emerging trends in diagnosis and condition assessment of power
TRANSCRIPT
Abstract—Health Index of transformer is a vital tool for relative
ranking of transformer from view point of its operation condition
criticality. It includes parameters that directly or indirectly affect the
operation and performance integrity of transformer. The present paper
envisages codes and criteria given under standards like IEC, IEEE,
CIGRE that are helpful for condition assessment and asset
management of power transformer . An exhaustive treatment of
affecting parameter has been covered entrusting vital information
related with criticality of Power Transformer outlay. It describes a
modern technique involving key parameters that can give clear cut
idea for classifying all transformer condition based on their HI under
the same umbrella.
Keywords—Dissolve gas analysis (DGA), Frequency domain
spectroscopy (FDS), Load Tap changer (LTC), Dissolved gas
analysis factor(DGAF),oil quality index factor(OQIF), Oil Quality
factor(OQF),Furan factor(FF) ,Load Tap changer Factor( LTCF),
Load index factor(LIF),Maintenance strategies and age factor
(MSAF).
I. INTRODUCTION
OWER transformer being most important equipment of a
power system utility whose cost accounts for around 60%
of the total investment.
The forced outage of transformer causes huge disturbances in
the electricity supply chain system and incur financial loss to
the company .Therefore its periodical or continuous condition
monitoring and proper diagnostics become crucial throughout
its life. From the time of manufacturing and transportation the
power transformer undergoes various faults and abnormalities
that may be incipient or external. Incipient fault are due to the
abnormalities within the transformer tank. That may be in its
insulation system, winding arrangement or associated parts
inside the transformer tank. These components actually
undergo various electrical and thermal stress deterioration due
to faults and abnormalities. The fault may be due to errors in
designing and malpractices in manufacturing technology that
may lead to abnormal operational parameters and deviation
Priyesh Kumar Pandey is with the National Institute of Technology,
Hamirpur, INDIA(+919805249405; e-mail:[email protected])
Harmendra singh is with the National Institute of Technology,
Hamirpur(H.P), INDIA (+9198882501243; e-mail:[email protected] )
M Rao is a faculty in EED with AITAM (.India)
R K Jarial is with the National Institute of Technology, Hamirpur(H.P),
INDIA (+919418847240; e-mail:[email protected] ).
from expected parameters. That ultimately led to failure of
transformer well below the expected life span.
Health Index (HI) is handy tool to represent the severity
and to quantify the various parameters that directly or
indirectly affect the aging and operational features of the
transformer. Also quality and priority based investment led
maintenance program can effectively optimise the asset
management 0needs [1, 2]. Several studies has been carried
out to develop a tool for asset management and monitoring of
substation and to formulate Health Index (HI) of transformers.
Introduction of smart diagnostics techniques such as SFRA,
DFR, PD Test, just to name a few, had eventually given idea
about the HI of the individual transformer on their individual
base but cannot give idea about relative HI of all transformer
within the utility on same platform simultaneously or sure shot
prescribed procedure that can cover all power transformer and
all parameters helpful to find HI because there is no
recommended standard. However HI calculation
recommended from [3] to [9] are based on all available data of
the transformer at a time.
II. PARAMETERS AND RECOMMENDED TESTS
According to the CIGRE WG 12 report, the main
subsystem of transformer that can directly or indirectly affect
the life of transformer and are involved in deterioration due to
the operational conditions are as follows [4]
A. Dielectric properties
Dielectric properties of insulation system. It consists of
major as well as minor insulation system. i.e. winding to
winding, winding to core, core to tank, interturn insulation,
insulation of bushings etc.
B. Magnetic properties
Magnetic properties of the magnetic system inside the
transformer. It consists of deterioration of core material or
clamping structure.
C. Tap changer
Tap changer healthiness .It may be referred to Load tap
changer (LTC).
