    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    Page 1

    Sept. 15, 1998

    June 1, 1994

    Section A Linear Diuser & Grilles

    A-1 SDS June1,1994

    A-2 SDA/SDAI June1,1994 A-3 LBP/LBPH June1,1994 A-4 LBMH June1,1994 A-5 LV1 June1,1994 A-6 LV2 June1,1994

    Section B Ceiling Component Diusers

    B-1 TBD3Series June1,1994 B-2 TBD4Series June1,1994 B-3 TBD7Series June1,1994 B-4 TBD8Series June1,1994 B-5 LTSeriesLightTroffers June1,1994

    Section C Ceiling Diusers

    C-1 SCD/ASCD June1,1994

    C-2 SCDA/ASCDA June1,1994 C-3 SPD/ASPD June1,1994 C-4 PDN/PDNE June1,1994 C-5 PDF/PDFE June1,1994 C-6 PDDR/PDDRE June1,1994 C-7 PDS June1,1994 C-8 PDR June1,1994 C-9 PE/PL June1,1994 C-10 SMD/AMD June1,1994 C-11 SMD/AMDReturn June1,1994 C-12 SMDA/AMDA June1,1994 C-13 SMCD/AMCD June1,1994 C-14 CVD(1&2WayBlow) June1,1994 C-15 CVD(3&4WayBlow) June1,1994

    C-16 RCD/RCDA June1,1994 C-17 RCDE June1,1994 C-18 RID June1,1994

    Section D Grilles & Registers

    D-1 SupplyGrilles June1,1994 D-2 ReturnGrilles June1,1994 D-3 MSLG/MSLGH June1,1994 D-4 HCD June1,1994 D-5 ATG Sept.15,1998 D-6 STG Sept.15,1998 D-7 MSPG Sept.15,1998 D-8 10Series Sept.15,1998

    Section E Medical / Cleanroom

    E-1 RFD June1,1994 E-2 LFD June1,1994 E-3 AMDC Sept.15,1998 E-4 RVDC Sept.15,1998 E-5 HORD Sept.15,1998 E-6 HORD Sept.15,1998

    Index

  • 8/3/2019 Eh Price Flow Factors

    3/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    A-1

    June 1, 1994

    November 1, 1989

    SDS 50, 75 & 100 Slot TypeLinear Ceiling Diusers

    Procedure: 1.Determinetheaveragevelocityasshown. 2. TheFlowRateinCFM=FlowFactorxAverageVelocityxL(L=Lengthodiuserint.).

    Flow Factors

    Model

    SDS50

    SDS75

    SDS100

    Pattern

    H

    V

    H

    V

    H

    V

    1

    .018

    .023

    .021

    .029

    .023

    .038

    2

    .036

    .046

    .042

    .058

    .046

    .076

    3

    .054

    .069

    .063

    .087

    .069

    .114

    4

    .072

    .092

    .084

    .116

    .092

    .152

    5

    .090

    .115

    .105

    .145

    .115

    .190

    6

    .108

    .138

    .126

    .174

    .138

    .228

    7

    .126

    .161

    .147

    .203

    .161

    .266

    8

    .144

    .184

    .168

    .232

    .184

    .304

    SUPPLY

    No. o Slots

    H = Horizontal Pattern V = Vertical Pattern

    1

    .033

    .039

    .044

    2

    .066

    .078

    .088

    3

    .099

    .117

    .132

    4

    .132

    .156

    .176

    5

    .165

    .195

    .220

    6

    .190

    .234

    .264

    7

    .231

    .273

    .308

    8

    .264

    .312

    .352

    RETURN

    No. o SlotsModel

    SDR50

    SDR75

    SDR100

    Note: AllactorsobtainedusingtheAlnor6070Pprobe.

    Alnor Probe 6070P Location

  • 8/3/2019 Eh Price Flow Factors

    4/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    A-2

    June 1, 1994

    July 1, 1989

    SDS 50, 75, 100 Slot Diuserwith SDA or SDAI Plenum Assembly

    Procedure: 1.Placevelometerprobe14inchesromeachandoslotandagainsttheslotedgeoppositetheinletshown.

    2.Recordandaveragetwovelocityreadingsoreachslot.

    3.TheFlowRateinCFM=FlowFactorxAverageVelocity.

    Flow Factors

    No. o

    Slots

    1

    2

    3

    4

    Pattern

    H

    H

    H

    H

    4

    .088

    .183

    .268

    .330

    5

    .112

    .215

    .320

    .420

    3

    .078

    .185

    .223

    .292

    4

    .106

    .221

    .286

    .454

    3

    .070

    .125

    .185

    .245

    5

    .133

    .239

    .380

    .600

    3

    .094

    .177

    .260

    .330

    4

    .111

    .231

    .350

    .460

    5

    .155

    .300

    .440

    .580

    SDS 50Nom. Length (t)

    SDS 75Nom. Length (t)

    SDS 100Nom. Length (t)

    Alnor Probe 6070P Location

  • 8/3/2019 Eh Price Flow Factors

    5/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    Note: Forsizesgreaterthan6"thefowactorint 2/tolengthmaybecalculatedbytheollowingequation:

    A-3

    June 1, 1994

    June 1, 1989

    LBP & LBPHLinear Bar Grilles

    Procedure: 1.DeterminetheaveragevelocityattheaceothegrillewiththeAlnor6070Pprobepositionedasshownbelow.

    2. ForlistedsizestheFlowRateinCFMis:

    CFM=FlowFactorxAverageVelocityxL(L=Lengthosectionint.)

    Core

    Style

    15A

    .25"O.C.

    0Deg.

    16A

    .25"O.C.

    15Deg.

    15B

    .50"O.C

    0Deg.

    16B

    .50"O.C.

    15Deg.

    25B

    .50"O.C.

    0Deg.

    26B

    .50"O.C.

    15Deg

    Listed

    Size

    Supply

    Return

    Supply

    Return

    Supply

    Return

    Supply

    Return

    Supply

    Return

    Supply

    Return

    Flow

    Factor

    Coe.

    .037

    .031

    .035

    .030

    .042

    .036

    .040

    .034

    .042

    .036

    .040

    .034

    Flow Factor t2 / t o Length

    5"

    .157

    .135

    .152

    .130

    .179

    .154

    .173

    .148

    .177

    .150

    .167

    .140

    1.5"

    .031

    .026

    .034

    .031

    .035

    .030

    .039

    .035

    .026

    .022

    .031

    .028

    2"

    .047

    .040

    .049

    .044

    .055

    .046

    .056

    .050

    .045

    .039

    .048

    .042

    2.5"

    .065

    .056

    .065

    .057

    .074

    .064

    .075

    .065

    .066

    .057

    .067

    .058

    3"

    .083

    .070

    .082

    .072

    .096

    .080

    .093

    .082

    .088

    .075

    .086

    .073

    3.5"

    .102

    .090

    .099

    .083

    .116

    .103

    .113

    .095

    .110

    .094

    .105

    .090

    4"

    .122

    .103

    .117

    .100

    .139

    .118

    .133

    .114

    .133

    .114

    .127

    .105

    6"

    .194

    .165

    .186

    .158

    .221

    .188

    .212

    .180

    .222

    .190

    .210

    .180

    FlowFactor = (W-0.75)xFlowFactorCoe.

    t.oLength W=ListedWidthininches

  • 8/3/2019 Eh Price Flow Factors

    6/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    A-4

    June 1, 1994

    June 1, 1989

    LBMHLinear Bar Grilles Mandrel Construction

    Procedure: 1.DeterminetheaveragevelocityattheaceothegrillewiththeAlnor6070Pprobepositionedasshown.

