emr 00 ge dia 0060 rev.d custom displays

40
C 29.01.2013 ISSUED FOR REVIEW PER JESA-TKF-DCS-2126 H.Eksi A.Bürümcek C.Ergun B 15.12.2012 REVIEWED BY TEKFEN ISSUED FOR INFORMATION H.Eksi A.Bürümcek C.Ergun A 06.12.2012 ISSUED FOR TEKFEN’S REVIEW H.Eksi A.Bürümcek C.Ergun Rev. No. Date Description Prepared Checked Reviewed ORIGINATOR TEKFEN Groupe OCP S.A. Casablanca, 2, rue Al Abtal, Hay Erraha, Morocco KHOURIBGA – JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM CONTRACTOR Document Title Custom Displays SUBCONTRACTOR Document No. Rev. No. Total pages (w. attachmts) Org. Code Area Code Disc. Code Doc. Type Seq. No. EMR 00 GE DIA 0060 D 40 D 26.04.2013 ISSUED FOR REVIEW PER JESA-TKF-DCS-2341 H.Eksi A.Bürümcek C.Ergun

Upload: -

Post on 21-Jan-2016

34 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: EMR 00 GE DIA 0060 Rev.D Custom Displays

C 29.01.2013 ISSUED FOR REVIEW PER JESA-TKF-DCS-2126 H.Eksi A.Bürümcek C.Ergun

B 15.12.2012 REVIEWED BY TEKFEN ISSUED FOR INFORMATION H.Eksi A.Bürümcek C.Ergun

A 06.12.2012 ISSUED FOR TEKFEN’S REVIEW H.Eksi A.Bürümcek C.Ergun

Rev. No. Date Description

Prepared Checked Reviewed ORIGINATOR TEKFEN

Groupe OCP S.A. Casablanca, 2, rue Al Abtal, Hay Erraha, Morocco

KHOURIBGA – JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

CONTRACTOR

Document Title

Custom Displays

SUBCONTRACTOR Document No. Rev.

No. Total

pages (w. attachmts) Org. Code Area Code Disc. Code Doc. Type Seq. No.

EMR 00 GE DIA 0060 D 40

D 26.04.2013 ISSUED FOR REVIEW PER JESA-TKF-DCS-2341 H.Eksi A.Bürümcek C.Ergun

Page 2: EMR 00 GE DIA 0060 Rev.D Custom Displays

KHOURIBGA – JORF LASFAR PHOSPHATE SLURRY PIPELINE S YSTEM

Groupe OCP S. A. Casablanca Morocco

Document Title:

Custom Displays

Issue date : 26-04-2013 Doc. no: EMR-00-GE-DIA-0060 Rev. D Page 2 of 40

CONTENTS 1 DOCUMENT SCOPE .................................................................................. 4

2 CUSTOM DISPLAYS ................................... ............................................... 4

2.1 MEA WASH PLANT .................................................................................... 5 2.1.1 Mea Feeder Pipelines ........................................................................... 5

2.2 DAOUI PUMP STATION ............................................................................ 6 2.2.1 Daoui Pump Station Overview .............................................................. 6 2.2.2 Daoui Pump Station .............................................................................. 7 2.2.3 Daoui Pump GSW Station ..................................................................... 8 2.2.3 Daoui Energy Monitoring ....................................................................... 9

2.3 EL HALASSA PUMP STATION ........................................................... 10 2.3.1 El Halassa Pump Station Overview ..................................................... 10 2.3.2 El Halassa Pump Station ..................................................................... 11 2.2.3 El Halassa Pump GSW Station ........................................................... 12 2.2.3 El Halassa Energy Monitoring ............................................................. 13

2.4 HEAD STATION ......................................................................................... 14 2.4.1 Head Station Overview ....................................................................... 14 2.4.2 Head Station Main Line Pumps ........................................................... 15 2.4.2 Head Station GSW Pumps .................................................................. 16 2.4.3 Head Station Feed Receivers ............................................................. 17 2.4.4 Head Station Storages Tank Group I ................................................... 18 2.4.6 Head Station Storages Tank Group II .................................................. 19 2.4.7 Head Station Dilution Water and Filter Unit ......................................... 20 2.4.8 Head Station Energy Monitoring .......................................................... 21

