Building and Environment, Vol. 18, No. 3, pp. 99-107, 1983 0360-1323/83 $3.00+0.00 Printed in Great Britain © 1983 Pergamon Pre~ Ltd

Energy in Context: A Multicriteria Model for Building Design

JOHN S. GERO* NEVILLE D'CRUZ*t ANTONY D. RADFORD*

A model is proposed far the representation and comparison of design alternatives which puts eneroy e.Oiciency in a context of performances in other criteria. The model utilizes notions of decision and performance spaces and multicriteria Pareto optimization. A simple example is described.

1. ENERGY AND BUILDING

UNTIL the mid-1970s energy use was not a criterion of great importance in building design. Abundant low-cost sources of energy led to buildings which were totally dependent on mechanical systems for heating, cooling and ventilation. In consequence, energy requirements of buildings grew steadily year by year until it accounted for 23.5% of the energy used in Australia [1] and for over 40% in the United States [2]. The so-called 'energy crisis' has led to a much greater concern by building owners about the energy performance of building proposals and to the introduction of regulatory codes requiring minimum standards of energy-conservative design, usually by restricting the freedom of designers in choosing values for wall and roof insulation and glass proportions (for example, part FF of the England and Wales building regulations). At the same time, the availability of digital computers has made possible new methods of modelling heat flow and energy demand and the development of computer simulation programs which can provide more accurate predictions of the operational energy demand of a building design proposal than was previously possible. By repeating this simulation process the energy performances of alternative proposals can be compared. However, this new importance of energy demand as a criterion in building design is additional to and not replacing any pre- existing design criteria. Architects cannot design a building for energy efficiency alone; indeed, the most energy efficient solution is no building. The purpose of this paper is to put forward a model for the representation and comparison of design alternatives which places energy efficiency in a context of performances in other criteria. The uses of energy in building are for heating and cooling, lighting, transportation (lifts and escalators) and the operation of equipment related to the building's occupancy and function. Building design can influence all but the last of these uses, but in this paper we shall restrict the discussion to thermal performance.

*Computer Applications Research Unit, Department of Architectural Science, University of Sydney, N.S.W. 2006, Australia.

t" On leave from Western Australian Institute of Technology, Bentley W.A., Australia.

The thermal performance of a building is dependent on the micro-meteorological conditions outside the building, the thermal behaviour of the building fabric and the comfort conditions required inside. The meteorological climate can be measured and to some extent predicted. Some measure of coarse control can be exercised in moderating its influence, for example, by planting and judicious choice of site. The prime factor, though, is the thermal behaviour of the building itself. The design variables that determine this thermal behaviour (for example shape, massing, enclosing materials and surface finishes) also influence performance in other criteria. Thus, in aiming to improve thermal performance an architect must consider the implications for other quantitative criteria such as capital cost and the usable area of the building, quite apart from his proper concern with qualitative aesthetic and social criteria.

2. DESIGN AND PERFORMANCE RELATIONSHIPS

The goal of design in architecture is, then, to achieve the best balance of performances in a complete set of applicable criteria. To achieve this goal the designer needs information on the relationships between the design variables he can manipulate and the performances he seeks. Most existing computer models explore one directed aspect of this relationship: given a set of design variables they will predict by simulation their performance consequences. We can call this the design --~ performance relationship. Designers also need to know something about performance - , design relationships (otherwise there is no starting point for design), and ideally learn something about performance --, performance and design --* design relationships as well.

2.1. Design ~ performance For thermal design there is now a considerable number

of computer simulation programs available. Some, such as DEROB [3] and ESP [4], require quite detailed descriptions of the building proposal and therefore cannot be used at the early stage of design unless numerous default assumptions are made. Others, such as those used in PACE [5] and SPEED [61 operate with simpler models

B~ 18:3-A 99

Page 2: Energy in context: A multicriteria model for building design

100 d. S. Gero et al.

requiring much less input data and are aimed at providing indicative measures before the design has been fully worked out. PACE (Package for Architectural Computer Evaluation) originated in the late 1960s and even at that early stage responded to the multicriteria nature of building design by predicting the cost (capital and maintenance), spatial (plan and mass compactness), and activity (closeness of related departments of other functional components) performances of a design proposal as well as its environmental performance [5].