D. Mechanical Integrity
Mechanical integrity of various parts of the transformer
such as bushing, tank, cooling system etc. In order to diagnose
Emerging Trends in Diagnosis and Condition
Assessment of Power Transformers Based on
Health Index
Priyesh Kumar Pandey, Harmendra Singh, M Rao, and R K Jarial
P
2nd International Conference on Emerging Trends in Engineering and Technology (ICETET'2014), May 30-31, 2014 London (UK)
http://dx.doi.org/10.15242/IIE.E0514591 108
faults within Power Transformer some important tests are
required to be conducted as per IEC/ASTM. TABLE I below
enumerate details of such test
TABLE I
CONDITION ASSESSMENT TEST
Online tests
Tests Detections Instruments
Dissolved
Gas
analysis
(DGA)
Measure gas concentration,
detects gas
intensity(ppm/time period),
sparking, Hotspot, Bad
electrical contact, Electric
discharge(High and low
energy) , Overheating,
cellulosic deterioration,
Internal flashover,
healthiness of insulation
system
Portable Dissolved Gas
Analyser, Kelmen,
Distributor India pvt ltd,
Bangalore.1
Partial
discharge
Partial discharge Partial discharge detection
using acoustic emission1.
Oil physical &
chemical
tests
Moisture in oil 1. DominoMoisture
in oil analyser(online)1
2. Karl fisher
Coulometric Titrator
(offline)1
Metal counts UV-VIS
spectrophotometer1
Furans cellulosic
deterioration
High performance liquid
chromatography (HPLC)1
sludge and sediment
formation
sludge and sediment
measuring system1
Acidity of oil Automatic acidity Titrator-
10200000 1
Oxidation inhibitor in oil Fourier Transform Infrared
Spectrometer1
Interfacial Tension Interfacial Tension
Analyser1
End of life of insulation
integrity(paper & oil +paper),
healthiness of insulation
system
Require laboratory
analysis for degree of
polymerization (DP)
measurement.
Oil
Electrical
tests
AC dielectric loss of oil,
Contamination, Relative
permittivity(dielectric
constant)
Automatic Capacitance &
tan delta test set(ELTEL)1
Breakdown voltage Microprocessor based oil
breakdown test1
Oil
Thermal
test
Flash point Automatic Flash point
Apparatus Model-FLPH,
Grabner Instrument1
Pour Point Pour point tester1
Paper
insulation
thermal test
Combined TGA-DTA-DSC Measures the thermal
changes in oil, oxidation
induction and
identification of paper
insulation degradation1
Physical
Inspection
(external)
Oil leaks, broken parts and
damages, cracks and external
arcing and overheating, loose
bolts and connections, pump
and radiators problems, Dust
accumulation of bushing and
its outer insulation system,
cooling problems, gauge
Done by expert staff with
binoculars for bushing
and lightening arrester
workings
Infrared
scan(IR
Imaging)
Hot spot, localised heating,
loose connections and joints,
Internal overheating(By
action of thermal
transmission), differential
over heating, cooling
troubles, overloading of
phases, circulating current,
bushing and Lightening
arrester thermal problems
Infrared thermal
imaging Camera1
Ultra sonic
and sonic
faults
detection
Internal partial discharge,
arcing , sparking, pump and
bearing impeller problems,
internal flash
UHF sensors and
Acoustic sensors
*Vibration
analysis
Internal core and winding
vibrations shield problems,
loose bolting.
Portable Dingle channel
Data collector cum
vibration analyser1
Sound
Level
Core energies problems and
external noise to compare
baseline for vibration tests
Sound level meter(e.g.
Quest 2400 sound meter)
Pollution,
humidity
level
Atmospheric conditions that
affect the flashover, treeing
and tracking
Corona Compare bushing and
Lightening arrester and all
high voltage connections
with same units
Corona scope, model cs-01-A
Offline tests
Doble
Power
factor and
insulation
resistance
between
ph-ph, ph –
ground
Loss of winding and bushing
insulation integrity, moisture
and contamination in
insulation of winding and
bushing.
