Energy Efficiency in HVAC system Prashant Bhanware 06 August 2015

Upload: duongkiet

Post on 30-Mar-2018

244 views

Category:

Documents


9 download

TRANSCRIPT

Page 1: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Energy Efficiency in HVAC system

Prashant Bhanware

06 August 2015

Page 2: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

CONTENTS

• Introduction to district cooling system– Applicability, benefits

– Heat flow diagram, energy split up

• Energy efficient practices in district cooling systems

– Central chilled water plant

– Building side systems

• Advanced Technologies

– Radiant Cooling Systems

– Thermal Energy Storage

• Summary – An Overall view

Page 3: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

What is District Cooling ??

• Chilled water is generated at a single point to meet the requirements of entire site

Section 1Central chilled water plant

Section 2Distribution System

Section 3 - Building levelEnergy transfer stations

Page 4: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Introduction to District Cooling

Applicability

• Higher building density and high cooling demand– Business districts

– Universities

• Diversity of cooling loads in different buildings

Benefits

• Reduction in system cooling capacity compared to aggregate capacities of buildings

• Operating all equipment near to their optimum conditions (Upon reaching to critical mass of cooling demand)

Page 5: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Heat flow diagram

Building loads

A H UsEnergy

Transfer Stations

ChillersCooling Tower

Atmo-sphere

Air loop

Energy transfer station- CHW loop

Chilled Plant CHW loop

Condenser water loop

Building Side Central Chiller Plant

Page 6: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Energy split up - Typical

Page 7: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Energy Efficiency in District

Cooling System

Central chilled water plant

Distribution system

Building side

At 3 levels

Page 8: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Centralized chiller plant

Chilled water supply

temperature – High

Condenser water supply

temperature – Low

Chiller selection & operation

Using VFD drives for

compressors, fans and

pumps

Energy Efficiency practices –

Centralized chiller plant

Page 9: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Chiller efficiency – C O P

Coefficient of performance or COP

Cooling provided in kW

Compressor Energy Consumption in kW=

• For a given cooling load, compressor

has to consume less energy, then C O P

increases

Expansion valve

Condenser

Evaporator

Condenser

water supply

temperature

CHW Supply

temperature

Compressor

• In other terms, COP of chiller increases,

if the temperature difference between

“Condenser water supply temperature ”

and “Chilled water supply temperature”

decreases

Page 10: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

3.6

4.7

5.8 6

.4 6.9 7.0

6.9

6.7

6.4

5.9

5.1

6.7

8.2

9.3 9.6

9.5

9.2

8.7

8.2

7.7

0.0

2.0

4.0

6.0

8.0

10.0

12.0

10

%

20

%

30

%

40

%

50

%

60

%

70

%

80

%

90

%

10

0%

CO

P

Loading

CHW - 6 /12 CHW - 12 /17

Effect of chilled water supply

temperature on chiller COP

Source: Johnson chiller data• Improvement in COP is in the range of 30 – 40 %

Constant condenser water temperatures - 28 / 34

Page 11: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

3.6

4.7

5.8 6

.4 6.9 7.0

6.9

6.7

6.4

5.9

2.8

2.8 3.2 3

.7 4.0 4.2 5

.0 5.1

5.1

5.0

0.0

2.0

4.0

6.0

8.0

10.0

10

%

20

%

30

%

40

%

50

%

60

%

70

%

80

%

90

%

10

0%

CO

P

Loading

Condenser water - 28 /34 Condenser water - 35 / 40

Effect of condenser water supply

temperature on chiller COP

Source: Johnson chiller data

• Improvement in COP is in the range of 40 – 50 %

Constant chilled water temperatures – 6 / 12

Page 12: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Gliding chilled water supply

temperature

• COP increases with increased chilled

water supply temperature

• Hence, rise the chilled water

temperature as per the load

100% load 50% load Source: Johnson chiller data

3.6

4.7

5.8 6

.4 6.9 7.0

6.9

6.7

6.4

5.9

5.1

6.7

8.2

9.3 9.6

9.5

9.2

8.7

8.2

7.7

0.0

2.0

4.0

6.0

8.0

10.0

12.0

10

%

20

%

30

%

40

%

50

%

60

%

70

%

80

%

90

%

10

0%

CO

P

Loading

CHW - 6 /12 CHW - 12 /17

Page 13: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

VFD onFan

VFD on CondenserPump

Constant PrimaryPump

Variable SecondaryPump

VFD on CondenserPump

Situation 1One chiller running at full load

600 kW

28 kW

60 kW50 kW

Using multiple chillers to meet

the total system load

Page 14: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

VFD onFan

VFD on CondenserPump

Constant PrimaryPump

Variable SecondaryPump

164 kW

28 kW

10.6 kW8.8 kW

VFD onFan

VFD on CondenserPump

Constant PrimaryPump

164 kW

28 kW

10.6 kW8.8 kW

Situation 2

Two chiller running at 50% part load

Page 15: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Performance Comparison