2.2 Performance --, design By repeating the simulation process with different values

for the design variables, some indication of the best forms of design for desired performance can be inferred. In this way Oughton [7] showed how the energy consumption of a building is influenced by building form, orientation and envelope construction. Through the concept of thermally equivalent walls, Arumi [8] has shown the appropriate- ness of size of insulation for different climates. This performance ~ design relationship is also directly in- vestigated by optimization formulations of the energy of thermalload problem, such as those by Gupta and Spencer [9], who minimize 'degree of discomfort' according to an objective function defined by Gupta [10]; Wilson and Templeman [ 11 ], who minimize the combined capital and operating costs of the heating plant and insulation; and Jurovics and Low [12] who minimize combined heating, lighting and cooling loads. There are many other examples in the literature. Almost all such optimization studies consider one criterion in isolation ; in parallel with these studies of thermal performance, other researchers have been working on performance --* design relationships for capital cost (e.g. Aguilar [ 13]) and planning efficiency (e.g. Eastman [14]).

2.3. Performance ~ performance By performance ~ performance relationships we mean

the implications of choosing a certain level of performance in one criterion on the performances that are then attainable in other criteria. The functional requirements of buildings and their components are often conflicting: at the whole building level the twin goals of maximizing area and minimizing cost frequently operate in conflict, and at the building component level a good example is provided by the twin goals of maximizing sound insulation (which is roughly proportional to mass) and minimizing mass for a partition. There is little published work exploring these conflicts and the tradeoffs necessary for their resolution in any explicit manner. Mattar et al. [15, 16] assess five performance characteristics for external walls (fire resistance rating, risk of condensation, thermal resistance, sound transmission and initial cost) and approach the performance tradeoff problem by articulating simple and partially-ordered preferences between the performance characteristics. Work at Sydney University (Radford and Gero [17, 18] ; Gero and Radford [19] ; Gero et al. [20]) has explored a more direct representation of tradeoffs through the presentation of Pareto-optimal sets of performances (see below) and developed a means through inverse goal programming (Gero et al. [20]) for choosing a 'best compromise' set of preferences between the performances.

2.4. Design ~ design By design ~ design relationships we mean the

implications of choosing a certain value for one design variable on the values that need to be given to other design variables if acceptable performance is to be maintained. Radford and Gero [18] derive 'environmental tradeoff diagrams' for daylighting and peak summer temperature in a room in a building, given a specific external environment and orientation. The diagrams show Pareto- optimal values (see below) for these performance measures and the associated values for a small set of design variables (glass type, wall type, window size and sun shade projection). By superimposing tradeoff diagrams with different restrictions on the design variables it is possible to trace design ~ design relationships. For example, the diagrams show how glass type and window size must be adjusted to keep peak summer temperature constant with least detriment to daylighting if sunshades are removed from a particular design proposal.

3. DECISION AND PERFORMANCE SPACES AND PARETO-OPTIMALITY

Before describing the formulation of a multicriteria model to explore the trade-offs between building thermal performance and other criteria, we shall briefly describe the notions of decision and performance spaces and Pareto-optimization which lie behind the work described in Sections 2.3 and 2.4 above.

In searching for a suitable design solution it is possible to delineate three representational aspects which may be used as vehicles in the description of decision making processes. These are: the decision space, the criteria space and the constraint set.

(i) The decision (or solution) space contains the description of all solutions. A design solution to a problem with N decision variables can be uniquely represented as a point in N-dimensional space.

(ii) The criteria (or performance) space contains the description of all performances. The performance of a solution to a problem with M criteria can be represented as a point in M-dimensional space.

(iii) The constraint set contains the description of all restrictions which limit the range of decisions or performances.

Each point in the decision space has associated with it a point in the performance space and vice versa. The constraint set defines feasible regions in these spaces: constraints on decision, for example, have an explicit effect on the feasible region in the decision space and an implicit effect (through the decision/performance relationships) on the feasible region in the criteria space. In this model, the design problem can be described quite simply as the identification of the'best feasible point' in the performance space and the corresponding point in the decision space. However, finding this 'best feasible point' is not always easy.