Doble Test Equipment1
*Solid
insulation
electrical
tests
Dielectric frequency response
of paper insulation for
moisture determination
Automatic Insulation
Diagnostics Analyser
Model-DIRANA1
Excitation
current
Shorter turns of the winding
and phase connections
problems
Doble Test Equipment1
*Turns ratio Shorted winding turns and
voltage ratio errors Doble Test Equipment
1
*Leakage
reactance/s
hort circuit
impedance
test
Change in percentage
impedance with the specified
name plate values
Doble Test Equipment1
*Sweep
frequency
response
analysis(SF
RA)
Core and Winding
dislocation, Structural
integrity, transportation
damages
SFRA model
No.M5200,DOBLE1
Internal
Inspection
Oil sludging, displacement of
winding, loose connection ,
internal sparking and arcing
Boroscope
*Degree of
polymerizat
ion
Cellulosic insulation
deterioration and Life
expectancy
Require laboratory
analysis
1this equipment is available from National institute of
technology, Hamirpur (H.P) (INDIA) under TIFAC-CORE
centre on Power Transformer Diagnosis *Following test does not show health of the transformer as
its abnormal value cannot be compromised it needs immediate
action for preventing catastrophic failure or transformer may
2nd International Conference on Emerging Trends in Engineering and Technology (ICETET'2014), May 30-31, 2014 London (UK)
http://dx.doi.org/10.15242/IIE.E0514591 109
be declared faulty.
This paper along with testing techniques [5] gives
consolidated parameters that can affect the performance
indices and life of transformer
a) Vibration of core
b) Environmental condition (Humidity, pollution level, rain per
year, altitude of the site, number of surges and their
intensity)
III. METHODOLOGY
The most common methods currently used for condition
monitoring and diagnostics of Power Transformer are as below
[5].i.e.
A. Dissolved gas analysis (DGAF)
B. Oil quality factor(OQF)
C. Furfural Factor(FF)
D. Load Tap changer factor (LTCF).
E. Load history and Maintenance data(LIF).
A. Dissolved gas analysis (DGA)
DGA technique is well known tool for preventive
maintenance and its interpreted results may indicate active
incipient faults or abnormalities within the transformer tank.
However DGA should be individually taken for bushings and
all other oil filled terminals for complete diagnosis of
transformer. Routine test, diagnostics methods finds the gas
generations and measures the gas ratios. Mechanism for the
gas generation in the transformer may be arcing, partial
discharge, low energy discharge, overheating of insulation due
to severe overloading, failure of forced cooling systems or any
of the above. Practically DGA interpretation by itself cannot
provide sufficient information for incipient fault and
abnormalities to evaluate the integrity of the transformer and
its various subsystem because the governing standard fail to
evaluate condition for some abnormal ratios.
Several classis method and methods has been evolved for
DGA interpretation over the past 30 years such as Rogers,
Dorenburg, Duval triangle and modified Dorenburg
.[6],[7],[8],[9].
A1.1 Rogers’s ratio
The Rogers ratio is a simple scheme based on ranges of
ratios is used for diagnoses of faults. It uses four gas ratios
that are CH4/H2, C2H6/CH4, C2H4/C2H6 and C2H2/C2H4
[4]. The four conditions of the oil insulated transformer that
are detectable are normal ageing, partial discharge with or
without tracking, electrical and thermal faults of various
degree of severity. This method is also based on thermal
degradation principles and is also included in ANSI/IEEE[7]
Standard C57.104-1991. The validity of this method is based
on the correlation of results of a much larger number of failure
investigations with the gas analysis of each case. There are
diagnostic codes for the various faults and in this method there
are values of ratios that do not fit into the diagnostic codes.
Also for dissolved gases below the normal concentration
value, no consideration is given and due to this the exact
implementation of the method may lead to many
misinterpreted cases [10].
