Session on Power Solution for AAISession on Power Solution Session on Power Solution for AAIfor AAI
Vikas Mishra
Date: 19-Dec-2011
We welcome AAI Officials to the Session
PreviewPreview� About Emerson
� Power Solution requirements
� SLD of Ideal Power Solutions
� Emerson’s Product Portfolio
� ATS
� TVSS
� UPS Systems
� Precision Air Conditioner
� Remote Monitoring
� Battery Chargers & DC Systems
Emerson: Creating Technology & Solutions For A World In ActionEmerson: Creating Technology & Solutions For A World In Action
� FY2011 Sales of $21 B
� We are one of The Fortune 500 Companies
� Founded in 1890
� Record of consistent long-term performance
� Global product/market leadership
� Recognized outstanding management process
� Strong global presence
� Solid financial position
� Over 108,000 employees and 245 worldwide plants
Emerson Network Power IndiaEmerson Network Power India
� Established in 1993 and formerly known as Tata-Liebert till 2001
� H.O. and R&D Center at Thane, Maharashtra
� ISO14001 and ISO-9001:2000 certified company
� Dedicated Team for tailored “Business-Critical Continuity” Solutions in:
� Infrastructure Vertical
� IT/ITES Vertical
� Telecom Vertical
� BFSI Vertical
� Government Vertical
Emerson India : ReachEmerson India : Reach
MUMBAI
PUNE
BANGALORE CHENNAI
COCHIN
SECUNDERABAD
BHUBANESHWARNAGPUR
INDOREBARODA
AHMEDABAD
JAMSHEDPUR
KOLKATA
GUWAHATI
LUCKNOW
NEW DELHI
CHANDIGARH
COIMBATORE
VIZAG
� 29 Branch Offices for sales & service divided in 4 zones
� 55 Business Partners across the country
� More than 1500 VARs / SIs across the country
� National Distributor –INGRAM MICRO
� Offices in Sri Lanka & Bangladesh
Power Solution requirementsPower Solution requirements� Higher Reliability
� Higher Availability
� Avoid potential failures
� Automatic recovery from critical failures
� Faster repair time
� Easy Manageability
� UPS management over the network (Remote UPS monitoring)
Power Solution with PRS Architecture for Critical Load, Option -1
Rectifier cum
ChargerInverter
Static
Switches
(Battery
Bank -1
1+1 // Card
Static Bypass
Maintenance Bypass
Rectifier cum
ChargerInverter Static
Switches
Static Bypass
Maintenance Bypass
Output ACDB
UPS- 2
1+1 // Card
SCVS
BCB-1
ATS
Input
TransformerPanel
UPS- 1
Spare
TVSS
TVSS
Battery
Bank -2
(BCB -2
TVSS
TVSS
3 Phase, 415 Vac,
4 Wire Paralleled
Output from
UPS-1 & 2
Power Solution with Dual Bus Architecture for Critical Load, Option- 2
Rectifier cum
ChargerInverter
Static
Switches
(Battery
Bank -1
LBS Card
Static Bypass
Maintenance Bypass
Rectifier cum
ChargerInverter Static
Switches
Static Bypass
Maintenance Bypass
Output ACDB
UPS- 2
LBS Card
SCVS
BCB-1
ATS
Input
TransformerPanel
UPS- 1
Spare
Output ACDB
Static Switch
Load
TVSS
TVSS
Battery
Bank -2
(BCB -2
Emerson’s Product PortfolioEmerson’s Product Portfolio� Automatic Transfer Switches (ATS)- ATS transfers the critical load to emergency sources reliably in the event of failure of utility power;
Features include neutral overlapping, repeatedly fast transfer operation, Microprocessor based control panel, Serial communication capability etc; Range: 30 - 4000A
� TVSS (Transient Voltage Surge Suppressior) - Offers Power Sure Panel Low & Medium exposure surge suppression systems; Features include compact; Repeatable surge current capability; monitors the status of all protection modes, including neutral to ground; easy, safe & maintenance free operation; Response time less than 0.5 ns; Available in 25kA, 50kA, 100kA & 160kA surge current capacities;
� UPS Systems (UPS) - Range: 600VA to 4800 KVA; State of the art Technology UPS Systems protecting the critical equipments from blackouts and brownouts.
� Precision Air Conditioners (PAC) - A complete line of high capacity precision air conditioning systems, from 6 to 60 tons, protects areas housing critical equipment with precise, reliable control of temperature, humidity and airflow. Floor mounted, Wall/Ceiling mounted, Rack mounted, Extreme density systems, Heat rejection & air conditioners for equipment rooms are available
� DC Power Systems - A complete line of DC power systems have been designed for modularity and easy servicing for the needs of DC dependent Telecommunication equipment (Network Access equipment, Transmission equipment, BTS, MSC, BSC, Microwave Communication equipment, Surface station of Satellite Communication); Range: (5A - 6600A) @ 48V . Also 110 V DC Power systems for Industrial applications.
