electrical safety in the workplace - egsa f07 deane...osha bases its electrical safety mandates on:...
TRANSCRIPT
![Page 1: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/1.jpg)
NFPA 70E Electrical Safety in the Workplace
KTR AssociatesEngineering Solutions Joseph Deane, PE
![Page 2: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/2.jpg)
Goal for Today
Better understanding of NFPA 70ERaise the awareness of Electrical HazardsWhy the sudden focusWhat one must do to become “70E”compliant
![Page 3: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/3.jpg)
Topics To Be Discussed
Define Electrical HazardsSafety NumbersIndustry Standards/Government RegulationsWhat is an Arc Flash?Sample Arc Flash StudyPPE Requirements
![Page 4: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/4.jpg)
Why do we need Electrical Safety?
Provide a safe work environmentReduce injuriesComply with regulationsReduce liabilityReduce operating costs
![Page 5: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/5.jpg)
What are the Electric Hazards?
ShockArc FlashArc Blast
![Page 6: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/6.jpg)
Terms and Definitions
• Electric Shock (Contact): Occurs when electricity (electric current) passes through the human body. Electric current passing through the chest area may result in death.
![Page 7: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/7.jpg)
Terms and Definitions
Arc Flash: Short circuit through air; defined as the rapid release of energy due to an arcing fault between two phase conductors (such as bus bar) or neutral or ground.
Arc Blast: Heating of the air and vaporization of metal creates a pressure wave than can damage hearing and other injuries. Flying metal parts are a hazard.
![Page 8: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/8.jpg)
Terms and Definitions
Incident Energy: Energy dissipated during an arc fault, or arc flash event. Measured in cal/cm2 .Arc Thermal Performance Value (ATPV): Minimum energy causing the predicted onset of second degree burns. A second degree burn is 1.2 cal/cm2 .
![Page 9: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/9.jpg)
Why the Recent Focus?
NFPA 70E standard now recognizes Arc Flash as a serious consequence and requires a Flash Hazard analysis be performed on facilities.OSHA has updated its Electrical Safety Procedures for the first time in 25 years.Effective date of OSHA’s updated regulations is August 13, 2007
![Page 10: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/10.jpg)
Electrical Statistics
At least one person a day is electrocuted in the workplace everyday
Over half of the deaths are from working “live”electrical circuits less than 600 volts.
Average of 4000 non-disabling and 3600 disabling electrical injuries occur in the US.
![Page 11: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/11.jpg)
Electrocutions by Year (Construction Safety Council)
474440
480 486
395
544
664
0
100
200
300
400
500
600
700
1992 1994 1996 1998
# Electrocutions
![Page 12: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/12.jpg)
Electrical Statistics
Five to 10 arc flash explosions occur in electrical equipment every day in the US.
Fourth leading cause of occupational fatalities.
Over 2000 workers are admitted to burn centers each year.
![Page 13: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/13.jpg)
Burn Costs
Average burn case costs $12 to $20 Million
Average hospital burn unit costs $400K per month
Average hospital burn unit stay 3 months
![Page 14: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/14.jpg)
Electrical Statistics
General IndustryOne fatality per 300 recordable injuries.
Electrical IndustryOne fatality per 10 recordable injuries.
![Page 15: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/15.jpg)
Electrician Survey
97% had experienced an electrical shock. 26% had witnessed an injury.58% were exposed to the possibility of an injury every day.
![Page 16: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/16.jpg)
Facts on Electrical Incidents
80% of electrically related accidents and fatalities among Qualified Workers are caused by Arc Flash.80% of electrically related accidents and fatalities among Unqualified Workers are caused by Electrocutions.Age 34 is the median age for someone killed working around electricity.
![Page 17: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/17.jpg)
OSHA & NFPA 70E
OSHA was created in 1969. It incorporated the National Electric Code (NFPA 70 standard 1971) into its electrical standard.
NFPA 70E Standard was created at the request of OSHA in 1979 to recognize the difference between design and workplace safety.
NFPA 70 (NEC) applies to installations (design).NFPA 70E addresses workplace safety.
![Page 18: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/18.jpg)
OSHA Regulations
OSHA bases its electrical safety mandates on:
CFR 1910 Subpart S (General Industry)CFR 1926 Subpart K (Construction)
OSHA recognizes NEC and NFPA 70E as an industry standards.
![Page 19: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/19.jpg)
OSHA Regulations
OSHA requires companies to follow its regulations and will cite companies for non-compliance under the General Duty Clause:
which states, “each employer shall furnish to each of its employees a place of employment that is free from recognized hazards that are likely to cause death or serious physical harm.”