A1.2 IEC Method
Fault diagnosis scheme recommended by International
Electro technical Commission (IEC) originated from Rogers’
method except that the ratio C2H6/CH4 was dropped since it
only indicated a limited temperature range of decomposition.
Normal ageing, partial discharge of low and high energy
density, thermal faults and electrical faults of various degrees
of severity are the four conditions that are detectable.
However, no attempt is made to identify both thermal and
electrical faults into more precise subtypes. The first edition of
IEC method (IEC 60599-1978) is based on simple coding
scheme while the second edition (IEC 60599 – 1999) utilizes
the revised ratio ranges directly. Assessment of dissolved
gases for ‘normality’ limits is required before being
interpreted using ratios. Comparison limits in ppm are shown
in Tables 2 with different recommendations. To quantify fault
levels, an idea about the scoring and weighting factor for
individual gasses is required. Scoring is numerically
representing the range amount of gas level in ppm for
calculating DGAF.
TABLE II
COMPARISON LIMITS IN PPM
Gas Dorenburg
(ppm) IEC(ppm)
IEEE
(ppm)
Bureau of reclamation
(ppm)
H2 200 100 100 500
CH4 50 75 120 125
C2H6 35 75 65 75
C2H4 80 75 50 175
C2H2 5 3 35 7
CO 500 700 350 750
CO2 6000 7000 2500 10000
Weighting factor represent the importance of the gas level
for diagnostics based on particular diagnostics methods. It
may happen that the weighting factor of particular gas differs
from test to test. The detail are presented in Table 3.
TABLE III
SCORING AND WEIGHTING FACTOR FOR DGA GAS LEVEL [PPM][11].
Score(Si) Weight
(Wi) Gas 1 2 3 4 5 6
H2 ≤100 101-
200
201-
300
301-
700
701-
1800
>1800 2
CH4 ≤120 121-
175
176 –
350
351-
600
601-
1000
>1001 3
C2H6 ≤65 65-
80
80-
100
100-
120
120-
150
>150 3
C2H4 ≤50 50-
80
80-
100
100-
150
150-
200
>200 3
C2H2 ≤5 6-15 16-
35
35-
50
50-
80
>80 5
C O ≤350 350-
700
700-
900
900-
1100
1100-
1400
>1400 1
CO2 ≤2500 ≤3000 ≤4000 ≤ 5000 ≤7000 >7000 1
TDCG 690 691-1250 1251-
1785
1785-
2720
2721-
4630
>4700 3
2nd International Conference on Emerging Trends in Engineering and Technology (ICETET'2014), May 30-31, 2014 London (UK)
http://dx.doi.org/10.15242/IIE.E0514591 110
Interpretation of result is one of major challenges in diagnosis
process which is given in Table-4
TABLE IV
INTERPRETATION OF RESULT IN GAS DISSOLVED IN OIL [14]
Gases Interpretation
Oxygen(O2) Transformer seal fault Carbon monoxide(C O) Cellulose degradation Carbon Dioxide (CO2) Cellulose degradation Hydrogen(H2) Electric Discharge(partial discharge,
corona) with overheating Acetylene(C2H2 ) Electric Fault (Arcing, sparking ,
Internal flash) Ethylene(C2H4) Thermal Fault (High Hot
Spots formation and local overheating ) Ethane(C2H6) Secondary indicator of Thermal Fault Methane(CH4) Secondary indicator of Arc
or serious overheating TDCG CH4+C2H6+C2H4+C2H4+C2H2
+H2+CO+O2
Based on the scoring and weight factor for gas levels
given in table 3, A ranking method can be developed as
equation 1 as Dissolved Gas Analysis Factor (DGAF)[11]
(1)
Where “Si” is the scoring for each gas based in table 2 and
Wi is weighting factor allocated for each individual gas level.
With different values of DGAF ≥0.1, different conditions of
transformer can be concluded as given in table 5 below.
