electric utility solutions: voltage regulation
DESCRIPTION
This is a systems engineering and analysis presentation from Milsoft's 2009 User Conference. It was originally presented by Bill Kersting. The Milsoft Electric Utility Solutions Users Conference is the premier event for our users and the vendors who provide interoperable solutions or services that enhance Milsoft Smart Grid Solutions. If you’d like to be on our mailing list, just email: [email protected].TRANSCRIPT
What is to be presented
• ANSI Voltage Standards• Methods of Voltage Regulation• Example of Regulator Settings• Example of Placement of Regulators
The ANSI Voltage Standards
• Range A– Nominal Utilization Voltage = 115 volts– Maximum Utilization Voltage = 126 volts– Minimum Service Voltage = 114 volts– Minimum Utilization Voltage = 110 volts
• Range B– Nominal Utilization Voltage = 115 volts– Maximum Utilization Voltage = 127 volts– Minimum Service Voltage = 110 volts– Minimum Utilization Voltage = 107 volts
Tools for Voltage Regulation
• Shunt Capacitors• Step-Voltage Regulators• Substation Load Tap Changing
Transformers
Distribution Line Voltage DropR jX
Load+
-VS
+VL
-
I
IRI
VS
VL jXI
ZI
0
Im(ZI)
Real(ZI)
( ) ( )Real Realdrop S r
drop L L L
V V V
V Z I R I jX I
= −
≈ ⋅ = ⋅ + ⋅
• Impedance (Z) and current (I) must be computed as accurately as possible.
• Impedance best computed using Carson’s Equations
• Current is a function of “load.”• If Z and I are not computed accurately, all bets
are off on the calculated system voltages.
Vdrop = Real(ZIL)
Capacitor Voltage RiseR X
Load+
_SV
+
_LV
LILRI
LjXI( )Real LZI
( )Im LZI
LV
LZI
SV
δ
θ
CI CRI
CjXI'SV
CIL CI I+
( ) ( )
'
Real Real
rise S S
rise C C C
V V V
V Z I R I jX I
= −
≈ ⋅ = ⋅ + ⋅
ANSI Range A Critical Voltages
LastCustomer
FirstCustomer
RegOutput
126124122120118
116114
Sub Reg
128
Laterals
Voltage Drop Assumptions
• 1 Volt drop on the service drop• 2 Volt drop on the secondary• 3 Volt drop through the transformer
• Minimum Voltage at the Transformer Primary Terminals will be 120 volts.
Voltage Profiles
LastCustomer
FirstCustomer
RegOutput
126124
122120118
116114
PointReg. Last
Xfm
Min Load
Max Load
Sub Reg
128
Laterals
Step Voltage Regulator
Type B Step Voltage Regulator
R
L
SeriesWinding
ReversingSwitch
PTControl
ControlCT
+
-
SL
-
+
ShuntWinding
S
L2N
PreventiveAutotransformer 1N
SV
LV
SI
LI
The Step Voltage Regulator Model
2
1
1
where: 1
L SR
L R S
R
V Va
I a INaN
= ⋅
= ⋅
=
1 0.00625 TapRa = ⋅
One tap change = 0.75 V change on 120 V base
Three Phase Voltage Regulator Model
[ ]L abcI[ ]S abcI
[ ]S abcV [ ]L abcV[ ] [ ][ ] [ ][ ] [ ]
S R L abcabc
S R L abcabc
L R Sabc abc
V a V
I d I
V A V
= ⋅
= ⋅
= ⋅
Voltage Regulator Model Matrix
[ ]
[ ] [ ] [ ]
_
_
_
1
0 0
0 0
0 0
R a
R R b
R c
R R R
a
a a
a
d A a −
=
= =
Compensator Circuit
+
-
+
-
line lineR Xj+
Reg. Point
dropV
regVPTN :1
1:1
p sCT CT−
RV VoltageRelay
cIc cR + jX
lineI
+ -
hi lowkVLL kVLL−
ratingMVA
Control Panel
Control Circuit
Line DropCompensator Relay
Voltage TimeDelay
MotorOperatingCircuit
Control Current TransformerLine Current
Control Potential Transformer
Regulator Control Settings
• Voltage Level – voltage to hold at the regulation point
• R and X setting (volts) – Equivalent impedance from the regulator to the regulation point
• Time Delay – time after a tap change required before the tap is changed
• Bandwidth – allowed deviation from the set voltage level
Equivalent Line Impedance
For , ,_
where: = actual line-to-neutral voltage output of regulator _ = actual line-to-neutral voltage at the regulation point
i ii
i
i a b cVreg Vreg ptZline
IregVregVreg ptIreg
=−
= Ω
= actual line current leaving the regulator
Compensator Impedance
Volts
where: equivalent line impedance in Ohms CT = current transformer primary rating
N potential transformer ratio = 120
pt
ratedpt
CTZcomp ZlineN
Zline
VLN
= ⋅
=
=
Bandwidth
Bandwidth = 2 V
123
122121Vo
ltage
Level
T∆
Modified IEEE 13 Node Test Feeder
1
13
2
3
5
6 789
14
1012 114
Modifications
• Line 4-12 changed to phases B-C• Transformer 6-7 changed to Ungrounded Wye – Delta• Load at Node 7 converted to Delta-PQ• Load at Node 8 converted to Delta-PQ• Load at Node 14 changed to phase B with constant Z
load• Load added at Node 5 phase c: 300 + j145.3 kVA• Interchange phase a and c distributed loads on line 3-4
Step 1
• Select regulation point to be Node 4.• Turn off regulator in Analysis Manager.• Run power-flow with source set to 126
volts (IEEE 13 Node Test Feeder Start.wm).• Display Voltage Profile.• Compute compensator impedance.