� Static Transfer Switches (STS) - The STS is a solid-state, three-pole, dual-position transfer switch designed to automatically and manually switch between two synchronized three-phase AC power sources without an interruption of power to the load; Sensing and transfer time 4-6 ms; Types include Static Switch (6 kVA); Static Transfer Switch - 3-ph, (100-1000A);
� Power Distribution Units (PDU) - PDUs are designed to efficiently deliver conditioned power from UPS to Critical loads. Features include monitoring, grounding, expansion capabilities & custom distribution; Types include Precision Power Center (Available with Isolation Transformer, in 3-ph, 15 -225 kVA systems, upto 4 Panels each 42 poles); Remote Distribution Center (3-ph, 4-wire-plus-ground, 225A, 168 poles); Free standing rack distribution unit (3-ph, 4-wire-plus-ground, 225A, 168 Poles); Power Distribution units are also available with Static Transfer Switches
� Site Scan ,Web - Site Monitoring Solutions : Web- Based Site monitoring, Alarm Management and Trending/Analysis for critical sites; Shows exactly where is the problem, monitors virtually any piece of critical equipment located in next room/in a facility on other side of the country; oversees multiple facilities located thousand miles apart; Ability to interface with Building Management System/other facility supervisory equipment; Can be tailored to the specific requirements of critical support infrastructure; Applications: Computer rooms, Telecommunication centers, Industrial process control facilities, locations housing sensitive electronic equipment
� Battery Monitoring Solutions - Battery Monitoring solutions help in preventing battery failure, extending battery life, reducing maintenance cost & increasing safety; Features - checks the health status of each cell by proactive DC resistance test, scans pertinent battery parameters for every 4 sec; Trend Analysis; Remote notification; Types include BDS - 40(Designed for 12V sealed batteries; monitors upto 32 cells); BDS -256(Supports 2V, 4V, 6V, 8V & 12V modules; NiCd cells; Monitors 256Cells);
� Racks & Enclosure systems - Product range: Network racks, Server Racks, 19"racks/enclosures, Outdoor cabinets, Street cabinets, Wall case - wall mounted enclosures, 10"/19" wall mounted enclosures; Water cooled server racks up to 35kW; MaxLoad seisimic racks & Heavy load racks; ETS racks; Applications: IT & Telecommunications
� Data Center Solution - Emerson provides total turnkey Data Center solution for the passive infrastructure with Adaptive architecture which provides modularity, scalability and optimum total cost of ownership .
� Avocent solution - For Data Center Infrastructure management- This covers servers, networking applications, telecom gears from a single console including power management at individual asset level.
� Active Harmonic Filters
� Power Quality Audits
Overview of Emerson Products for You Overview of Emerson Products for You
AutomaticTransferSwitch
Generator
InboundPower
UtilityAC
DC Power Systems
TVSSDC Power System DC Power Interface
AC Power Systems
TVSSUPS PPC / PDU
OEM Embedded
Services- Maintenance
- Power Quality Audits
Racks
Precision Air
Conditioning SystemsTVSS
RACKS
Comprehensive Site Monitoring
ACTIVE FILTERSSTS
Commonly Used Transfer Switching MethodsCommonly Used Transfer Switching Methods
� Interlocking of Magnetic Contactors
(IEC 60947-4)
� Interlocking of Circuit Breakers
(IEC 60947-2)
� Switch Disconnectors or Changeovers
(IEC 60947-3)
Their Technical LimitationsTheir Technical Limitations
� Electrically Interlocked Magnetic Contactors
AC hum
Limited to approximately 600 amps
Continuous power consumption
� Interlocked Circuit Breakers
No AC hum
Not designed for repetitive switching
Contacts designed to open under overcurrents
Contacts not easily serviced
Automatic Transfer Switch (ATS)Automatic Transfer Switch (ATS)Automatic Transfer Switch (ATS)
� UL-1008 : 1.4 : “a transfer switch as covered by these requirements is a device that automatically transfers a common load from a Normal Supply to an Alternate Supply in the event of failure of the the normal supply and automatically returns the load to the normal supply when the normal supply is restored.”
� IEEE, NEMA ICS : “An automatic transfer switch is self acting equipment for transferring one or more load conductor connections from one power source to another.”
Automatic Transfer Switch (ATS)Automatic Transfer Switch (ATS)Automatic Transfer Switch (ATS)
A device which transfers electrical loads between two sources of power by using automatic controls.
Seven Functions of ATSSeven Functions of ATS
� Carries current continuously
� Withstands fault currents
� Detects power failures
� Initiates alternate source
� Transfers load
� Senses restoration of Normal
� Re-transfers load
ATS - Design CriteriaATS - Design Criteria
Single Solenoid Operator
� Simple and reliable
� True double-throw design
� Inherently interlocked
� Speed of operation
Single-Solenoid Operator – Normal PositionSingle-Solenoid Operator – Normal Position
Single-Solenoid Operator – Transferring Single-Solenoid Operator – Transferring
Single-Solenoid Operator – Emergency Supply Single-Solenoid Operator – Emergency Supply
Transfer Switch - FeaturesTransfer Switch - Features
� No Overheating
� True double-throw operation
� Wide Arc gaps
� Protection of main contacts
� Handle currents dependably beyond listed rating.
� Fastest operation
� Operates continuously on Either source
� Operator powered by the live source
� Neutral switching with overlapping contacts
� Inphase monitor for transfer of motor loads
Transfer Switch – available RATINGSTransfer Switch – available RATINGS
� Must be capable of carrying its rated current.
� 24 hrs. a day and 7 days a week
� No overheating
30 / 70 / 100
150 / 200
260 / 400
600 / 800
1000 / 1200
1600 / 2000
3000
4000
Automatic Transfer SwitchAutomatic Transfer Switch
� Complies with IEC-947-6-1
� CE Marked
� UL 1008 listed for total system loads
� Meets National Electric Code requirement
� Kema Keur Marked
Overview of Emerson Products for You Overview of Emerson Products for You
AutomaticTransferSwitch
Generator
InboundPower
UtilityAC
DC Power Systems
TVSSDC Power System DC Power Interface
AC Power Systems
TVSSUPS PPC / PDU
OEM Embedded
Services- Maintenance
- Power Quality Audits
Racks
Precision Air
Conditioning SystemsTVSS
RACKS
Comprehensive Site Monitoring
ACTIVE FILTERSSTS
BLACKOUTS
BLACKOUTS
HA
RM
ON
ICS
HA
RM
ON
ICS
SU
RG
ES
SU
RG
ES
LIGHTNING
LIGHTNING
EARTHINGEARTHING
SYSTEMSSYSTEMS
LINELINE
NOISENOISE
WIRINGWIRING
METHODSMETHODS
EMI
EMIR
FIR
FI
TE
LC
O
TE
LC
O
LIN
ES
LIN
ES
NE
TW
OR
KS
NE
TW
OR
KS
POPO
WE
R
WE
R Q
UA
LIT
Y
QU
AL
ITY
TH
ET
HE
BIG
BIG
PU
ZZ
LE
PU
ZZ
LE
Power Quality ProblemsPower Quality Problems
Voltage
Voltage
Fluctuations
Fluctuations
TRANSIENTSTRANSIENTS
Transients are (typically a few milliseconds duration)
SURGE
SURGENOISE
SURGE- LARGE AMPLITUDE VOLTAGE / CURRENT PROBLEM > 2x nominal Vp
EFFECT- HARDWARE DAMAGESOLUTION- TVSS WITH FILTERING ( LIFE INSURANCE)
NOISE - SMALL AMPLITUDE FAST RISE VOLTAGE PROBLEM < 2 x nominal VpEFFECT- SOFTWARE / HARDWARE ERRORS, SYSTEM LOCK-UP SOLUTION- FILTERING SYSTEMS OF CAPACITORS ARE GOOD
CAPACITORS & INDUCTORS ARE BETTER ( HEALTH INSURANCE )
TRANSIENT SOURCESTRANSIENT SOURCESêê Lightning StrikesLightning Strikes
êê Utility Line Work / System FaultsUtility Line Work / System Faults
êê MotorsMotors
êê Arc WeldersArc Welders
êê SwitchesSwitches
êê Power Factor Correction Power Factor Correction Capacitors ICapacitors Isurgesurge
E = I x R + L di/dt E = I x R + L di/dt
switch time switch time
STATISTICS ON POWER PROBLEMSSTATISTICS ON POWER PROBLEMS
IEEE Report “Impact of Utility Distribution Systems on Power Line Disturbance” 1976 GW-Allen and Seagall.
