-60

    NC-55

    NC-50

    NC-45

    NC-40

    NC-35

    NC-30

    NC-25

    NC-20

    39

    37

    37

    36

    42

    HT-C368DLA0

    HT-C488DLA0

    41

    42

    48 45

    HT-C306HLA0

    HT-C368DLA0

    OctaveBandCenterFrequency (Hz)

    02

    er

    Bd(leveL

    erusserP

    dnuoS

    )

    aP

    1020

    30

    40

    50

    60

    70

    80

    90

    63 125 250 500 1000 2000 4000 8000

    NC-15

    NC-70

    NC-65

    NC-60

    NC-55

    NC-50

    NC-45

    NC-40

    NC-35

    NC-30

    NC-25

    NC-20

    OctaveBandCenterFrequency (Hz)

    0

    2er

    Bd(leveL

    erusserP

    dnuoS

    )

    aP

    10

    20

    30

    40

    50

    60

    70

    80

    90

    63 125 250 500 1000 2000 4000 8000

    NC-15

    NC-70

    NC-65

    NC-60

    NC-55

    NC-50

    NC-45

    NC-40

    NC-35

    NC-30

    NC-25

    NC-20

    OctaveBandCenterFrequency (Hz)

    02

    er

    Bd(leveL

    erusserP

    dnuoS

    )

    aP

    10

    20

    30

    40

    50

    60

    70

    80

    90

    63 125 250 500 1000 2000 4000 8000

    NC-15

    NC-70

    NC-65

    NC-60

    NC-55

    NC-50

    NC-45

    NC-40

    NC-35

    NC-30

    NC-25

    NC-20

    HT-C246HLA0(1)HT-C186HLA0(1)

    14. Sound Levels

    HT-C306DLA0

    HT-C488DLA0

  • 7/27/2019 Engineering Data Cassette 4 Way

    38/52

    38 Ceiling Cassette(50Hz, R22)

    15.Installation

    15.1Selectthe bestlocation

    15.1.1IndoorUnit

    t There should not be any heat source or steam neartheunit.

    t There should not be any obstacles to the air circula-tion.

    tThereshould beeasyprovisionofcondensatedrain.

    t Taking into account the noise prevention criteria,spottheinstallationlocation.

    t Keep proper distance of the unit from ceiling, fence,walls & otherobstaclesasshownfigure.

    t The indoor unit must have the maintenance spacearound.

    Above fgure means minimum value. Please keep these

    value at least.

    I H is 2700~3200mm: High ceiling operation control requied

    I H is ~2700: Normal operation

    NOTE

    1500 or more1500ormore

    1500 or more

    1

    500ormore

    Unit:mm

    Unit:mm

    Ceiling

    False ceilingFalse ceiling

    20 or more

    1500

    ormore 1500 or

    more

    H

    1500 ormore

    Floor

    t In case o the multi ow type, use the high humidity kit.

    Otherwise the dew drops can be seen on the unit body.

    t Rerigerant piping: Increase the piping insulationthickness upto 20mm or more.

    t Others: Inside the ceiling near th air tight seal places

    (no escape o the humidity)

    In case of multiple indoor cassette units

    (recommended)

    Rerigerant piping

    Grill or ventilation

    Above 1500mm

    Indoor unit

    Lighting

    Ventilator

    Indoor unit

    Above 2000mm

    Above 3000mm

  • 7/27/2019 Engineering Data Cassette 4 Way

    39/52392007 Product Data

    15.Installation

    15.1.2 OutdoorUnit

    t If a roof is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from thecondenserisnotrestricted.

    tDonotplaceanimalsandplantsinthepathofthe warmair.

    tTaketheairconditioner weightintoaccountandselectaplace wherenoiseandvibrationareminimum.

    t Selectaplacesothatthe warmairandnoisefromtheairconditionerdonotdisturb neighbors.

    t Rooftop Installations : If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure theroof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftopmounting.

