High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
HIGH-VOLTAGE CIRCUIT BREAKERS DYNAMIC
CHARACTERISTICS TESTING INSTRUMENT
User manual
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
2/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
Catalog
HIGH-VOLTAGE CIRCUIT BREAKERS DYNAMIC CHARACTERISTICS
TESTING INSTRUMENT ......................................................................................................I
CHAPTER 1.ABOUT THE PRODUCT.................................................................................1
CHAPTER 2.THE FRONT-PANEL INTRO.........................................................................4
CHAPTER 3.OPERATE INTRO............................................................................................8
CHAPTER 4.PC SOFTWARE INTRO................................................................................17
CHAPTER 5.EXAMPLE.......................................................................................................21
CHAPTER 6.COMMON FAULT ANALYSIS.....................................................................25
CHAPTER 7.BILL OF ASSEMBLY.....................................................................................26
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
3/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
CHAPTER 1. ABOUT THE PRODUCT
1.1 Summarize
The High-Voltage Circuit Breakers dynamic characteristics testing
instrument is my company designed to meet the need of testing High-
Voltage Circuit Breakers . It takes the ARM7 unit for core to sample,
process and then output; the main characteristic is that its operated in
alt. It has many advantages such as intelligence, multi-function, accurate
data, strong anti-jamming, easy operation, small size, beautiful
appearance, etc; It can test the Circuit Breakers as follows: indoors or
outdoors Circuit Breakers with less oil or more oil, vacuum Circuit
Breakers, SF6 Circuit Breakers and so on.
1.2 Major testing items and functions
1Twelve contacts closing time and opening time
2Reclosing time
3Opening or closings asynchronism
4springing time or springing times
5 clearance between open contacts/gaps, over-travel, over-shoot
and springback
6speed at instant of contacts touching (separating)7Opening (Closing) max speed
8Opening (Closing) average speed
9Operating current curve
10Display and Print data and curve
1.3 Major technique parameter
1Time
Simultaneity measure Contacts 12
range06s
resolution ratio0.01ms
2Travel
range250mm
resolution ratio0.01mm
3Error
Time measure error0.1%
Travel measure error1mm
4Speed measure range020m/s
5Internal Power
Output Voltage20V265V error1%
27 1
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
4/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
6Operating conditions
operating voltageAC220V10 %
frequency50Hz
Power dissipation 60wambient temperature040C
ambient humidity 90%RH
bulk400350200 mm3 weight7kg
1.4 Definition of Terms
Touch speed Circuit Breakers is closing the speed at instant of
contacts touching
pswhen cant measureusing the average speed at 10ms as far
as the Circuit Breakers touched to instead of
Separate speedCircuit Breakers is openingthe speed at instant
of contacts separating
pswhen cant measure using the average speed at the Circuit
Breakers separating as far as 10ms to instead of
Average speed clearance between open contacts/gaps divide
time
Picture 1 Closing Curve Analyze
2
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
5/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
2 Opening Curve Analyze
3
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
6/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
CHAPTER 2. The front-panel Intro
1.5 The front-panel disposal diagram
Picture 3 Panel
4
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
7/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
1.6 Test Contacts time
Picture 4 Contacts
Picture 5 Contacts connection
The socket in right upper panelpicture 4is times contact.
Using the time measure lines connector to insert the socket and the
other connector, three clamps, to clamp the Circuit Breakers A, B and C.
three phase.
connect as picture 5
Grounding port connects each moving contacts (each moving
5
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
8/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
contact jumps out themselves).
Ps : A1 contact is installed the senor
1.7 Power Circuit Breakers
Picture 6 Power Switch
Please using the power wire by our company supply connects to the
power socket in the flank of the instrument, turn on the power Circuit
Breakers. If the instrument no work, check the fuse within the power
socket
Power requirementthe input AC Power must require
220V10%,50Hz.Make sure earthing.
1.8 Control Output
When power on, user can choose internal power or external power
in software. if choose internal power, the instrument supply power by
closing socket or opening socket(DC +) and common socket(DC -)(as
picture 7),if choose external power, the instrument dont supply power.
When chosen, the corresponding led will light.
6
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
9/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
Picture 7 operating
Picture 8 Power Led
warning: 1. External power, common socket connect K+.
2. Internal power, common socket connect K-.
3. Internal power, system DC source turn off.
1.9 Senor
Picture 9 senor
Using the senor data wire connects the senor and sample input
socket.