2.5 PRESSURE MONITORING SYTEM AND VALVE STATION .......... 22 2.5.1 Pressure Monitoring System and Valve Station .................................. 22

2.6 TERMINAL STATION ................................................................................ 23 2.6.1 Terminal Station Overview ................................................................... 23 2.6.2 Terminal Station Export Tanks Group I ................................................ 24 2.6.3 Terminal Station Export Tanks Group II ............................................... 25 2.6.4 Terminal Station Local User Tank Group ............................................. 26 2.6.5 Terminal Station Choke Station ............................................................ 27 2.6.6 Terminal Station Energy Monitoring ..................................................... 28

Page 3: EMR 00 GE DIA 0060 Rev.D Custom Displays

KHOURIBGA – JORF LASFAR PHOSPHATE SLURRY PIPELINE S YSTEM

Groupe OCP S. A. Casablanca Morocco

Document Title:

Custom Displays

Issue date : 26-04-2013 Doc. no: EMR-00-GE-DIA-0060 Rev. D Page 3 of 40

2.7 PIPELINE ADVISORY SYSTEM............................................................. 29 2.7.1 Leak Detection System Signals ............................................................ 29 2.7.2 Mea Batch Tracking ............................................................................. 30 2.7.3 Daoui Batch Tracking ........................................................................... 31 2.7.4 El Halassa Batch Tracking ................................................................... 32 2.7.5 Head Station Batch Tracking ................................................................ 33

2.8 ANCILLARY SIGNALS .............................................................................. 34 2.8.1 Pressure Monitoring and Valve Station Ancillary Signals ..................... 34 2.8.2 Pump and Terminal Stations Ancillary Signals ..................................... 35

2.9 EQUIPMENT BASED DISPLAYS ........................................................... 36 2.9.1 General Input/Output Equipment Faceplates ....................................... 36 2.9.2 Motor Type Equipment Faceplates ....................................................... 37 2.9.3 Valve Equipment Faceplates ................................................................ 38 2.9.4 Electrical Equipment Faceplates .......................................................... 39 2.9.2 Hydraulic Power Unit, Filter Unit and Analyzer Faceplates .................. 40

Page 4: EMR 00 GE DIA 0060 Rev.D Custom Displays

KHOURIBGA – JORF LASFAR PHOSPHATE SLURRY PIPELINE S YSTEM

Groupe OCP S. A. Casablanca Morocco

Document Title:

Custom Displays

Issue date : 26-04-2013 Doc. no: EMR-00-GE-DIA-0060 Rev. D Page 4 of 40

Emerson Process Management 2013– Confidential and Proprietary

1. DOCUMENT SCOPE This document shows the SCADA screen pictures according to P&ID drawings for the KHOURIBGA – JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM Project.

2. CUSTOM DISPLAYS The SCADA screens are shown according to locations in below.

Page 5: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.1- MEA WASH PLANT

2.1.1- Mea Feeder Lines

Screens P&ID's

PAC-03-PR-PID-0001 Customer : TEKFEN INSAAT

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

PAC-03-PR-PID-0001

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

5 of 40Rev:

D

Customer : TEKFEN INSAAT

Controlled By

A. Bürümcek

Page 6: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.2- DAOUI PUMP STATION

2.2.1- Daoui Pump Station Overview Screen

Screens P&ID's

PAC-07-PR-PID-0001 PAC-07-PR-PID-0004

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-07-PR-PID-0001 PAC-07-PR-PID-0004

PAC-07-PR-PID-0002 PAC-07-PR-PID-0005 Drawn By Approved By Date

PAC-07-PR-PID-0003 PAC-07-PR-PID-0006 H. Eksi A. Doğan 26.04.2013Page:

6 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 7: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.2.2- Daoui Pump Station(Storage Tanks-Feeder Line Pumps-Pig Launcher And Spillage Pump)