According to prominent IEEE report, 88.5% of all external
and internal power disturbances are Transients, Spikes and Noise.
Transient Voltageand noise
48.5%
Voltages Spikes40%
Under voltage, Under voltage,
Over voltage, Over voltage,
outages and others 21.5%outages and others 21.5%
IEEE STD 1100IEEE STD 1100-- EMERALD BOOKEMERALD BOOK
SECTION 8.4.2.5 SURGE PROTECTIVE DEVICES
Recommended practice is that surge protective devices (TVSS)
be applied to service entrance electrical switchboards and panelboards,
and panelboards on the secondary of separately derived systems
that support information technology equipment (ITE),
telephone, telecommunications,signaling,television
and other forms of electronic load equipment.
IEEE STD 1100IEEE STD 1100--1992 EMERALD BOOK1992 EMERALD BOOK
SECTION 9.11.3 UPS Surge Protection“Lightning and other transient voltage producing phenomena are
harmful to most UPS equipment and to sensitive electronic load
equipment (e.g., via an unprotected static-switch bypass path
around a UPS). Therefore, it is recommended practice that both
the rectifier-charger input circuit to the UPS and the associated
UPS bypass circuits ( including the manual maintenance bypass
circuit ) be equipped with effective Category “B” TVSS protection
as specified in IEEE Std. C62.41-1991.
The required protection should be attached in both the line-to-line
and line-to-ground modes. Low - inductance connections should
be employed for this protection. TVSS devices should be connected
to the available equipment grounding conductors, not to isolated
grounding conductors.”
IEEE Recommended TVSS Selection and all Mode ProtectionIEEE Recommended TVSS Selection and all Mode ProtectionIEEE
Std 1100-1999 CHAPTER 8
8.6.1 Selection
The selection of surge protective devices typically depends on the location of the device. The
surge protective devices are recommended to be sized per IEEE Std C62.41-1991 and IEEE
Std C62.45-1992 requirements to achieve proper coordination. Surge protective devices
should be listed to UL 1449-1996. Surge protective devices used for three-phase, four-wire
circuits are generally recommended to be connected in all combinations of line-to-line, line
to-neutral, line-to-ground, and neutral-to-ground. Surge protective devices for three-phase,
three-wire circuits are recommended to be attached in both the line-to-line and line-to-ground
modes. Surge protective devices may also be specified with high-frequency filtering
characteristics.
REQUIREMENTS OF SUPPRESSION REQUIREMENTS OF SUPPRESSION
EVALUATIONEVALUATION
uu VOLTAGE PROTECTION LEVEL <1000VpVOLTAGE PROTECTION LEVEL <1000Vp
uu LISTED WITH UL 1449LISTED WITH UL 1449--3 / CE / CUL 3 / CE / CUL
uu ALL MODE PROTECTION (LALL MODE PROTECTION (L--L/LL/L--N/LN/L--G/NG/N--G)G)
uu TESTING & MONITORING (LED / DRY Contacts)TESTING & MONITORING (LED / DRY Contacts)
uu RESPONSE TIME < 0.5nSRESPONSE TIME < 0.5nS
uu NOISE FILTERING NOISE FILTERING –– EMI/RFI EMI/RFI –– 40dB40dB
uu SAFE COORDINATED FUSINGSAFE COORDINATED FUSING
uu SERVICE AND SUPPORT SERVICE AND SUPPORT
uu VERIFIED SURGE CURRENT PROTECTIONVERIFIED SURGE CURRENT PROTECTION
ONE TIME / MULTIPLE TIMESONE TIME / MULTIPLE TIMES
Interceptor II LM Series
PowerSure AccuGuide
Accuvar
Liebert – TVSS ProductsLiebert – TVSS Products
DRS-SPD
Liebert PowerSureLiebert PowerSureLiebert PowerSure
• Ideal for Distribution & Sub Dist Board
• Surge Rating Capacity:
25kA, 50kA, 100KA per phase
• Fault Current Rating: 22 kAIC
• MCOV: 320VAC
• Response Time: < 0.5 nanoseconds
• EMI/RFI Attenuation: 40dB
• Standard Indication: LED, form C contacts
• Certifications: UL 1449-3, CUL
• Standard enclosure: ABS Plastic
• Standard LEDS indication, form C contacts
• Coordinated Silver Link Fusing with
individual MOV
Powersure - Low Exposure - LPL
Powersure - Medium Exposure - LPM
• Ideal protection for Distribution Boards
• Surge Rating Capacity:
100kA & 160kA per phase
• Fault Current Rating: 65 kAIC
• MCOV: 320VAC
• Response Time: < 0.5 nanoseconds
• EMI/RFI Attenuation: 40dB
• All Mode Protection: (L-L, L-N, L-G, N-G)
• Certifications: UL 1449-3, CUL
• Standard Enclosure: NEMA 12
• Standard indication:
LEDS, form C contacts & Audible Alarm
• Coordinated Silver Link Fusing with
individual MOV
� Ideal protection at Service Entrances (MDB)
� Surge Current Capacity:
160 kA to 1000 kA per phase
� Fault Current Rating: 200KAIC
� MCOV: 320VAC
� Response Time: < 0.5 nanoseconds
� EMI/RFI Attenuation: 60dB
� All Mode Protection: (L-L, L-N, L-G, N-G)
� Listed with UL 1449-3, UL 1283
� Complete NEMA LS 1 testing
� Standard Enclosure: NEMA 4
� Standard LEDS indication, form C contacts and Audible Alarm
� Coordinated Silver Link Fusing
� Optional: Rotary Disconnect, Surge Counters
� Built-In Testing- By pressing a push button to monitor each MOV/fuse link status
Interceptor IIInterceptor II-- High ExposureHigh Exposure
IEEE EMERALD BOOKIEEE EMERALD BOOK
Section 9.11.4
“Data (e.g.,control,data I/O cables,and other communication or signaling) that are metallic (not fiber optic) should also be equipped with suitable
surge protector devices.”