Taken alone, the performance space gives no clear indication of which solution is to be preferred: if we adopt the convention that increasing distance from the origin corresponds to increasing desirability then in Fig. 1, A is better than B in criterion 1 and B is better than A in criterion 2. Consider, though, the third solution C.

Page 3: Energy in context: A multicriteria model for building design

Energy in Context: A Multicriteria Model for Buildinff Design 101

(1 ) (2)

d. I / cl I / / I

I A+¢ /

" J I

decision space d2 cr i ter ia space c2b

Fig. 1. Decision and criteria spaces for two decision variables dt and d 2 and two criteria cl and c2, with constraints on (1) a decision variable and (2) combination of decision variables.

Solution A offers better performance in both criteria 1 and 2 than does C and we can therefore state that C is dominated by A. If we identify the set of all solutions that are not dominated by any other solutions in both criteria we find that their performances lie along a boundary of the performance space. They are known formally as the set of non-dominated, non-inferior or Pareto-optimal solutions (Fig. 2). Extending this concept to the general case of M criteria, a feasible solution to a multicriteria design problem is Pareto-optimal if there exists no other feasible solution which is better in at least one criterion and no worse in the others. For two criteria the Pareto set traces a curve along the edge of the criteria space. Higher dimensions are difficult to visualize but for M criteria the Pareto set will form a surface in M-dimensionai space. For one criterion, on the other hand, the criteria space reduces to a vector and the Pareto set reduces to a point--the optimal solution in traditional single criterion optimization.

4. A MULTICRITERIA MODEL OF THERMAL PERFORMANCE, CAPITAL COST AND

USEABLE AREA

The purpose of this model is to provide designers with prescriptive information on the relationships between thermal performance, capital cost and useable area for a building proposal before the building form is finalized. This is achieved by simultaneously considering the effect on these three criteria of systematic changes to the design variables. Initially, the form of buildings considered is rectangular parallelopiped shells with similar construc- tional properties throughout. The shape and massing of the building are varied through the aspect ratio (ratio of north to east walls) and the number of storeys. Orientation ofthe building (relationship of north facade to north), glass fractions and glass type complete the design variables~

The performance prediction models required are those that reflect the skeletal information available at the early

c 1

- ~ Pare to opt imal values

\ /

i- ©riterie specs ¢2

Fig. 2. The Pareto-optimal set for two criteria.

stage of design while being responsive to the options available. For example, for thermal performance it is appropriate to calculate the building thermal load rather than its energy use, as the latter requires knowledge oftbe mechanical system characteristics. In this section we describe the selected thermal, cost and usable area models.

4.1. The thermal model The thermal load within a building envelope is a result of:

(a) variation in climatic data such as outside air temperature and solar radiation;

(b) the heat gain/loss due to the thermal characteristics of the building envelope construction;

(c) the required inside conditions; and (d) the internal heat gain, which is not considered at

present.

4.1.1. Prediction method. Long-range values of outside air temperature for most locations follow a sinusoidai pattern. From tabulated data (Bureau of Meteorology [21]) an average pattern can be constructed for tem- perature variations over a design day in each month for a particular location. The intensity of direct solar radiation on all surfaces for the design day can be calculated by a formula which assumes sky conditions and an attenuated solar constant intensity. From these, the sol-air tem- perature on each exposed surface is calculated.

Building elements neither heat up nor cool down instantaneously and thus have some thermal inertia associated with them. This results in an attenuation and a time delay between cause and effect. When thermal inertia is considered the calculation is said to be dynamic. When thermal inertia is ignored the calculations are known as the static approximation [8]. Since the construction properties are not varied in this exercise, the static solution is used. The purpose here is to establish the relative thermal performance for different configurations of building rather than to predict individual performances with the greatest possible accuracy. Air infiltration is calculated by the air change method, assuming a fixed number of air changes occurring per hour in the space. The inside air temperature is assumed to be controlled by a thermostat setting which varies for cooling and heating periods and has temperature setbacks during periods of non-occupancy.

