Energy & Heat Transfer in Healthcare HVAC
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 1
Shawn Wilson, PE
TME, Inc.
![Page 2: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/2.jpg)
Agenda
• Why target HVAC Systems?
• Shifting the Paradigm
• Controls are the Key
• 4 Opportunities
– Chilled Water Pumping
– Cooling Tower Relief
– Air Handler Controls, Resets
– Air Terminal Controls, Troubleshooting
• Closing, Q&A
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 2
![Page 3: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/3.jpg)
Hospital HVAC
• Unique regulatory requirements for temperature and RH, airflow, and pressure relationships.
• Special applications (Surgery, Lab, Pharmacy, Sterile Processing etc…)
• Energy intensive facilities.
• Complex Systems, Complex Controls
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 3
![Page 4: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/4.jpg)
Hospital Operating Costs
60% 20%
10% 3% 7%
People
Supplies
Debt Service
Energy
Other
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 4
![Page 5: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/5.jpg)
Hospital Business Environment
• Higher Costs
• Lower Revenues
• Insufficient Margins for Reinvestment
• Mounting Backlog of Deferred Maintenance
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 5
![Page 6: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/6.jpg)
Hospital Energy Costs
Average $4.09/SF
![Page 7: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/7.jpg)
Hospital Operating and Maintenance Budgeting
27%
8%
14%
51%
Materials
Service Contracts
Staffing
Energy
Typical Hospital Operating and
Maintenance Budget ($7 to $12 per SF)
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 7
![Page 8: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/8.jpg)
• Reduced Operating Budgets
• Staffing Levels are already too Low
27%
8%
14%
51%
Materials
Service Contracts
Staffing
Energy
Hospital Operating and Maintenance Budgeting
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 8
![Page 9: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/9.jpg)
• Reduced Operating Budgets
• Staffing Levels are already too Low
• Higher Material Costs 27%
8%
14%
51%
Materials
Service Contracts
Staffing
Energy
Hospital Operating and Maintenance Budgeting
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 9
![Page 10: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/10.jpg)
• Reduced Operating Budgets
• Staffing Levels are already too Low
• Higher Material Costs
• Higher Service Contract Costs
27%
8%
14%
51%
Materials
Service Contracts
Staffing
Energy
Hospital Operating and Maintenance Budgeting
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 10
![Page 11: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/11.jpg)
• Reduced Operating Budgets
• Staffing Levels are already too Low
• Higher Material Costs
• Higher Service Contract Costs
• Energy Costs must be Reduced
27%
8%
14%
51%
Materials
Service Contracts
Staffing
Energy
Hospital Operating and Maintenance Budgeting
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 11
![Page 12: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/12.jpg)
Energy Use In Hospitals
HAAHE/TAFHM Facility Manager Basic Training 12 12/5/2013
![Page 13: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/13.jpg)
Agenda
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 13
• Why target HVAC Systems?
• Shifting the Paradigm
• Controls are the Key
• 4 Opportunities
– Chilled Water Pumping
– Cooling Tower Relief
– Air Handler Controls, Resets
– Air Terminal Controls, Troubleshooting
• Closing, Q&A
![Page 14: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/14.jpg)
Current Paradigm
• Selecting Systems and Equipment based on First Cost
• Using the Same Design for Every Project
• Conservative Over-Sizing of Equipment
• Selecting Systems and Equipment without Considering Current and Future Utility Rates
• Control Systems Designed by Control System Manufacturers (not the Engineer)
• Commissioning included but often becomes construction phase QC and documentation exercise.