“Surge protectors should be placed on both ends of data cables for optimum effect.”
Main Dist.
Board3-Phase 415 VAC
Distribution Board
Sub Dist. Board
415VAC/ 230VAC
230VAC
LM,250kA/Phase Accuvar,160kA/Phase LPL,100kA/Phase
TV
SS
TV
SS
TV
SS
TVSS Installation at Electrical Panels(Standard Protection Solution)TVSS Installation at Electrical Panels(Standard Protection Solution)
Overview of Emerson Products for You Overview of Emerson Products for You
AutomaticTransferSwitch
Generator
InboundPower
UtilityAC
DC Power Systems
TVSSDC Power System DC Power Interface
AC Power Systems
TVSSUPS PPC / PDU
OEM Embedded
Services- Maintenance
- Power Quality Audits
Racks
Precision Air
Conditioning SystemsTVSS
RACKS
Comprehensive Site Monitoring
ACTIVE FILTERSSTS
Uninterruptible Power Supply (UPS)Uninterruptible Power Supply (UPS)
• Micro UPS (0~3kVA) for desktops, servers, telecom closets
• Small UPS (3~20kVA) with completely redundant system controls, power modules, battery modules and monitoring options
• Medium UPS (30~100kVA) with smaller footprint, higher efficiency and superior performance
� Large UPS (>100kVA) with continuous availability
–Dual-UPS Systems in Parallel
• Micro UPS (0~3kVA) for desktops, servers, telecom closets
• Small UPS (3~20kVA) with completely redundant system controls, power modules, battery modules and monitoring options
• Medium UPS (30~100kVA) with smaller footprint, higher efficiency and superior performance
� Large UPS (>100kVA) with continuous availability
–Dual-UPS Systems in Parallel
Medium UPS
Micro UPS Small UPS
Large UPS
Micro & Small UPS Product BasketMicro & Small UPS Product Basket
Range : 600VA to 20KVA
1KVA to 6KVA
10 & 20 KVA
6KVA
10KVA/20KVA
GXT – MT + and Adapt SeriesGXT – MT + and Adapt SeriesProduct Range
� GXT – MT + Series -1KVA / 2KVA / 3KVA
� Adapt Series – 6 KVA / 10 KVA / 20 KVA
� True ONLINE double Conversion Technology.
� Option of Using as Rack mountable Cum Tower Mountable
Key FeaturesKey Features
� Online VFI technology with Sinewave Output.
� Power Factor Corrected Input >0.9
� Cold Start on Batteries
� Internal Static and Mannual Bypass
� Handles all Potential Power Problems i.e Spikes, Transient, EMI/RFI, Harmonics etc
� Wide Input Voltage Window
119V to 280V up to 3KVA
176V to 276V for 6KVA
� Wide Input Frequency Range
40Hz to 70Hz ( Auto Sensing )
Other Features / Options Other Features / Options
� Remote monitoring through SNMP.
� Advanced Early Warning Shutdown through Multilink Software
� USB Port
� User configurable Settings ,Voltage & Frequency.
� Automatic Battery Test Feature Enable/Disable
� Flexibility of operation ( UPS or CVCF)
FEATURES OF S400DFEATURES OF S400D
Input Unity Power Factor Rectifier.
IGBT Based Rectifier and Inverter.
Input current distortion < 5%.
Parallel Redundant UPS.
Wide Input Voltage Variation of +15%, -25%.
Wide Input Frequency Variation of +/-10%.
Each UPS can support a Battery Backup of 1 Hours duration without the Need of Additional Charger.
Black start facility at full load as standard.
Battery test facility.
Black start disable facility if battery in fully discharged condition.
Inverter output short circuit protected.
Rectifier output short circuit protected.
Reverse Phase sequence operation.
Auto retransfer facility.
Adjustable synchronisation band from
+/-1 Hz to +/- 3 Hz in the steps of 1Hz.
FEATURES OF S400DFEATURES OF S400D (Contd.)
Liebert SX Liebert SX Powering real time businessPowering real time business
Salient featuresSalient featuresSalient features-High efficiency up to 94% in dual conversion mode-up to 98% in DIM mode
THDi<3%Clean grid
I/p PF >.99
No De-ration through entire load PF range
Automatic power adjustment on operating temperature
Maximum power availabilitykVA=kW
Full galvanic isolation as built in option
Rating available(kVA) : 66,88,110,132,176,220
Full compatibility with all type of load Full compatibility with all type of load Full compatibility with all type of load
Full compatibility with all types of loads
with PF up to 1 without de-rating
Fully compliant with leading power
factor loads
UPS do not require de-rating for
leading power factors and can be
connected to any load within the
nominal kVA and kW rating of the UPS
regardless of power factor.