    15.2 Settlementofoutdoorunit

    tAnchortheoutdoorunit witha boltandnut(10mm)tightlyandhorizontallyonaconcreteorrigidmount.

    t Wheninstallingonthe wall,rooforrooftop,anchorthemounting basesecurely withanailorwire

    assumingtheinfluenceofwindandearthquake.

    tInthecase whenthevibrationoftheunitiscon-veyedtothehose,securetheunit withananti-vibra-tionrubber.

    BoltTubingconnection

    Morethan30cm fo

    ornu

    S

    roec

    neF

    selcat

    sbo

    Morethan 70cm

    Morethan50cm

    More than30cmMorethan30cm

    Morethan30cm

    roec

    neF

    selcat

    sbo

    Morethan 70cm

    Morethan50cm

    More than30cmMorethan30cm

    foor

    nuS

    Morethan50cm

    (Servicespace)

  • 7/27/2019 Engineering Data Cassette 4 Way

    40/52

    40 Ceiling Cassette (50Hz, R22)

    1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.

    2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion

    on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunc-

    tion or inefficient performance.

    3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it

    needs additional anticorrosion treatment on the heat exchanger.

    1. If you cant meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment.

    2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water.

    15.3 Installation guide at the seaside

    15.3.1 Selecting the location(Outdoor Unit)

    1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.

    Install the outdoor unit on the opposite side of the sea wind direction.

    2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.

    3) Select a well-drained place.

    the sea wind from the sea.

    the outdoor unit.

    between outdoor unit and the windbreak for easy

    air flow.

    Sea wind Sea wind

    Sea wind

    Windbreak

    CAUTION

    15.Installation

  • 7/27/2019 Engineering Data Cassette 4 Way

    41/52

    412007 Product Data

    15.4 Ceiling Openingdimensionsandhanging boltlocation

    tThedimensionsofthepapermodelforinstallingarethesameasthoseoftheceilingopeningdimensions.

    Unit:mm

    840UnitsizeezistinU048

    )tlob

    gnignaH(

    276

    )g

    ninepognilieC(078

    870 (Ceilingopening)

    785(Hanging bolt)

    TH,TD1Chassis

    t

    Ceiling board

    t Selectandmark thepositionforfixing boltsandpipinghole.

    t Decide the position for fixing bolts slightly tilted to the drain direc-

    tionafterconsideringthedirectionofdrainhose.

    t Drilltheholeforanchorboltonthe wall.

    Levelgauge

    CeilingtThisair-conditionerusesadrainpump.

    tInstalltheunithorizontallyusingalevelgauge.

    t During the installation, care should be taken not to

    damageelectric wires.

    CAUTION

    Usetheventilation fanforsmoke-collectinghood withsufficientcapacity.

    Cookingtable

    Airconditioner

    Takeenoughdistance

    NOTE:tAvoidthefollowinginstallationlocation.

    1. Suchplacesasrestaurantsand kitchen wherecon-

    siderableamountofoilsteamandflourisgenerat-

    ed.

    Thesemaycauseheatexchangeefficiencyreduc-

    tion,orwaterdrops,drainpumpmal-function.

    Inthesecases,takethefollowingactions;

    t Makesurethatventilationfanisenoughtocoverall

    noxiousgasesfromthisplace.

    tEnsureenoughdistancefromthecookingroomto

    installtheairconditionerinsuchaplace whereit

    maynotsuck oilysteam.2. Avoidinstallngairconditionerinsuchplaces where

    cookingoilorironpowderisgenerated.

    3. Avoidplaces whereinflammablegasisgenerated.

    4. Avoidplace wherenoxiousgasisgenerated.

    5. Avoidplacesnearhighfrequencygenerators.

    15.Installation

  • 7/27/2019 Engineering Data Cassette 4 Way

    42/52

    42 Ceiling Cassette(50Hz, R22)

    15.Installation

    Wall

    mm7~5

    Indoor Outdoor

    Setscrew ofpapermodel (4pieces)

    Papermodelforinstallation

    Ceiling board

    mm051

    Adjustthesameheight

    Ceiling board

    Ceiling

    Flat washer forM10(accessory)

    Keepthelengthofthe boltfromthe bracketto40mm

    Opentheceiling boardalongtheouteredgeofthe

    papermodel

    Flat washer forM10(accessory)

    Hanging bolt(W3/8orM10)

    Nut(W3/8orM10)

    Nut(W3/8orM10)

    Spring washer(M10)

    AirConditionerbody

    tThefollowingpartsarelocalpurchasing.