    2. ForlistedsizestheFlowRateinCFMis:

    CFM=FlowFactorxAverageVelocityxL(L=Lengthosectionint.)

    Core

    Style

    15A

    .25"O.C.

    0Deg.

    16A

    .25"O.C.

    15Deg.

    15B

    .50"O.C

    0Deg.

    16B

    .50"O.C.

    15Deg.

    25B

    .50"O.C.

    0Deg.

    26B

    .50"O.C.

    15Deg

    Listed

    Size

    Supply

    Return

    Supply

    Return

    Supply

    Return

    Supply

    Return

    Supply

    Return

    Supply

    Return

    Flow

    Facto

    Coe.

    .036

    .030

    .032

    .028

    .041

    .035

    .037

    .031

    .043

    .037

    .040

    .034

    Flow Factor t2 / t o Length

    5"

    .152

    .128

    .135

    .115

    .173

    .146

    .154

    .131

    .180

    .152

    .165

    .140

    1.5"

    .027

    .023

    .031

    .028

    .030

    .026

    .035

    .031

    .030

    .025

    .032

    .028

    2"

    .043

    .036

    .044

    .039

    .049

    .041

    .050

    .045

    .049

    .042

    .048

    .042

    2.5"

    .059

    .056

    .059

    .051

    .067

    .064

    .067

    .058

    .071

    .060

    .066

    .058

    3"

    .078

    .067

    .072

    .062

    .089

    .077

    .082

    .071

    .095

    .080

    .085

    .073

    3.5"

    .098

    .082

    .087

    .073

    .111

    .094

    .099

    .083

    .114

    .098

    .106

    .090

    4"

    .116

    .100

    .105

    .089

    .132

    .114

    .120

    .102

    .135

    .115

    .125

    .105

    6"

    .190

    .160

    .165

    .140

    .216

    .182

    .188

    .160

    .225

    .193

    .210

    .180

    FlowFactor = (W-0.75)xFlowFactorCoe.

    t.oLength W=ListedWidthininches

    Note: Forsizesgreaterthan6"thefowactorint 2/tolengthmaybecalculatedbytheollowingequation:

  • 8/3/2019 Eh Price Flow Factors

    7/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    A-5

    June 1, 1994

    July 1, 1989

    LV1 (1-Way)Linear Vane Diuser

    Procedure: 1.Determinetheaveragevelocityintherontslotonlyasillustratedbelow. 2.TheFlowRateinCFM=FlowFactorxLxV

    L=Lengthosectionin(t)

    V=Averagemeasuredvelocityin(pm)

    Flow Factors

    Size

    3.504.25

    5.00

    5.75

    6.50

    A

    0.0530.076

    0.101

    0.131

    0.167

    B

    0.0400.067

    0.079

    0.108

    0.140

    C

    0.0440.063

    0.081

    0.099

    0.120

    SUPPLY RETURN

    (A) Theseactorsapplywhenthediuserhasintegralstraighteningvanesordampers.

    (B) Theseactorsapplywhenthediuserhasnointegralstraighteningvanesordampers.

    (C) Theseactorsapplywithdiuserwhenusedasareturnintake.

    Alnor Probe 6070P Location

  • 8/3/2019 Eh Price Flow Factors

    8/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    A-6

    June 1, 1994

    July 1, 1989

    Procedure: 1.Determinetheaveragevelocityintherontslotsinbothdirectionsasillustratedbelow. 2.TheFlowRateinCFM=FlowFactorxLxV.

    L=Lengthosectionin(t)

    V=Averagemeasuredvelocityin(pm)

    LV2 (2-Way)Linear Vane Diuser

    Flow Factors

    Size

    6.257.75

    9.25

    10.75

    12.25

    0.1030.156

    0.210

    0.267

    0.328

    Supply

    0.0900.130

    0.170

    0.210

    0.250

    Return

    TheactorsapplytoallLV2diusers,bothwithandwithoutstraighteningvanesand/ordampers.

    Alnor Probe 6070P Locations

  • 8/3/2019 Eh Price Flow Factors

    9/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    B-1

    June 1, 1994

    July 1, 1989

    TBD & TBDI 350, 375, 3100Ceiling Diusers or Steel T-Bar

    Procedure: 1.Setpatterncontrollersorthepatternrequiredeitherhorizontalorvertical. 2. TakevelocityreadingsatslotodiuserwithAlnor6070Pprobeatthelocationsshownabove.Two

    readingsoroneslotdiusersandourreadingsortwoslotdiusers.Averagethevelocityreadings

    3. Selectfowactorordiuserlengthandpatternandcalculateairfowromtheequation

    CFM=FlowFactorxAverageVelocityFlow Factors

    2 Slot

    .078

    .096

    .100

    .125

    .160

    .210

    .200

    .270

    1 Slot

    .039

    .045

    .050

    .059

    .079

    .100

    .100

    .130

    Pattern

    H

    V

    H

    V

    H

    V

    H

    V

    TBD 350

    1 Slot

    .054

    .066

    .069

    .085

    .112

    .145

    .140

    .185

    2 Slot

    .109

    .140

    .137

    .185

    .222

    .320

    .280

    .410

    1 Slot

    .068

    .085

    .086

    .110

    .139

    .185

    .175

    .240

    2 Slot

    .137

    .185

    .175

    .235

    .280

    .400

    .350

    .520

    TBD 375 TBD 3100Diuser

    Length

    2' 0"

    2' 6"

    4' 0"

    5'0"

    Diuser Pattern Controller Positions

    Alnor Probe 6070P Location

    Diuser Dist XLength rom End

    2'-0" 8"

    2-6" 9"

    4'-0" 14"

    5'-0" 14"

  • 8/3/2019 Eh Price Flow Factors

    10/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    B-2

    June 1, 1994

    July 1, 1989

    TBD & TBDI 475 / 4100 / 4150High Capacity Diusers or Steel T-Bar

    Procedure: 1.Placeprobeatlocationsshown. 2.Recordandaveragevelocityreadings(2perslot).

    3.F lowRateinCFM=FlowFactor&AverageVelocity.

    Flow Factors

    Diuser

    Length

    2' - 0"

    2' - 6"3' - 0"

    4' - 0"

    5' - 0"

    TBD 4100

    1 Slot 2 Slot

    .073 .146

    .093 .185 .112 .223

    .150 .300

    .188 .376

    TBD 4150

    1 Slot 2 Slot

    .107 .166

    .136 .208 .164 .252

    .220 .338

    .276 .425

    TBD 475

    1 Slot 2 Slot

    .064 .128

    .080 .161 .098 .195

    .130 .261

    .164 .328

    Alnor Probe 6070P Location

  • 8/3/2019 Eh Price Flow Factors

    11/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    B-3

    June 1, 1994

    August 1, 1989

    TBD7 & TBDI7T-Bar Ceiling Diusers

    Procedure: 1. Locate the velometer probe in the slot o the diuser in the position illustratedbelow. Two velocity readings are to be taken at the locations rom each end as il-

    lustrated.

