  • SPECIF ICAT ION SUBMITTAL Page

    Job Name:

    Job Number:

    Model Numbers:

    Energi Savr Node EcoSystem Digital Fixture Controller

    369248n 1 04.07.17

    Energi Savr Node with EcoSystem

    The Energi Savr Node family is a group of intelligent, modular products for the control of lighting loads. This document describes the Energi Savr Node unit with EcoSystem, which can control all EcoSystem compatible products including EcoSystem ballasts and modules and Hi-lume EcoSystem LED drivers.

    EnergiSavrNode unit with EcoSystem with 1 EcoSystem Digital Loop (QSN-1ECO-S).

    EnergiSavrNode unit with EcoSystem with 2 EcoSystem Digital Loops (QSN-2ECO-S).Features

    Powersupto2EcoSystemDigitalLoops(QSN-2ECO-S).EasysystemprogrammingwithanintuitiveapplicationforApple iPhone or

    iPod touch mobile digital devices (required for non-Quantum systems).Fouroccupancysensorinputsforautomatedcontroloflights.Fourdaylightsensorinputsautomaticallyadjustlightlevelsbasedon

    the amount of natural light entering through the windows.FourIRreceiverinputsforpersonalcontrol.IncludesQScontrollinkforseamlessintegrationoflights,control

    stations, and QS sensor modules.ExpandthenumberofsensorsandcontrolsusingtheQSSensorModule(QSM)orsensorsconnectionsonEcoSystem ballasts and modules.

    ConnectdirectlytootherEnergiSavrNodeunits,GRAFIKEyeQS units, or Quantum systems toexpandfunctionalityandcontrol.

    BAA-compliantmodelnumbersavailable.AddaUprefixtothemodelnumber.

    System Example

    Wireless Communication

    Wired Daylight Sensors (up to 4) 1,2

    Wired Occupancy Sensors (up to 4) 1

    Wired EcoSystem Wallstation orIRreceivers (up to 4) 1

    IRTransmitterOR OR

    RadioPowrSavrOccupancy Sensor (upto10perQSM)

    RadioPowrSavr Daylight Sensor (upto10perQSM)

    PicoWirelessController (up to 10perQSM)

    Notes: 1 Upto4wiredinputstotal(ofanytype).2 Upto16wireddaylightsensorstotalperEcoSystem loop. Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.

    QS Link

    GRAFIK Eye QS Control Unit

    Energi Savr Node Unit

    QSM

    Wired Inputs

    Sivoia QS shades / draperiesControlwithPico wireless controller onlythroughQSM

  • SPECIF ICAT ION SUBMITTAL Page

    Job Name:

    Job Number:

    Model Numbers:

    Energi Savr Node EcoSystem Digital Fixture Controller

    369248n 2 04.07.17

    SpecificationsEnergi Savr Node with EcoSystem

    Regulatory Approvals

    UL ListedCSANOMCertifiedLutronQualitySystemsregisteredtoISO9001.2008 Complieswithrequirementsforuseinotherspaces

    used for environmental air (plenums) per NEC 2014 300.22(C)(3)

    MeetstheCanadianNationalBuildingCodeplenumrequirements for a concealed space used as a plenum within a floor or roof assembly

    Forcommercialuse,ClassAonly

    Power

    ControlPower:120-277V~50/60HzLightningstrikeprotectionmeetsANSI/IEEEstandard62.31-1980.Canwithstandvoltagesurgesofupto 6000V~ andcurrentsurgesofupto3000A

    Currentdraw:0.5A10-yearpowerfailurememory:restoreslightingto

    levels prior to power interruption

    Environment

    AmbientTemperatureOperatingRange:32Fto104F (0Cto40C)

    Relativehumidity:lessthan90%non-condensing.Forindooruseonly

    Terminals

    ControlPowerwiring:14AWGto12AWG (2.5 mm2 to 4.0 mm2)

    EcoSystemDigitalLoopWiring:18AWGto12AWG (1.0 mm2 to 4.0 mm2)

    InputGroupWiring:22AWGto12AWG (0.5 mm2 to 4.0 mm2)

    QSLoopWiring:22AWGto12AWG (0.5 mm2 to 4.0 mm2)

    Physical Design

    NEMAType1,IP-20protection.

    Mounting

    Surface-mount

    Programming Requirements

    AnApple iPod touch or iPhone mobile digital device with the Energi Savr app is required for programming Energi Savr Node with EcoSystem systems

    TheEnergiSavrappisavailablefromtheApple App Store online store

    TheEnergiSavrappcannotbeusedtoprogramtheEnergi Savr Node with EcoSystem units when installed as part of a Quantum system

    TheApple iPod touch or iPhone communicates with the Energi Savr Node unit viaaWiFirouter (not included)

    SeeWiring:SystemProgrammingConnectionsection for further information

    Input Default Associations

    EnergiSavrNodewithEcoSystemunitsare pre-programmed from the factory to respond to inputs wired directly to the Energi Savr Node with EcoSystem unit

    ProgrammableCCIactivatesasceneusinganormallyopen momentary closure by default

    Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.AppStoreisaservicemarkofAppleInc.

  • SPECIF ICAT ION SUBMITTAL Page

    Job Name:

    Job Number:

    Model Numbers:

    Energi Savr Node EcoSystem Digital Fixture Controller

    369248n 3 04.07.17

    Specifications (continued)

    EcoSystem

    Controlupto64EcoSystem compatible devices (ballast, modules, or LED drivers) per EcoSystem Digital Loop(upto128devicesperEnergiSavrNodewithEcoSystemunit):

    EcoSystem ballasts and modules Hi-lume EcoSystem LED driversDigitallydefineareasandzones.Configurewiredorwirelesssensorsandcontrolsto

    control devices on multiple EcoSystem Digital Loops and/or multiple Energi Savr Node units.