7
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
10/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
1.10 DC output Intro
Picture 10 DC output
User can choose internal power in software, set the DC output valueand turn on air Circuit Breakers. When into closing, opening or
reclosing test interface, the +,-sockets output DC current. This is using
stored energy to High-voltage Circuit Breakers Motor.
1.11 Button intro
Picture 11 Button
Reset Buttonreset machine
Optical Encoder: make the cursor move and change the value.
Turn leftCursor moves to left or upper.
Turn rightCursor moves to right or bottom.
Push downchoosing
Ps: On normal Optical Encoder turn once, cursor move once. But at
curve analyze Encoder turn once, cursor moving until Encoder turn
back.
CHAPTER 3. Operate intro
1.12 Closing Test
8
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
11/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
When power on, display as picture 12
Picture 12 the main interface
First choose the kinds of Circuit Breakers, oil, vacuum,SF6 Circuit
Breakers. appear the next menuas picture 14user can set the
instrument configure, average speed and instant speed(vacuum no)
the instrument configure,
first choose internal or external powerif choose internal
powermust set the output DC value between 0V~220V
secondchoose internal trigger or external trigger
thirdif sample input connect the linear Sensor, choose linear and
set the total length(25 or 250 mm). if sample input connect the Angle
Sensor, choose Angle and set mm/.
This setting can auto save.
9
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
12/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
Picture 13 Next menu
After, user can choose the Close to run closing test.
Set time. For example, if the Circuit Breakers need 200ms to run, we
can set time 0.3s.
Click runinto the interface as Picture 14.
Picture 14 closing test running
If no error tip, turn to the result interface. But if Relays inside the
machine no work, will turn to the error interface as Picture 15,16
10
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
13/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
Picture 15 relays error Picture 16 Circuit Breakers error
1.13 Opening test
When power on, display as picture 12
First choose the kinds of Circuit Breakerses, oil, vacuum,SF6 Circuit
Breakers. appear the next menuas picture 14user can set the
instrument configure, average speed and instant speed(vacuum no)
the instrument configure,
first choose internal or external powerif choose internal
powermust set the output DC value between 0V~220V
secondchoose internal trigger or external trigger
thirdif sample input connect the linear Sensor, choose linear and
set the total length(25 or 250 mm). if sample input connect the Angle
Sensor, choose Angle and set mm/.
This setting can auto save.
After, user can choose the Open to run opening test.
Set time. For example, if the Circuit Breakers need 200ms to run, we
can set time 0.3s.
If no error tip, turn to the result interface. But if the relays inside the
machine dont work, will turn to the error interface as Picture 15, 16.
1.14 Reclosing Test
When power on, display as picture 12
First choose the kinds of Circuit Breakers, oil, vacuum, SF6 Circuit
Breakers. appear the next menuas picture 14user can set the
instrument configure, average speed and instant speed(vacuum no)
the instrument configure,
first choose internal or external powerif choose internal
powermust set the output DC value between 0V~220V
secondchoose internal trigger or external trigger
thirdif sample input connect the linear Sensor, choose linear and
11
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
14/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
set the total length(25 or 250 mm). if sample input connect the Angle
Sensor, choose Angle and set mm/.
This setting can auto save.
After, user can choose the Reclose to run Reclosing test. as picture2122the option of time is like the closing test and the opening test.
Choosing the next option ,rotate the Optical Encoder, choose you want
testing fromO-C(opening-closing),C-O(closing-opening),O-C-O(closing-
opening-closing),C-O-C(closing-opening-closing).Push down, will appear
one time to set(O-C-O,C-O-C will appear two),this time is a delay time
between the Circuit Breakers open and close(0.0s~9.9s).
Picture 17 C-OO-C Picture 18 C-O-C,O-C-O
If no error tip, turn to the result interface. But if Relays inside the
machine no work, will turn to the error interface as Picture 17,18.
1.15 Separate test
When power on, display as picture 12
First choose the kinds of Circuit Breakers, oil, vacuum,SF6 Circuit
Breakers. appear the next menuas picture 14user can set the
instrument configure, average speed and instant speed(vacuum no)
the instrument configure,
first choose internal or external powerif choose internalpowermust set the output DC value between 0V~220V
secondchoose internal trigger or external trigger
thirdif sample input connect the linear Sensor, choose linear and
set the total length(25 or 250 mm). if sample input connect the Angle
Sensor, choose Angle and set mm/.
This setting can auto save.
After, user can choose the Low Voltage to run Separating test. At first
will into choosing power interface, confirm the choosing, into the set
interface of the separating test. As picture 14.
12
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
15/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
Picture 19 Separating Test
Confirm the power choosinginto the interface as picture 19.
