electric power quality: voltage sags momentary interruptions · pdf file9.9 kw. slide 17...
TRANSCRIPT
![Page 1: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/1.jpg)
Slide 1
Electric Power Quality: Voltage Sags
Momentary Interruptions
Ward Jewell
Wichita State University
![Page 2: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/2.jpg)
Slide 2
Power Quality Events
Voltage sags
Outages/interruptions
Voltage swells
Capacitor switching transients
Lightning
Voltage notching
Harmonic distortion
Voltage flicker
EMI/RFI
![Page 3: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/3.jpg)
Slide 3
Power Quality Events
Voltage sags
10-90% of nominal
Outages/interruptions
< 10% of nominal
Instantaneous
½ to 30 cycles (½ sec)
Momentary
½ to 3 seconds
Temporary
3 seconds to 1 minute
Sustained
> 1 minute
![Page 4: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/4.jpg)
Slide 4
Table 2 of IEEE Standard 1159-2009 IEEE Recommended Practice for Monitoring
Electric Power Quality defines power quality events
![Page 5: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/5.jpg)
Slide 5
Voltage Sags also called voltage dips
Voltage drops to between 10% and 90% of its normal value – 120 V: Between 12 V and 108 V
– 480 V: Between 48 V and 432 V
Voltage stays low for at least ½ cycle
(0.008 seconds) to as long as 3 seconds – Less than ½ cycle is a transient
![Page 6: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/6.jpg)
Slide 6
Momentary Interruptions
Voltage drops to less than 10% of its normal value – 120 V: 0 – 12 V
– 480 V: 0 – 48 V
Voltage stays low for at least ½ cycle
(0.008 seconds) to as long as 3 seconds
![Page 7: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/7.jpg)
Slide 7
Who is causing voltage sags?
Georg Simon Ohm
(1789 – 1854)
V = I R
Voltage (V) = Current (A) x Resistance (W)
![Page 8: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/8.jpg)
Slide 8
Impedance for ac
Z = 𝐑𝟐 + 𝐗𝟐 (ohms W)
Ohm’s Law
Voltage (volts) =
Current (amps) x Impedance (ohms)
So voltage sags are a result of significant, intermittent increases in
current or impedance
![Page 9: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/9.jpg)
Slide 9
The cause of voltage sags: Impedance
(resistance and inductance)
![Page 10: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/10.jpg)
Slide 10
The cause of voltage sags: Impedance
(resistance and inductance)
![Page 11: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/11.jpg)
Slide 11
The cause of voltage sags: Impedance
(resistance and inductance)
![Page 12: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/12.jpg)
Slide 12
Motor
200 hp, 460 V
Full load current:
221 A
0000 copper wire
500’
Resistance:
0.025 W
460 V Breaker
Contact : 200 mW
Wire to lug: 100 mW
Breaker
Contact : 200 mW
Wire to lug: 100 mW
20 volts
= 4.3%
440 V
-4.3%
At the end of line 3:
Transformer
13.2 kV: 460 V
![Page 13: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/13.jpg)
Slide 13
Voltage drops are usually ok. What causes them to increase?
Georg Simon Ohm
(1789 – 1854)
V = I Z
Voltage (V) = Current (A) x Impedance (W)
![Page 14: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/14.jpg)
Slide 14
What causes impedance to increase?
![Page 15: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/15.jpg)
Slide 15
Motor
200 hp, 460 V
Full load current:
221 A
0000 copper wire
500’
Resistance:
0.025 W
460 V Breaker
Contact : 200 mW
Loose wire to lug: 0.2 W
Breaker
Contact : 200 mW
Wire to lug: 100 mW
Transformer
13.2 kV: 460 V
97 volts
= 21%
363 volts
-21%
![Page 16: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/16.jpg)
Slide 16
Motor
200 hp, 460 V
Full load current:
221 A
0000 copper wire
500’
Resistance:
0.025 W
460 V Breaker
Contact : 200 mW
Loose wire to lug: 0.2 W
Breaker
Contact : 200 mW
Wire to lug: 100 mW
Transformer
13.2 kV: 460 V
363 volts
-21%
Heat at good connection:
5.0 W Heat at loose connection:
9.9 kW
![Page 17: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/17.jpg)
Slide 17
Finding bad connections: Infrared Thermography
![Page 18: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/18.jpg)
Slide 18
Infrared Thermography
http://www.flir.com/flirone/ FlirOne for Iphone, $349
http://www.flir.com/instruments/content/?id=64755, TG165 Imaging IR Thermometer, $500
http://www.extech.com/cameras/ $1,000
http://en-us.fluke.com/products/infrared-cameras/
$1,500
![Page 19: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/19.jpg)
Slide 19
What causes current to increase?