Screens P&ID's

PAC-07-PR-PID-0001 PAC-07-PR-PID-0005

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-07-PR-PID-0001 PAC-07-PR-PID-0005

PAC-07-PR-PID-0002 PAC-07-PR-PID-0006 Drawn By Approved By Date

PAC-07-PR-PID-0003 H. Eksi A. Doğan 26.04.2013Page:

7 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 8: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.2.3- Daoui Pump Station GSW(GSW Pumps)

Screens P&ID's

PAC-07-PR-PID-0004

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-07-PR-PID-0004

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

8 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 9: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.2.4- Daoui Energy Monitoring

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

9 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 10: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.3- EL HALASSA PUMP STATION

2.3.1- El Halassa Pump Station Overview

Screens P&ID's

PAC-08-PR-PID-0001 PAC-08-PR-PID-0005

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-08-PR-PID-0001 PAC-08-PR-PID-0005

PAC-08-PR-PID-0003 PAC-08-PR-PID-0006 Drawn By Approved By Date

PAC-08-PR-PID-0004 PAC-08-PR-PID-0007 H. Eksi A. Doğan 26.04.2013Page:

10 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 11: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.3.2- El Halassa Pump Station

Screens P&ID's

PAC-08-PR-PID-0001 PAC-08-PR-PID-0006

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-08-PR-PID-0001 PAC-08-PR-PID-0006

PAC-08-PR-PID-0003 PAC-08-PR-PID-0007 Drawn By Approved By Date

PAC-08-PR-PID-0004 H. Eksi A. Doğan 26.04.2013Page:

11 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 12: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.3.3- El Halassa GSW Pump Station

Screens P&ID's

PAC-08-PR-PID-0005

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-08-PR-PID-0005

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

12 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 13: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.3.4- El Halassa Energy Monitoring

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

13 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 14: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.4- HEAD STATION

2.4.1- Head Station Overview

Screens P&ID's PAC-10-PR-PID-0010

PAC-10-PR-PID-0001 PAC-10-PR-PID-0004 PAC-10-PR-PID-0007 PAC-10-PR-PID-0011

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-10-PR-PID-0001 PAC-10-PR-PID-0004 PAC-10-PR-PID-0007 PAC-10-PR-PID-0011

PAC-10-PR-PID-0002 PAC-10-PR-PID-0005 PAC-10-PR-PID-0008 PAC-10-PR-PID-0012 Drawn By Approved By Date

PAC-10-PR-PID-0003 PAC-10-PR-PID-0006 PAC-10-PR-PID-0009 PAC-10-PR-PID-0014 H. Eksi A. Doğan 26.04.2013Page:

14 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 15: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.4.2- Head Station Mainline Pumps

Screens P&ID's

PAC-10-PR-PID-0005

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-10-PR-PID-0005

PAC-10-PR-PID-0007 Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

15 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 16: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.4.3- Head Station GSW Pumps

Screens P&ID's

PAC-10-PR-PID-0008

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-10-PR-PID-0008

PAC-10-PR-PID-0009 Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

16 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 17: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.4.4- Head Station Feed Receivers

Screens P&ID's

PAC-10-PR-PID-0001 PAC-10-PR-PID-0011

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-10-PR-PID-0001 PAC-10-PR-PID-0011

PAC-10-PR-PID-0002 PAC-10-PR-PID-0013 Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

17 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 18: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.4.5- Head Station Storage Tank Group I

Screens P&ID's

PAC-10-PR-PID-0004

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-10-PR-PID-0004

PAC-10-PR-PID-0010 Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

18 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 19: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.4.6- Head Station Storage Tank Group II

Screens P&ID's

PAC-10-PR-PID-0003

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-10-PR-PID-0003

PAC-10-PR-PID-0010 Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

19 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 20: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.4.7- Head Station Dilution Water And Filter Unit

Screens P&ID's

PAC-10-PR-PID-0003

CUSTOM DISPLAYS: FALSE

Customer : TEKFEN INSAATPAC-10-PR-PID-0003

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

20 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 21: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.4.8- Head Station Energy Monitoring