�
�
�
Enhanced power qualityEnhanced power qualityEnhanced power quality
Improvement of short circuit behaviour, as individual phases can be
controlled more quickly
Synchronisation or phase angle precision between UPS output and
bypass supply even in the case of a distorted mains voltage
High flexibility in parallel operation
Advantages
�
�
�
Vector control technology
The performance of the converter is enhanced
A quick and flexible processing of data in DSP
Rapidly generating variable as a result
This allows a real time control of the UPS electronics
�
�
�
�
ABC : Battery Life Maximized up to 50%ABC : Battery Life Maximized up to 50%
1. Temperature compensated battery charger operation
2. Low ripple current
3. Time compensated end of discharge voltage
4. Wide input voltage range
5. Battery temperature monitoring
Cost Saving: Extended Battery LIFECost Saving: Extended Battery LIFE
• The parallel control is integrated in the renewed hardware architecture.
• No tests are required to convert a single unit into a parallel unit.
• A UPS can be paralleled within 10 minutes and only one communication cable is required.
Up to 8 units in parallel
Each UPS includes a bypass line
Modular parallel configurationModular parallel configuration
Parallel ready UPS-Plug and Play solution
Full Galvanic isolation (optional)*Full Galvanic isolation Full Galvanic isolation (optional)*(optional)*
Full Galvanic isolation (optional)*Full Galvanic isolation Full Galvanic isolation (optional)*(optional)*
Flexible DC bus Voltage Flexible DC bus Voltage Flexible DC bus Voltage
• Battery Compatibility
VRLA /Wet –acid / Ni-cd
• Flexib;ity in battery blocks
40 -50 12V monoblocks (240 cells to 300 cells )- 2V cells
Connectivity optionsConnectivity optionsConnectivity options
Overview of Emerson Products for You Overview of Emerson Products for You
AutomaticTransferSwitch
Generator
InboundPower
UtilityAC
DC Power Systems
TVSSDC Power System DC Power Interface
AC Power Systems
TVSSUPS PPC / PDU
OEM Embedded
Services- Maintenance
- Power Quality Audits
Racks
Precision Air
Conditioning SystemsTVSS
RACKS
Comprehensive Site Monitoring
ACTIVE FILTERSSTS
What is High Performance Air-conditioningWhat is High Performance Air-conditioning
HPAC systems are primarily designed for
– Cooling electronic / electrical equipment, rather than people.
– These pre-packaged systems offer excellent reliability.
– Typically have a high ratio of sensible-to-total cooling capacity and a high CFM/ton ratio.
2424ooCC
2727ooCC 2222ooCC 2424ooCC
2323ooCC
Office Technology room
2121ooCC
35%
50%
65% 45% 55%
50%
Temperature and RH RequirementsTemperature and RH Requirements
Defining today's Technology RoomDefining today's Technology Room
� Not just merely Computer / Server Rooms
� Encompasses
– Signalling Control Room
– Telicom Equipment Rooms
– Substation Control Rooms
– Server rooms / Data Centers
Server Room
Data Centre
Laboratories
Telecom Equipment room
VFD Room
Clean Room
MRI CAT scan
Signaling & sub station Control Room
Precision A.C
Application areas of Precision A.C.Application areas of Precision A.C.
Item Description HPAC Comfort Split/Window AC’s
Type of Mounting Wall / Floor Wall/Floor
Type of Discharge Room Room
Sensible Heat Ratio 0.9 - 1 0.6 – 065
Air Quantity 600 to 650 Cfm/TR 300-375 Cfm/TR
Duty Cycle Designed for 24X7X365 Hrs. Operation
Designed for 8X7X365 Hrs. Operation
Average Life Min.- 10 Years for 24Hrs. Operation
Max. life- 3 Years for 24Hrs. Operation
Body Construction Rigid (CRCA Powder-Coated Riveted Design
(Rugged Design)
CRCA Powder-Coated Screwed Unit ( 2.5TR) & Plastic Body Type
(1.5TR)
Running Cost (at nominal capacity Conditions)
1.05KW/TR 1.2KW/TR
Clubbing with Fire detection system
Possible No
Designed Ambient Temperature
Up to 43 deg C Designed at 38 deg C but Decrease in cooling at 43degC
HPAC Vs. Comfort Split / Window SolutionHPAC Vs. Comfort Split / Window Solution
HPAC Vs. Comfort Split / Window SolutionHPAC Vs. Comfort Split / Window Solution
Item Description HPAC Comfort Split/Window AC’s
Filtration 80%-85% down to 20 Microns
70% down to 20 Microns
Overload protection for individual components
Yes No
Indoor-Outdoor Copper Piping
Heavy Gauge Copper Soft Copper Piping
Piping Insulation FR Rated Ordinary foam
Cabling work FR LS Normal Type
Capital Investment ( Capex)
high Low
Running Cost (Opex) Low Higher
Indoor Unit Motor Direct Coupled with Blower & IP-44 Protection
Ordinary motor
Summary & Conclusion:- Technology Trend in CoolingSummary & Conclusion:- Technology Trend in Cooling
Tech
no
log
y �� ��
Window / SplitUnit
Comfort PAC
Chilled water& DX Plant
CW + PAHUCW + Dual Fluid
Industrial AC System
Time ����
Comfort High Performance
Solution for Modern Control Room
PAHU5 TR to 40 TR PeX
5 TR to 30 TR
UCS 24x7
3.5Tr,
6.5Tr,
7.5Tr
I/Split
2Tr,
3Tr,
4Tr
Overview of Emerson Products for You Overview of Emerson Products for You
AutomaticTransferSwitch
Generator
InboundPower
UtilityAC
DC Power Systems
TVSSDC Power System DC Power Interface
AC Power Systems
TVSSUPS PPC / PDU
OEM Embedded
Services- Maintenance
- Power Quality Audits
Racks
Precision Air
Conditioning SystemsTVSS
RACKS
Comprehensive Site Monitoring
ACTIVE FILTERSSTS
Comprehensive Site Monitoring Comprehensive Site Monitoring
SiteScan Web Server
A computer running SiteScan Web Server Software under Windows 2000, XP or other Java compliant OS. The SiteScan Web Server manages the database and servers web pages to the SiteScan Web Clients.SiteScan Web Client
Any PC on the network running Microsoft Internet Explorer 5.5 or higher.