    Dimension "x" and the applicable ow actors are listed the table below.

    2. Record and average velocity readings (2 per slot).

    No. o Slots

    1

    2

    3

    4

    2 Foot / x = 8"

    No. o Slots

    1

    2

    3

    4

    4 Foot / x = 18"

    Alnor Probe 6070P Location

    Flow Factors (1 or 2 Way Pattern)

    Flow Factor

    0.095

    0.210

    0.225

    0.298

    Flow Factor

    0.150

    0.300

    0.490

    0.670

  • 8/3/2019 Eh Price Flow Factors

    12/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    B-4

    June 1, 1994

    July 1, 1989

    TBD8 SeriesT-Bar Ceiling Diusers

    Procedure: 1. Placethevelometerprobe14"romeachendoslotasillustratedbelow.Forhorizontalpatternplacagainsttheslotedgeasshown.Forverticalpatternplaceincentreotheslotasshown.

    2.Recordandaveragethesetwovelocityreadings.

    3.TheFlowRateinCFM=FlowFactorxAverageVelocity.

    Flow Factors

    Nominal Length

    (t.)

    3

    4

    5

    3

    4

    5

    3

    4

    5

    Model No.

    TBD850

    TBDI850

    TBD875

    TBDI875

    TBD8100

    TBDI8100

    Flow Factor

    H

    .058

    .096

    .140

    .071

    .104

    .155

    .065

    .100

    .135

    V

    .086

    .125

    .155

    .099

    .127

    .165

    .092

    .143

    .220

    Alnor Probe 6070P Location

  • 8/3/2019 Eh Price Flow Factors

    13/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    B-5

    June 1, 1994

    July 1, 1989

    LT SeriesLight Troer Diusers

    Procedure: 1. Locatethevelometerprobeintheslotothediuseratthepositionsillustratedbelow.Twovelocityreadingsarerequiredoreachslot.DimensionXandtheapplicablefowactors

    canbeoundinthetableaboveorthevariousdiusermodels.

    2.Recordandaveragethesetwovelocityreadings.

    3.TheFlowRateinCFM=FlowFactor&AverageVelocity.

    Flow Factors

    Dimension X

    (in.)

    6

    6

    5

    5

    5

    5

    Model No.

    LTF/LTA10-4

    LTF/LTA14,LTF/LTA24

    LTF/LTA10-3

    LTF/LTA13,LTF/LTA23

    LTF/LTA33

    LTF/LTA10-2

    LTF/LTA12,LTF/LTA22

    Flow Factor

    .068

    .135

    .045

    .095

    .033

    .062

    Alnor Probe 6070P Location

  • 8/3/2019 Eh Price Flow Factors

    14/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-1

    May 1, 1992

    Jan. 1, 1987

    SCD / ASCDSquare Cone Ceiling Diusers

    Procedure: 1. LocatethevelometerprobeinthecentreotheoursidesoconeCasillustrated. 2.Recordandaveragetheourvelocityreadings.

    3.F lowRateinCFM=FlowFactorxAverageVelocity.

    Flow Factors

    Factor

    0.06

    0.09

    0.12

    0.15

    0.18

    0.15

    0.24

    0.34

    0.16

    0.25

    0.36

    0.49

    0.620.68

    Neck Diam

    (in.)

    4

    56

    7

    8

    6

    8

    10

    6

    8

    10

    12

    1415

    Nominal Overall

    Face Size

    12x12

    12x1212x12

    12x12

    12x12

    20x20

    20x20

    20x20

    24x24

    24x24

    24x24

    24x24

    24x2424x24

    Alnor 6070P Probe Location

  • 8/3/2019 Eh Price Flow Factors

    15/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-2

    June 1, 1994

    Jan. 1, 1987

    SCDA / ASCDASquare Cone Ceiling Diusers, Adjustable

    Procedure: 1.Setdiuserpatternbyadjustinghingestotherequiredpositionasillustratedaboveoreitherhorizontalorverticalpattern.

    2. Locatethevelometerprobeinthecentreotheoursidesothediuserconeasillustratedorthe

    patternselected.

    3.Recordandaveragetheourvelocityreadings.

    4.F lowRateinCFM=FlowFactorxAverageVelocity.

    H

    .07

    .09

    .12

    .15

    .18

    0.15

    0.24

    0.35

    .20

    .29

    .38

    .48

    .58

    .64

    Neck Diam

    (in.)

    4

    5

    6

    7

    8

    6

    8

    10

    6

    8

    10

    12

    14

    15

    Nominal Overall

    Face Size

    12x12

    12x12

    12x12

    12x12

    12x12

    20x20

    20x20

    20x20

    24x24

    24x24

    24x24

    24x24

    24x24

    24x24

    V

    .09

    .10

    .11

    .12

    .13

    0.23

    0.26

    0.29

    Flow Factor

    Alnor Probe 6070P Location

    Flow Factors

  • 8/3/2019 Eh Price Flow Factors

    16/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-3

    June 1, 1994

    Jan. 1, 1987

    SPD / ASPDSquare Plaque Ceiling Diusers

    Procedure: 1. Locatethevelometerprobeinthecentreotheoursidesotheplaqueasillustrated. 2.Recordandaveragetheourvelocityreadings.

    3.F lowrateinCFM=FlowFactorxAverageVelocity.

    Alnor Probe 6070P Location

    Flow Factors

    .06

    .07

    .09

    .10

    .12

    .15

    .21

    .27

    .19

    .25

    .32

    .38

    .44

    .48

    Neck Diam

    (in.)

    4

    56

    7

    8

    6

    8

    10

    6

    8

    10

    12

    1415

    Nominal Overall

    Face Size

    12x12

    12x1212x12

    12x12

    12x12

    20x20

    20x20

    20x20

    24x24

    24x24

    24x24

    24x24

    24x2424x24

    Flow

    Factor

  • 8/3/2019 Eh Price Flow Factors

    17/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    PDN / PDNE / APDN / APDNEPerorated Diusers, Supply

    C-4

    May 1, 1992

    Jan. 1, 1987

    Procedure: 1. Locatethevelometerprobeatthecentreoeachpatterncontrollerontheperoratedaceasil-lustrated.

    2.Recordonevelocityreadingperactiveside.

    3.Averagetherecordedvelocityreadings.

    4.ThefowrateinCFM=FlowFactorxAverageVelocity.