Step 1 Voltage Profile
1 2 3 4 5110
112.5
115
117.5
120
122.5
125
127.5
130
132.5
135
Node
Volt
age
135
110
V.a
V.b
V.c
51 Node
Voltages and Currents from Power-Flow Run
eg.
V2
2521.87 ej 0⋅⋅
2521.87 e j− 120⋅ deg⋅⋅
2521.87 ej 120⋅ deg⋅⋅
:= V4
2310 e j− 3.5⋅ deg⋅⋅
2377.5 e j− 124.6⋅ deg⋅⋅
2284.2 ej 116.1⋅ deg⋅⋅
:=
Ireg
590.8 e j− 34.4⋅ deg⋅⋅
632.5 e j− 150.5⋅ deg⋅⋅
651.9 ej 81.4⋅ deg⋅⋅
:=
Compensator R and X Setting
CTp 700= Npt 20=
Zlinei
V2iV4i
−
Iregi
:= Zline
0.1671 0.4037j+
0.0541 0.3817j+
0.1426 0.4188j+
=
Zavg mean Zline( ):= Zavg 0.1212 0.4014j+=
Zset ZavgCTp
Npt⋅:= Zset 4.2 14j+= volts
IEEE 13 with Regulator Set
• Set source voltage to 120 V.• Set regulator control.
– R and X = 4.2 + j14– Set voltage output (level) to 121.
• Analysis Manager– Set regulator to step.
• Run voltage drop.– Show results– Show profile
IEEE 13 with Regulator Set
Full Load with Regs, no Caps
1 2 3 4 5115
117
119
121
123
125
127
129
131
133
135
Node
Volt
age
135
115
V.a
V.b
V.c
51 Node
Use WindMil “Set Regulation”
• Select Voltage Drop.– Analysis Manager
• Set regulators to infinite. • Set source to 126 volts.
• Select Set Regulation.– Analysis Manager
• Select substation regulator.• Select Node 4 as load center.• Most desirable voltage = 121• Tolerance 2%• Unbalanced study
Set Voltage Regulation
WindMil R and X settings
WindMil with R 4.8, X = 14.4 and no feeder caps
• Set source voltages to 120.• Set voltage level (output voltage) to 121 V.• Run Voltage Drop.
WindMil R and X setting with no feeder capacitors
WindMil with regs, no caps
1 2 3 4 5115
117
119
121
123
125
127
129
131
133
135
Node
Volt
age Va
Vb
Vc
Node
WindMil Voltage Profile
Observations
• Regulator taps– Phase a: 12– Phase b: 13– Phase c: 15
• Concern that Phase c is near maximum tap• Concern about high voltage at Node 2• Need to add shunt capacitors
Shunt Capacitors
• Source reactive power– Phase A: 834 kVAr– Phase B: 805 kVAr– Phase C: 1040 kVAr
• Install shunt capacitors– Node 3: 100 kVAr per phases a,b,c– Node 4: 300 kVAr per phases a,b,c– Node 4: Switched 300 kVAr per phases a,b,c
WindMil R and X settings with capacitors
Full Load with Regs and Caps
Observations
• Regulator taps– Phase a: 6– Phase b: 6– Phase c: 8
• Concern for voltage unbalance at Node 4
Node 4 Voltage Unbalance
V4
119.8
124
121.4
:= Vavg mean V4( ):= Vavg 121.7333=
Devi V4iVavg−:= Dev
1.9333
2.2667
0.3333
=
Vunbalancemax Dev( )
Vavg100⋅:= Vunbalance 1.862= %
Minimum load of 50%
• Analysis manager– Set load growth to -50%
• Run voltage drop– Observe power factor at source– Switch 900 kVAr at Node 4
50% load reduction with all capacitors
50% load with all Capacitors
50% load with 900 kVAr at Node 4 switched off
1 2 3 4 5115
117
119
121
123
125
127
129
131
133
135
Node
Volt
age Va
Vb
Vc
Node
10% Growth with Original Capacitors
10% Load Growth
• Analysis Manager– Set load growth to 10%.
• Run voltage drop– Voltage profile– Check kVAr supplied by sub.– Install new shunt capacitors if necessary.