Site Gate
Gateway/router module that interfaces the control module network to the BACnet/IP network. Site Link
Interface Module for Liebert Equipment. Also provides Modbus or BACnet to BMS systems.Site I/O
Interface Module for Dry Contact Closures or Analog Sensors
Site TPI-M
Interface Module for Modbus devices.
1
2
3
4
5
6
Ethernet LAN / WAN
Site Gate
Site I/O Temperature
SiteScan Web
Client
Fire / SmokeFire / Smoke
Site TPI-M
Site Link
1
2
3
4
5
6
Ethernet LAN / WAN
SiteScan Web
Server
SiteScan Web
Client
Typical Remote Monitoring Screen
Overview of Emerson Products for You Overview of Emerson Products for You
AutomaticTransferSwitch
Generator
InboundPower
UtilityAC
DC Power Systems
TVSSDC Power System DC Power Interface
AC Power Systems
TVSSUPS PPC / PDU
OEM Embedded
Services- Maintenance
- Power Quality Audits
Racks
Precision Air
Conditioning SystemsTVSS
RACKS
Comprehensive Site Monitoring
ACTIVE FILTERSSTS
TechnologyTechnology
Existing
Phase Controlled Thyristor Based Conventional Technology
Latest
High Frequency Switch Mode Technology
TechnologyTechnology
� Battery Charger function
TechnologyTechnology
� Ferroresonant Battery Charger
�
TechnologyTechnology
� SCR Controlled Battery Charger
TechnologyTechnology
Typical Switchmode Power Supply
TechnologyTechnology
SMPS Battery Charger
TechnologyTechnology
Technology ComparisonCOMPARISON
CRITERIAFERRORESONANT SCR SWITCHMODE
Efficiency Medium at full load
Low at light load
Medium High
Response Very Slow Medium Very Fast
Control Minimal Medium High
Size and Weight
Large / Heavy Large / Heavy
Small / Light
Noise Very Audible Audible Non Audible
Complexity Low Medium High
FeaturesFeatures� Efficiency > 90%
� Power Factor > 0.90
� Low EMI
� DC ripple ≤0.5%, regulation ≤1.0%
� MTBF > 3,00,000 Hours
� Hot swappable Charging Modules
� Intelligent Battery Management
� Online Insulation Monitoring
� Remote Monitoring
� Parallallable for redundancy
� Smaller in size & weight
Advantages
Performance ReasonsEnergy Efficient � Much better efficiency.
� Improved power factor.
High Reliability � Paralleling feature of charging modules.
� Very good MTBF of Charging modules.
� Compatibility to IEC & UL standards.
Increase in Battery Life
� Intelligent battery management.
� Improved DC characteristics.
Online Maintenance � Hot swappable design of charging module.
Suitable For All Type
of Batteries
� Wide DC output voltage range of charging modules.
AdvantagesAdvantages
Performance ReasonsCapacity Expansion � Modular Concept of Charging modules.
Space Saving � Smaller in size & light in weight.
Suitable For Manned & Unmanned Stations
Remote monitoring of parameters through RS485/ RS232 interface for the following.
� System status, performance & alarm functions.
� Status of individual battery cell voltage.
� Earth fault of individual feeders with fault indication.
� Individual feeder On / Off / Trip status.
Thyristor vs SMPS TechnologyThyristor vs SMPS Technology
Parameter Thyristor SMPSPrinciple of operation Phase Angle
Control Of Mains Frequency
High Frequency Pulse Width Control
Voltage Stabilization Tolerance
≥ ± 2% ≤ ± 1.0%
Current Stabilization Tolerance
≥ ± 2% ≤ ± 1.0%
Ripple Coefficient ≥ 2% ≤ 0.5%
Response Time ≥ 800 m. sec ≤ 1 m. sec
Power Factor at 100% Load ≤ 0.7 ≥ 0.9
Efficiency at 100% Load ≤ 80% ≥ 90%
Efficiency at 50% Load ≤ 70% ≥ 80%
MTBF ≤ 1,00,000 Hours ≥ 3,00,000 Hours
Standby Mode ( 1 + 1 ) Off line ( n + 1 ) Modules On line
Remote Control & Monitoring Poor Very Good
ComparisonComparison
Efficiency
� 10% more efficient at full load
� Much more efficient at 50% load ( normal working load )
� Net saving in energy units –
10% ( Minimum )70
75
80
85
90
95
Efficiency ( % )
Thyristor
Switch Mode
74
76
78
80
82
84
86
88
90
Efficiency ( % )
Thyristor
Switch Mode
ComparisonComparison
Power Factor
� Huge improvement in AC input Power factor
� Current drawn from the AC Mains is much lesser
� Reduction in current ratings of AC input cables, circuit breakers, fuses etc.
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
Power Factor
Thyristor
Switch Mode
Rectifier Operating PrincipleRectifier Operating Principle
Input
EMI
3PH
passive
PFC
AC/DC
DC/ACOutput
EMI
AC
inp
ut
de
tec
tion
pro
tec
tion
DC/DC
control and
protection
Ou
tpu
t vo
lt.,
cu
rren
t, an
d
tem
p s
ign
al
PCURS485
High
frequency
transformer
PWM
generator
3PH AC
input
DC
output
Rectifi-
cation
and
filtering
Au
xilia
ry
po
we
r
Charging ModuleCharging Module
� Features :
� Three phase three wire input.
� Wide input voltage range .
� Wide output voltage range.
� Efficiency up to 90% with low EMI.
� Hot swappable design.
� Active current sharing.
� EMC and Safety complies with IEC standard.
� Low output ripple, very good regulation.
� Increased battery life expectancy.
� Remote adjustment of parameters ensures
suitability for unattended installations.
Standard Models
110V DC / 10A
110V DC / 20A110V DC / 40A
220V DC / 05A220V DC / 10A
220V DC / 20A
Rectifier Module : 24V/ 75ARectifier Module : 24V/ 75A
Power Control Unit
� Features ;
� Remote monitoring.