Georg Simon Ohm
(1789 – 1854)
V = I Z
Voltage (V) = Current (A) x Impedance (W)
![Page 20: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/20.jpg)
Slide 20
What causes current to increase?
Induction motor starting – 150-500% current until full speed
Resistance heater starting – 150% current until hot
Short circuits
![Page 21: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/21.jpg)
Slide 21
NEMA starting codes
Letter
Designation
KVA per
Horsepower*
A
B
C
0.0 - 3.15
3.15 - 3.55
3.55 - 4.0
D
E
F
G
4.0 - 4.5
4.5 - 5.0
5.0 - 5.6
5.6 - 6.3
H
J
6.3 - 7.1
7.1 - 8.0
Letter
Designation
KVA per
Horsepower*
K
L
M
8.0 - 9.0
9.0 - 10.0
10.0 - 11.2
N
P
R
S
11.2 - 12.5
12.5 - 14.0
14.0 - 16.0
16.0 - 18.0
T
U
V
18.0 - 20.0
20.0 - 22.4
22.4 - & up
NEMA V: 22.4 kVA/hp = 25 x full load current!
NEMA D: 4.5 kVA/hp = 5 x full load current
![Page 22: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/22.jpg)
Slide 22
0000 copper wire
500’
Resistance:
0.025 W
460 V Breaker
Contact : 200 mW
Wire to lug: 100 mW
Breaker
Contact : 200 mW
Wire to lug: 100 mW
102 volts
= 22%
358 V
-22%
Transformer
13.2 kV: 460 V Motor
200 hp, 460 V
Full load current:
221 A
NEMA D
Starting current:
1130 A
![Page 23: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/23.jpg)
Slide 23
CBEMA curve
![Page 24: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/24.jpg)
Slide 24
CBEMA curve
78%, ½ second = 8 cycles
![Page 25: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/25.jpg)
Slide 25
Motor
200 hp, 460 V
Full load current: 223 A
0000 copper wire
500’
Resistance: 0.025 W
460
volts
Breaker
Contact : 200 mW
Loose wire to lug: 0.2 W
Breaker
Contact : 200 mW
Wire to lug: 100 mW
97 volts
= 21%
363 volts
79%, duration unknown
![Page 26: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/26.jpg)
Slide 26
CBEMA curve
79%, duration unknown
![Page 27: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/27.jpg)
Slide 27
Induction motor soft starter
30 hp (460 V, 40 A) – http://www.automationdirect.com
$450 for very basic – Start Time, Starting Voltage, Stop Time
$890 for full featured – Programmable, fault history,
communications for remote control,
30 hp motor $2,000 and up
Variable frequency drive ($>5,000) will soft start
![Page 28: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/28.jpg)
Slide 28
Short Circuits
![Page 29: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/29.jpg)
Slide 29
Phase A to ground fault at end of line 3
Substation
13.2 kV
End of line 1
Phase A: 8.8 kV
End of line 2
4.4 kV
End of line 3
0 kV
Phase B: 14.1 kV
+6.5%
15.0 kV
+14%
16.2 kV
+22.3%
6055 amps 6055 amps 6055 amps
![Page 30: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/30.jpg)
Slide 30
Protection against short circuits
Holz Kurzschluss an 20kV tree touches power line short circuit
![Page 31: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/31.jpg)
Slide 31
Protection against short circuits
![Page 32: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/32.jpg)
Slide 32
Short circuits utility system protection
substation recloser fuse
![Page 33: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/33.jpg)
Slide 33
Short circuits utility system protection
reclosers and fuses cause momentary
(or longer) interruptions
Utility might disable first (fast) trip. – fewer momentary interruptions
– longer sags
– more sustained interruptions.
