Energy Saving Opportunities for Transformers
Hans De Keulenaer
Outokumpu Tara Mines
Energy Efficient Motors & Transformers Workshop
May 7, 2002
![Page 2: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/2.jpg)
15-May-02 2
Content
• Introduction
• Technical issues & standards
• Economic equations
• Ecological equations
• The business case for high efficiency transformers
• Conclusion
![Page 3: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/3.jpg)
15-May-02 3
Why transformer efficiency is an issue?
• All electricity passes through several stages of transformation
• Savings potential of 22 TWh / year for EU
• Technology exists
• Economic potential
• Many pieces to the sustainable energy puzzle
![Page 4: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/4.jpg)
15-May-02 4
Losses in distribution transformers
• No load loss, or iron loss (Po)
• Load loss, or copper loss (Pk)– DC loss– Extra losses
• eddy current loss in windings• stray loss
• Other losses (ventilation, …)
![Page 5: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/5.jpg)
15-May-02 5
No load loss
Extra loss
Resisitive loss
Conventional loadloss excl harmonics
Extra loss due toharmonics
Unloaded Rated load Actual load Actual load (excl harmonics) (incl harmonics)
Load loss
Losses in distribution transformers
![Page 6: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/6.jpg)
15-May-02 6
Iron loss
• Occurs 24 hours / day, 365 days / year
• Example: 1,600 KVA, Po = 2,600 W– Annually 2,600 W * 8,760 hrs = 22.8 MWh / yr– 30 yrs = 684 MWh
– Emissions (0.4 kg CO2 / kWh) = 274 tonnes
– 5 c / kWh = 34,200 €
![Page 7: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/7.jpg)
15-May-02 7
Historical evolution in the production of magnetic steel
YEAR(approx.)
CORE MATERIAL THICKNESS(mm)
EPSTEIN VALUE(W/kg at 50Hz)
TYPE
1895 Iron wire 6 (1.0T)1910 Warm rolled FeSi 0.35 2 (1.5T)1950 Cold rolled CGO 0.35 1 (1.5T) M6x1960 Cold rolled CGO 0.3 0.9 (1.5T) M5x1965 Cold rolled CGO 0.27 0.84 (1.5T) M4x1970 Cold rolled HiB 0.3 0.8 (1.5T) M0H1975 Amorphous metal 0.03 0.2 (1.3T)1980 Cold rolled CGO
Cold rolled HiB0.230.23
0.75 (1.5T)0.70 (1.5T)
M3xM0H
1983 Laser treated HiB 0.23 0.6 (1.5T) ZDKH1985 Cold rolled CGO 0.18 0.67 (1.5T) M2x1987 Plasma treated HiB 0.23 0.6 (1.5T) Plasma PJ1991 Chem.Etched HiB 0.23 0.6 (1.5T) PDR
![Page 8: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/8.jpg)
15-May-02 8
Evolution of magnetic steel since the introduction of cold-rolled magnetic steel
![Page 9: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/9.jpg)
15-May-02 9
Copper loss
• Occurs only when transformer is loaded• Varies quadratically with the load• Example: 1,600 kVA, Pk = 17 kW, 50% loaded
– Annually 17 kW * 8,760 hrs * 0.5^2 = 37.2 MWh/yr– 30 yrs = 1.11
GWh
– Emissions (0.4 kg CO2 / kWh) = 444 tonnes
– 5 c / kWh = 55,500 €
![Page 10: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/10.jpg)
15-May-02 10
Loading
• Case 1:– 30% of time 80% load– 70% of time 10% load
• Case 2:– 8 hours @ 80%– 8 hours @ 40%– 8 hours @ 10%
![Page 11: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/11.jpg)
15-May-02 11
Typical load profilekW (15 avg)
-50
0
50
100
150
200
250
300
350
400
450
500
550
600
650
700
750
800
22/1
0/01
19:
45
23/1
0/01
0:1
5
23/1
0/01
4:4
5
23/1
0/01
9:1
5
23/1
0/01
13:
45
23/1
0/01
18:
15
23/1
0/01
22:
45
24/1
0/01
3:1
5
24/1
0/01
7:4
5
24/1
0/01