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 14
![Page 15: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/15.jpg)
Current Best Practices Don’t Always Yield High Performance
• LEED
• Efficient Design
• Standard Commissioning
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 15
![Page 16: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/16.jpg)
LEED Certification
• LEED Buildings are no more Energy Efficient than their Peers
• More than half of LEED Buildings not eligible for Energy Star Label
• 15% of LEED Buildings have an Energy Star Rating less than 30
• LEED is not Bad…
Some Buildings not Living up to Green Label
By Mirya Navarro August 30, 2009
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 16
![Page 17: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/17.jpg)
Standard Commissioning
• LEED Certified Facilities have been Commissioned
• Many low Performing Hospitals were Commissioned
• Standard Commissioning is not bad…
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 17
![Page 18: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/18.jpg)
Potential Causes of Low Performance
• Energy Efficient Features are frequently “Value Engineered” out of the Project
• Systems are too complex for O&M Staff to Operate and Maintain
• “Drive By” Commissioning does Occur
• Facility Performance is not Measured and Verified
• Commissioning Agent Design Reviews are restricted to “Commissionability” Only
• O&M Staff have traditionally focused on Regulatory Compliance, Infection Rates, Comfort, and not Energy Efficiency
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 18
![Page 19: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/19.jpg)
Potential Causes of Low
Performance
• Control System Programming is not Consistent with the Design Intent
• Energy Management Systems are under Utilized
• Air Terminal Air Flow Setpoints are not Programmed in Correctly
• O&M Staff Training by Contractors does not Focus on Energy Conservation
• CxA is not Responsible for Building Performance
• O&M Staff are not Vested in a Positive Outcome
• Excess Simultaneous Heating and Cooling
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 19
![Page 20: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/20.jpg)
Shifting the Paradigm
Albert Einstein’s Definition of Insanity:
“Doing the same thing over and over again and expecting different results.”
12/5/201
3
HAAHE/TAFHM Facility Manager Basic Training 20
![Page 21: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/21.jpg)
ASHE’s Commissioning Guidelines and Handbook
• Meeting the Energy Efficiency Goals is not Optional
• Current Best Practices don’t always Work
• Causes of Low Performance are Known
• ASHE’s Commissioning Guidelines and Handbook focus on Meeting Facility and Project Energy Efficiency Goals
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 21
![Page 22: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/22.jpg)
New Paradigm
• Construction Costs and Operating Costs must be Considered Holistically
• Minimize Reheat
• Create Synergy between Systems that Remove and Generate BTUs
• Pay Attention to the Control Programming
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 22
![Page 23: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/23.jpg)
Setting the Energy Efficiency Goal
“If you aim at nothing, you’ll hit it every time.”
Zig Ziglar
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 23
![Page 24: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/24.jpg)
Benchmarking
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 24
• EPA “Target Finder”
• Weather Adjusted
• Occupancy Adjusted
• Free Service
• Internet Based
• Simplified Input
• Percentile Ranking
![Page 25: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/25.jpg)
Measurement and Verification
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 25
• Measuring on routine basis is critical.
• Review regularly.
![Page 26: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/26.jpg)
Agenda
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 26
• Why target HVAC Systems?
• Shifting the Paradigm
• Controls are the Key
• 4 Opportunities
– Chilled Water Pumping
– Cooling Tower Relief
– Air Handler Controls, Resets
– Air Terminal Controls, Troubleshooting
• Closing, Q&A
![Page 27: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/27.jpg)
Designing the Control System
• Consider Design Conditions and Off-Design Conditions
• Design should Include Diagram, Sequence of Operation, Point List, Valve Schedule, and Damper Schedule
• Design should be Detailed, but not Manufacturer Specific
• Control System Design, Sequence, and Programming have more Impact on Hospital Energy Efficiency than System and Equipment Selections
27 HAAHE/TAFHM Facility Manager Basic Training 12/5/2013
![Page 28: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/28.jpg)
Developing the Sequence of Operation
• Goal is Optimum Performance
• Include Fail-Safe Provisions
• Identify Inputs, Loop Statements, Table Statements, Logical Operators, Setpoints, Local Variables, and Outputs
• Consider Using a Flow Chart to Convey Design Intent
• Must be Very Detailed to Prevent Misunderstandings
• Lack of a Detailed Sequence is the Reason why most Buildings Fail to Achieve their Energy Efficiency Goals
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 28
![Page 29: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/29.jpg)
Developing the Sequence of Operation
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 29
AHU Supply Air Temperature Reset
Control Loops
Cooling Loopout /Chilled Water Control Valve is equal to the
output of the following PI loop:
Action – Direct
Input – Supply Air Temperature
Setpoint – Cooling Setpoint
Minimum Output – 0
Maximum Output – 100
Supply Air Temperature: The supply air temperature setpoint
(“cold deck temperature”) is increased and decreased from the
minimum to the maximum and vice versa according to the
following logic:
Input – Request for more cooling from Air Terminals
Output – Supply Air Temperature Setpoint. Equal
to the lower of comparison of Calculated Supply Air
Temperature Setpoint (reset based on polling
zones described in this section) and
Dehumidification Override Supply Air Temperature
Setpoint (section 9.c).