    HangingBolt - W 3/8orM10

    Nut - W 3/8orM10

    Spring Washer- M10

    Plate Washer - M10

    t Drill the piping hole on the wall slightly tilted to the

    outdoorsideusinga 70hole-coredrill.

    t Tightenthenutand bolttopreventunitfromfallingoff.

    CAUTION

    15.5 TheIndoorUnitInstallation

  • 7/27/2019 Engineering Data Cassette 4 Way

    43/52

    432007 Product Data

    15.6 WiringConnection

    Thepowercordconnectedtotheoutdoorunitshould becompliedwiththefollowingspecifications(Rubberinsulation,typeH05RN-Fapproved byHARorSAA).

    Ifthesupplycordisdamaged,itmust bereplaced byaspecialcordorassemblyavailablefromthemanufactureroritsserviceagent.

    Theconnectingcableconnectedtotheindoorandoutdoorunitshould becompliedwiththefollowingspecifications (Rubberinsulation,typeH05RN-Fapproved byHAR orSAA).

    CAUTION

    mm5.8

    mm02

    LY/N

    Gmm5.7

    mm02

    LY/N

    G

    NORMAL

    CROSS-SECTIONAL

    AREA0.75mm2(18k/24k/30k)

    Makesurethatthescrewsoftheterminalarefreefromlooseness.WARNING

    1. All wiringmustcomply withLOCAL REGULATIONS.

    2. Selectapowersourcethatiscapableofsupplyingthecurrentasrequired bytheairconditioner.

    3. Feedthepowersourcetotheunitviaadistributionswitch boarddesignedforthispurpose.

    4. Theterminalscrewsinsidethecontrol boxmay belooseduetovibrationduringtransport.Check thescrewsforlooseconnection.(Runningtheairconditioner withlooseconnectioncanoverloadanddamageelectricalcomponents.)

    5. Alwaysgroundtheairconditioner withagrounding wireandconnectortomeettheLOCAL REGULATION.

    TerminalBlock inIndoor

    1(L) 2(N) 3 4

    Connectedtoindoorunit

    1(L) 2(N) 3(L) 4(N) 5 6 7 8

    outdoorunit

    Main

    TerminalBlock inIndoor

    1(L) 2(N) 3 4

    Connectedtoindoorunit

    outdoorunit

    Main

    1(R) 2(S) 3(T) 4(N) 6(L) 7(N) 8 9

    3 ,380V,50HZ1 ,220V,50Hz

    Capaci ty 1Phase 3Phase

    18k/24k/30kBtu/h

    36kBtu/h

    2.5mm2 -

    4mm 2

    4mm 2

    -

    -

    AREA1.25mm2(36k/48k)

    15.Installation

    48kBtu/h

  • 7/27/2019 Engineering Data Cassette 4 Way

    44/52

    44 Ceiling Cassette(50Hz,R22)

    15.Installation

    1. Form the piping according to its routing. Avoid bending

    and bending back the same piping point more than three

    times. (This will result in hardening the pipe.)2. Ater deorming the piping, align centers o the union

    ftting o the indoor unit and the piping, and tighten them

    frmly with wrenches.

    3. Connect pipe to the service valve or ball valve which is

    located below the outdoor unit.

    4. Ater completing the piping connection, be sure to check

    i there is gas leakage in indoor and outdoor connection.

    Ater completing the piping connection, execute vacuum

    drying or the connecting piping and the indoor unit.

    The vacuum drying must be carried out using the service

    ports o both the liquid and gas side valves.