    Flow Factors

    Square Inlet Sizes Round Inlet Sizes

    12 x 12

    0.19

    -

    -

    -

    -

    -

    -

    24 x 24

    0.19

    -

    0.33

    0.50

    0.72

    0.96

    1.10

    16 x 16

    0.19

    -

    0.33

    0.50

    -

    -

    -

    20 x 20

    0.19

    -

    0.33

    0.50

    -

    -

    -

    Size

    6 x 6

    6 x 18

    8 x 8

    10 x 10

    12 x 12

    14 x 14

    15 x 15

    Ceiling Opening or Module

    12 x 24

    0.19

    0.55

    -

    -

    -

    -

    -

    12 x 12

    0.15

    -

    -

    -

    -

    -

    24 x 2

    0.15

    0.26

    0.40

    0.57

    0.72

    1.05

    16 x 16

    0.15

    0.26

    0.40

    -

    -

    -

    20 x 20

    0.15

    0.26

    0.40

    -

    -

    -

    Size

    6

    8

    10

    12

    14

    15

    Ceiling Opening or Module

    12 x 24

    0.15

    -

    -

    -

    -

    -

    Alnor 6070P Probe Location

  • 8/3/2019 Eh Price Flow Factors

    18/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    Procedure: 1. Locatethevelometerprobeatthecentreoeachsideotheperoratedaceplateasillustrated. 2.Recordonevelocityreadingperactiveside.

    3.Averagetherecordedvelocityreadings.

    4.F lowRateinCFM=FlowFactorxAverageVelocity.

    C-5

    June 1, 1994

    Jan. 1, 1987

    PDF / PDFE / APDF / APDFEPerorated Diusers, Supply

    Flow Factors

    Square Inlet Sizes Round Inlet Sizes

    12 x 12

    0.37

    -

    -

    -

    -

    -

    24 x 24

    0.49

    -

    0.62

    0.74

    0.86

    0.97

    16 x 16

    0.37

    -

    0.52

    -

    -

    -

    20 x 20

    0.37

    -

    0.52

    0.69

    -

    -

    Size

    6 x 6

    6 x 18

    8 x 8

    10 x 10

    12 x 12

    14 X 14

    Ceiling Opening or Module

    12 x 24

    0.37

    0.72

    -

    -

    -

    -

    12 x 12

    0.32

    -

    -

    -

    -

    -

    24 x 2

    0.62

    0.74

    0.82

    0.90

    0.90

    1.03

    16 x 16

    0.32

    0.46

    0.60

    -

    -

    -

    20 x 20

    0.32

    0.46

    0.60

    0.74

    0.90

    -

    Size

    6

    8

    10

    12

    14

    15

    Ceiling Opening or Module

    12 x 24

    0.32

    -

    -

    -

    -

    -

    Alnor Probe 6070P Locations

  • 8/3/2019 Eh Price Flow Factors

    19/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-6

    June 1, 1994

    Jan. 1, 1987

    PDDR / APDDR / PDDRE / APDDREPerorated Diusers, Return

    Procedure: 1. Locatethevelometerprobefushagainsttheperoratedaceasillustrated. 2. Recordonevelocityreading.

    3.F lowRateinCFM=FlowFactorxAverageVelocity.

    Alnor Probe 6070P Locations

    Flow Factors

    12 x 12

    .21

    -.32

    -

    -

    -

    -

    -

    -

    -

    -

    .18

    -

    -

    -

    -

    -

    24 x 24

    .21

    .31

    .43

    .56

    .70

    .78

    -

    -

    -

    1.50

    -

    .18

    .27

    .37

    .48

    .60

    .68

    16 x 16

    .21

    .31

    .43

    -

    .62

    -

    -

    -

    -

    -

    -

    .18

    .27

    .37

    -

    -

    -

    20 x 20

    .21

    .31

    .43

    .56

    -

    -

    1.00

    -

    -

    -

    -

    .18

    .27

    .37

    .48

    .60

    -

    Ceiling Module Size

    12 x 24

    .21

    --

    -

    -

    -

    -

    .46

    .69

    .18

    -

    .18

    -

    -

    -

    -

    -

    Neck

    Size

    6 x 6

    8 x810 x 10

    12 x 12

    14 x 14

    15 x 15

    18 x 18

    6 x 18

    10 x 22

    22 x 22

    22 x 46

    6" Diam.

    8" Diam.

    10" Diam.

    12" Diam.

    14" Diam.

    15" Diam.

    24 x 48

    -

    --

    -

    -

    -

    -

    -

    -

    -

    3.00

    -

    -

    -

    -

    -

    -

  • 8/3/2019 Eh Price Flow Factors

    20/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-7

    June 1, 1994

    Jan. 1, 1987

    PDSPerorated Diusers c/w Standard Pattern Controller

    Procedure: 1. Locatethevelometerprobeatthecentreoeachsideotheperoratedaceplateasillustrated. 2. Recordourvelocityreadingsperoutletorsquarediuserandtwovelocityreadingsperoutletor

    rectangulardiusers.Note:Forthe6x18inletsize,ourvelocityreadingsarerequired.

    3.Averagetherecordedvelocityreadings.

    4.F lowRateinCFM=FlowFactorxAverageVelocity.

    Flow Factors

    12 x 1212 x 3612 x 48

    0.22

    -

    -

    -

    0.44

    24 x 3624 x 48

    0.55

    0.66

    0.79

    0.90

    -

    Size

    6 x 68 x 8

    10 x 1012 x 126 x 18

    12 x 12

    0.22

    -

    -

    -

    -

    16 x 16

    0.32

    0.40

    -

    -

    -

    20 x 20

    0.44

    0.54

    0.63

    -

    -

    24 x 24

    0.55

    0.66

    0.79

    0.90

    -

    Ceiling Opening or Module

    Round Inlet Sizes

    Square Inlet Sizes

    16 x 16

    0.32

    0.34

    0.37

    0.39

    0.42

    -

    -

    20 x 20

    0.47

    0.50

    0.53

    0.56

    0.60

    0.65

    -

    12 x 12

    12 x 3612 x 48

    0.20

    0.21

    0.23

    -

    -

    -

    -

    24 x 3624 x 48

    0.62

    0.66

    0.70

    0.74

    0.80

    0.87

    0.92

    Size

    5678

    101214

    12 x 12

    0.20

    0.21

    0.23

    -

    -

    -

    -

    24 x 24

    0.62

    0.66

    0.70

    0.74

    0.80

    0.87

    0.92

    Ceiling Opening or Module

    Alnor Probe 6070P Locations

  • 8/3/2019 Eh Price Flow Factors

    21/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-8

    June 1, 1994

    Jan. 1, 1987

    PDRPerorated Diusers, Return

    Procedure: 1. Locatethevelometerprobefushagainsttheperoratedaceasillustrated. 2. Recordthevelocityreading.

    3.F lowRateinCFM=FlowFactorxAverageVelocity.

    Flow Factors

    Nominal Duct

    Size (in.)

    10 x 10

    14 x 1418 x 18

    22 x 22

    10 x 22

    10 x 34

    10 x 46

    22 x 34

    22 x 46

    Ceiling Opening

    or Module (in.)

    12x12

    16x1620x20

    24x24

    12x24

    12x36

    12x48

    24x36

    24x48

    Flow

    Factor

    0.29

    0.590.97

    1.50

    0.61

    1.03

    1.38

    2.25

    3.05

    Alnor Probe 6070P Location

  • 8/3/2019 Eh Price Flow Factors

    22/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-9

    June 1, 1994

    Jan. 1, 1987

    PE / PLSquare Perorated Diusers

    Procedure: 1. Locatethevelometerprobeinthecentreotheperoratedacefushagainstthesuraceasillustratedabove.