TABLE V
CONDITION BASED ON DGAF
Rating
Code Condition Description
4 Very Good DGAF<1.2
3 Good 1.2≤DGAF<1.5
2 Fair and acceptable 1.5≤DGAF<2
1 Fair but Caution 2≤DGAF<3
0.01 Need attention DGAF≥3
However it is recommended that proper period of oil
sampling and DGA should be done, if the result found is not
satisfactory and the condition is transformer is no below Fair
and acceptable values
B. Oil quality
Oil quality is a good indicator of condition of transformer, its
electrical, chemical properties clearly indicate the
deterioration of the internal parts of the transformer subsystem
but it has disadvantage that if the regular reclamation is being
carried out then actual condition of insulation inside the
transformer winding cannot be predicted. However evaluation
based on oil quality can be done by considering table 6
testing.
Oil quality is a good indicator of condition of transformer,
its electrical, chemical properties clearly indicate the
deterioration of the internal parts of the transformer subsystem
but it has disadvantage that if the regular reclamation is being
carried out then actual condition of insulation inside the
transformer winding cannot be predicted. However evaluation
based on oil quality can be done by considering table 6
testing.
TABLE VI
OIL QUALITY SCORE AND WEIGHT
Sr. Test IEC ASTM IS Score
(Si) Wi
1. Color and
appearance
ISO
2049
D-1524 IS-335 1,2,3,4 1
2. Dielectric
Breakdown
voltage
IEC-
60156
D-877 IS-6792 1,2,3,4 1
3. Water
content or
moisture
IEC-
60814
D-
1533B
IS-
13567
1,2,3,4 4
4. Acidity(NN
)
IEC-
62021
D-974 IS-1448
(P-2)
1,2,3,4 2
5. Dielectric
dissipation
factor(D)
IEC-
60247
D-924 IS-6262 1,2,3,4 3
6. Resistivity IEC-
60247
D-924 IS-6103 1,2,3,4 1
7. Sediments
and sludge
IEC-
61125
D-1524 IS-1866 1,2,3,4 1
8. Interfacial
Tension
ISO-
6295
D-971 IS-6104 - 1
9. Flash point ISO-
2719
D-92 IS-1448 1,2,3,4 1
10. Pour point ISO-
3016
D-97 IS-1448 1,2,3,4 1
11. Density IEC-
60814
D-1298 IS-1448 1,2,3,4 1
12. Kinematic
Viscosity
ISO-
3104
D-445 IS-1448
(P-25)
1,2,3,4 1
B.1 Transformer oil classification based on Neutralization
number (NN) and Interfacial Tension (IFT) and color [15]
In order to classify level of degradation of insulating liquid in
power transformer oil quality index number is ascertained as
Oil Quality Index Number (OQIN) =
TABLE VII
PROVIDE DETAIL OF MONITORING “OQIN”
Parameter
s
Range of values Quality of oil Score(Si)
IFT 30.0-45.0 Healthy and efficient, oil
in very good condition
4
NN 0.00-0.04
COLOUR PALE YELLOW
OQIN 300-1500
IFT 27.1-29.9 Beginning of sludge
Formation, Oil condition
normal
3
NN 0.05-0.10
COLOUR YELLOW
OQIN 270-600
IFT 24.0-27.0 Acid formation and
sludge accumulation on
winding and insulation
voids, oil need
Reclamation
2
NN 0.11-0.15
COLOUR BRIGHT
YELLOW
IFT 14.0-23.9 Continuous acid
formation and
deterioration of
transformer internals and
insulation system
1 NN 0.16-0.65
COLOUR AMBER,
BROWN,
OQIN 22-159
IFT <13.9 Sludge has been
deposited in and on
transformer parts at all
possible reach and
equipment may fail at any
time
0.01 NN >0.66
COLOUR DARK BROWN,
BLACK
OQIN <21
2nd International Conference on Emerging Trends in Engineering and Technology (ICETET'2014), May 30-31, 2014 London (UK)
http://dx.doi.org/10.15242/IIE.E0514591 111
The Dielectric strength test of oil is not extremely important
as the moisture in combination with oxygen and heat will
deteriorate cellulose insulation much before the dielectric
strength of oil indicates any symptom of abnormality. It also
lacks about information of sludge and acid formation.