� Control of system performance.
� Monitoring of system status.
� Visual / audio alarm for system failure.
� Event log.
� Can be used with both 110V & 220V Systems.
� Switching between float & boost charging.
� Current limiting charging.
� Temperature compensation.
RST button
Alarm indicator
Run indicator
Function keys
LCD
Power Control Unit
▪ Monitoring : The following parameters can be monitored on LCD display
.
• AC Voltage
• Load Voltage
• Battery Voltage
• Battery Current
• Load Current
▪ Status : Display the status of the following.
• AC input Circuit breaker
• DC output circuit breaker
• Battery fuse
• Surge Protection Device fault
Power Control Unit
▪ Alarms : The following alarms are provided.
• Input Circuit breaker trip • AC under / over voltage / fail
• Output Circuit breaker trip • DC under/ over voltage
• Battery fuse fail • Battery Cell under / over voltage
• Surge protection device fault • Battery bank temperature
abnormal
• Rectifier module fault • System insulation fail
• Communication interruption
▪ Host Communication : Communicate with the host in RS232 mode.
Insulation MonitorInsulation Monitor� Features ;
� Monitoring of
* On line insulation between DC bus &
earth.
* 2 independent buses simultaneously.
* Maximum 768 nos. of subsidiary branches.
� Suitable for
* Both 110V & 220V DC systems.
* Variable alarm settings to adopt to
different climates.
� EMC and safety meets relevant IEC
standards.
Battery DetectorBattery Detector
� Features :
� Monitoring of
* On line individual battery cell voltage
* Input Voltage range : 80 – 320V DC
* Maximum 24 nos. of battery cell voltages/
detector
* battery cell voltage range : 0.1V – 16.5V
� Isolated voltage measurement ensures stable &
safe operation.
� Capable for variable settings to adapt to
batteries of different makes..
Block Schematic DiagramBlock Schematic Diagram
ACDistribution
Unit
ChargingModule
( 1 )
SwitchingBus
ChargingModule( N+1 )
Distribution Monitoring
Unit
ControlBus
VoltageRegulator
InsulationMonitor
PowerControl
Unit
BatteryBank
Remote Monitoring
Outputs
Outputs
- ve
Output
+ ve
+ ve
AC Input - A
AC Input - B
BatteryMonitor
• Indicates DC Current path incase of AC Input failure
DC Power SystemDC Power System
AC Input DC Output
InsulationMonitor
DCDistribution
BatteryBank
Battery Detector
Power Control Unit(Monitoring Module)
Monitoring Center
DC Output :110.00 Volts
Charging
Modules
DC Power Systems – 220V/ 450ADC Power Systems – 220V/ 450A
Wall Mounted SystemWall Mounted System
Power indicator
Alarm indicator
PCU
Voltage regulator
Rectifier (two)
Bypass switch of
voltage regulatorCable entry hole
Cable entry holeInstallation hole (four)
EDCF-1 Sub rack SystemEDCF-1 Sub rack System
ApplicationsApplications
� Energy & Power : Generation, Transmission &
Distribution
� Petrochemicals, Oil & Gas : On shore, Off Shore
Pipelines
� Transportation : Railways, Airports, Shipping
� Instrumentation & Process Control : Chemicals, Steel,
Cement, Paper
� Other Industrial Facilities of Process Plants
Customer ListCustomer List• Adani Power- 220V/ 450A
• Numalighar Refinery Ltd. : 110V/ 400A
• Nirma - Ahmedabad : 110V/ 80A
• Reliance, Hazira - 220V/ 100A
• Jupiter - Jamshedpur : 110V/ 40A
• NTPC - Barh : 24V/ 400A / 600A / 900A
• Tisco - Jamshedpur: 110V/ 60A
• Essar Power Ltd - Hazira : 24V/ 600A
• Reliance Energy : 48V/ 35A
• Rainbow Papers Ltd – Ahmedabad : 220V/ 30A
• L&T : 110V/ 20A
• Ultratech Cement Ltd : 110V/ 40A
• DMRC : 110V/ 30A
Introduction to Liebert AF3Introduction to Liebert Introduction to Liebert AF3AF3
True Active Harmonic SolutionTrue Active Harmonic Solution
� Increasingly Sensitive Loads
� Increasing use of power electronics in equipments
� Increasing emphasis on power system efficiency and maximum utilisation
Why Power Quality Is Important?Why Power Quality Is Important?Why Power Quality Is Important?
Equipment demands this BUT gets this…..
Spike
Sag
Surge/SwellPower Fails
FrequencyChangeTransients Harmonic Distortion Noise
Types of Power Quality ProblemTypes of Power Quality ProblemTypes of Power Quality Problem
�Most commonly
detected problem
Harmonics Harmonics Harmonics
Harmonics Originators :
Nonlinear Load
� SMPS, DC power supply/chargers
� Uninterruptible Power System (UPS)
� Frequency converters
� AD/DC variable speed driver (VFD, ASD)
� Fluorescent lamps
� Welding machines
� Computers and peripherals
�What are harmonics?
� - Voltage or current waveform that are not at the desired 50 or 60 Hz fundamental
� frequency, but at some multiple frequency.
Effect Of HarmonicsEffect Of HarmonicsEffect Of Harmonics
� Overheating of Generator, motor, transformer.
� Overvoltage conditions on supply system.
� Increased transformer losses (need to over-size)
� Nuisance tripping of circuit breakers
� Improper operation of microprocessor-based equipment
� Overheating and possible resonance with capacitors
� Cause fire in wiring & other distribution system equipment
� Neutral burnout & the list can go on & on.
More than half of the total harmonics distortion is caused
by Third harmonics .