4.1.2. Thermal load ratios. March and Martin [22] have shown that for a simple rectangular block of given volume the built form which will minimize heat losses is one whose thermal image is a cube, i.e. the relationship of the sides is in

Page 4: Energy in context: A multicriteria model for building design

102 J. S. Gero et al.

the proportion of the average thermal transmittance of the opposite faces. Notationally this is

x l : x2: x3: ul : u2: ua

where x I is the length of building (m); x2, width of building (m); xs, height of building (m); ul, average thermal transmittance of surfaces along the length (W/m 2 K); u 2, similar for width (W/m 2 K); u s, average thermal transmittance of roof and floor (W/m 2 K).

For a given volume and thermal transmittance this 'optimum' building size can be determined, and hence the 'optimum' cooling, heating and total thermal load this will generate can also be determined. This can be used as a standard for comparing other building configurations. The calculated cooling, heating and total thermal loads are divided by the 'optimum' loads to yield thermal load ratios. These ratios, rather than the raw load figures, are used here as the criteria of thermal performance.

4.2. The capital cost model All cost models are fundamentally based on an analysis

of constructed buildings to establish an appropriate rate for a particular type of building (Ferry [23]). This base cost is adjusted to account for market conditions that affect current price levels. For this work, with thermal load the prime consideration, a cost model is required that reflects variations in shape, massing, window configurations, constructional properties and surface finishes. The technique currently used is the storey enclosure method [23]. The areas of the various floors are calculated and weighted by a factor of 2.0 for the ground floor, 2.15 for the first floor, 2.30 for the second floor, adding a factor of 0.15 for each additional floor above the ground floor. The weighted areas are summed and to this is added the area of the projection of the roof and the external walls. This total is the number of storey enclosure units in the building.

The cost of a constructed building divided by its storey enclosure units yields the cost per storey enclosure unit. The estimated cost of any other configuration of similar building type is then the product of its storey enclosure units multiplied by the cost per enclosure unit. To this cost is added the cost of staircases and mechanical services such as lifts. The total cost divided by the gross floor area is the cost per square metre of the building.

The number and size of staircases were calculated according to the requirements of the New South Wales, Australia, building regulations (N.S.W. Government [24]). The required number of lifts is predicted by a statistical model derived by Marmot and Gero [25]. The cost of these items were priced from Cordell's Building Cost Book [26].

4.3. The usable area model The net usable area is calculated as a measure of utility of

the building configuration. In this case, the net usable area is calculated to be the area inside the external walls less the area taken by services (lifts and staircases), with an allowance for circulation and toilet facilities. These allowances are as follows :

Circulation Ground floor 10% of net area Upper floors 5% of net area

Toilets, etc. 5% of net area per floor

Staircases

Lifts

Based on the requirements of fire exits in New South Wales building regulations Based on the statistical model of Marmot and Gero.

5. CASE STUDY: A BUILDING IN SYDNEY, AUSTRALIA

The case study considers a parallelopided building in Sydney, Australia. The base data is :

Building volume 4000 m 2 Minimum area per floor 800 m 2 Storey height 2.7 m Thermostat settings: Heating 20°C

Cooling 25°C.

The design variables with their range of values are :

Aspect ratio 1, 2 or 3 Orientation 0 °, 30 ° or 60 ° Massing (number of storeys) 1, 2, 3, 4 or 5 Glazing fractions on each facade 0.4, 0.5 or 0.6 Glazing type (single pane) Clear, heat reflecting

or heat absorbing Shading None.

Making 405 possible design solutions. Rather than plot their performances in thermal load, capital cost and usable area directly in a three-dimensional criteria space we have plotted the projections of this space on its constituent two- dimensional faces.

5.1. The solution space Figure 3 shows the complete set of performances. They

group themselves into five bands, within which solutions have very similar capital cost and very similar usable area but widely differing thermal load ratios.