    Automaticreplacementofasinglefailedballast,module, or driver.

    Simplemethodofreplacingmultiplefailedballasts,modules, or drivers.

    EcoSystem DigitalLoopcanbewiredasClass1orIECPELV/NECClass2formaximumwiringflexibility.

    Occupancy Sensors

    UseLutronLOSseriesofwiredoccupancysensorsinoccupancy mode to control one or more areas.

    UseLutronoccupancysensorsinvacancymode to automatically turn the lights off in an area after it becomes vacant.

    UseLutronoccupancysensorstoautomaticallyturnthe lights on in area when it becomes occupied and to automatically turn the lights off in an area after it becomes vacant.

    EachofthefouroccupancyinputscanpoweroneLutron occupancy sensor.

    Eachareasoccupiedlightlevelandunoccupiedlightlevel can be programmed independently.

    UptofouradditionalLutronWiredOccupancy SensorsortenadditionalRadioPowrSavr Occupancy/VacancySensorscanbeassignedperQSSensorModule(QSM)ontheQSlink.

    seeTouch QS Controls

    seeTouchQSwallstationscanbeconfiguredas azonetoggleorscenewallstation.

    Inzonetogglemode,zonebuttonsareabletoturnoneormorezonesonandoff.

    Inscenemode,buttonsareabletorecallscenesinone or more areas.

    Allbuttonsonawallstationwillbeinthesame mode-zonetoggleorscene.

    LEDindicatordisplayszoneorscenestatus.Asinglebuttoncancontrollightsorshades/draperies,

    but not both.

    IR Wallstation or Receiver Input

    FourinputsforIRreceiversorwallstationsforcontroloflightingzonescanbeconnecteddirectlytotheEnergi Savr Node with EcoSystem unit.

    UseLutronCC-4BRL-WHwallstationstocontroloneormorezones.

    UseLutron EC-IR-WHorEC-DIR-WHceilingmount sensorstocontroloneormorezones.

    UptofouradditionalwiredwallstationsorIR receiverscanbeassignedperQSMontheQSlink

    Daylight Sensors

    Lutrondaylightsensorsallowdaylightharvesting with programmable effect on light output.

    Fourdaylightsensorscanbeconnecteddirectlyto the Energi Savr Node with EcoSystem unit.

    UseLutronEC-DIR-WHsensorstocontrolone or more daylight rows.

    Alternatively,uptofouradditionalLutronWired DaylightSensorsortenadditionalRadioPowrSavr DaylightSensorscanbeassignedperQSMontheQSlink.

    Control4daylightrowsperareawithamaximum of 2 daylight sensors per area.

  • SPECIF ICAT ION SUBMITTAL Page

    Job Name:

    Job Number:

    Model Numbers:

    Energi Savr Node EcoSystem Digital Fixture Controller

    369248n 4 04.07.17

    Specifications (continued)

    Contact Closure Input (CCI)

    Activatescenesusingmomentaryormaintained closuresfromanexternaldevicelikeatimeclock.

    StartorstopAfterhoursmodeusingamaintainedclosure.

    EnableordisableLoadShedmodetosaveenergyduringpeakdemandperiodsusingamaintained closure.

    Theattacheddevicemustprovideadrycontact closure or solid-state output.

    Configurablefornormallyopen(NO)ornormallyclosed (NC) operation.

    Inputismiswire-protectedupto36V-.

    Emergency Contact Closure Input

    Bydefault,contactclosureinputfromLutron EmergencyLightingInterface(LUT-ELI-3PH),security,orfirealarmsystemsturnsallzonesontofulloutputwhen emergency state is detected.

    Emergencycontactclosureinputisnormallyclosed(NC). The Energi Savr Node unit with EcoSystem isshippedwithajumperpre-installed.

    Responseofeachzoneisconfigurable.Attacheddevices,bydefault,willgotomaximum

    output and ignore control inputs.Nooperationswillbealloweduntilemergencysignal

    is cleared.Theattacheddevicemustprovideanormally-closed

    (NC) dry contact closure or solid-state output.Inputismiswire-protectedupto36V-.EmergencyCCIcannotcontrolotherEnergiSavr

    Node units.SeeApplicationNote#140,EcoSystemBallasts andEmergencyWiringatwww.lutron.comfor more details.

    Functionality with GRAFIK Eye QS

    EnergiSavrNodewithEcoSystemareasfollowGRAFIKEye QS unit scene activations when associated with the GRAFIKEye QS unit.

    EnergiSavrNodewithEcoSystemareasrespondtocommandsinitiatedbytheGRAFIKEye QS unit astronomictimeclockwhenassociatedwiththeGRAFIKEye QS unit.

    EnergiSavrNodewithEcoSystemareas operateinAfterhoursmodewhenassociatedwithaGRAFIKEyeQSunitthatisinAfterhoursmode.

    ZonesonEnergiSavrNodeunitscannotbe associatedwithzonecontrolsonGRAFIKEye QS units.

    Functionality with QSE-IO

    EnergiSavrNodeunit with EcoSystem responds toscenecommandsinitiatedbytheQSE-IO,ifthe QSE-IODIPswitcheshavebeensettoeitherSceneSelectionmode,ZoneTogglemode,Partitionmode,or Occupancy Sensor mode.

    Functionality with QSE-CI-NWK-E

    IntegratetheEnergiSavrNodeunitwithEcoSystem withtouchscreens,PCs,A/Vsystems,orotherdigitalsystems and devices.

    Recallscenes