� Third (triple-n) harmonics in the phase conductors add in the neutral
- Neutral current can be up to 172% of phase currents
� Third harmonics circulate in the delta winding, causing overheating of the
Transformer
� Neutral conductors must be oversized
� Eddy current losses cause excessive heating in the transformer: De-rating
required
� Breakers Must be oversized
� Standard transformers DO NOT cancel harmonics
3rd Harmonics 3rd Harmonics 3rd Harmonics
�“3rd harmonics is also called triple-n harmonics which has 150Hz frequency “
� ( 3 * fundamental frequency i.e 50 Hz)
�Effects
� Survive
- De-rate Up-stream equipments
� Isolate
- Isolated the harmonic rich load
- Use of Line Reactors or Isolation transformers
� Divert
- Use tuned filters to reduce selected harmonics
�Cancel
- Use phase shifting techniques to cancel load generated harmonics
Harmonic Control TechniquesHarmonic Control TechniquesHarmonic Control Techniques
�Neutralize- Active Harmonic Filter
“Harmonics” one stop solution : Liebert AF3““HarmonicsHarmonics”” one stop solution : one stop solution : Liebert Liebert AF3AF3
What is Liebert AF3?
It is an active harmonic filter which neutralize the effects of harmonics & correct the power factor at the chosen level
Functions:
� Harmonic Compensation
� Reactive Compensation
� Load balancing
� Selectivity
Ratings Available - 30,60,100,150,300 Amps
Modus OperandiModus OperandiModus Operandi
� It is based on source current harmonic sensing.
� Source current is fed to high speed AD Converter of DSP.
� Source current harmonics are extracted by DSP.
� These harmonics are injected to the load by filter.
� This in turn takes only fundamental harmonic current from the mains.
Improves-Reliability of the electrical system -Reduces cable-Transformer losses…..
� Liebert AF3 latest technology to eliminate harmonics injected into the
mains supply by non-linear loads.
�Cancel the loads harmonic current and then obtain a sinusoidal current
in the utility.
Single Line Diagram for AF3Single Line Diagram for Single Line Diagram for AF3AF3
Product Features Product Features Product Features
� Synchronous Rotating Reference Frame principle
� 32 bit, DSP control
� PF compensation, leading as well as lagging
� Load Balancing
� Employees high speed IGBTs in power circuit
� Internal CAN Communication
� Closed loop active filter with source current sensing
�Continued …..
Product FeaturesProduct FeaturesProduct Features
� Required PF can be set from 0.7 to unity
� Selection between PF and harmonic compensation
� Remote monitoring and diagnosis
� Automatic current limit modification with respect to ambient temperature
� Alarm log with date and time stamp for fault diagnosis.
Close Loop Control Close Loop Control Close Loop Control
� Close Loop Control: CT installed at Source side
Close Loop Control is recommended.
External CT
xxxx/1
Close Loop Control
A B C
X2
CTA
X1
X1
X2
X1
CTB
X2
X2
CTC
X1
X2
X1
X2
X1
CTA CTB CTC
Enersine
Control ModuleExternal Terminal Input Terminal
Phase A
Phase B
Phase C
SOURCE
POWER
Phase C
Phase B
Phase A
LOAD
Control & Power Module
3CTs Wiring Schematic Diagram at Source Side for 3 phase 4 wires / 3 wires
� Close Loop Control
Liebert AF3
Close Loop ControlClose Loop ControlClose Loop Control
Case Study :120 kVA UPS with AF3 150 ACase Study :Case Study :120 kVA UPS with AF3 150 A120 kVA UPS with AF3 150 AA. Without Active Filter
Input Current 164 A
THDV 4.80%
PF 0.87
Voltage 217 V
THDI 27.40%
Power 93 KW
�Load Characteristics :
Continued..Continued..Continued..B. With AF3 (Only Harmonic Correction selected)
Input Current 146 A
THDV 3.70%
PF 0.92
AF3 Current 48 A
Voltage 221 V
THDI 4.00%
Power 93 KW
�Load Characteristics :
Continued..Continued..Continued..C. With AF3 (Power factor + Harmonic Correction)
Input Current 135 A
THDV 2.20%
PF 1
AF Bridge 95 A
Voltage 223 V
THDI 3.90%
Power 93 KW
�Load Characteristics :
Application AreaApplication AreaApplication Area
1. At the Input side of Rectifier, AC Drive, UPS
Harmonic & PF compensation
Continued 2..Continued 2..Continued 2..2.PF Compensation
Continued 3..Continued 3..Continued 3..3.At the source input.
1 AF3 at the Input of multiple UPS system
Liebert AF3 : Sizing calculationLiebert AF3 : Sizing calculationLiebert AF3 : Sizing calculation
� Present load current
� Measured value of THDi
� Power consumed
� Input PF measured
� Phase to Phase Voltage.
For sizing AF3 ,following data must be available;
Intuitive HMIIntuitive HMIIntuitive HMI
1. Status
2. ID
3. Input Voltage
4. Input Voltage Waveform
5. Input Voltage FFT
6. Input Current
7. Input current Waveform
8. Input current FFT
9. Input Power (KW)
10. Input Power (KVA)
11. No. of failures
12. Total Filter ON Time
13. Alarm log
14. Power Factor
15. DC bus Voltage
16. Filter Load %
17. Mains Frequency
18. Heat Sink Temperature
19. Date & Time
Following parameters are displayed
locally as well as remotely ;Front LCD Display on Liebert AF3
HMI Characteristics HMI Characteristics HMI Characteristics
� Harmonic spectrum upto 64 th harmonic of load & line current.
� True measurement of Input/output voltage ,current,Kva,kw,pf.
� Waveform-Showing real time display visual of input current, load current &Input voltage.
� Harmonics & pf configuration.
� All front display parameters including waveform can
be monitored through PC.
� Supports MODBUS protocol.
� Potential free contacts for monitoring the status of filter.
� Inbuilt SNMP & HTTP support*
*optional
OLED based graphic display showing :
Remote monitoring & Diagnosis.
CommunicationCommunication
Communication Application
RS-485/RS-422Ethernet
Remote Monitoring
Center
Monitoring
at site
Service at site
Local Control
Center
USB
RS-232
Connectivity DiagramConnectivity DiagramConnectivity Diagram
SpecificationSpecificationSpecification
We Welcome Your Queries & Views …..We Welcome Your Queries & Views …..
Colossal Thanks for your Valuable Time