    2. Recordthevelocityreading.

    3.F lowRateinCFM=FlowFactorxAverageVelocity.

    Duct Size

    Flow

    Factor

    6

    .252

    8

    .395

    10

    .505

    12

    .592

    14

    .668

    Model PE - Alnor Probe 6070P Location

    Flow Factors

    Model PL - Alnor Probe 6070P Location

  • 8/3/2019 Eh Price Flow Factors

    23/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-10

    June 1, 1994

    Jan. 1, 1987

    SMD / AMDSquare & Rectangular Ceiling Diusers, Supply

    Procedure: 1. LocateAlnor6070Pprobeagainsttheoutletasshown.Takeanumberoreadingsatuniormlyspacpositionsovertheaceothediuser.

    2. Averagethevelocityreadings.

    3.ThefowrateinCFM=FlowFactorxAverageVelocityxNeckArea.

    (seetablebeloworneckareas)

    Areas o Squares and Rectangles (in Sq. Ft.)

    Size 1.5" 3" 4.5" 6" 7.5" 9" 10.5" 12" 13.5" 15" 16.5" 18" 19.5" 21" 22.5" 24" 25.5" 27" 28.5" 30"

    3" .031 .063

    4.5" .047 .094 .141

    6" .063 .125 .187 .250

    7.5" .078 .156 .234 .313 .390

    9" .094 .188 .281 .375 .469 .560

    10.5" .109 .219 .328 .438 .547 .656 .766

    12" .125 .250 .375 .500 .625 .750 .875 1.000

    13.5" .141 .281 .422 .563 .703 .844 .984 1.130 1.270

    15" .156 .313 .469 .625 .781 .938 1.100 1.250 1.410 .156

    16.5" .172 .344 .516 .688 .859 1.030 1.200 1.380 1.550 1.720 1.890

    18" .188 .375 .563 .750 .938 1.125 1.310 1.500 1.690 1.875 2.060 2.250

    19.5" .203 .406 .610 .813 1.015 1.220 1.420 1.630 1.830 2.030 2.230 2.440 2.640

    21" .219 .438 .656 .875 1.090 1.310 1.530 1.750 1.970 2.190 2.410 2.62 2.840 3.060

    22.5" .234 .469 .703 .938 1.170 1.410 1.640 1.880 2.110 2.340 2.580 2.810 3.050 3.280 3.520

    24" .250 .500 .750 1.000 1.250 1.500 1.750 2.000 2.250 2.500 2.750 3.000 3.250 3.500 3.750 4.000

    25.5" .266 .531 .797 1.060 1.330 1.590 1.860 2.130 2.390 2.660 2.920 3.190 3.450 3.720 3.980 4.250 4.520

    27" .281 .563 .844 1.125 1.410 1.690 1.970 2.250 2.530 2.810 3.090 3.375 3.660 3.940 4.220 4.500 4.780 5.060

    28.5" .297 .594 .891 1.190 1.480 1.780 2.080 2.380 2.670 2.970 3.270 3.560 3.860 4.160 4.450 4.750 5.050 5.340 5.640

    30" .313 .625 .938 1.250 1.560 1.875 2.190 2.500 2.810 3.125 3.440 3.750 4.060 4.375 4.690 5.000 5.310 5.625 5.940 6.25

    Flow Factors

    Alnor 6070P

    Alnor Probe 6070P Location

    Flow Factor

    .40

  • 8/3/2019 Eh Price Flow Factors

    24/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-11

    May 1, 1992

    Jan. 1, 1987

    SMD / AMDSquare and Rectangular Ceiling Diusers, Return

    Procedure: 1. Locatethevelometerprobeasillustratedbelowandrecordthereadings. 2. RepeatStep1atvariouslocations.

    3.Averagethesereadings.

    4.Selecttheactorbasedonthediuserneckarea.

    5.F lowRateinCFM=FlowFactorxAverageVelocity.

    Flow Factors

    Duct Area

    (t

    2

    )

    0.25

    0.30

    0.35

    0.40

    0.45

    0.50

    0.60

    0.70

    0.80

    0.90

    1.00

    0.150

    0.120

    0.135

    0.152

    0.167

    0.184

    0.216

    0.242

    0.268

    0.300

    0.320

    Duct Area

    (t

    2

    )

    1.10

    1.20

    1.30

    1.40

    1.50

    1.60

    1.80

    2.00

    2.20

    2.40

    2.60

    0.360

    0.390

    0.415

    0.440

    0.465

    0.490

    0.535

    0.580

    0.630

    0.680

    0.730

    Duct Area

    (t

    2

    )

    2.80

    3.00

    3.20

    3.40

    3.60

    3.80

    4.00

    4.59

    5.00

    5.50

    6.00

    0.770

    0.810

    0.855

    0.900

    0.940

    0.980

    1.020

    1.110

    1.210

    1.330

    1.440

    Alnor Probe 6070P Locations

    Flow Factor

    (Ak)

    Flow Factor

    (Ak)

    Flow Factor

    (Ak)

    Alnor 6070P Probe

  • 8/3/2019 Eh Price Flow Factors

    25/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-12

    June 1, 1994

    Jan. 1, 1987

    SMDA / AMDASquare Ceiling Diusers, Adjustable

    Procedure: 1.Setdiuserpatternbyadjustingthepatternvanestotherequiredsettingasillustratedbeloworeitherhorizontalorverticalpattern.

    2. Locatethevelometerprobeasillustratedontheoursidesothediuserandrecordandaverageth

    readings.

    3.Obtainthetotalneckarearomthetablebelow.

    4.TheFlowRateinCFM=NeckAreaxFlowFactorxAverageVelocity.

    Flow Factors

    Flow Factor

    0.440

    0.350

    Pattern

    Horizontal

    Vertical

    Alnor Probe 6070P Location

    Areas o Squares and Rectangles (in Sq. Ft.)