The prime purpose of this study is to examine the relationships between thermal load and these other criteria of cost and usable area. However, no clear pattern emerges. What we can say is that the range of values of thermal load ratio is smallest for single storey solutions and increases as the height of the building increases. What is clear, however, is that the design decisions have very much more proportional effect on the thermal load than on either capital cost or usable area. The lowest capital cost is about A$720/m 2, the highest is A$770/m 2, an improvement of about 6%. The highest usable area is 84%, the lowest is 74.6%, an improvement of about 13%. For thermal load, the lowest performance is a thermal load ratio of 1.2 while the highest is 6.7, representing an improvement of lowest over highest of about 80%. Although if we assess all these criteria in cost-benefit terms the potential variations in capital cost and usable area may be as important, or even more so, than those in thermal load, it is clearly worthwhile designing to minimize that load. This is especially so because Figs 3(a) and (b) show that there is little conflict between designing for minimum thermal load and either designing for minimum capital cost or designing for maximum usable area.

When we plot usable area against capital cost (Fig. 3c) each band collapses into groups of just three points. Tracing back to the design solutions we find that each group corresponds to a number of storeys and each point within a group corresponds to one of the three values of

Page 5: Energy in context: A multicriteria model for building design

Energy in Context: A Multicriteria Model for Building Design 103

(a)

(b)

g

o -

8.

L g

• , % . . ' * . , . . , ~ . , . , , , . - , - - -

• . % . , " , ~ , I L , ' ; , , A J u ~ • • a •

• , ~ , , , ' , , . . . - ' . . . ' , . . ~

• . " , , , - . . . . ~ . . . ' . . - -

i %'.0~ ' , t ~ o ' 6lAD' s [60 ' 4 [ * 0 ' 4 [00 ' ~'.~0' ~'.40' , [Ro ' 0 [ ~ ' - ; . c ,

TOTAL LOAD ( R A T I O ) SYDNEY

o

o-

"<' o -

• t t ~ t , d k ~ a l l t

• : ~ " . : - . ' - : : . : . : , , ~

~ . i ) ) '. ' '. ' '. ' '. ' '. ' '. . . . . o ' . , o ' - o . o o 0 O0 ~' 20 6 40 $ 6 0 4 6 0 4 O0 3 2 0 2 . 4 0 t . 6 0

TOTAL LOAD I R A T I O ) STONEY

o

4.. w

o -

o-

o -

o- =o-

o - ,,:,

o.

o -

o -

(el

A M M

A 8

. . A

) l i ) r J I [ r ) l ) w l I r ) l ~ i 4 . 0 0 | 4 8 . 0 0 0 3 2 . 0 0 | ) 6 . 0 0 i O 0 . O 0 7 8 4 . 0 0 T O i . O0 7 5 2 . 0 0 7 3 6 . 0 0 7 2 0 , 0 0 7 0 4 . 0 0

C A P I T A L CO$T (S PER SO M) SYDNEY

Fig. 3. The complete set of capital cost, total load ratio and useable area performances for the case study building.

aspect ratio. This collapse of the bands into points is, of course, a result of the prediction models used, which do not relate capital cost to glazing fraction or type. A more detailed cost model would spread these points into a neighbourhood. Single storey solutions are most expensive but offer the largest usable area. Three storey solutions are cheapest while in between in order of increasing cost are the two-, four- and five-storey solutions, the relatively high cost of the latter two being due to the additional cost for lifts required in these solutions. For usable area, the lower the building the better since increasing the number of floors means increasing the area devoted to stairs and lifts.

5.2. Desion --+ performance and performance performance The relative lack of conflict between thermal load and

the other criteria is demonstrated if we carry out a Pareto- optimization over the three criteria. Of the 405 original

solutions only 5 prove to be Pareto-optimal (Fig. 4) and these span a very small part of the total load ratio axis. Table 1 details the values of the design variables and criteria for these Pareto-optimal solutions.

The design --* performance relationships are apparent from the table. All five solutions are oriented due north with a window fraction of 0.4 and a heat reflecting glass type. The only differentiation is in aspect ratio (which in fact has very little effect) and massing. Single-storey is best for usable area, thr~-storey best for capital cost and thermal load. Four- and five-storey solutions are dominated out in the Pareto-optimization. Performance - ,performance relationships are apparent from the graphs. From Figs 4(a) and (b), the total load varies little whatever the decisions about usable area and cost, as long as the choice of design is restrictexi to the Pareto set. From Fig. 4(c), improving usable area ratio means increasing cost. The two-storey solutions (Nos 2 and 3) appear to be a reasonable compromise.