Minimum SAT Setpoint (60F)
Maximum SAT Setpoint (65F)
Sampling Rate/Rate of Change: 1F/5 mins
![Page 30: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/30.jpg)
Agenda
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 30
• Why target HVAC Systems?
• Shifting the Paradigm
• Controls are the Key
• 4 Opportunities
– Chilled Water Pumping
– Cooling Tower Relief
– Air Handler Controls, Resets
– Air Terminal Controls, Troubleshooting
• Closing, Q&A
![Page 31: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/31.jpg)
Chilled Water System Issues
• Improper Chiller, Cooling Tower, and/or Pump Sequencing
• Differential Pressure Setpoint Reset Overridden
• Condenser Water Supply Temperature Reset Overridden (or not programmed).
• Low Chilled Water Temperature Difference (Low Delta T)
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 31
![Page 32: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/32.jpg)
CV Primary/ Variable Flow Secondary
Chilled Water System
• First developed by B&G in 1954.
• 2 Hydraulically Independent loops via Decoupler bypass pipe (“neutral bridge”).
• Primary pumps interlocked with each Chiller to provide design (constant) gpm.
• Secondary pumps are modulated to meet system DP requirement.
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 32
![Page 33: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/33.jpg)
CV Primary/ Variable Flow Secondary Chilled Water System
• Perfect world – Primary Loop GPM = Secondary Loop GPM.
• No flow in Decoupler pipe.
• In the real world this is seldom the case.
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 33
![Page 34: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/34.jpg)
CV Primary/ Variable Flow Secondary Chilled Water System
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 34
![Page 35: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/35.jpg)
CV Primary/ Variable Flow Secondary Chilled Water System
KEY PERFORMANCE INDICATORS
• Secondary Loop Delta T.
– Low Delta T indicates excessive pumping.
– Chillers, AHU Coils are more efficient at higher delta T.
• System Operating DP.
– High system differential pressure can mask other problems.
– Higher DP = higher pumping horsepower.
– High DP’s can adversely affect control valve/coil performance.
T500Btu/h GPM
For a given load, Flow and ΔT are inversely proportional.
As GPM increases, ΔT drops.
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 35
![Page 36: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/36.jpg)
CV Primary/ Variable Flow Secondary Chilled Water System
Control Sequence
• Reset DP setpoint based on actual AHU demand (chilled water valve positions).
• Stage chillers based on tonnage but watch the temperature of water in decoupler and secondary loop Delta T for fault detection.
• Add secondary loop Delta T to dashboard.
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 36
![Page 37: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/37.jpg)
Variable Primary Chilled Water
• Variable Flow through Chillers
• Only 1 Set of Pumps
• Pumps Sequenced to Maintain Delta P and Minimum Flow
• Bypass Valve Modulates to Maintain Minimum Flow
• Requires Electronic Flow Safeties
• Lower Capital Cost, Energy Cost, and Maintenance Cost
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 37
![Page 38: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/38.jpg)
Agenda
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 38
• Why target HVAC Systems?
• Shifting the Paradigm
• Controls are the Key
• 4 Opportunities
– Chilled Water Pumping
– Cooling Tower Relief
– Air Handler Controls, Resets
– Air Terminal Controls, Troubleshooting
• Closing, Q&A
![Page 39: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/39.jpg)
Condenser Water Relief
• Still many plants control tower water to single setpoint (80F aquastat)
• Chiller Efficiency improves with colder condenser water.