![Page 34: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/34.jpg)
Slide 34
Short circuits and protective
operations also happen
during lightning
Transmission and distribution
lines should follow design
guidelines to minimize strikes
![Page 35: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/35.jpg)
Slide 35
Voltage sags and momentary outages: Effects on equipment
Usually a dc device
Low voltage on dc bus
Not enough energy stored in device to ride through low voltage
Example: a spinning motor has significant energy stored in its rotating mass. Turn off the power for a few seconds, it keeps spinning.
The same motor with a drive needs the drive to continue or resume operating .
![Page 36: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/36.jpg)
Slide 36
Voltage sags and momentary outages: Effects on equipment
Usually a dc device
Low voltage on dc bus
Not enough energy stored in device to ride through low voltage
Example: an oven has significant energy stored in its thermal mass. Turn off the power for a few seconds, it stays hot.
The same motor with a digital controller needs the controller to continue or resume operation.
![Page 37: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/37.jpg)
Slide 37
Effects on equipment
Usually a dc device
Low voltage on dc bus
Not enough energy stored in device to ride through low voltage
Example: digital devices – PCs and any device controlled by a microprocessor or
microcontroller
![Page 38: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/38.jpg)
Slide 38
Digital devices I have known
Spring winder
CT scanner
Gamma camera
ECG
Radio/TV transmitters
Theater lighting
Photo processing
Battery manufacturing/ charging
Printing
a/c testing
Cash registers
Industrial ovens
Motor drives
![Page 39: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/39.jpg)
Slide 39
If your equipment is malfunctioning, how do you
know it’s voltage sags or momentary interruptions?
Lights dim or go out
A motor started
There is a thunderstorm or wind
To confirm, you can measure
![Page 40: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/40.jpg)
Slide 40
Measuring power quality
![Page 41: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/41.jpg)
Slide 41
PMI Eagle 120
Single phase 120 V
$450
www.powermonitors.com
True RMS Voltage and Current
IEEE 1453/IEC61000-4-15 Flicker
Harmonics to the 51st
Minimum/Maximum/Average Recording
Real/Reactive/Apparent Power Recording
Waveform capture
![Page 42: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/42.jpg)
Slide 42
PMI Revolution
Three phase up to 600 V
$7,300 with current probes
www.powermonitors.com
Added features:
1 Megahertz, 5 kV voltage transients
USB/Ethernet/Bluetooth/Cell
![Page 43: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/43.jpg)
Slide 43
Power Standards
PQ1 Power Quality Relay
240 V
www.powerstandards.com/PQ1.php
$ 349
![Page 44: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/44.jpg)
Slide 44
Power Standards Lab
PQube
www.powerstandards.com/PQube.php#pqube
$1,645 for voltage only
690 V, 50/60 Hz
Voltage dips, swells, and interruptions - waveforms and RMS graphs
Frequency events, impulse detection, time-triggered snapshots
THD, TDD, Voltage and current unbalance, RMS Flicker
Daily, weekly, monthly trends. Cumulative probability, histograms, and more.