Page 6: Energy in context: A multicriteria model for building design

104 J. S. Gero et al.

(a)

( b )

o -

8-

oo_

~ : o o _

u _ _

g ,

g-

g~

. 4

2. '5 3"

,1

~ ) i i i T ) l l l i ] ) [ $ s i l F I T ) | . 0 0 7 . 2 0 S . 4 0 3 . S 0 4 . 1 0 4 . 0 0 3 . 2 0 2 . 4 0 I . $ 0 0 . 1 0 - 0 . 0 0

TOTAL LOkD (RATIO) S'/ONEY

o

u

g- Q -

~ 2 ¢

o- 3

-~- 4 t

~- 5

~o

i ) , i i i u O0 L 2 0 * . 4 0 3 , $ 0 41. I 0 , 41.00 ' 31.20 ' 21.40 " 11.60 ' O" , iO ' - 0 , 0 0

TOI IL LOAD (RATIO) S¥ON[¥

<

.

..2 3

4 5

1;0 I~1 ) ) ' ' ' ' ' ' ' ~ ~ ' ' r ) , ~ - I 4 I O0 |3;~ O0 0 1 S O0 100 O0 ?14 O0 ? S g O0 ?S2 O0 ; '35 O0 Z20 .O0 ~ '04 ,00 C A P I T A L COST ( | P [ ! SO M)

S';ON('r

(c) Fig. 4. The Pareto set of performances for the case study building.

Table 1. Pareto-optimal solutions (best; orientation 0 °, 30 ° or 60 °, glass fraction 0.4, 0.5 or 0.6)

Design variables Criteria

Number Solution Orien- Window Glass Aspect of Capital number tation fraction type ratio storeys cost (A$/m z)

Useable Total thermal area (%) load (ratio)

1 0 0.4 2 1 1 830.3 84.15 1.77 2 0 0.4 2 1 2 733.6 81.38 1.25 3 0 0.4 2 2 2 735.6 81.30 1.25 4 0 0.4 2 1 3 720.4 79.48 1.16 5 0 0.4 2 2 3 722.8 79.38 1.15

Before we try different values for the design variables, it is worthwhile inverting the Pareto-optimizat ion to find the very worst (instead of the best) solutions (Table 2). The configurations with the worst overall performance are those with the largest aspect ratio, oriented the maximum away from north, with clear glass windows of maximum size on all facades. The massing of the two buildings is very

different, however, one being square and elongated while the other is narrow and high.

5.3. Design --. design To investigate design ~ design relationships we extend

the range of values for the design variables, exploring orientations close to north and glazing fractions less than

Page 7: Energy in context: A multicriteria model for building design

Eneroy in Context: A Multicriteria Model for Buildin9 Desion 105

Table 2. Pareto-optimal solutions (worst; orientation 0 °, 30 ° or 60 °, glass fraction 0.4, 0.5 or 0.6)

Design variables Criteria

Number Solution Orien- Window Glass Aspect of Capital Useable Total thermal number tation fraction type ratio storeys cost (A$/m 2) area (%) load (ratio)

1 60 0.6 1 3 1 833.9 84.01 4.15 2 60 0.6 1 3 5 770.0 74.79 6.71

previously allowed, and remove some values which do not appear to be useful. The design variables with their range of values are now :

Aspect ratio 1, 2 or 3 Orientation 0 °, 5 ° or 10 ° Massing (number of storeys) 1, 2, 3, 4 or 5 Glazing fractions on each facade 0.2, 0.3 or 0.4 Glazing type (single pane) Clear, heat reflecting

or heat absorbing Shading None.

We find that Pareto-optimization with this new set of values produces a new set of Pareto-optimal performances. Looking first at design ~ performance relationships (Table 3), we find that the Pareto set includes at least one solution from each of the five storey groups. All have heat reflecting glass and the minimum window fraction.