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 39
![Page 40: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/40.jpg)
Lots of hours of operation – even in South Texas…
![Page 41: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/41.jpg)
It’s all about LIFT
• Condensing temperature minus the suction temperature
• Two ways to decrease Lift by adjusting DDC:
– Lower Condenser Water Temperature
– Raise Chilled Water Supply Temperature
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 41
![Page 42: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/42.jpg)
Condenser Water Relief Implementation for Constant Volume Pumping
• Tower fan energy versus lower chiller kW
• Reset loop setpoint based on wet bulb and run the condenser loop as cold as possible
– 2 tower cells paired with 1 Chiller
• Be aware of lower limit.
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 42
![Page 43: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/43.jpg)
Variable Volume Condenser Water
System
• Valves Modulate to Maintain Proper Flow
• Flow at Design with Minimum Refrigerant Lift Override
• Chillers can Operate with Very Cold Condenser Water (eliminates transition issues with hydronic free cooling)
• Any Chiller with any Tower with any Pump
• Pumps Sequenced in a Best Efficiency Manner
• Towers Sequenced in Best Efficiency Manner
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 43
![Page 44: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/44.jpg)
3.0 GPM per Ton Condenser Water Flow Rate
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 44
![Page 45: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/45.jpg)
Agenda
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 45
• Why target HVAC Systems?
• Shifting the Paradigm
• Controls are the Key
• 4 Opportunities
– Chilled Water Pumping
– Cooling Tower Relief
– Air Handler Controls, Resets
– Air Terminal Controls, Troubleshooting
• Closing, Q&A
![Page 46: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/46.jpg)
Air Handling Unit Issues
• Static Pressure Setpoint Reset Overridden
• Malfunctioning Control Valves
• Supply Air Temperature Setpoint Reset Overridden
• Failed Air Flow Measuring Stations
• Malfunctioning Dampers
• Weekly Schedules Overridden
• Simultaneous Heating and Cooling
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 46
![Page 47: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/47.jpg)
Multiple Loop Temperature Control
Loop 1
Loop 2 Loop 3
Loop 4
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 47
![Page 48: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/48.jpg)
Multiple Loops
2022 Loop (0, Input, Output, Setpoint, P, I, D, Min, Max, Bias)
• 4 Setpoints
• 4 Sets of Proportional and Integral Gains
• Setpoints may Inadvertently Overlap
• Tuning is very Difficult
• Outputs will Overlap due to Hunting
• Simultaneous Heating and Cooling
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 48
![Page 49: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/49.jpg)
Multiple Loops
Time
Mixed Air Preheat CHW Coils
Mixed Air Temperature
Mixed Air Setpoint
Output Preheat
Temperature Preheat Setpoint
Output Coil Leaving
Air Temperature
Supply Air Temperature
Supply Air
Setpoint Output
3:00 55.3 55 51 55.3 50 0 40.7 47.5 48 24
3:05 48.0 55 76 57.6 50 24 41.6 48.1 48 27
3:10 57.7 55 42 57.7 50 0 42.0 48.9 48 26
3:15 60.5 55 33 60.5 50 0 42.2 48.3 48 30
3:20 54.9 55 51 54.9 50 0 40.9 47.2 48 23
3:25 47.5 55 79 54.7 50 18 41.0 47.6 48 23
3:30 58.3 55 39 58.3 50 0 41.8 48.4 48 28
3:35 62.0 55 29 62.0 50 0 42.3 48.7 48 33
3:40 54.1 55 55 54.1 50 0 41.4 48.2 48 21
3:45 48.5 55 75 52.9 50 11 41.1 47.6 48 20
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 49
![Page 50: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/50.jpg)