Picture 20 Separating Test setting
Set the percent of the voltage value, then choose the Close(closing
test run) or the Open(opening test run) push downafter , choose print or
back. On the basic of the Standard for hand-over test of electric
equipment, the Circuit Breakers should be false-action reliability on lower
than 30% of rated voltage, the Circuit Breakers should action reliability on
higher than 65%.
After push down run, will appear the interface as picture 21.if the
instrument dont check out the opening or closing sign at A1,the interface
will display false action, if check out, display action.
13
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
16/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
Picture 21 Separating test
Push down the option Print, will print out the result of this test.
1.16 Result of test
The interface of Result of test have, DataDisplay,
TimeCurve SpeedTravelCurve TravelTimeCurve, four interface
options.
1.16.1DataDisplay
DataDisplay, displays the time of opening or closing, closing springing. clearance
between open contacts overtravel Contact bouncing duration overshoot average
speedmax speedtouching (separating) speed. as picture 23,24
Picture 23 when oil switch Picture 24 when vacuum switch
The option of the interface as picture 23,24
14
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
17/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
1Printprint out the result of this test, the opening(closing) time,
Bounce time or times, clearance between open contacts, overtravel,
Contact bouncing duration, overshoot, Avg.speed, max speed, Inst.Speed
(separating) speed.2SaveSave the data of this test, no current data. If you have saved,
this button will change to delete.
3PageIf the test is reclosing test, this button can display the other
result. For example, test is closing opening test, first display the result of
the closing, push down Page, display the result of the opening.
1.16.2Timing Curve
Display the Breaks curve of twelve contacts and the current-timing
curve within 200ms of the operate current. As picture 25
Picture 25 breaks curve
The option of the interface:
1Datago to the DataDisplay interface.
2Analysewhen push down, will have a line which can get the data
of the curve and the data will be displayed at right of the interface.
When push down again, this line is sure and have the other line until
user push down this button.
3Next
display the others data of the reclosing test.
4Printpint out the timing curve.
5Returnback to The interface of Result of test
1.16.3Travel-Timing Curve
Display the Distance-Time curve of the moving contact. as picture
26.
15
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
18/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
Picture 26 Distance-Time curve
The option of the interface:
1Datago to the DataDisplay interface.
2Analysewhen push down, will have a line which can get the data
of the curve and the data will be displayed at right of the interface. When
push down again, this line is sure and have the other line until user push
down this button.
3Nextdisplay the others data of the reclosing test.
4Print
pint out the timing curve.
5Returnback to The interface of Result of test.
1.16.4 Speed-Travel Curve
Display the Speed-Distance curve of the moving contact. as picture 27
Picture 27 Speed-Distance Curve
16
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
19/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
The option of the interface:
1Datago to the DataDisplay interface.
2Analysewhen push down, will have a line which can get the data
of the curve and the data will be displayed at right of the interface. Whenpush down again, this line is sure and have the other line until user push
down this button.
3Nextdisplay the others data of the reclosing test.
4Printpint out the timing curve.
5Returnback to The interface of Result of test
1.17 State of Contacts
User can see the real-time state of the twelve contacts .push down
the back option, back to main interface.
1.18 History Data
Display the history data. the instrument can save 24 group of opening
test or closing test data and save 8 group of reclosing test. if save more
data, will cover the oldest data.
The option of the interface:
1Loadwhen push down first, user can choose which group to read.
Push down again, will read the cursor point data.
2Nexthistory data of the opening test or closing test change to
history data of the reclosing test.3Deleteclear the history data of the opening test or closing test or
the history data of the reclosing test. if user wish delete the specifically
data, can first get in the data which want to delete, and then push down
the delete in the DisplayData interface.
4Returnback to the main interface.
1.19 PC communication
Use the USB cable connects the compute and the instrument. Push
down the PC-Com option in the main interface. This function can make PC
to control the instrument testing and receive the history data.
1.20 Date
Change Date & Time.
CHAPTER 4. PC software intro
1.21 Installation
This software is Installationfree version, user can unzip to hard disk as
17
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
20/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
picture 29 30.
picture 29 Software package picture 30 software main program
runGKStudio.exeto use.
1.22 Operation
1.22.1 Communication
First, Use the USB cable connects the compute and the instrument.
Push down the PC-Com option in the main interface.
Second,user can check the state of communication by push theConnect button. if the PC connected the instrument, user can use all
function. If no, will give a tip as picture 31
Picture 31 USB connect failure
1.22.2 Read the history data in the instrument
Push down Upload,PC will receive all data which saved in the
instrument. User can choose one group data to check by choosing in drop
down listResult of test at left interface. The oscilloscope will display
curve, then pushing down view data will see all detailed data of this
group data. User can save this group data by pushing save, the data will
be saved by .GK at hard disk.