Resistivity (specific resistance ρ) It is ratio of the DC potential
gradient in volt per centimeter paralleling the current flow
within the specimen to the current density in ampere per
square centimeter at a given instant of time and under
prescribed condition, measured in Ω-cm. It represents the
electrical property of oil in the test condition. Higher the value
of resistivity lower is the value of free oil, ion-forming
particle and no electrically active contamination. Based on the
above weighting and scoring percentage given in table 6, Oil
Quality Factor (%OQF) can be calculated as in equation (2)
(%)OQF= (2)
C. Furfural analysis
Furans are the group of organic compound that are formed
by the deterioration of cellulosic material in the transformer.
Overheating along with moisture and oxidation accelerate the
degradation of paper that results in furanic compounds.
Furfural test along with Degree of polymerization (DP) test
provide the information about the degradation of paper
insulation in the transformer oil. High level of carbon dioxide
and carbon monoxide generation indicate the need of furfural
analysis. Types of Furans that can be formed are [12].
1. 2-Furaldehyde(2-Fal)
2. 2-acetyl furan(2-ACF)
3. 2-Furfuryl alcohol(2-FOL)
4. 5-methul-2-furaldenhyde(5-MEF)
5. 5-hydroxylemethy-2-furaldehyde(5-HMF)
For scoring of the Furan analysis for transformer following
table 8 is helpful TABLE VIII
CONDITION OF TRANSFORMER BASED ON FURFURAL ANALYSIS
Normal
Paper
at 55 C
(2-FAL
counts)
hermally
upgraded
paper 65 C
(Total
Furan
counts)
Degree of
Polymerization
(DP)
Condition of
paper based on
Furan analysis
Furfural
factor
(FF)
60-300 50-200 800-6003 Normal
ageing 4
650-
2000
390-980 500-360 Accelerated
ageing 3
2375-
3275
1115-1450 340-300 Excessive
ageing,
Equipment in
danger zone
2
3850-
4525
1665-1900 280-260 High risk of
failure or high
probability of
fail
1
5300-
7333
2175-2845 240-200 End of life of
paper insulation 0.01
D. Tap changer (LTC) condition [5].
Insulation of tap changer basically depends upon the insulation
in the tap changer. i.e. oil, epoxy resin, fibreglass, pressboard etc.
Therefore individual diagnostics test can give cumulative idea
about the condition of Tap changer.DGA for oil in LTC can give
idea about the condition of insulation integrity of LTC. Scoring
and weighting of different LTC for various gasses in DGA
analysis in Table 9 TABLE IX
SCORING AND WEIGHTING FACTOR FOR LTC
Score(Si) Weight
Vaccume
LTC
Gas 1 2 3 4 Wi
CH4 <30 30-
50
50-
100
>100 3
C2H6 <20 20-
30
40-
50
≥50 3
C2H4 <50 50-
100
100-
200
≥200 4
C2H2 <3 3-4 4-5 ≥5 5
Resistive
LTC
CH4 <100 100-200 200-300 ≥300 3
C2H6 <50 50-
100
100-200 ≥200 3
C2H4 <200 200-400 400-600 ≥600 5
C2H2 <500 500-
1000
1000-
5000
≥5000 3
Reactive
LTC
CH4 <50 50-
150
150-250 ≥250 3
C2H6 <30 30-
50
50-100 ≥100 3
C2H4 <100 100-200 200-500 ≥500 5
C2H2 <10 10-
20
20-
25
≥25 3
E. Maintenance strategies, loading history and age
IEEE C.57-1995 and IEC 354 give recommendation of
conductor & oil temperature inside the transformer. However
IEC gives more conservative recommendation for conductor
temperature [16]
M0: Number of Si/SB that are lower than 0.6,i=0
