DESCRIPTION
EMS ROMC Environment monitoring system for ROMC. Applying system. Supervisory control of engineering infrastructure Data center Mobile switching center ( MSC ) Operating management center(OMC) , ( ROMC) Any other place of computing and communications equipment. Functionality. - PowerPoint PPT PresentationTRANSCRIPT
EMS ROMCEnvironment monitoring systemfor ROMC.
Applying system
Supervisory control of engineering infrastructure
Data center
Mobile switching center (MSC)
Operating management center(OMC), (ROMC)
Any other place of computing and communications equipment
Functi onal ity
Control and monitoring of climatic parameters – temperature and humidityControl and monitoring of environmental parameters – fumes and dustDoor opening, smokescreen and water leak alarmsProcess and fault signaling, forming messages about excess values of regulated controlling parameters
Surveillance in the premises, videos fixation with long-term storage
Control, management and monitoring guaranteed and backup systems power
Control system power
Controlling access to premises and individual rack units
Functi onal ity
Health-monitoring
Fault manager system
Forming SMS and sending e-mail to designated staff
Administration and audit users
Inventory management system
Functi onal ity
PVS-LX
Server with the program EMS NC
PVS LX controller
User program EMS AV
Service program
Components of the system
Architecture
Operator
IP NETWORK
NETWORK OPERATIONS CENTER
Database
ROMC
PVS LX
ROMC
OMC
EMS NC
ProgramsEMS AV
Informing
External management system
Sensors and system equipment
PVS LX control ler
Computer: CPU ARM9 544 MHz; DRAM 128 MB; Flash 32 MB
Interfaces: 1x LAN, 1x WAN Ethernet 10/100 BaseT (RJ45);
5 Serial RS-232/RS485/С2; 2x USB 2.0; 1x 1-Wire;
16 x 3-level digital inputs; 2x outputs relay contacts
Temperature: -20℃~+55℃
Supply: 48V or 24V DC or 220V AC
Form factor: 1U rack
Hardware specifications:
READY / POWER
48V DC CLIMATE
COOLER / HEATER
LANPVS LX15
1 2 3 4 5WAN USB DIGITAl INPUTRS – 232/485
OS: Linux Kernel Version: 2.6.27
Network protocols: TCP, UDP, IPv4, SNMP(v1,v2), ICMP, ARP,
SSH, DHCP, Telnet, FTP, PPP, DNS, HTTP, HTTPS, SMS, SMTP, SSL
Transfer protocols: RS232/RS485/С1, Modbus over TCP/ІР
Telecontrol protocol: IEC 60870-5-104
Electrical meter protocol: IEC 61107, IEC 1142,
IEC 61334 (DLMS/COSEM)
Security data: Secure Real COM, Secure TCP Server,
Secure TCP Client и Secure Pair Connection
Software and protocols:
PVS LX control ler
• Measuring and monitoring of temperature and humidity• Playback profiles with graph plotting• Self/distance on/off coolers/heaters• Remote control and diagnostic of air conditioning system• Generating alarm messages in excess of limits
Cl imate control system
Alarm system
• Tracking the signal of digital inputs alarms and fireproof, backup power system etc.
• Forming alarm messages to designated staff and external information processing system events FMS
• Alarm system administration
CCTV system
• Simultaneous CCTV many different points or areas on a single monitor with the ability to track movement in the frame
• Distributed video surveillance with the ability to view the recordings at any time for analysis
• Video by motion detectors• Synchronic alarm signals tracking
Electr ic power metering system
• Automatic data collection of technological and commercial accounting of power consumption
• Accumulation parameters of accounting (processing, storage in a database, documentation)
• Control of electrical parameters at the interval (current, voltage, соs ϕ, frequency)
Energy accounti ng system
• Calculation of average energy consumption in view of losses • Providing multiple-zonal metering of electric energy• Accounting and support agreements with energy supplying
organization• Generating reports of energy consumption (daily, monthly, annual)• Providing control over limits energy
Fault manager system
• Control availability and fixing the lack of communication with controllers and with the equipment connected to it
• Fixation the alarm messages• Forming alarm messages to designated staff and external information
processing system events FMS
User permission editor
• User registration system• Providing access rights to the system, separate objects and components • Registration of user actions
Creating and editing reports
• Create and save a report• Automatic filing of data processed by the system• Print and export to other forms of reports
Inventory management
• Accounting system hardware ROMС and connected devices• Automatic inventory of equipment for a set period of time• The replacement equipment registration
The control and management of power supply systems
• Remote control of parameters• Changing the settings• Testing battery• Diagnostics of power supply systems
Backup power generator Control & monitor ing
• Remote start/stop the generator• Remote on/off the load• Control of voltage, current, frequency, battery voltage• Control of temperature, level and oil pressure• Control of fuel level, condition, and operating time
Air conditi oner remote control
• Control of environmental parameters • Remote control and diagnostic• Parameters setting• Analysis and diagnostic of cooling efficiency
Free Cooler
• Remote control and parameters setting • Setting the operating temperature limits inside the container• Inside/outside temperature control • On/off cooler/heater• Switching to emergency cooling • Emergency processing
Conformity declarati on
9, Ivan Franko str, 79005 Lviv, UKRAINEtel./fax: +38 032 235 8287www.mikrokod.com.ua
9, Ivan Franko str, 79005 Lviv, UKRAINEtel./fax: +38 032 235 8287www.mikrokod.com.ua