12:
15
24/1
0/01
16:
45
24/1
0/01
21:
15
25/1
0/01
1:4
5
25/1
0/01
6:1
5
25/1
0/01
10:
45
25/1
0/01
15:
15
25/1
0/01
19:
45
26/1
0/01
0:1
5
26/1
0/01
4:4
5
26/1
0/01
9:1
5
26/1
0/01
13:
45
26/1
0/01
18:
15
26/1
0/01
22:
45
27/1
0/01
3:1
5
27/1
0/01
7:4
5
27/1
0/01
12:
15
27/1
0/01
16:
45
27/1
0/01
21:
15
28/1
0/01
1:4
5
28/1
0/01
5:1
5
28/1
0/01
9:4
5
28/1
0/01
14:
15
28/1
0/01
18:
45
28/1
0/01
23:
15
29/1
0/01
3:4
5
29/1
0/01
8:1
5
29/1
0/01
12:
45
kW to T1
kW to T4
kW tot
![Page 12: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/12.jpg)
15-May-02 12
Results
• Energy transformed:– 1,600 kVA * 0.5 * 8,760 = 7,008 MWh / year
• Efficiency = 7,008 / (7,008 + 22.8 + 37.2) = 99.2%
• Lifetime cost:– Transformer: 10,000 € 10%– Iron loss: 34,200 € 35%– Copper loss: 55,500 € 55%– Total 99,700 € 100%
![Page 13: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/13.jpg)
15-May-02 13
Transformer efficiency
90%
91%
92%
93%
94%
95%
96%
97%
98%
99%
100%
0% 25% 50% 75% 100%
400 kVA,400 kVA,efficiencyefficiencylevel A-A’level A-A’(HD428) (HD428)
![Page 14: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/14.jpg)
15-May-02 14
Efficiency @ low load
75%
80%
85%
90%
95%
100%
0% 5% 10% 15% 20% 25%
400 kVA,400 kVA,efficiencyefficiencylevel A-A’level A-A’(HD428)(HD428)
![Page 15: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/15.jpg)
15-May-02 15
Efficiency standards
• Two approaches– European approach: specify Po and Pk
• CENELEC HD428 (oil) Po class A’, B’, C’Pk class A, B, C(nine combinations)
• CENELEC HD538 (dry) one class for Po, Pk
– US approach: specify efficiency at average load (typically 35-50%)
![Page 16: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/16.jpg)
15-May-02 16
Load Losses for Distribution Transformers No-Load Losses for Distribution Transformers
RATED
POWER
OIL-FILLED (HD428) UP TO 24kV2) DRY TYPE
(HD538)
OIL-FILLED (HD428) UP TO 24kV2) DRY TYPE
(HD538)
LIST A LIST B LIST C 12kV
PRIMARY 3)
LIST A’ LIST B’ LIST C’ 12kV
PRIMARY 3)
kVA W W W W W W W W
50 1,100 1,350 875 N/A 190 145 125 N/A
100 1,750 2,150 1,475 2,000 320 260 210 440
160 2,350 3,100 2,000 2,700 460 375 300 610
250 3,250 4,200 2,750 3,500 650 530 425 820
400 4,600 6,000 3,850 4,900 930 750 610 1,150
630 /4%1) 6,500 8,400 5,400 7,300 1,300 1,030 860 1,500
630 /6% 6,750 8,700 5,600 7,600 1,200 940 800 1,370
1000 10,500 13,000 9,500 10,000 1,700 1,400 1,100 2,000
1600 17,000 20,000 14,000 14,000 2,600 2,200 1,700 2,800
2500 26,500 32,000 22,000 21,000 3,800 3,200 2,500 4,300
Source: CENELEC
Distribution transformer efficiency standards
![Page 17: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/17.jpg)
15-May-02 17
Extreme cases
High loss >> AA’ Low loss >> CC’
![Page 18: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/18.jpg)
15-May-02 18
97.5%
98.5%
99.5%
Rating (kVA)
HD428 BA'
HD428 CC'
NEMA TP1
China S9
HD428 AA'
C-Amorphous
Comparison of efficiency at 50% loadComparison of efficiency at 50% load
![Page 19: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/19.jpg)
15-May-02 19
Conductor materials
• Cu and Al transformers can be built to comply to the same performance and quality standard
• Smaller ratings are typically cheaper with Cu• In general, use of Cu leads to:
– heavier, but more compact windings– a smaller core– a smaller, more compact transformer– a lower noise level– less oil-content