M1: Number of Si/SB that are between 0.6 and 1,i=1
M2: Number of Si/SB that are between 1.0 and 1.3,i=2
M3: Number of Si/SB that are between 1.3 and 1.5,i=3
M4: Number of Si/SB that are bigger than1.5,i=4
Si : monthly peak load & SB is the rated loading of the
transformer
Then Load factor index can be given as (LFI)
LIF= (4)
Based on above equation 4 score can be given as in table 10
TABLE X
SCORING OF LIF
Score
(Li)
LIF
4 LIF≥3.5
3 2.5≤LIF≤3.5
2 1.5≤LIF≤2.5
1 0.5≤LIF≤1.5
0.01 LIF≤0.5
TABLE XI
2nd International Conference on Emerging Trends in Engineering and Technology (ICETET'2014), May 30-31, 2014 London (UK)
http://dx.doi.org/10.15242/IIE.E0514591 112
VARIOUS CORING TABLE FOR SCORING VARIOUS FACTOR FOR THI
Factors Score(Si)
DGAF 4,3,2,1,0.01
OQF 4,3,2,1,0.01
FF 4,3,2,1,0.01
LTCF 4,3,2,1,0.01
LIF 4,3,2,1,0.01
Taking the total accountability of factors given in table 11.
Total health index can be formulated as
Total health index(THI) =
TABLE XII
CONCLUDE ABOUT THE HEALTH OF TRANSFORMER AT THE TIME OF TESTING
THI Condition of
transformer
Maintenance requirement
1 Very good Normal maintenance
0.50 good Normal maintenance
0.25 poor Carry out diagnostic test and
refurbishment
<0.25 Poor and need caution Carry out diagnostic test well earlier
than normal and need clear attention
for parameter
<0.20 Very poor, invite
failure, Need urgent
replacement
Shut down transformer and carry out
refurbishment for further use and to
avoid catastrophic failure
IV. CONCLUSION
The determination of criticality level of fault in oil filled
power transformer is a virtual issue that can be resolved by
adhering to strict condition monitoring regime. The present
paper has highlighted novel technique to decide the criticality
and remedial aspect through exhaustive tests by forming HI.
The author are of firm opinion that if HI of equipment of
substation i.e. Power Transformer is evaluated, It can prevent
catastrophic failure and moreover a strategy can be evolved by
developing proper data bank of power transformer to
safeguard the Power Transformer.
ACKNOWLEDGMENT
The Author are thankful to TIFAC-CORE for providing
Testing facilities to conduct experiment and other
infrastructure for condition assessment of Power Transformer
for Thesis and Dissertation
REFERENCES
[1] hior Hjartarson,Shawn Otal. “Predicting Future Asset condition Based
on Current Health Index and Maintenance Level” IEEE 11th
International Conference on Transmission and distribution constrution,
Operation and Live-Line Maintenance ,2006,ESMO,Oct,2006.
[2] Nick Dominelli, "Equipment Health Rating of Power Transformers",
IEEE International Symposium on Electrical Insulation, Indianapolis, IN
USA, 19-22 September 2004, pp. 163 -168.
[3] "ABB Service Handbook for Transformers", 2nd edition, ABB
Management Service Ltd, Switzerland, 2007.
[4] I. Hhlein, A. J. Kachler, S. Tenbohlen, M. Stach, "Transformer
Management German Experience with Condition
Assessment"Contribution for CIGRE SC 12/A2, June 2003.
[5] A naderian,S .Cress,R.Piercy,F.wang,J.Service Kinenectrics Inc, "An
Aproach to Dtermine the health Index of power Transformers", IEEE
Electrical Insulation Magazine, November/December 2002 Vol. 18, No.