    Outdoor

    unit

    Liquid side

    Flare connection

    Flare connection

    Gas side

    Indoor

    unit

    15.7 Piping Connection

    15.8 Vacuum dryingModel Liquid side piping Gas side piping

    30kBtu/h 6.35mm 15.88mm

    36kBtu/h

    9.52mm 19.05mm48kBtu/h

    24kBtu/h

    18kBtu/h 6.35mm 12.70mm

  • 7/27/2019 Engineering Data Cassette 4 Way

    45/52

    452007 Product Data

    15.Installation

    15.9 InstallationofDecorationPanel

    1. Temporarilyfixtwodecorationpanelfixingscrews (hexagon M5screw)ontheunit body. (Tighten by

    amount10mminlength.)

    Thefixingscrews (hexagon M5screw)areincludedtheindoorunit box.

    2. Removetheairinletgrillefromthedecorationpanel. (Removethehook fortheairinletgrillecord.)

    3. Hook thedecorationpanel keyhole ( )onthescrewsfixedinstepabove,andslidethepanelso

    thatthescrewsreachthe keyholeedge.

    4. Retightencompletelytwotemporarilyfixedscrewsandothertwoscrews. (Total4screws)

    5. Connectthelouvermotorconnectoranddisplayconnector.

    6. Aftertighteningthesescrews,installtheairinletgrille (includingtheairfilter).

    Thedecorationpanelhasitsinstallation

    direction.

    Beforeinstallingthedecorationpanel,

    alwaysremovethepapertemplate.

    Decorationpanelfixingscrews(hexagon M5screws)

    Temporallyfittingat2places(Tighteningabout10mm)

    Control boxcover

    Pipingside

    InletGrilleInletGrille

    InletGrilleLouvermotor

    Decorationpanelfixingscrews

    (Hexagon M5screw)

    Airconditionerunit

    Decorationpanel

    Keyholes

    Display

    Lead wireforlouvermotoranddisplay

    CAUTIONInstallcertainlythedecoration

    panel.

    Coolairleakagecausessweating.

    Waterdropsfall.

    Airconditionerunit

    Ceilingboard

    Decorationpanel DecorationpanelFittheinsulator(thispart)and

    becarefulforcoolairleakage

    Goodexample

    Air Coolairleakage(nogood)

    Badexample

    Ceilingboard

    Airconditionerunit

  • 7/27/2019 Engineering Data Cassette 4 Way

    46/52

    46 Ceiling Cassette(50Hz, R22)

    15.Installation

    15.11DrainPipe Work

    Drainpipegradientandsupport

    1) - The drain pipe must be ftted at a gradient o at least 1/100.

    - The drain pipe should be as short as possible and ree rom airlocks.

    2) Suspension bolts should be used to support long stretches o drain pipe in order to ensure that a gradient

    o 1/100 is maintained.(PVC pipe should not be bent)

    Spacingofsupportsforhorizontalpiping

    3) The length o pipe laid horizontally should be kept a minimum.

    Class Nominal diameter Spacing

    Rigid PVC pipe 25~40mm 1.0m or less

    Indoor unit

    Gradient o at least 1 / 100

    (1cm/ 1m)

    t Drain piping must have down-slope (1/50 to 1/100): be sure

    nottoprovideup-and-downslopetopreventreversalflow.

    t During drain piping connection, be careful not to exert extra

    forceonthedrainportontheindoorunit.

    t The outside diameter of the drain connection on the indoor

    unitis32mm.

    t

    Besuretoinstallheatinsulationonthedrainpiping.

    Piping material: Polyvinyl chloride pipe VP-25

    andpipefittings

    Heat insulation material: Polyethylene foam with

    thicknessmorethan8mm.

    Maintenancedrainport

    Upwardroutingnotallowed

    Pipeclamp

    Indoorunit

    1/50~1/100

    MAX 700mm

    Theairconditionerusesadrainpumptodrain water.

    Usethefollowingproceduretotestthedrainpumpoperation:

    t Connect the main drain pipe to the exterior

    and leave it provisionally until the test

    comestoanend.

    t Feed water to the flexible drain hose and

    check thepipingforleakage.

    t Be sure to check the drain pump for normal

    operating and noise when electrical wiring is

    complete.

    t When the test is complete, connect the flexi-

    ble drain hose to the drain port on the

    indoorunit.