![Page 45: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/45.jpg)
Slide 45
Fluke
1750 3-Phase Power Quality Recorder
en-us.fluke.com
$14,000
voltage and current
3 phases plus ground
5 MHz, 8000 V waveform
![Page 46: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/46.jpg)
Slide 46
Fluke
435 Power Quality and Energy Analyzer
en-us.fluke.com
$8,000
voltage and current
3 phases plus ground
![Page 47: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/47.jpg)
Slide 47
Examples of sags and outages RMS vs. time plot
![Page 48: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/48.jpg)
Slide 48
Examples of sags and outages RMS vs. time plot
![Page 49: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/49.jpg)
Slide 49
Examples of sags and outages RMS vs. time plot
![Page 50: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/50.jpg)
Slide 50
Examples of sags and outages RMS vs. time plot
Voltage
10 minutes per division
122
0
![Page 51: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/51.jpg)
Slide 51
Examples of sags and outages Waveform Plot
10 ms/division
![Page 52: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/52.jpg)
Slide 52
Examples of sags and outages Waveform Plot
![Page 53: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/53.jpg)
Slide 53
Examples of sags and outages Waveform Plot
![Page 54: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/54.jpg)
Slide 54
Voltage and
current waveform
plots
![Page 55: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/55.jpg)
Slide 55
RMS voltage
and current plots
![Page 56: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/56.jpg)
Slide 56
Examples of sags and outages Text
![Page 57: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/57.jpg)
Slide 57
Solutions
Reprogram drives and PLCs
![Page 58: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/58.jpg)
Slide 58
Drive faults: page 8 of 9
![Page 59: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/59.jpg)
Slide 59
Drive faults: page 9 of 9
![Page 60: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/60.jpg)
Slide 60
Drive alarms: page 4 of 5
![Page 61: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/61.jpg)
Slide 61
Parameters: page 30 of 41
![Page 62: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/62.jpg)
Slide 62
Power Loss Ridethru
DC Bus Undervoltage Detection Level
– Factory setting: 380 V for 460 V drive
– Available settings: 300-420V
– If this is set lower than the factory setting, additional AC input reactance or DC bus reactance may be necessary. Consult the factory before changing this parameter setting
![Page 63: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/63.jpg)
Slide 63
Reactors for reduced dc bus voltage setting
http://www.mtecorp.com/products/dc-link-chokes/
http://www.mtecorp.com/products/rl-line-and-load-reactors/
480 V
drive
ac reactor
(can also be on the drive dc bus)
![Page 64: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/64.jpg)
Slide 64
Reactors for reduced dc bus voltage setting
low ac V
Low dc bus voltage
Reactors limit current surge to recharge dc bus
when ac voltage recovers
![Page 65: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/65.jpg)
Slide 65
Voltage notching
• Caused by dc motor drives • Causes other machines to behave strangely • Also solved with series reactors on dc drive
![Page 66: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/66.jpg)
Slide 66
Parameters: page 30 of 41
![Page 67: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/67.jpg)
Slide 67
Power Loss Ridethru
Momentary Power Loss Detection Selection – Factory setting: disabled
– Ridethru time up to 25 seconds or
– Ridethru if CPU power is still active
Momentary Power Loss Minimum Base Block Time
Momentary Power Loss Voltage Recovery Ramp Time
Momentary Recovery Time
![Page 68: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/68.jpg)
Slide 68
Solutions
»Apply these to digital part of system only whenever possible:
Uninterruptible power supplies
Ferroresonant transformers
Active series compensators
![Page 69: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/69.jpg)
Slide 69
Solutions Uninterruptible power supplies
Sizes available: watts to MW
Apply only to digital part of the load whenever possible – Keep it active, or gracefully shut down
For large loads, ride through until backup generator starts
ac in
Rectifier
(ac to dc)
Battery
charger Batteries
Inverter
(dc to ac)
Critical load)
UPS
![Page 70: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/70.jpg)
Slide 70
Uninterruptible Power Supplies
Cost depends on – Power capacity (kW or A at V; what is it powering?)
– Energy capacity (kWh, number and size of batteries; how long do you want it to run?)
Examples from apc.com: – 2.7 kW, 7 hours: $1,450 - $2,050
– 700 W, 1 hour, $310
– 40 kW, 30 seconds, $38,100
![Page 71: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/71.jpg)
Slide 71
Solutions Ferroresonant Transformers
Sola Constant Voltage Transformer – www.emersonindustrial.com
Sizes available: 10 to 7500 VA
Will not power inductive loads – Including induction motors
Cost 30 VA: $356 to 7500 VA: $7,200 – About $1/VA
1% output voltage regulation for input voltages between 80% and 110% of rated.
Protects against temporary voltage sags and swells between 65% and 120% of rated
![Page 72: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/72.jpg)
Slide 72
Solutions Active Series Compensator
120 – 240 V single phase
1000 - 5000 VA
www.measurlogic.com
![Page 73: Electric Power Quality: Voltage Sags Momentary Interruptions · PDF file9.9 kW. Slide 17 Finding bad ... Transmission and distribution lines should follow design ... 1 Megahertz, 5](https://reader031.vdocuments.mx/reader031/viewer/2022022501/5aa784a47f8b9ac5648c36ab/html5/thumbnails/73.jpg)
Slide 73
Solutions Active Series Compensator