![Page 20: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/20.jpg)
OSHA Regulations
OSHA is also citing companies for the following:
29 CFR 1910.335 (a)(1)(i): requires the use of protective equipment when working where a potential electrical hazard exists.29 CFR 1910.132 (d)(1): requires an employer assessment of all workplace hazards and the use of personal protective equipment.
![Page 21: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/21.jpg)
Who is the NFPA?
The National Fire Protection Association (NFPA) develops, publishes, and disseminates more than 300 consensus codes and standards intended to minimize the possibility and effects of fire and other risks.Virtually every building, process, service, design, and installation in society is affected by the NFPA documentation (Ex. the National Electric Code…NFPA 70).
![Page 22: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/22.jpg)
National Electric Code (NFPA 70)
Utilized for design and installation of electric facilities
Wiring and ProtectionWiring Methods and MaterialEquipment for General UseSpecial Equipment and Conditions
![Page 23: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/23.jpg)
Intent of NFPA 70E
Objective is to minimize exposure to electrical hazards for personnel working around electricity. This includes:
ElectriciansMechanicsHVAC techniciansPaintersPlumbersCarpentersProduction Workers
![Page 24: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/24.jpg)
Intent of NFPA 70E
Define Safe Work Practices to avoid injury.Define the requirements for an Electrical Safety Program.Define the requirements for TrainingDefine the requirements for PPE Applies to all types of employers and facilities, including employees, contractors, and construction workplaces.
![Page 25: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/25.jpg)
NFPA 70E Electrical Safety Standard in the Workplace
Chapter 1 – Safety Related Work PracticesChapter 2 – Safety Related Maintenance RequirementsChapter 3 – Safety Requirements for Special EquipmentChapter 4 – NEC Related Installation Material
![Page 26: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/26.jpg)
NFPA 70E covers…
Public and private buildingsCarnivalsIndustrial SubstationsAny installation of electrical equipment to the supply of electricity
![Page 27: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/27.jpg)
NFPA 70E does not cover…
UtilitiesShipsMinesRailwaysCommunication equipment under control of communication utilities
![Page 28: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/28.jpg)
NFPA 70E Chapter 1
Article 110 – Provides General RequirementsResponsibilityElectrical Hazard AnalysisTraining RequirementsElectrical Safety Program
Article 120 – Emphasizes Working De- energized & Describes the Work PracticesArticle 130 – Provides Requirements for Working On or Near Electrical Components
![Page 29: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/29.jpg)
Chapter 1 Responsibility
Employers are responsible for providing work practices and procedures.Employees are responsible for implementing them.
![Page 30: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/30.jpg)
Chapter 1 Multiemployer Relationship
Recognizes that more than one employer may be responsible for hazardous conditions on a worksite.Outside contractors are contractually obligated to the onsite employer.Both employers must share their Electrical Safety Programs with each other.
![Page 31: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/31.jpg)
Chapter 1 Multiemployer Relationship
Onsite employers and outside contractors shall inform each other:
Of existing hazardsPPE requirementsSafe work practice proceduresEmergency procedures
Coordination should include a meeting and documentation
![Page 32: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/32.jpg)
Chapter 1 Electrical Safety Program
What needs to be in it?
ScopePhilosophyPrinciplesResponsibilitiesSafety Procedures
![Page 33: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/33.jpg)
Chapter 1 Electrical Safety Program
PPE RequirementsControlsTraining RequirementsAuditingOther?
![Page 34: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/34.jpg)
Chapter 1 Training Requirements
Trained to understand the specific risks associated with electric energy.Trained on safe work practices and procedures.Trained on emergency procedures.Training may be both classroom and on the job.
![Page 35: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/35.jpg)
Training Session
Misc. Real World ExamplesRefeeding Panels (What needs to be checked?)Transformer Connections (Why they are important)Types of Grounding SystemsExplain how voltage is a difference in potential
![Page 36: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/36.jpg)
Chapter 1 Electrical Hazard Analysis
Requires an electrical hazard analysis, which is a study of a worker’s potential exposure to:
ShockArc Flash/Blast
It determines the appropriate levels of Personal Protective Equipment (PPE) and work practices.