All but two have an orientation of 5 ° east of north with aspect ratio of one; the two odd ones out have an orientation due north and aspect ratios of two. Looking at the performances, we see that these two are part of the Pareto set because of their marginally better thermal performance than the alternative solutions with the same massing. Amongst this Pareto set, then, the only design variable that varies significantly is massing. Broadly, the taller and thinner the building, the better the thermal performance, but not in a linear relationship.

Turning again to the performance--+ performance relationships (Fig. 5), we find that the four- and five-storey solutions (solutions 4-7) would be dominated if we only considered usable area and capital cost, but have a slight edge in total load ratio over the three storey solution. This slight edge is probably not enough to justify their selection. The performance tradeoff choice, then, is between high usable area but high cost and good (amongst the Pareto set) thermal load ratio (solution 1), low cost and low thermal load ratio but significantly worse usable area (solution 3), or a compromise between the two (solution 2).

For design --, design relationships we need to compare Figs 4 and 5. If we discount, as suggested above, solutions 4-7 of Fig. 5 the two graphs are remarkably similar. What this means in design terms is that we have design freedom in orientation between 5 ° east and due north (possibly more if we investigated further), and between window fractions of 0.2 and 0.4, without needing to take compensating action with other design variables.

6. DISCUSSION

We have shown that it is possible to treat the objective of energy conservative design within the context of overall building design through the use of a multicriteria model based on Pareto optimality. The simple example used demonstrates the practicality of generating a set of relationships not normally available to designers. The relationships have the potential to provide both qualitative and quantitative information about the tradeoffs between disparate performances. This infor- mation would not otherwise be available to the designer. Obviously, a more detailed example would provide a fuller set of results. Such an example would probably make use of the available, more sophisticated, optimization techniques.

In general, the characteristics of the Pareto-optimal set produce a range of qualitative information and the performance ~ design relationships [19]. Furthermore, if the Pareto-optimal set is heavily convex then there is a rational basis for developing a 'rule of thumb'.

Acknowledgements--Support for this work was provided under the National Energy Research, Development and Demonstration Program which is administered by the Commonwealth Department of National Development and Energy, and by a continuing grant from the Australian Research Grants Scheme.

Table 3. Pareto-optimal solutions (orientation 0 °, 5 ° or 10 °, glass fraction 0.2, 0.3 or 0.4)

Design variables Criteria

Number Solution Orien- Window Glass Aspect of Capital number tation fraction type ratio storeys cost (A$/m 2)

Useable Total thermal area (%) load (ratio)

1 5 0.2 2 1 2 5 0.2 2 1 3 5 0.2 2 1 4 5 0.2 2 1 5 0 0.2 2 2 6 5 0.2 2 1 7 0 0.2 2 2

1 830.3 84.15 1.60 2 733.6 81.38 1.00 3 720.4 79.48 0.84 4 744.8 75.52 0.79 4 747.6 75.52 0.79 5 762.1 74.69 0.78 5 765.2 74.69 0.77

Page 8: Energy in context: A multicriteria model for building design

106 d. S. Gero et al.

(a)

( b )

o -

o

o

o -

= -

o -

o -

o -

~- ~ -

N-

.3

.2 .4 "5

6. 7"

.1

o o ' ,~2o' s140' 51=o' ,~=o' ,~00' £zo' ~,o' ,I~o' o i . o ' - L 0 o TOTAL LOAO ( N A T I O ) SYONET

.2

.3

o

o -

o -

.1

.2

.3

o- ~" 5 4 ~- 5 . 4 ~- .. ° 7 6 o- 7 , 6

~ , i i r w r i w r i r ~ i i r ~ i ~ ' l " - - - W - ' r - " T i i , i i i i i 1 i i ~ ~ i i ~ ~ f J . O 0 ~ r . 2 0 6 . 4 0 5 . 6 0 4 . 8 0 4 . 0 0 ~ 5 . 2 0 2 . 4 0 1 . 6 0 0 . | 0 - 0 . 0 0 0 6 4 . 0 0 0 4 0 . 0 0 I ; 3 2 . 0 0 0 1 6 . 0 0 | 0 0 . 0 0 7 1 t 4 . 0 0 7 6 1 1 . 0 0 1 5 2 . 0 0 7 3 6 . 0 0 ; ' 2 0 : 0 0 7 0 ' ; . 0 0

TOTAL LOAD ( R A T I O ) $ ' t D N E T C A P I T A L COST ( l PER SO MI STDNEY

(c) Fig. 5. The Pareto set of performances for the case study building with a modified range for orientation and

glass fraction values.