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

21 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 22: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.5- PRESSURE MONITORING SYSTEM AND VALVE STATION

2.5.1- Pressure Monitoring System and Valve Station

Screens P&ID's

PAC-11-PR-PID-0001 PAC-14-PR-PID-0001

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-11-PR-PID-0001 PAC-14-PR-PID-0001

PAC-12-PR-PID-0001 PAC-15-PR-PID-0001 Drawn By Approved By Date

PAC-13-PR-PID-0001 H. Eksi A. Doğan 26.04.2013Page:

22 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 23: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.6- TERMINAL STATION

2.6.1- Terminal Station Overview

Screens P&ID's

PAC-16-PR-PID-0001 PAC-16-PR-PID-0004 PAC-16-PR-PID-0007

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-16-PR-PID-0001 PAC-16-PR-PID-0004 PAC-16-PR-PID-0007

PAC-16-PR-PID-0002 PAC-16-PR-PID-0005 Drawn By Approved By Date

PAC-16-PR-PID-0003 PAC-16-PR-PID-0006 H. Eksi A. Doğan 26.04.2013Page:

23 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 24: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.6.2- Terminal Station Export Tank Group I

Screens P&ID's

PAC-16-PR-PID-0002

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-16-PR-PID-0002

PAC-16-PR-PID-0003 Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

24 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 25: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.6.3- Terminal Station Export Tank Group II

Screens P&ID's

PAC-16-PR-PID-0002

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-16-PR-PID-0002

PAC-16-PR-PID-0004 Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

25 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 26: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.6.4- Terminal Station Local User Tank Group

Screens P&ID's

PAC-16-PR-PID-0002

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-16-PR-PID-0002

PAC-16-PR-PID-0005 Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

26 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 27: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.6.5- Terminal Station Choke Station

Screens P&ID's

PAC-16-PR-PID-0001

CUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY PIPELINE SYSTEM

Customer : TEKFEN INSAATPAC-16-PR-PID-0001

PAC-16-PR-PID-0007 Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

27 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 28: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.6.6- Terminal Station Energy Monitoring

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

28 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 29: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.7- PIPELINE ADVISORY SYSTEM

2.7.1- Leak Detection System Signals

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

29 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 30: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.7.2- Mea Batch Tracking

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

30 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 31: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.7.3- Daoui Batch Tracking

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

31 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 32: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.7.4- El Halassa Batch Tracking

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

32 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 33: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.7.5- Head Station Batch Tracking

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

33 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 34: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.8- ANCILLARY SIGNALS

2.8.1- Pressure Monitoring And Valve Station Ancillary Signals

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

34 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 35: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.8.2- Pump And Terminal Stations Ancillary Signals

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

35 of 40Rev:

DA. Bürümcek

Customer : TEKFEN INSAAT

Controlled By

Page 36: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.9- EQUIPMENT BASED DISPLAYS

2.9.1- General Input/Output Equipment Faceplates

Digital Input Note 3

Analog Input Faceplate Note 1

Digital Output Note 4

Analog Output Faceplate Note 2

Note 1: For details, refer the FDS document, EMR-00-PR-DSR-0037 AI Modules Functional Design Specification (FDS)

Note 2: For details, refer the FDS document, EMR-00-PR-DSR-0117 AO Modules Functional Design Specification (FDS)

Note 3: For details, refer the FDS document, EMR-00-PR-DSR-0092 DI Modules Functional Design Specification (FDS)

Note 4: For details, refer the FDS document, EMR-00-PR-DSR-0112 DO Modules Functional Design Specification (FDS)

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

36 of 40Rev:

DA. Bürümcek

Controlled By

Page 37: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.9.2- Motor Type Equipment Faceplates

General Motor Faceplate Note 1

Pump with Gearbox Faceplate Note 2

Agitator Faceplate Note 3

Note 1: For details, refer the FDS document, EMR-00-PR-DSR-0101 MOTOR MODULES FUNCTIONAL DESIGN SPECIFICATION (FDS)