    Draintest

    Feed water

    DrainPump

    Drainpan

    Flexibledrainhose(accessory)

    Maindrainpipe

    Gluethe jointDrainport

    DrainhoseconnectionUsetheclip (accessory)

  • 7/27/2019 Engineering Data Cassette 4 Way

    47/52

    472007 Product Data

    15.Installation

    CAUTION

    Thesuppliedflexibledrainhoseshouldnot becurved,neitherscrewed. Thecurvedorscrewedhosemaycausealeakageofwater.

    1/50~1/100

    MAX 700mm

    Flexible drain hoseFlexibledrainhose

    Aftertheconfirmationoftheaboveconditions,preparethe wiringasfollows:

    1) Never fail to have an individual power specialized for the air conditioner. As for the method ofwiring, be guided by thecircuitdiagrampastedontheinsideofcontrol box cover.

    2)Provideacircuit breakerswitch betweenpowersourceandtheunit.3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which

    the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (Iftheyareloose, itcouldgiveriseto burn-outofthe wires.)

    4)Specificationofpowersource5)Confirmthatelectricalcapacityissufficient.6) Besurethatthestartingvoltageismaintainedatmorethan 90percentoftheratedvoltagemarkedonthenameplate.7) Confirmthatthecablethicknessisasspecifiedinthepowersourcesspecification.

    (Particularlynotetherelation betweencablelengthandthickness.)8)Neverfailtoequipaleakage breaker whereitis wetormoist.9)Thefollowingtroubles would becaused byvoltagedrop-down.

    t Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of aoverloadprotectiondevice.t Properstartingpowerisnotgiventothecompressor.

    CAUTION

    Groupeddrainpiping

    1) Itisstandard work practicetomakeconnectionstothemainpipefromabove. Thepipecomingdownfromthecombinationshould beaslargeaspossible.

    2) Thepipe work should be keptasshortaspossibleandthenumberofindoorunitspergroup kepttoaminimum.

    Facetheventpipemouthdownwardto keep

    foreignmatterfrompenetratingthesystem

    Ventpipe

    Facepiping

    downward

  • 7/27/2019 Engineering Data Cassette 4 Way

    48/52

    48 Ceiling Cassette(50Hz,R22)

    15.Installation

    15.12 Optional Operation (For wire remote)

    1) TwoThermistorSystem

    (1)Opentherearcoverofthe wiredremote-controllertosetthemode.

    (2) Selectoneofthreeselectablemodesasfollows.

    tPosition1:

    Theroomtemperatureiscontrolled bythethermistorofthemain body.

    tPosition2:

    Theroomthemperatureiscontrolled bythethermistorofthe wiredremote-controller, controlthe

    temperatureaccordingtothepositionofwiredremote-controller.

    tPosition3:

    Theroomtemperatureiscontrolled bylowertemperature betweenthetemperatureofmain bodyandof

    remote-controllersensor.

    (3) Movetheslideswitchtosetposition.

    (4)Closetherearcoverandcheck ifit worksnormally.

    TH

    R14HSW TH

    REMOMAIN2TH OP7R18H

    R17H

    OP6

    LOSTAND

    SW HIGH

    HI R03S

    070C

    S40R

    S20R

    R01S

    OP3 OP2 OP1R19H

    R11H

    R13H R12H OP5R16H OP4

    R15H

    CO1H

    REMO

    Room Temp. sensor

    2TH

    MAIN

    Position2

    Position1

    Position3

    Slide switch forceilingheight

    Slide switch for2 Thermistor

    t Selectthepositionaftercounselling withacustomer.

    tIncaseofcoolingmode,roomtemperatureiscontrolled bythemain bodysensor.

    t To control the room temperature by a wired remote controller, install controller(room temp. sensor) to

    sensethetemperaturemoreaccurately.

    t Maunfacturedintheposition3.

    CAUTION

  • 7/27/2019 Engineering Data Cassette 4 Way

    49/52492007 Product Data

    15.Installation

    2)Adjustingairvolumetotheheightofceiling

    You can choose the RPM(or air volume) of indoor motor according to the height of ceiling to supply the

    comfortableatmospheretoconsumers.