REFERENCES

1. NEAC, National Energy Advisory Committee Report No. 13, Energy Conservation in Buildinos, Australian Government Publishing Service, Canberra (1981).

2. R.G. Stein, Architecture and Eneroy. Anchor Press, New York (1977). 3. F. Arunfi, DEROB III; User's Manual for the DEROB System. School of Architecture, University of

Texas, Austin (1979). 4. J. Clark, Environmental system performance. Ph.D. thesis, University of Strathclyde, Glasgow (1977). 5. T.W. Mayer, PACE 1 : computer aided building appraisal, Architects JI, 28.6.1971, 207-214 (1971). 6. A.J. Baxter, Computer aided sketch plan design. Heating & Ventil. Engr March, 6-11 (1979). 7. D.R. Oughton, Predicted energy consumption for air conditioning systems related to the building

envelope and form. Bldg Services Engng Res. & Tech. 1, 189-198 (1980). 8. F. Arumi, Passive energy systems. Class Notes, School of Architecture, University of Texas, Austin

(1981). 9. C.L. Gupta and J. W. Spencer, Building design for optimal thermal performance. Austral. Refrio., Air

Condition. and Heating 24, 18-25 (1970). 10. C.L. Gupta, A systematic approach to optimal thermal design. Bldg Sci. 5, 165 (1970). 11. A.J. Wilson and A. B. Templeman, An approach to the optimal thermal design of office buildings. Bldg

Envir. 11, 39-50 (1976). 12. S.A. Jurovics and D. W. Low, Optimizing the passive solar characteristics of buildings. Working paper

(unpublished), IBM Los Angeles Scientific Center, Los Angeles (1978).

Page 9: Energy in context: A multicriteria model for building design

Energy in Context : A Multicriteria Model for Building Design 107

13. R.J. Agnilar, Systems Analysis and Design in Engineering, Architecture, Construction and Planning. Prentk~-Hall, Englewood Cliffs (1973).

14. C.M. Eastman, Spatial Synthesis in Computer-Aided Building Design. John Wiley, New York (1975). 15. W. Mattar, W. Bitterlich, P. Manning and P. Fazio, A decision model for the design of building

enclosures. Bidg Envir. 13, 201-216 (1978). 16. S. Mattar, P. Manning, P. Fazio and W. Bitterlich, Application of the decision by exclusion rule: the

design of external walls. Bidg Envir. 13, 217-232 (1978). 17. A.D. Radford and J. S. Gero, On opfimiTation in computer aided architectural design. Bldg Envir. 15, 73-

8O. 18. A.D. Radford and J. S. Gero, Tradeoffdiagrams for the integrated design of the physical environment in

buildings. Bldg Envir. 15, 3-15 (1980). 19. J. S~ Gcr~ and A~ D. Radford~ The p~ac~ of mu~ti~riteria ~ p ~ t i o n in design~ Pr~ceedings ~f the Design

Policy Conference, London (1983). 20. J.S. Gcro, A. D. Radford and N. S. Murthy, What if? Exploring the consequences of design and

performance decisions in computer-aided design. CAD82 (A. Pipes, ed.). Butterworths, Guildford, pp. 633-646 (1982).

21. Bureau of Meteorology, Climatic Averages Australia, Australian Government Publishing Service, Canberra (1975).

22. L. March and L. Martin, Urban Space and Structures. Cambridge Univorsity Press, Cambridge (1972). 23. D.J. Ferry, Cost Planning of Buildings. Granada, Hcmol Hcmpstead (1980). 24. N.S.W. Government, Ordinance 70: Building. New South Wales Govornment Publishing Service,

Sydney (1972). 25. A. Marmot and J. S. Gero, Towards the development of an empirical model ofelevator lobbies. Bldg Sci.

9, 277-288. 26. Cordelrs Building Cost Book, New Construction, Vol. 11, No. 2, Cordell Cost Services, Sydney (1981).