6
[6] M wang ,K D .Srivastva, “Review of the condition Assessment of
power transformer in service “,IEEE Electrical Insulation magazine,
November/December 2002-Vol.18,No.6
[7] IEEE Std C57.104-1991, "IEEE Guide for the Interpretation of Gases
Generated in Oil-Immersed Transformers", Transformer Committee of
PES, 1991
[8] IEEE Std C57.106-2006, "IEEE Guide for Acceptance and Maintenance
of Insulating Oil in Equipment", IEEE Transformers Committee, 2006.
[9] Michel Duval, "A Review of Faults Detectable by Gas-in-Oil Analysis
in Transformers", IEEE Insulation Magazine, May/June 2002 Vol. 18,
No. 3, pp. 8-17.
http://dx.doi.org/10.1109/MEI.2002.1014963
[10] Rogers, R., ‘IEEE and IEC codes to interpret incipient faults in
transformer, using gas in oil analysis’, IEEE ransactions on Electrical
Insulation, October 1978;13(5):349–54.
http://dx.doi.org/10.1109/TEI.1978.298141
[11] R.Phadungthin,E.Chaidee,J .Haema, and .Suwanasari, “Analysis of
Insulating oil to evaluate the condition of power transformer”,
ECTICON, Changmai ,Thailand,May 19-21,2010.
[12] Juthathip Haema, Rantankorn Phadungthin, “Condition Assessment of
the health Index for Power ransformer”
[13] ANSI/ IEEE Std. C57.94-1982, "IEEE Recommended Practice for
Installation, Application and Maintenance of Dry-Type Distribution and
Power Transformers."
[14] IEC publication standard 60599, “Guide for interpretation of dissolved
and free gases analysis” 1999-2007-05
[15] A GUIDE TO TRANSFORMER OIL ANALYSIS BY I.A.R. GRAY
Transformer Chemistry Services
[16] An Approach to Determine the Health Index of Power Transformers A.
Naderian, S. Cress, R. Piercy, F. Wang, J. Service Kinectrics Inc.,
Transmission and Distribution Technologies 800 Kipling Avenue
Toronto, ON, M8Z 6C4
[17] Facilities Instruction, Standards and Techniques Volume 3-31
Priyesh kumar pandey graduated in Electrical
Engineering from Atmiya institute of technology
and science Rajkot, Gujarat in the year 2009. He
worked as lecturer in Atmiya institute of
technology and science Rajkot for six months.
Then he worked in Gujarat state electricity
corporation Ltd for two years in the field of
operation and maintenance. His current research
interests include insulation condition assessment
techniques, specialising in the diagnosis of solid
insulation in transformer based of moisture
assessment. He is currently pursuing his M.Tech in Condition Monitoring
Control and Protection of Electrical Apparatus from NIT Hamirpur, India
Email: [email protected]
Harmendra Singh was born in Dehradun
Uttarakhand, India. He received B.Tech. degree
in Electrical and Electronics Engineering from
Graphic Era Institute of Technology, India, He
is currently pursuing the M.Tech. degree in
Condition Monitoring Control and Protection of
Electrical Apparatus from National Institute of
Technology, Hamirpur
Dr. R K Jarial received PhD from University of Rajashtan through MNIT,
Jaipur, India in 2007 and Masters Degree from National Institute of
technology Kurukshetra, Haryana, India in 1993 respectively. He is currently
working as Assosiate Professor in Electrical Engineering Department of NIT
Hamirpur, HP, India for the last twenty years. He has obtained One Patent
and has been instrumental in the establishment of TIFAC-CORE in Power
Transformer Diagnostics at NIT Hamirpur. His current areas of interests are
Power electronic drives and High voltage engineering.
2nd International Conference on Emerging Trends in Engineering and Technology (ICETET'2014), May 30-31, 2014 London (UK)
http://dx.doi.org/10.15242/IIE.E0514591 113