![Page 20: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/20.jpg)
15-May-02 20
400 KVA AA' design
90%
100%
110%
120%
130%
cost total mass noise volume
Cu
-re
f =
100
Cu design
Al design
400 KVA CC' design
90%
100%
110%
120%
130%
cost total mass noise volume
Cu
-re
f =
100
Cu design
Al design
1600 KVA AA' design
90%
100%
110%
120%
130%
cost total mass noise volume
Cu
-re
f =
100
Cu design
Al design
1600 KVA CC' design
90%
100%
110%
120%
130%
cost total mass noise volume
Cu
-re
f =
100
Cu design
Al design
Copper and Aluminium Designsfor the same efficiency
![Page 21: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/21.jpg)
15-May-02 21
Dry-type versus oil-filled transformers
• higher initial cost
• higher no-load losses
• lower load losses
• harmonics cause less extra heating and ageing
• better fire protection
• no oil spilling container
![Page 22: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/22.jpg)
15-May-02 22
79%
9%
12% Resistance
Magnetic
Eddy Current
Total loss = 1685 W
Full load losses in a 100kVA C-C’ transformer
![Page 23: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/23.jpg)
15-May-02 23
Harmonic profile of a typical Personal Computer
![Page 24: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/24.jpg)
15-May-02 24
41%53%
6%
Resistance
Magnetic
Eddy Current
Total loss = 3245 W
Full load losses in a 100kVA C-C’ transformer
![Page 25: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/25.jpg)
15-May-02 25
CP
PttempWorking
f
k 17393.190
102t
TtimeLife
yearsTtimeLife
f
fk
P
PPt
13.02402 3.8
10
where T is working temperature at rated fundamental power, Pf,, Pk is the total power and T is the rated life-time in years
Effect of additional losses on life-time
![Page 26: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/26.jpg)
15-May-02 26
Harmonic cultureTHD and K-factor (30 min. average)
0
10
20
30
40
50
60
22/1
0/01
20:
30
23/1
0/01
2:0
0
23/1
0/01
7:3
0
23/1
0/01
13:
00
23/1
0/01
18:
30
24/1
0/01
0:0
0
24/1
0/01
5:3
0
24/1
0/01
11:0
0
24/1
0/01
16:
30
24/1
0/01
22:
00
25/1
0/01
3:3
0
25/1
0/01
9:0
0
25/1
0/01
14:
30
25/1
0/01
20:
00
26/1
0/01
1:3
0
26/1
0/01
7:0
0
26/1
0/01
12:
30
26/1
0/01
18:
00
26/1
0/01
23:
30
27/1
0/01
5:0
0
27/1
0/01
10:
30
27/1
0/01
16:
00
27/1
0/01
21:
30
28/1
0/01
2:0
0
28/1
0/01
7:3
0
28/1
0/01
13:
00
28/1
0/01
18:
30
29/1
0/01
0:0
0
29/1
0/01
5:3
0
29/1
0/01
11:0
0
29/1
0/01
16:
30
V1 HD THD SD
I1 HD THD SD
I1 HD KF TD
![Page 27: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/27.jpg)
15-May-02 27
Economic evaluation
• 2 approaches to buy a transformer– Specify Po and Pk– Specify A & B factors
Ct = Purchase price + A * Po + B * PkCt = Purchase price + A * Po + B * Pk
8760)1(
1)1(
C kWhn
n
ii
iA
2
8760)1(
1)1(
r
lkWhn
n
I
I
ii
iB C
With I = interest rate 7%n = lifetime 30 yrsCkWh = cost / KWh 0.05 cIl/Ir = loading 50%
![Page 28: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/28.jpg)
15-May-02 28
Example
• 1600 KVA, 50% load, oil-cooled:• (A = 5.4 euro / Watt; B = 1.3 euro / Watt)
– Efficiency AA’ CC’– Purchase 9,700 € 10,300 €– Load loss 22,100 € 18,200 €
(1.3 * 17,000) (1.3 * 14,000)– No load loss 14,040 € 9,180 €
(5.4 * 2,600) (5.4 * 1,700)– Total 45,840 € 37,680 €
![Page 29: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/29.jpg)
15-May-02 29
A and B values for selected countries
Euro / Watt A (NLL) B (LL)Netherlands 4.0 1.2Germany (86) 4.0 1.0Germany (93) 11.3 4.0CH 7.5 1.9China 5.0 0.7Sweden 4.0 0.5