    Procedure

    1. Choosetheselectablepositioninthetableaftermeasuringtheheightofceiling.

    2. Inthecaseofchangingtheheightas "high" or"low",opentherearcoverofthe wiredremote-controller.

    3. Movetheslideswitchtothesetposition.

    4. Closetherearcoverandcheck ifit worksnomally.TH

    R14H

    SW TH

    REMOMAIN2TH OP7R18H

    R17H

    OP6

    LO

    STAND

    SW HIGH

    HI R03S

    070C

    S40R

    S20R

    R01S

    OP3 O P2 O P1R19H

    R11H

    R13H R12H OP5R16 H O P4

    R15H

    CO1H

    Lo

    Hi

    STAND

    Slide switch forceilingheight

    Slide switch for2 Thermistor

    Standard(Default)

    Low ceiling

    HighCeiling

    Ceilingheight Modeofslideswitch Changeofairvolume Remark

    morethan3.3m HighCeiling Increasing

    2.7~3.3m Standard -

    lessthan2.7m Low Ceiling Decreasing

    Maunfacturedinstan-dardmode

    3) GroupControl(Optional Wiring)

    tBecarefulnottoexchangethecolorofwires.

    tThemaximumlengthofconnecting wireshould be below 200m(25)onconnectingeachunits.

    tUsea wiremorethan0.5mm2

    CAUTION

    Itoperatesmaximum16Units byonlyone Wired RemoteController,andeachUnitstartssequentiallytopre-ventovercurrent.

    Wiringdesign

    Operationunit

    ZONE 1 2 3 4

    HumidifyJETAUTO

    AUTOSWIN G OPERATION FANSPEED

    Programset

    SUBFUNCTIONSET TEMPRoomTemp

    HIMEDLO

    HeaterDefrostFilter

    Preheat

    Outdoor

    Time

    TimerOn

    Setno . Time

    Off0 1 0 3 0 5 0 7 09 1 1 1 3 1 5 17 19 2 1 2 3

    IndoorUnit1

    Terminal(Local Supply)Block

    Terminal(Local Supply)Block

    Terminal(Local Supply)Block

    MainPCB#1

    MainPCB#2

    MainPCB#16

    Wired RemoteController

    IndoorUnit2

    MainPCB

    IndoorUnit16

    ConnectorRED(12V)

    YL(SIGNAL)

    BR(GND)

    RED(12V)

    YL(SIGNAL)

    BR(GND)

    YL(SIGNAL)

    BR(GND)

    ConnectingCable(Local Supply)

    Connector Connector

    ....

    ....YL(SIGNAL)BR(GND)

    YL(SIGNAL)

    BR(GND)

    YL(SIGNAL)

    BR(GND)

    RemoteController

    PCB

    SingleGroupS/W GR

    t Using the supplied Wired Remote Controller, wire

    themlikeabove.

    t Move S/W GR to "Group" position.

    tCheck thelinecolorofthe wire.

  • 7/27/2019 Engineering Data Cassette 4 Way

    50/5250 Ceiling Cassette(50Hz,R22)

    16.1 WiredLCDRemoteControl

    Cooling Model

    1 OperationindicationscreenDisplaystheoperationconditions.

    2Swirl button

    3 2ndF button

    16.FunctionofRemoteControl

    NameandFunctionofRemoteControl.

    Usedtoselectswirlcoolmode.

    4 Timerset/cancel/Program/WeekHoliday/Hour/Min/SET/Clr/Ventilator

    5Settemperature button

    Usedtosetthetemperature whenrequired.

    6ON/OFF button

    Operationstarts whenthis buttonispressedandstops whenthe buttonispressedagain.

    7FanoperationUsedtocirculateroomairwithoutcoolingorheating.

    8Operationmodeselection buttonUsedtoselecttheoperationmode.

    9 Fanspeed buttonUsedtosetthedisiredfanspeed.

    10 Horizontal/Verticalairflow direction button

    11 Roomtemperature/filtersignrelease button

    Usedtocheck theroomtemperatureand

    releasethefilterin SecondFunction Mode.