Situation 1One chiller running on full load

Situation 2Two chiller running on 50% part load

Page 16: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Installing VFDs for Centrifugal

Chillers

• VFD operation of compressor increases COP at part load

• VFD operation decreases energy consumption with same output , hence the higher COP

at part loads

Page 17: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Cooling Tower

• Cooling tower supplies water to

condenser, Hence performs the heat

rejection part of the chiller

• Condenser water supply temperature

effects the COP of the chiller

• Lesser the condenser water supply

temperature, higher the COP of

chiller

• Condenser supply temperature depends

on effectiveness of the cooling towerSource: Johnson chiller data

3.6

4.7

5.8 6

.4 6.9 7.0

6.9

6.7

6.4

5.9

2.8

2.8 3

.2 3.7 4

.0 4.2

5.0 5.1

5.1

5.0

0.0

1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

10

%

20

%

30

%

40

%

50

%

60

%

70

%

80

%

90

%

10

0%

CO

P

Loading

Condenser water - 28 /34Condenser water - 35 / 40

Page 18: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Cooling tower - Performance

Ra

ng

eA

pp

roa

ch

Hot Water Temperature (In)

Cold Water Temperature (Out)

Wet Bulb Temperature

(Ambient air )

Effectiveness =

Range / (Range + Approach)

Cooling

tower

• Condenser supply temperature is limited by

wet bulb temperature of ambient air

• Approach should be as less as possible

• Approach depends on the effective

heat transfer between air and water. It

depends on Heat transfer medium (fills).

Page 19: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Sum up - Energy Efficiency practices

Centralized chiller plant

Gliding CHW temperature at part loads

Selecting higher part

load efficient chiller

Approach of cooling tower should be low

Using VFD drives for

compressors, fans and pumps

Page 20: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Energy Efficiency practices -

Building side

Page 21: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Building side systems

• Energy Transfer stations

– Plate HX

– Tertiary chilled water loop

• Air distribution system

– AHU

– Fans

Page 22: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Heat flow diagram

Building loads

A H UsEnergy

Transfer Stations

ChillersCooling Tower

Atmosphere

Air loop

Energy transfer station- CHW loop

Chilled Plant CHW loop

Condenser water loop

Building Side Central Chiller Plant

Page 23: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Installing VFD drives for

fans and pumps

• Varying flows by VFD is more efficient mode of control

• Reduction in energy savings in the range of 50 to 60 % at part loads compared to

damper control

50 % savings

60 %60 %

Page 24: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Heat Recovery at AHU units

• Heat recovery with Enthalpy wheels– Effectiveness (Sensible & Latent) ≥ 75%

Exhaust Air

Supply Air

38oC DB24oC DB

43oC DB29oC DB

• Purge section to control

air quality and cross

contamination

Page 25: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Potential for Free Cooling in

Gandhinagar

25% of the hours of the

year the outside air

temperature in

Gandhinagar is below 24°C

Page 26: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Free Cooling at AHU units

• Control logic for opening/closing of dampers & fan operation

– Zone set point, Ambient air temperature & enthalpy, Return air

enthalpy

Opening/closing of dampers is automatic through building management system (BMS)

• Provision to

bypass cooling

coil to

minimize fan

energy

Page 27: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Incorporating Advanced