Overlapping Setpoints
Time
Mixed Air Preheat CHW Coils
Mixed Air Temperature
Mixed Air Setpoint
Output Preheat
Temperature Preheat Setpoint
Output Coil Leaving
Air Temperature
Supply Air Temperature
Supply Air
Setpoint Output
3:00 55.3 55 51 55.3 50 0 40.7 47.5 48 24
3:05 48.0 55 76 57.6 50 24 41.6 48.1 48 27
3:10 57.7 55 42 57.7 50 0 42.0 48.9 48 26
3:15 60.5 55 33 60.5 50 0 42.2 48.3 48 30
3:20 54.9 55 51 54.9 50 0 40.9 47.2 48 23
3:25 47.5 55 79 54.7 50 18 41.0 47.6 48 23
3:30 58.3 55 39 58.3 50 0 41.8 48.4 48 28
3:35 62.0 55 29 62.0 50 0 42.3 48.7 48 33
3:40 54.1 55 55 54.1 50 0 41.4 48.2 48 21
3:45 48.5 55 75 52.9 50 11 41.1 47.6 48 20
50 12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 50
![Page 51: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/51.jpg)
Simultaneous Heating and Cooling
Time
Mixed Air Preheat CHW Coils
Mixed Air Temperature
Mixed Air Setpoint
Output Preheat
Temperature Preheat Setpoint
Output Coil Leaving
Air Temperature
Supply Air Temperature
Supply Air
Setpoint Output
3:00 55.3 55 51 55.3 50 0 40.7 47.5 48 24
3:05 48.0 55 76 57.6 50 24 41.6 48.1 48 27
3:10 57.7 55 42 57.7 50 0 42.0 48.9 48 26
3:15 60.5 55 33 60.5 50 0 42.2 48.3 48 30
3:20 54.9 55 51 54.9 50 0 40.9 47.2 48 23
3:25 47.5 55 79 54.7 50 18 41.0 47.6 48 23
3:30 58.3 55 39 58.3 50 0 41.8 48.4 48 28
3:35 62.0 55 29 62.0 50 0 42.3 48.7 48 33
3:40 54.1 55 55 54.1 50 0 41.4 48.2 48 21
3:45 48.5 55 75 52.9 50 11 41.1 47.6 48 20
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 51
![Page 52: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/52.jpg)
What is the Problem?
Time
Mixed Air Preheat CHW Coils
Mixed Air Temperature
Mixed Air Setpoint
Output Preheat
Temperature Preheat Setpoint
Output Coil Leaving
Air Temperature
Supply Air Temperature
Supply Air
Setpoint Output
3:00 55.3 55 51 55.3 50 0 40.7 47.5 48 24
3:05 48.0 55 76 57.6 50 24 41.6 48.1 48 27
3:10 57.7 55 42 57.7 50 0 42.0 48.9 48 26
3:15 60.5 55 33 60.5 50 0 42.2 48.3 48 30
3:20 54.9 55 51 54.9 50 0 40.9 47.2 48 23
3:25 47.5 55 79 54.7 50 18 41.0 47.6 48 23
3:30 58.3 55 39 58.3 50 0 41.8 48.4 48 28
3:35 62.0 55 29 62.0 50 0 42.3 48.7 48 33
3:40 54.1 55 55 54.1 50 0 41.4 48.2 48 21
3:45 48.5 55 75 52.9 50 11 41.1 47.6 48 20
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 52
![Page 53: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/53.jpg)
Single Loop Temperature Control
0
20
40
60
80
100
0 20 40 60 80 100
Ta
ble
Sta
tem
en
t
Ou
tpu
t
Supply Air Temperature Control Statement Output
Preheat Valve
First Stage Economizer Cycle(Maximum OSA Damper)
Second Stage EconomizerCycle (Return Air and ReliefAir Dampers)
Secondary Chilled Water Valve
Primary Chilled Water Valve
Stage 1
Stage 4
Stage 3
Stage 2
Stage 5
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 53
![Page 54: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/54.jpg)
Single Loop Humidity Control
0
20
40
60
80
100
0 20 40 60 80 100
Ta
ble
Sta
tem
en
t O
utp
ut
Return Air Humidity Control Statement Output
Disable Second Stage ofEconomizer Cycle (OpensReturn and Closes ReliefDampers)
Disable First Stage ofEconomizer Cycle (ClosesMaximum OSA Damper)
Humidifier Steam Valve
Stage 3 Stage 2 Stage 1
12/5/2013 ©2012 American Society for Healthcare Engineering of the American Hospital
Association 54
![Page 55: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/55.jpg)
Adaptive Resets
• Reset Supply Air Temperature (“Cold Deck Reset”).
• Reset Duct Static Pressure Setpoint
• ASHRAE 90.1, Energy Code
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 55
![Page 56: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/56.jpg)
Dedicated Outside Air AHU
• Pre-treat ventilation air. Ducted to outside air damper on individual AHUs.