    12 Plasma/Heater button

    Usedplasmaandsavedpowerin SecondFunction.

    13 Timereset button

    ResetUsedtosetthecurrenttimeandclearthesettingtime.

    14 Operationlamp

    Timer

    Program

    Hour

    Cancel 2ndF

    Week Holiday

    Set/Clr

    MinRESET

    PLASMA

    ZONE 1 2 3 4

    Operation unit No Func

    HumidifyJET

    SLo

    AUTO

    AUTO SWING OPERATION FAN SPEED

    Program set

    SUB FUNCTIONSET TEMPRoom Temp

    HI

    MED

    LO

    Heater

    Defrost

    Filter

    Preheat

    Out door

    Time

    Timer

    On

    Se tn o. T imeOff

    01 03 05 07 09 11 1 3 1 5 17 1 9 21 23

    2ndF

    1

    2

    5

    6

    7

    8

    9

    10

    11

    12

    13

    3

    4

    14

  • 7/27/2019 Engineering Data Cassette 4 Way

    51/52

    512007 Product Data

    16.FunctionofRemoteControl

    This air-conditioner is equipped with wired remote controller basically . But i you want to be available with

    wireles s remote controller, you pay or it.

    ON OFF

    CANCEL

    AUTO CLEAN

    SET

    1

    3

    5

    4

    9

    10

    12

    14

    16

    7

    2

    8

    13

    15

    11

    6

    Flip-up door

    (opened)

    Signal transmitter

    17

    Controls

    The controls will look like the ollowing.

    1.START/STOP BUTTONOperation starts when this button is pressed

    and stops when the button is pressed again.2. OPERATION MODE SELECTION BUTTON

    Used to select the operation mode.

    3. ROOM TEMPERATURE SETTINGBUTTONSUsed to select the room temperature.

    4. INDOOR FAN SPEED SELECTORUsed to select an speed in our stepslow, medium, high and CHAOS.

    5. JET COOLUsed to start or stop the speed cooling.(speedcooling operates super high fan speed incooling mode.)

    6. CHAOS SWING BUTTON

    Used to stop or start louver movement andset the desired up/down airfow direction.

    7. ON/OFF TIMER BUTTONSUsed to set the time o starting and stoppingoperation.

    8. TIME SETTING BUTTONSUsed to adjust the time.

    9. TIMER SET/CANCEL BUTTONUsed to set the timer when the desired timeis obtained and to cancel the Timeroperation.

    10. SLEEP MODE AUTO BUTTONUsed to set Sleep Mode Auto operation.

    11. AIR CIRCULATION BUTTON

    Used to circulate the room air withoutcooling or heating.

    12. ROOM TEMPERATURE CHECKINGBUTTONUsed to check the room temperature.

    13. NEO PLASMA(OPTIONAL)Used to start or stop theplasma-purication unction.

    14. HORIZONTAL AIRFLOW DIRECTIONCONTROL BUTTON (OPTIONAL)Used to set the desired horizontal airfowdirection.

    15. RESET BUTTONUsed prior to resetting time.

    16. 2nd F ButtonUsed prior to using modes printed in blueat the bottom o buttons.

    17. AUTO CLEAN (OPTIONAL)

    Used to set Auto Clean mode.CAUTION:ofhandlingtheRemoteController

    tAimatthesignalreceiveronthe wiredremotecontrollersoastooperate.tTheremotecontrolsignalcan bereceivedatadistanceofuptoabout 7m.t Besurethattherearenoobstructions betweentheremotecontrollerandthesignalreceptor.tDonotdroporthrow theremotecontroller.tDonotplacetheremotecontrollerinalocationexposedtodirectsunlight, orneartheheatingunit, oranyother

    heatsource.t Blockastronglightoverthesignalreceptorwithacurtainoretc.soastopreventtheabnormaloperation.(ex:elec-

    tronicquickstart, ELBA, invertertypefluorescentlamp)

    16.2.WirelessRemoteController

    NameandFunctionofRemoteController.