![Page 37: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/37.jpg)
Electric Shock
The original purpose of NFPA 70EDetermine the voltage to which personnel will be exposed.Boundary RequirementsPPE Requirements
![Page 38: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/38.jpg)
Exposure to Shock
Requires exposure to a difference of potentialThe National Electric Code reduces this risk under normal conditions.NFPA 70E reduces the risk under abnormal conditions
![Page 39: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/39.jpg)
NEC Protects - Normal Conditions
![Page 40: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/40.jpg)
70E Protects - Abnormal Condition
![Page 41: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/41.jpg)
Effects of Electric Current on the Human Body
Amps < 1 mA Barely perceptible
5 - 10 mA Tingling sensation (annoying)
10 - 20 mA “Let Go” threshold (discomfort)
20 – 50 mA Painful, cannot “Let Go”
50 - 100 mA Ventricular fibrillation
Amps > 100 mA Cardiac arrest
![Page 42: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/42.jpg)
Electric current greater than the “Let Go” threshold ( current > 20 mA) contracts the human body’s muscles. Individuals unable to “Let Go” an energized line face life threatening damage to their bodies. If this current level continues for an extended period of time, respiratory paralysis is possible. Ventricular fibrillation (uneven pumping of the heart) causes death to lack of oxygen to the brain.
Effects of Electric Current on the Human Body
![Page 43: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/43.jpg)
Arc Flash/Blast
Electrical Arc between ConductorsIntense LightMolten MetalPressure WaveSound WaveShrapnelHot Air Rapid Expansion
![Page 44: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/44.jpg)
Dangers of Arc Flash
Arcs in enclosures, such as MCCs and switchgear, magnify a blast outward as energy is transmitted to the open side of the enclosure.Fatal Burns (Molten metal at high speed pressure).Falls from ladders (Blast pressure waves).
Hearing loss from sound blast.
![Page 45: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/45.jpg)
Causes of Arc Flash
ContaminationDust, Dirt or VaporCorrosionMoisture Ingress
Dropping tools or equipmentInsulation Breakdown/AgingNarrow Gaps
![Page 46: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/46.jpg)
NFPA 70E Arc Flash Hazard Analysis
A flash hazard analysis shall be done for two purposes:
Determine the arc flash protection boundary.Determine the proper PPE (rating of flame retardant clothing).
The Flash Protection Boundary is the approach limit from which a person could receive a second degree burn if an arc flash occurs.
![Page 47: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/47.jpg)
Sample Arc Flash Study
How do you do an Arc Flash Study?
Results of an Arc Flash Study
![Page 48: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/48.jpg)
IEEE 1584 Standard – Guide for Performing Arc Flash Hazard Calculations
Performing the Arc Flash Study
![Page 49: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/49.jpg)
IEEE 1584 Standard – Guide for Performing Arc Flash Hazard Calculations
Nine Step ProcessCollect system and installation dataDetermine system mode of operationDetermine bolted fault currentsDetermine arc fault currentsFind protective device characteristics and arc duration
![Page 50: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/50.jpg)
IEEE 1584 Standard – Guide for Performing Arc Flash Hazard Calculations
Nine Step Process (continued)Document system voltages and equipment classSelect working distancesCalculate the incident energyCalculate the Flash Protection Boundary
From this info, select the proper PPE
![Page 51: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/51.jpg)
![Page 52: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/52.jpg)
KTR Associates
![Page 53: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/53.jpg)
Purpose of Safety Related Work Practices (Article 120)
A set of rules that ensure an Electrically Safe Work Condition.De-energizing is safest work condition.Protect employees from:
ShockArc Flash burnsArc Blast injuries
![Page 54: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/54.jpg)
Steps to Create an Electrically Safe Work Condition (De-energized state)
Check drawings and identify all possible sourcesInterrupt load current and open disconnectsVisually verify opening of contacts where possibleApply lockout/tagout devices according to policyTest voltage and verify operation of testerApply grounds where necessary
![Page 55: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/55.jpg)
Working on or near energized circuits (Article 130)
Why work on energized circuits?
![Page 56: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/56.jpg)
Examples of working on energized equipment
Startup or troubleshootingLife Support systemsEmergency systemsVentilation systems for hazardous locations
![Page 57: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/57.jpg)
Examples of working on energized equipment
Infeasibility due to equipment design or operational limitations Circuits that are part of integral process.
![Page 58: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/58.jpg)
NFPA 70E Requirements for Working on or Near Live Parts
Complete Energized Electrical Work PermitPerform Hazard/Risk AnalysisSelect PPEEnsure task specific trainingConduct a job briefing
![Page 59: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/59.jpg)
Energized Electrical Work Permit
Requires written authorizationRequires the worker to:
Identify and understand the hazardsBe a qualified personWear proper PPERestrict access to unqualified personsComplete a job briefing
![Page 60: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/60.jpg)
No Permit Required When…
Testing (voltage, current, phasing)TroubleshootingCircuit Identification
![Page 61: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/61.jpg)
Approach Distances to Exposed Live Parts
![Page 62: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/62.jpg)
PPE Requirements
Protect against shock and burnsDesigned to protect specific areas of the body:
Head, face, neckEar protectionEye protectionBody protectionHand and arm protectionFoot and leg protection
![Page 63: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/63.jpg)
Flash Protection Boundary & PPE
When working within the flash protection boundary, PPE must be worn.PPE is determined by the level of incident energy exposure.