    Size 1.5" 3" 4.5" 6" 7.5" 9" 10.5" 12" 13.5" 15" 16.5" 18" 19.5" 21" 22.5" 24" 25.5" 27" 28.5" 30"

    3" .031 .063

    4.5" .047 .094 .141

    6" .063 .125 .187 .250

    7.5" .078 .156 .234 .313 .390

    9" .094 .188 .281 .375 .469 .560

    10.5" .109 .219 .328 .438 .547 .656 .766

    12" .125 .250 .375 .500 .625 .750 .875 1.000

    13.5" .141 .281 .422 .563 .703 .844 .984 1.130 1.270

    15" .156 .313 .469 .625 .781 .938 1.100 1.250 1.410 .156

    16.5" .172 .344 .516 .688 .859 1.030 1.200 1.380 1.550 1.720 1.890

    18" .188 .375 .563 .750 .938 1.125 1.310 1.500 1.690 1.875 2.060 2.250

    19.5" .203 .406 .610 .813 1.015 1.220 1.420 1.630 1.830 2.030 2.230 2.440 2.640

    21" .219 .438 .656 .875 1.090 1.310 1.530 1.750 1.970 2.190 2.410 2.62 2.840 3.060

    22.5" .234 .469 .703 .938 1.170 1.410 1.640 1.880 2.110 2.340 2.580 2.810 3.050 3.280 3.520

    24" .250 .500 .750 1.000 1.250 1.500 1.750 2.000 2.250 2.500 2.750 3.000 3.250 3.500 3.750 4.000

    25.5" .266 .531 .797 1.060 1.330 1.590 1.860 2.130 2.390 2.660 2.920 3.190 3.450 3.720 3.980 4.250 4.520

    27" .281 .563 .844 1.125 1.410 1.690 1.970 2.250 2.530 2.810 3.090 3.375 3.660 3.940 4.220 4.500 4.780 5.060

    28.5" .297 .594 .891 1.190 1.480 1.780 2.080 2.380 2.670 2.970 3.270 3.560 3.860 4.160 4.450 4.750 5.050 5.340 5.640

    30" .313 .625 .938 1.250 1.560 1.875 2.190 2.500 2.810 3.125 3.440 3.750 4.060 4.375 4.690 5.000 5.310 5.625 5.940 6.25

  • 8/3/2019 Eh Price Flow Factors

    26/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-13

    June 1, 1994

    Jan. 1, 1987

    SMCD / AMCDModular Core Diuser

    Procedure: 1. Locatethevelometerprobeasillustratedbelowandrecordreadings. 2.SelecttheFlowFactor(Ak)ortheappropriateCoresize.

    3.F lowRateinCFM/Core=FlowFactor(Ak)xVelocity.

    Flow Factors

    Core Size

    8 x 8

    9 x 9

    10 x 10

    11 x 11

    12 x 12

    15 x 15

    18 x 18

    Core Size

    3 x 3

    4 x 4

    4.5 x 4.5

    5 x 5

    6 x 6

    7 x 7

    7.5 x 7.5

    Alnor Probe 6070P Locations

    Flow Fac-

    tor

    .026

    .047

    .060

    .075

    .110

    .151

    .175

    Flow Fac-

    tor

    .200

    .257

    .320

    .391

    .470

    .750

    1.100

  • 8/3/2019 Eh Price Flow Factors

    27/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-14

    June 1, 1994

    Jan. 1, 1987

    CVDCurved Vane Diusers, 1 & 2 Way Blow

    Procedure: 1. LocateAlnor6070Pprobeagainsttheoutletasshownabove.Takeanumberoreadingsatuniormlyspacedpositionsovertheaceotheunit.

    2. Averagethevelocityreadings.

    3.TheFlowRateinCFM=FlowFactorxAverageVelocityxL

    L=(corelengthparalleltovanesininches)

    Corelength=(Nominal-0.75in.)

    Flow Factors

    1 Way

    Width

    4

    6

    8

    10

    12

    14

    16

    18

    20

    24

    No. o

    Vanes

    4

    7

    9

    12

    15

    17

    20

    23

    25

    31

    K-Factor

    .0084

    .0160

    .0210

    .0280

    .0350

    .0400

    .0470

    .0550

    .0600

    .0740

    2 Way

    Width

    4

    6

    8

    10

    12

    14

    16

    18

    20

    24

    No. o

    Vanes

    4

    6

    10

    12

    14

    18

    20

    22

    26

    30

    K-Factor

    .0064

    .0110

    .0210

    .0260

    .0310

    .0400

    .0450

    .0500

    .0600

    .0700

    Note: Widthreerstonominaldimensionperpendiculartovanes.

    Alnor 6070P Probe Location

  • 8/3/2019 Eh Price Flow Factors

    28/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-15

    June 1, 1994

    Jan. 1, 1987

    CVDCurved Valve Diusers, 3 & 4 Way Blow

    Procedure: 1. LocateAlnor6070Pprobeagainsttheoutletasshownabove.Takeanumberoreadingsatuniormlyspacedpositionsovertheaceotheoutlet.

    2. Averagethevelocityreadings.

    3.TheFlowRateinCFM=FlowFactorxAverageVelocity.

    Flow Factors

    Size

    8x4

    8x58x6

    8x8

    10x4

    10x5

    10x6

    10x8

    10x10

    12x4

    12x5

    12x6

    12x8

    12x10

    12x12

    14x414x5

    14x6

    14x8

    14x10

    14x12

    14x14

    16x4

    16x6

    16x8

    16x12

    16x16

    18x4

    3 WayFlow Factor

    .057

    .067.097

    .130

    .060

    .080

    .110

    .145

    .190

    .095

    .120

    .155

    .215

    .275

    .340

    .095.125

    .165

    .225

    .295

    .365

    .420

    .135

    .225

    .310

    .495

    .665

    .140

    4 WayFlow Factor

    .055

    .075.090

    .135

    .055

    .080

    .095

    .145

    .185

    .085

    .125

    .145

    .215

    .270

    .325

    .090

    .130

    .150

    .225

    .285

    .345

    .425

    .130

    .210

    .310

    .475

    .655

    .130

    Size

    18x6

    18x818x12

    18x18

    20x4

    20x6

    20x8

    20x12

    20x18

    20x20

    24x4

    24x6

    24x8

    24x12

    24x18

    24x2430x12

    20c18

    20x24

    20x30

    36x12

    36x18

    36x24

    36x30

    36x36

    48x12

    48x24

    3 WayFlow Factor

    .235

    .320.515

    .795

    .160

    .270

    .370

    .595

    .915

    1.000

    .200

    .340

    .460

    .735

    1.150

    1.550.980

    1.550

    2.050

    2.600

    1.150

    1.750

    2.350

    3.000

    3.600

    1.600

    3.350

    4 WayFlow Factor

    ..215

    .325.490

    .770

    .150

    .245

    .370

    .565

    .890

    1.000

    .185

    .305

    .465

    .700

    1.100

    1.500.940

    1.450

    2.000

    2.550

    1.100

    1.700

    2.350

    2.950

    3.550

    1.550

    3.300

    Note: Sizeogrillereerstonominaldimension.

  • 8/3/2019 Eh Price Flow Factors

    29/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-16

    June 1, 1994

    Jan. 1, 1987

    RCD, RCDARound Ceiling Diusers

    Procedure: 1.Adjusttheairpatterntotherequiredsettingortheapplication.Veriythesettingasindicatedbydimension"x"aslistedinthetableandillustrationbelow.

    2. PlacethevelometerprobeatourequallyspacedpositionsaroundconeBasillustrated.

    3.Recordandaveragetheourvelocityreadings.

    4.F lowRateinCFM=FlowFactorxAverageVelocity.

    Flow Factors

    Neck Diam

    (in.)