10% load growth with original capacitors
50% load reduction, switch off 900 kVAr at Node 4
10% Load Growth with original caps
10% Growth with 300 kVAr added at Node 10
10% Load Growth100 kVAr per phase added at Node 10
IEEE 34 Node Test Feeder
• Will be used to:– Determine location of downstream step
voltage regulators– Voltage level– R and X settings
• My method• WindMil method
Modified IEEE 34 Node Test Feederhttp://ewh.ieee.org/soc/pes/dsacom/testfeeders.html
9
301
8
21
22
23
2414
33
11 12 25
19 20
2615
27
28
29
16 1718
31
Sub
32
5
10
13
2 3 4 6 7
To Start
• System is very unbalanced.• System is very long (35 miles).• Voltage level is 24.9 kV.• Set substation output voltage to 126 volts.• Run power flow for the IEEE 34 node system
with no regulators or shunt capacitors (IEEE 34 Node Bare Bones).
IEEE 34 with no regulators and no capacitors
IEEE 34 with no regulators or capacitors
Install substation regulators
• Install 3 Step Voltage Regulators connected in grounded Y in the substation to start the regulation process.
• Potential transformer ratio = 14,400/120• Current transformer ratio = 100/0.1• Voltage level = 126 volts• Bandwidth = 2 volts• R and X = 0• Run power flow.
Modified IEEE 34 Node Test Feederhttp://ewh.ieee.org/soc/pes/dsacom/testfeeders.html
30
32
21
22
23
2414
33
13
10 11 12 25
19 20
2615
27
28
29
16 1718
31
Sub
1
2 3 4 5 6 7
8
9
IEEE 34 with Y connected sub regulators,Voltage Output (level) = 126, R and X = 0
Voltage Profiles with Substation Regulators with Voltage Level = 126
Observations and next step• Node 5 is the first node downstream where the voltage
drops below 120.• Select Node 5 as the regulation point for the substation
regulator.• Set regulators to infinite.• Run Set Regulator to compute R and X settings.• Set R and X on the sub regulator control.• Set voltage level on regulator to 120 volts.• Run power flow with regulators set as step.
Sub Regulator set with R = 14.4 and X = 9.6Voltage Output (level) = 120
Install Regulators at Node 5
• Set voltage level = 126• Regulator set to infinite• R and X = 0
IEEE 34 Node Test Feederhttp://ewh.ieee.org/soc/pes/dsacom/testfeeders.html
30
32
21
22
23
2414
33
13
10 11 12 25
19 20
2615
27
28
29
16 1718
31
Sub
1
2 3 4 5 6 7
8
9
Substation Regulators SetRegulators Installed at Node 5 Voltage Level = 126
Observations
• All voltages at Node 5 are between 119 and 121 volts.• The first downstream node where all of the voltages drop
below 120 V is Node 11.• Set regulators to Infinite.• Run Regulation Set to compute R and X from Node 5 to
Node 11.• Set regulators to step.• Run power flow.
Sub and Node 5 (R=16.8, X = 7.2) Regulators Set
Observations
• Install a regulator at Node 11.• Set voltage level to 126.• Set regulators to step.• Run Voltage Drop.
Regulator Installed at Node 5
30
32
21
22
23
2414
33
13
10 12 25
19 20
2615
27
28
29
16 1718
31
Sub
1
2 3 4 5 6 7
8
9
11
Reg at Node 11 Set to 126 Volts, R and X = 0
Regulator at Node 5 set with V = 126No R and X
• With the regulator set at 126 volts, all of the downstream voltages in the main feeder are greater/equal to 120 volts.
• No need to set R and X for this regulator• The only problems occur on the 4.16 kV
line from 19 to 20.
Profile including the 4.16 kV line
Install regulator at secondary terminals of the transformer
• Potential Transformer Ratio = 2400/120• Primary CT Rating = 100 amps• Calculate R and X.• Set regulators to Infinite.• Load center is Node 20. • Run Set Regulation.
System does not converge4.16 Reg set with V = 122, R = 12, X = 7.2
• Use Set Regulation to compute R and Xfor Reg 11 and Reg 20 with voltage output = 122.
Node 5: R = 9.6, X = 4.8; Voltage Output = 122 Node 20: R = 12, X = 9.6; Voltage Output = 122
Set source voltage to 120
• Run with no capacitors.• Add capacitors.
Source set to 120, no capacitors
Correct feeder power factor to near 1
• Display P and Q on 4.16 kV line.– Install a three phase capacitor bank to supply most of
the 4.16 kV kVAr load.– 75 kVAr/phase at Node 20
• Need to add 200 kVAr/phase– Node 16, 100 kVAr/phase– Node 822: 100 kVAr/phase A– Node 848: 100 kVAr/phase
Final with capacitors
Final Regulator Tap Positions
• Sub Regulator: 9, 8, 7• Node 812: 10, 6, 7• Node 830: 5, 6, 7• Node 888: 12, 12, 12
Final kVAr supplied by source
• Source power factor:– Phase a: 43 (PF = 99.8 %)– Phase b: 71 (PF = 99.5 %)– Phase c: 16 (PF = 99.9 %)
To be continued by you
• Minimum load– Which capacitors to switch
• Load growth– Where and how big new capacitor banks