![Page 30: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/30.jpg)
15-May-02 30
0
5,000
10,000
15,000
20,000
25,000
30,000
35,000
A-A' A-A' C-C' C-C' A-AMDT C-AMDT
Design
To
tal
ow
nin
g c
os
t
Total owning cost NL Total owning cost D 86 Total owning cost D 93
Total owning cost China Total owning cost CH Total running cost Sweden
Investment costs
Lifetime owning cost400 kVA oil-cooled
![Page 31: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/31.jpg)
15-May-02 31
Beyond the magic of A & B
A factor
0,00
2,00
4,00
6,00
8,00
10,00
12,00
14,00
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
jaren
A f
ac
tor
(eu
ro/W
) b
ij e
lek
tric
ite
its
tari
ef
= 1
00
Eu
ro/M
Wh
3% 4% 5% 6% 7% 8% 9% 10% 11% 12%
6,75
Rentepercentage
![Page 32: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/32.jpg)
15-May-02 32
Example - revisited
• 1600 KVA, 50% load, oil-cooled:– Efficiency AA’ CC’– Purchase 9,700 € 10,300 €– Load loss 1,850 € / yr 1,533 € / yr– No load loss 1,140 € / yr 745 € / yr– Result
• Payback 10 months• IRR 119% @ 30 years
![Page 33: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/33.jpg)
15-May-02 33
Ecological evaluation
• 1600 KVA, 50% load, oil-cooled:– Efficiency AA’ CC’– Energy 210 GWh 210 GWh
transformed– No load loss 684 MWh 447 MWh– Load loss 1,110 MWh 921 MWh– Emissions 718 tonnes 547 tonnes– Emission savings 171
tonnes
![Page 34: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/34.jpg)
15-May-02 34
Soft benefits
• Save energy
• Save emissions
• Noise?
• Reduced heating
• Improved lifetime
• Reliability?
• More robust against harmonics
![Page 35: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/35.jpg)
15-May-02 35
What’s the catch?
• Increased capital outlay
• Commercial policy of suppliers
• Small amounts
• Risk of being a pioneer
![Page 36: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/36.jpg)
15-May-02 36
Energy & emission savings potentials related to transformers & standby power
Region Energy savingsTWh / yr
CO2 SavingsMillion tonne / yr
Source
EU 22 9 THERMIE
C&EE 5 5 ECI
US 45 34China 47 52 IIEC
Japan 24 Toprunner
Total 143 100
![Page 37: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/37.jpg)
15-May-02 37
More information
• www.efficient-transformers.org– electronic library– calculation tools
• K-Factor & Factor K• Investment evaluation spreadsheet
• www.supertrafo.com– daily, on-line measurement of energy saving for 4
high efficiency transformers installed in Poland
![Page 38: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/38.jpg)
15-May-02 38
![Page 39: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/39.jpg)
15-May-02 39
![Page 40: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/40.jpg)
15-May-02 40
Super-trafo demonstration
![Page 41: Energy Saving Opportunities for Transformers Hans De Keulenaer Outokumpu Tara Mines Energy Efficient Motors & Transformers Workshop May 7, 2002](https://reader036.vdocuments.mx/reader036/viewer/2022062314/56649d955503460f94a7e782/html5/thumbnails/41.jpg)
15-May-02 41
Conclusions
• Evaluate transformers for lifetime cost– oil-cooled
• Buy only CC’ or higher• Evaluate transformer with 15-20% less loss than CC´
– dry-type• if you need the advantages• evaluate transformer with 15% less loss than HD538
• Check harmonic culture
• Consider replacement of veteran transformers