    6

    8

    10

    12

    14

    16

    18

    20

    24

    30

    36

    X

    0.625

    0.812

    1.000

    1.187

    1.375

    1.625

    1.812

    2.000

    2.375

    3.000

    3.000

    X

    1.312

    1.750

    2.187

    2.625

    3.062

    3.500

    3.937

    4.375

    5.250

    6.625

    6.625

    Cones Up Cones Down

    Flow Factor

    0.12

    0.20

    0.32

    0.45

    0.61

    0.79

    1.00

    1.25

    1.80

    2.80

    3.18

    Flow Factor

    0.15

    0.27

    0.42

    0.59

    0.80

    1.05

    1.30

    1.63

    2.35

    3.60

    4.15

    Alnor 6070P Probe Location

  • 8/3/2019 Eh Price Flow Factors

    30/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-17

    June 1, 1994

    Jan. 1, 1987

    RCDERound Ceiling Diusers

    Procedure: 1.Adjusttheairpatterntotherequiredsettingortheapplication.Veriythesettingasindicatedbydimension"x"aslistedinthetableandillustrationbelow.

    2. PlacethevelometerprobeatourequallyspacedpositionsaroundconeBasillustrated.

    3.Recordandaveragetheourvelocityreadings.

    4.F lowRateinCFM=FlowFactorxAverageVelocity.

    Factor

    0.12

    0.17

    0.32

    0.47

    0.53

    0.75

    1.00

    1.25

    2.00

    Neck Diam

    (in.)

    6

    8

    10

    12

    14

    16

    18

    20

    24

    X

    0.625

    0.812

    1.000

    1.187

    1.375

    1.687

    1.750

    1.937

    2.437

    Factor

    0.10

    0.13

    0.25

    0.32

    0.41

    0.59

    0.76

    0.98

    1.62

    X

    0.875

    1.187

    1.500

    1.750

    2.000

    2.312

    2.562

    2.812

    3.437

    Cones Up Cones Down

    Alnor 6070P Probe Location

    Flow Factors

  • 8/3/2019 Eh Price Flow Factors

    31/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    C-18

    June 1, 1994

    Jan. 1, 1987

    RIDRound Cone Industrial Diuser

    Procedure: 1.Setairpatterntoeitherhorizontalorverticalasrequiredortheapplication. 2.Locatethevelometerprobeasshownbelowinaccordwiththeselectedairpattern.

    3. Placethevelometerprobeatourequallyspacedpositionsandtakevelocityreadings.

    4.Recordandaveragetheourvelocityreadings.

    5.F lowRateinCFM=FlowFactorxAverageVelocity.

    Flow Factors

    Neck Diam

    (in.)

    10

    12

    14

    16

    18

    20

    24

    Alnor 6070P Probe Locations

    HORIZONTAL

    Flow

    Factor0.21

    0.35

    0.49

    0.58

    0.80

    0.97

    1.35

    VERTICALFlow

    Factor

    0.61

    0.88

    1.20

    1.57

    1.98

    2.44

    3.52

  • 8/3/2019 Eh Price Flow Factors

    32/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    D-1

    June 1, 1994

    June 1, 1989

    Supply Air Grilles / RegistersSingle & Double Deection

    Flow Factors

    Note: Factorobtainedor0degreedefection.

    Core

    Style

    510/520

    610/620

    710/720

    21/22

    31/32

    151/152

    Damper

    yes

    yes

    yes

    no

    no

    no

    yes

    no

    yes

    no

    yes

    no

    Defection

    0

    221/2

    O

    45O

    0

    221/2

    O

    45O

    0

    0

    0

    0

    0

    0

    x

    3/

    4

    3/4

    3/4

    3/4

    3/4

    3/4

    13/16

    13/16

    13/16

    13/16

    13/16

    13/16

    Flow Factor

    0.66

    0.58

    0.51

    0.70

    0.60

    0.52

    0.78

    0.83

    0.68

    0.72

    0.87

    0.92

    Procedure: 1. TakeanumberoreadingsatgrilleacewithAlnor6070Pprobeatcenteroequalareas.Spacingoprobelocationnottoexceed6inchesineitherdirection.Donottakereadings

    directlyinrontobladesupports.

    2. Averagethevelocityreadings.

    3.Obtaincorearearomcalculation(insquareeet).

    4. CoreArea(t2)=[NominalDuctWidth(inches)-X]x[NominalDuctHeight(inches)-X]

    144

    WhereX=Coreundersizinglistedbelow.

    5.F lowRateinCFMisobtainedromollowingequation:

    CFM=(Ak/Acactor)(CoreArea,t 2)X(AverageVelocity,pm)

  • 8/3/2019 Eh Price Flow Factors

    33/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    D-2

    June 1, 1994

    June 1, 1989

    Return Air Grilles / Registers

    Procedure: 1. TakeanumberoreadingsatgrilleacewithAlnor6070Pprobeatcenteroequalareas.Spacingoprobelocationnottoexceed6inchesineitherdirection.Donottakereadings

    directlyinrontobladesupports.

    2. Averagethevelocityreadings.

    3.Obtaincorearearomcalculation(insquareeet).

    4. CoreArea(t2)=[NominalDuctWidth(inches)-X]x[NominalDuctHeight(inches)-X]

    144

    WhereX=Coreundersizinglistedbelow.

    5.F lowRateinCFMisobtainedromollowingequation:

    CFM=(Ak/Acactor)(CoreArea,t 2)(AverageVelocity,pm)

    Flow Factors

    Core

    Style

    530/630/730

    535/655/735

    60

    70

    80

    90

    9195

    96

    97

    98

    Defection

    (degrees)

    45

    45

    45

    45

    0

    0

    450

    45

    0

    45

    Flow Factor

    0.312

    0.309

    0.309

    0.343

    0.470

    0.477

    0.3410.555

    0.482

    0.470

    0.300

    x

    3/4

    3/4

    13/16

    "

    "

    "

    ""

    "

    "

    "

    Note: AllactorsobtainedromAlnor6070Pprobe.

  • 8/3/2019 Eh Price Flow Factors

    34/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    D-3

    June 1, 1994

    October 1, 1989

    MSLG / MSLGHMaximum Security Grilles

    Procedure: 1.DeterminetheaveragevelocityattheaceothegrillewiththeAlnor6070Pprobepositionedasshown.

    2.ForthelistedsizestheFlowRateinCFMis:CFM=AverageVelocityxAk

    Flow Factors

    Nominal Size

    4x4

    6x6

    8x8

    10x10

    12x12

    14x14

    16x16

    18x18

    20x20

    22x22

    24x24

    Alnor Probe 6070P Location

    Flow Factor

    0.027

    0.060

    0.104

    0.160

    0.230

    0.310

    0.400

    0.510

    0.620

    0.750

    0.890

  • 8/3/2019 Eh Price Flow Factors

    35/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    D-4

    Sept. 15, 1998

    June 1, 1994

    HCDHigh Capacity Diusers

    Procedure: 1. LocateAlnor6070Pprobeasshownbelow. 2. Averagethevelocityreadings.

    3.TheFlowRateinCFM=FlowFactorxAverageVelocity.