![Page 64: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/64.jpg)
Personal Protective Equipment (PPE)
Flash Hazard
Risk Category
Range of Calculated
incident energy
Min. PPE Rating Clothing Required
0 0 to 1.2 cal/cm2
N/A Untreated cotton
1 1.2+ to 4 cal/cm2
4 cal/cm2 FR shirt and pants
2 4+ to 8 cal/cm2
8 cal/cm2 Cotton underwear plus FR shirt and pants
3 8+ to 25 cal/cm2
25 cal/cm2 Cotton underwear plus FR shirt and pants plus FR
coveralls
4 25+ to 40 cal/cm2
40 cal/cm2 Cotton underwear plus FR shirt, pants, plus multilayer layer flash
suit
![Page 65: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/65.jpg)
Personal Protective Equipment (PPE)
Category 0 (Min. PPE Arc Rating N/A)Untreated CottonSafety Glasses
Category 1 (Min. PPE Arc Rating 4)Long Sleeve FR Shirt & PantsHard HatSafety GlassesLeather Gloves & Shoes
![Page 66: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/66.jpg)
Personal Protective Equipment (PPE)
Category 2 (Min. PPE Arc Rating 8)Cotton UnderwearFR Shirt & PantsArc Rated Face ShieldSafety GlassesHearing ProtectionLeather Gloves & Shoes
Category 3 (Min. PPE Arc Rating 25)Same as Cat 2 but include FR coveralls & Flash Suit Hood
![Page 67: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/67.jpg)
Personal Protective Equipment (PPE)
Category 4 (Min. PPE Arc Rating 40)Cotton UnderwearFR Shirt & PantsFull Flash Suit & HoodHearing ProtectionLeather Gloves & Shoes
![Page 68: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/68.jpg)
Labeling
NEC Article 110.16 requires arc flash labeling in electrical enclosures that might be maintained and accessed while energized.Switchboards, panelboards, industrial control panels, MCCs, etc.
![Page 69: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/69.jpg)
Arc Flash Labeling
![Page 70: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/70.jpg)
Warning Label Examples
![Page 71: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/71.jpg)
Recent Example of Arc Flash Incident
Electrician using multimeter shorted out resulting in three phase arc flash.Gloves and radiological PPE were melted and he suffered minor burns.Test equipment defective (CEN-TECH Digital Multimeter). No certification from a national testing laboratory.
![Page 72: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/72.jpg)
KTR Associates
![Page 73: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/73.jpg)
KTR Associates
![Page 74: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/74.jpg)
KTR Associates
![Page 75: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/75.jpg)
KTR Associates
![Page 76: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/76.jpg)
KTR Associates
![Page 77: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/77.jpg)
Sample Electrical Power Design
• Maintenance Mode Switch (utilizing Microprocessor- based Protective Relays Alternate Settings)
• Control cabinet containing switches to close breakers
![Page 78: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/78.jpg)
What must I do to become NFPA 70E compliant?
Conduct an Arc Flash hazard analysis.Provide labeling on electrical equipment per NEC article 110.16 “Flash Protection”.Document your Electrical Safety Program.Provide training to your employees.Provide the proper tools and PPE for job tasks employee would be performing.
![Page 79: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/79.jpg)
Other Issues to Think About
Determine Qualified vs Un-QualifiedWho’s permitted to reset CBs? Anyone?Which methodology should I use for calculating incident energy?
NPFA 70EIEEE 1584
Energized Work Permit…when do I need this?Circuit Breaker Interrupting RatingsWhen do I apply OSHA 1910.269?
![Page 80: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/80.jpg)
Don’t Learn Safety by Accident
KTR Associates
![Page 81: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/81.jpg)
Don’t Learn Safety by Accident
Stop ! Think ! Then Act !NFPA 70E is your guide for
Electrical Safety in the Workplace
![Page 82: Electrical Safety in the Workplace - EGSA F07 Deane...OSHA bases its electrical safety mandates on: CFR 1910 Subpart S (General Industry) ... Electrical Safety in the Workplace ...Authors:](https://reader034.vdocuments.mx/reader034/viewer/2022051509/5ad4a98b7f8b9a6d708be27f/html5/thumbnails/82.jpg)
Questions
Thank-you for your interest!