Note 2: For details, refer the FDS document, EMR-00-PR-DSR-0110 PUMP WITH GEARBOX MODULES FUNCTIONAL DESIGN SPECIFICATION (FDS)

Note 3: For details, refer the FDS document, EMR-00-PR-DSR-0109 AGT Modules Functional Design Specification (FDS)

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Controlled ByDrawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

37 of 40Rev:

DA. Bürümcek

Controlled By

Page 38: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.9.3- Valve Equipment Faceplates

Valve with 2 Input 2 Output Faceplate Note 1

Valve with 2 Input 1 Output Faceplate Note 2

Valve with Partial Stroking Faceplate Note 3

Valve with Analaog Setpoint Faceplate Note 4

Note 1: For details, refer the FDS document, EMR-00-PR-DSR-0097 TEK_VLV_22_CL Valve Module Functional Design Specification (FDS)

Note 2: For details, refer the FDS document, EMR-00-PR-DSR-0096 TEK_VLV_12_CL VALVE MODULE FUNCTIONAL DESIGN SPECIFICATION (FDS)

Note 3: For details, refer the FDS document, EMR-00-PR-DSR-0119 TEK_VLV_22PS_CL VALVE MODULE FUNCTIONAL DESIGN SPECIFICATION (FDS)

Note 4: For details, refer the FDS document, EMR-00-PR-DSR-0098 TEK_VLV_22PID_CL VALVE MODULE FUNCTIONAL DESIGN SPECIFICATION (FDS)

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Controlled ByDrawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

38 of 40Rev:

DA. Bürümcek

Controlled By

Page 39: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.9.3- Electrical Equipment Faceplates

Battery Charger Faceplate Note 2

Capacitor Bank Faceplate Note 3

Energy Monitoring Type 1 Faceplate Note 1

Energy Monitoring Type 2 Faceplate Note 1

Circuit Breaker Faceplate Note 4

Note 1: For details, refer the FDS document, EMR-00-PR-DSR-0100 Power Monitor Modules Functional Design Specification (FDS)

Note 2: For details, refer the FDS document, EMR-00-PR-DSR-0108 BATTERY CHARGER Modules Functional Design Specification (FDS)

Note 3: For details, refer the FDS document, EMR-00-PR-DSR-0114 CAPACITOR BANK MODULES FUNCTIONAL DESIGN SPECIFICATION (FDS

Note 4: For details, refer the FDS document, EMR-00-PR-DSR-0107 TEK_CB_CL CIRCUIT BREAKER MODULE FUNCTIONAL DESIGN SPECIFICATION (FDS)

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

39 of 40Rev:

DA. Bürümcek

Controlled By

Page 40: EMR 00 GE DIA 0060 Rev.D Custom Displays

2.9.4- Hydraulic Power Unit, Filter Unit and Anaylzer Faceplates

Filter Unit Faceplate Note 2

Filter Unit Faceplate

Hydraulic Power Unit Faceplate Note 1

Analyzer Type 1 Faceplate Note 3

Analyzer Type 2 Faceplate Note 3

Note 1: For details, refer the FDS document, EMR-00-PR-DSR-0118 HYDRAULIC POWER UNIT MODULES FUNCTIONAL DESIGN SPECIFICATION (FDS)

Note 2: For details, refer the FDS document, EMR-00-PR-DSR-0113 FILTER UNIT MODULES FUNCTIONAL DESIGN SPECIFICATION (FDS)

Note 3: For details, refer the FDS document, EMR-00-PR-DSR-0099 ANALYZER MODULES FUNCTIONAL DESIGN SPECIFICATION (FDS)

Screens P&ID'sCUSTOM DISPLAYS: KHOURIBGA-JORF LASFAR PHOSPHATE SLURRY

PIPELINE SYSTEM

Customer : TEKFEN INSAAT

Drawn By Approved By Date

H. Eksi A. Doğan 26.04.2013Page:

40 of 40Rev:

DA. Bürümcek

Controlled By