Technologies in District cooling

Page 28: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Click to edit

Master title style

Click to edit

Master title style

28Indo-Swiss Building Energy Efficiency Project

RADIANT COOLING SYSTEM

Page 29: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

29Indo-Swiss Building Energy Efficiency Project

H R

Radiant Cooling Systems – Integration at

GIFT City

Energy transfer station - 1

Central Chiller plant @ 12 0C

CHW loop

CHW loop

130 C

20 0 C

A H U

Small chillerAt building level

CHW loop

5 0 C

10 0 C

Sensible Loads – Slab cooling Latent Loads – D O A S

Air loop – only fresh air

Air in

Air out

Page 30: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

30Indo-Swiss Building Energy Efficiency Project

3.6

4.7

5.8 6

.4 6.9 7.0

6.9

6.7

6.4

5.9

5.1

6.7

8.2

9.3 9.6

9.5

9.2

8.7

8.2

7.7

0.0

2.0

4.0

6.0

8.0

10.0

12.0

10

%

20

%

30

%

40

%

50

%

60

%

70

%

80

%

90

%

10

0%

CO

P

Loading

CHW - 6 /12 CHW - 12 /17

Chiller C O P - Improvement

Source: Johnson chiller data

• Improvement in COP is in the range of 40 – 50 %

Constant condenser water temperatures - 28 / 34

Page 31: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

31Indo-Swiss Building Energy Efficiency Project

Additional Benefits

• Savings on fan energy consumption

– Only fresh air supply (No recirculation)

– Estimated overall energy savings in the range of 30 – 45 % compared

to air systems

• Better IEQ (Indoor Environment Quality)

– Less noise due to less draft

– Even temperature distribution

Page 32: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

32Indo-Swiss Building Energy Efficiency Project

CASE STUDYInfosys - SDB 1 Building , Hyderabad

Conventional half Radiant half

• Symmetric building with 2 halves

• Building built up area = 23 200 m2

• Long facades facing north and south

• Total occupancy = 2 500

• Envelope heat load = 10.8 W / m2

= 1 W / ft2

• Lighting load = 0.45 W / ft2

• Equipment load = 3.5 W / ft2

• Built in 2011

Source : Infosys_TechnicalPapaer_Guruprakash sastry

Page 33: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

CASE STUDYInfosys - SDB 1 Building , Hyderabad

Building Energy Index for 2011 – 12

• Radiant cooling system consumed 56 % less energy for HVAC than VAV cooling system for 2011 – 12 FY

8.114.4

35.5

58.7

116.7

8.817.2

34.225.7

85.9

0

20

40

60

80

100

120

140

Lighting Misc. Power Computers HVAC Total

kWh

/ S

q m

Utilty

Conventional Radiant

Source : Infosys_TechnicalPapaer_Guruprakash sastry

Page 34: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

CASE STUDYInfosys - SDB 1 Building , Hyderabad

No UtilityConventional Radiant

INR

1 Chiller 31 45 200 31 45 200

2 Cooling tower 13 06 400 13 06 400

3 HVAC low side works 2 28 39 000 1 53 10 000

4 AHUs, DOAS, HRW 51 18 200 28 78 900

5Radiant piping, accessories,

installation, etc.0 90 75 800

6 Building Automation System 61 84 000 65 84 000

7 Total cost (INR) 3 85 92 600 3 83 00 300

8 Area (m 2) 11 600 11 600

9 Cost / m2 area 3 327 3 302

Cost analysis for both the systems:

Almost same capital cost incurred for both the systems

Source : Infosys_TechnicalPapaer_Guruprakash sastry

Page 35: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Click to edit

Master title style

THERMAL ENERGY STORAGE

– T E S

Page 36: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

3.0

4.0

5.0

6.0

7.0

8.0

10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

C O

P

Loading

Chilled water in / out - 6 /12Condenser water in / out - 28 / 34

Chiller Operation - According to

building loads

• Chiller is being operated at lesser efficient load during both Peak load and

Off - peak load periods

Off Peak load – day time

Peak load – night time

Page 37: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

3.0

4.0

5.0

6.0

7.0

8.0

10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

C O

P

Loading

Chilled water in / out - 6 /12Condenser water in / out - 28 / 34

Chiller with T E S - Operation

Charging - T E S

Best efficient operation

• Chiller is operated at best efficient point• During off peak periods, chilled water is stored• During Peak period , stored chilled water is used to meet the peak load

Discharging - T E S

Charging - T E S

Page 38: Energy Efficiency in HVAC system - beepindia.org. Energy efficiency in HVAC...Chillers Cooling Tower Atmo ... • Cooling tower supplies water to ... •Radiant cooling system consumed

Summary –An overall view

• Selecting high efficient chiller at part loads

• Increasing the CHW supply temperature to gain the COP

advantage

• Installing VFDs for Compressors, fans and pumps

• Thermal Energy Storage integration

• Radiant cooling system integration

• Heat recovery

• Free cooling concept

Chiller Plant

Building Side Systems