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 56
![Page 57: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/57.jpg)
Air-Side Economizer Cycles
• Air-Side Economizer Cycles often incorrectly programmed/configured and difficult to maintain.
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 57
![Page 58: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/58.jpg)
Economizer Damper Control Loop not Tuned
0
10
20
30
40
50
60
70
80
90
3:0
0
3:0
5
3:1
0
3:1
5
3:2
0
3:2
5
3:3
0
3:3
5
3:4
0
3:4
5
EconomizerDamper Output
Mixed Air Setpoint
Mixed AirTemperature
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 58
![Page 59: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/59.jpg)
Air-Side Economizer Cycles on AHU’s with Humidifiers
• ASHRAE Standard 90.1 Requires Hydronic Free Cooling if Humidification Dewpoint is > 35 deg. F (30% RH at 68 deg. F)
• Cooling Savings are more than Offset by Higher Humidification Costs
• Air-Side Economizer Cycles are Costly to Implement and Difficult to Maintain
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 59
![Page 60: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/60.jpg)
Operating Room Challenges
• Surgeons/staff want 60F/50% rh
• Difficult if not impossible to achieve with typical chilled water system
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 60
![Page 61: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/61.jpg)
Operating Room Challenges
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 61
![Page 62: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/62.jpg)
Operating Room Challenges
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 62
• Desiccant Technology provides lower dewpoints.
• Dedicated OSA AHU with Type III passive dessicant wheel shown.
![Page 63: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/63.jpg)
Operating Room Challenges
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 63
Air change rates, pressure differentials difficult to optimize – often are not reset based on occupancy.
![Page 64: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/64.jpg)
Unoccupied/Occupied Reset for Operating Rooms
• Occupied – 15 to 25 ACH
• Unoccupied – 5 to 8 ACH
• DP – 0.01” w.g.
![Page 65: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/65.jpg)
Agenda
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 65
• Why target HVAC Systems?
• Shifting the Paradigm
• Controls are the Key
• 4 Opportunities
– Chilled Water Pumping
– Cooling Tower Relief
– Air Handler Controls, Resets
– Air Terminal Controls, Troubleshooting
• Closing, Q&A
![Page 66: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/66.jpg)
Air Terminal Issues
• Failed Averaging Velocity Sensors
• Malfunctioning Terminal Dampers
• Malfunctioning Heating Water Control Valves
• Insufficient Air Flow to Accommodate Space Sensible Cooling Load
• Incorrect Air Flow Setpoints
• Deadband too Small
• Thermostat Range not Restricted
• Weekly Schedules Overridden
• Occupancy Sensors Overridden
• Failed Points
• Simultaneous Heating and Cooling
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 66
![Page 67: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/67.jpg)
VAV Air Terminal with Heating
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 67
![Page 68: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/68.jpg)
VAV Air Terminal with Heating – Minimizing Reheat
Best Practice: Modulate HW Valve to a Discharge Setpoint and Reset the Setpoint from Minimum up to Maximum before Increasing Air Flow.
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 68
![Page 69: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/69.jpg)
VAV Air Terminal Troubleshooting
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 69
• Failed Averaging Velocity Sensors
• Malfunctioning Terminal Dampers
• Malfunctioning Heating Water Control Valves
• Insufficient Air Flow to Accommodate Space Sensible Cooling Load
• Don’t apply a system wide correction to a zone level problem.
![Page 70: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/70.jpg)
Closing Thoughts • You can’t manage what you
don’t measure.
• The code is the key. Get it right and good things happen.
• Don’t use a sledge hammer to drive a finish nail.
12/5/2013 HAAHE/TAFHM Facility Manager Basic Training 70
![Page 71: Energy & Heat Transfer in Healthcare HVAC - c.ymcdn.comc.ymcdn.com/sites/tahfm.site-ym.com/resource/resmgr/Files/Shawn... · Energy & Heat Transfer in Healthcare HVAC ... Setting](https://reader034.vdocuments.mx/reader034/viewer/2022052608/5ac3720c7f8b9a2b5c8bf3d9/html5/thumbnails/71.jpg)
Thank You! Questions?