18
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
21/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
Picture 32 history data display
19
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
22/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
33 history data display by word
Pushing read will see the last uploading history data.
1.22.3 PC control of the instrument to test
When PC connected the instrument, check the set of speed, trigger
and power, choose type of test, type of switch, type of senor and so on.
Click Start, please make sure all right, click OK. The instrument will
run the test and upload the result of test.
1.22.4 Save the data on PC
All the result of test and uploading history data can be save as 1.as
word,2.as excel,3 print the report.
1. Click the export, as picture 35, choose save as word. if
users PC installed the Microsoft office 2003,will save data
report as word.
2. Click the export, as picture 35, choose save as excel.
3. Click the print, will get into print preview, user can set page
header and footer at the Preferences windows. Click the print.
20
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
23/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
Picture .35 export report
CHAPTER 5. Example
1.23 How to connection
Require: fix the senor to the A1.
1when using the internal power supply, closing control connects to
picture 36 using our lines; opening control connects to in picture
36; Common connects to -KM in picture 36; the fuse in picture 36
must be removed.
2when using the external power supply, closing control connects to
in picture 36 using our lines; opening control connects to in picture
36; Common connects to +KM in picture 36
21
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
24/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
+KM -KM
closing control
HC
5 8
LD DL1
11 10
HD
16 13
6 7
+ DL2
TQ
+HM opening control -HM
Hc HQ Hc
Picture 36 console panel connection
1.24 Fit sensor in oil Circuit Breakers
open the cover of the explosion chamber, insert the transmission pole into
the explosion chamber, and screw the inside end of the transmission pole
tightly to the screw of the moving contact, the other end of the pole connects to
the sample ruler.
The ruler should glide in the runner easily, and the base of the ruler must be fixed
to the explosion chamber.
Requirements: connect the contact to the A1 on the front-panel, the signal
lines plug of the sampler connects to the Sample Input interface, when fix the
sample pole ,the sample ruler should be kept clean and straight. when theres
pollute like oil or dust in the sample ruler, the ruler should be cleaned by gasoline
or alcohol., or the measured results may be discrete.
How to connect: all the moving contacts of the switches connects to the
ground hole in the front-panel of the tester, the ground hole then connects to the
earth ground reliably; the static contacts to the A,B,C hole correspondingly.(see
Picture 38)
22
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
25/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
1 2
3
Picture 37 explosion chamber
Picture 37it shows a sample ruler for 110KV-220KV switches; if 1,2,3 parts
are removed, the sample ruler is applied to the 10KV switches.
Picture 38 Fit sensor in oil Circuit Breakers
1.25 Fit sensor in vacuum Circuit Breakers
Let the switch be at a open state, fix the senor to fixed shelf in the bottom
of the switchs, make the probe just touch the moving contact by adjusting the
23
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
26/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
spring, use the line to connect the probe and the External Trigger hole in the
front-panel, how to connect the remainder lines is just like the method for oil
switch.(see picture 39)
Picture 39 Fit sensor in vacuum Circuit Breakers
1.26 Fit sensor in SF6 Circuit Breakers
Remove the glass window of the lift-pole room, fix the fixing board with the
infrared-induction head into the screw hole in the room, fix the sample ruler to
the corresponding position , adjust the fixing parts to make the ruler to slide in the
runner up and down, how to connect the lines is just like the methods for other
switches.(as picture 40)
24
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
27/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
Picture 40 Fit sensor in sf6 Circuit Breakers
CHAPTER 6. Common Fault Analysis
1.27 Display too bright or too dark
if the LCD display too bright or too dark,please adjust the potentiometer by a
screw until the display show comfort you.
1.28 System halted
press the Reset key when the tester is halted.
25
-
7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306
28/28
High-Voltage Switch Dynamic Characteristics Testing Instrument User manual
1.29 Print abnormality
Power down the instrument when the printer operates abnormally, and wait
for about half a minute.
CHAPTER 7. bill of assembly
list 7.1 bill of assembly
instrument 1 unit
Seniors 1 set
User manual 1 copy
Mini printer User manual 1 copyTest cables 1 set
We are responsible for the customer who use
our products, guarantee to keep the products in
good repair in one year after we sell them to you.
Welcome to feedback the invaluable advice and
information of the products to us .Thanks for
your cooperation.
Forgive us not to inform you the possible
changes.