    Flow Factors, Ak

    Size

    6/9 6/12

    6/15

    6/18

    6/24

    6/30

    6/36

    6/42

    6/48

    6/54

    6/60

    10/18

    10/24

    10/30 10/36

    10/42

    10/48

    10/54

    10/60

    10/66

    10/72

    0 Degree

    Defection

    0.1160.165

    0.216

    0.270

    0.383

    0.503

    0.628

    0.757

    0.891

    1.028

    1.169

    0.503

    0.714

    0.9361.169

    1.411

    1.660

    1.916

    2.178

    2.446

    2.720

    15 Degree

    Defection

    0.0840.123

    0.165

    0.210

    0.306

    0.410

    0.521

    0.638

    0.761

    0.888

    1.020

    0.410

    0.599

    0.8031.020

    1.249

    1.489

    1.738

    1.996

    2.262

    2.536

    30 Degree

    Defection

    0.0650.096

    0.129

    0.165

    0.242

    0.326

    0.416

    0.511

    0.611

    0.716

    0.724

    0.326

    0.479

    0.6460.824

    1.012

    1.210

    1.417

    1.631

    1.853

    2.081

    0 Degree

    Defection

    0.6280.891

    1.169

    1.460

    1.761

    2.073

    2.392

    2.720

    3.055

    3.396

    0.824

    1.169

    1.534

    1.9162.312

    2.720

    3.139

    3.569

    4.009

    4.457

    15 Degree

    Defection

    0.5210.761

    1.020

    1.296

    1.587

    1.892

    2.208

    2.536

    2.874

    3.223

    0.699

    1.020

    1.368

    1.7382.128

    2.536

    2.961

    3.400

    3.854

    4.321

    30 Degree

    Defection

    0.4160.611

    0.824

    1.051

    1.292

    1.544

    1.808

    2.081

    2.364

    2.656

    0.561

    0.824

    1.110

    1.4171.741

    2.081

    2.436

    2.805

    3.186

    3.579

    Flow Factors For HCD1 And HCD2

    Size

    12/18 12/24

    12/30

    12/36

    12/42

    12/48

    12/54

    12/60

    12/66

    12/72

    15/18

    15/24

    15/30

    15/36 15/42

    15/48

    15/54

    15/60

    15/66

    15/72

  • 8/3/2019 Eh Price Flow Factors

    36/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    ATG Transer Air ApplicationsTranser / Door Grilles

    Procedure: 1.WithAlnor6070Pprobeconnectedorexhaustapplication,obtainvelocityreadingsasindicatedondiagrambelow.Averagevelocityreadings.

    2.Calculatecoreareaormodelotransergrillebeingused.

    3.TheFlowRateinCFM=FlowFactorxAverageVelocityxCoreArea.

    Flow Factors, Ak

    Alnor 6070P Flow Factor

    0.316

    D-5

    Sept. 15, 1998

    initial

    Alnor Probe 6070P Location

    Probelocationsonaceogrille.Lessthan1sq.t.,use9to12

    readingsspacedevenly.Forareasomorethan1sq.t.,use

    12to16readingsspacedevenly.Distancebetweenreadings

    nottoexceed6".

    Alnor Probe 6070P Probe

    Core Area in sq. t.W x H is listed in inches.

    a)ATG -CoreArea =(W-0.75) (H - 0.75) / 144

    b)ATG1A -CoreArea =(W-0.75) (H - 0.75) / 144c)ATG1B -CoreArea =(W-0.78) (H - 0.78) / 144

    d)ATG1BF-CoreArea =(W-0.78) (H - 0.78) / 144

    e)ATG1C -CoreArea =(W-1.78) (H-0.78)/144

  • 8/3/2019 Eh Price Flow Factors

    37/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    Flow Factors, Ak

    Probelocationsonaceogrille.Lessthan1sq.t.,use9to12

    readingsspacedevenly.Forareasomorethan1sq.t.,use

    12to16readingsspacedevenly.Distancebetweenreadings

    nottoexceed6".

    Alnor Probe 6070P Probe

    Core Area in sq. t.W x H is listed in inches.

    a)STG1 -CoreArea =(W-0.75) (H - 0.75) / 144

    b)STG1A -CoreArea =(W-0.75) (H - 0.75) / 144

    c)STG1B -CoreArea =(W-0.78) (H - 0.78) / 144

    d)STG1BF-CoreArea =(W-0.78) (H - 0.78) / 144

    STG Transer Air ApplicationsTranser / Door Grilles

    Procedure: 1.WithAlnor6070Pprobeconnectedorexhaustapplication,obtainvelocityreadingsasindicatedondiagrambelow.Averagevelocityreadings.

    2.Calculatecoreareaormodelotransergrillebeingused.

    3.TheFlowRateinCFM=FlowFactorxAverageVelocityxCoreArea.

    Alnor Probe 6070P Location

    Alnor 6070P Flow Factor

    0.323

    D-6

    Sept. 15, 1998

    Initial

  • 8/3/2019 Eh Price Flow Factors

    38/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    MSPGPerorated Face Maximum Security Grille

    Procedure: 1.WithAlnor6070PprobeorRotatingVaneAnemometer,obtainvelocityreadingsasindi-catedondiagrambelow.Averagevelocityreadings.

    2.TheFlowRateinCFM=FlowFactorxAverageVelocityxDuctArea.

    Rotating Vane Flow Factor

    Anemometer 0.57

    Alnor 6070P Flow Factor

    0.22

    D-7

    Sept. 15, 1998

    Initial

    1 2

    3 4

    AirFlow

    Alnor Probe 6070P Location

  • 8/3/2019 Eh Price Flow Factors

    39/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    10 SeriesPerorated Face

    Procedure: 1.WithAlnor6070Pprobeconnectedorexhaustapplication,obtainvelocityreadingsasindicatedondiagrambelow.Averagevelocityreadings.

    2.TheFlowRateinCFM=FlowFactorxAverageVelocityxCoreArea.

    Alnor 6070P Flow Factor

    0.227

    D-8

    Sept. 15, 1998

    Initial

    1 2

    3 4

    AirFlow

    Alnor Probe 6070P Location

  • 8/3/2019 Eh Price Flow Factors

    40/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    E-1

    June 1, 1994

    June 1, 1989

    RFD1-Way / 2-Way / 3-Way Pattern

    RFD 1-Way Pattern

    RFD 2-Way Pattern (24" x 24" module)

    RFD 2-Way Pattern (48" x 24" module)

    Flow Factor

    4.607.331.69

    Module Size

    48x1248x2424x24

    CFM=AverageVelocity(FPM)xFlowFactor

  • 8/3/2019 Eh Price Flow Factors

    41/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    E-2

    June 1, 1994

    June 1, 1989

    LFDLaminarFlowDiuser

    DuetothelowacevelocitygeneratedbytheLFDdiusers,aFlowHoodisrecommendedoraccurate

    volumemeasurement.

  • 8/3/2019 Eh Price Flow Factors

    42/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    AMDC Supply Air Applications

    24 x 48 Ceilling Diuser

    Procedure: 1. LocateAlnorCompufowprobeagainsttheoutletasshown.Takereadingwhereshown. 2.TheFlowRateinCFM=FlowFactorxAverageVelocityxDuctArea.

    Alnor Compufow Flow Factor

    2.216

    E-3

    Sept. 15, 1998

    Initial

    Alnor Probe Compufow Location

    16"16"

    1 2

    4 3

  • 8/3/2019 Eh Price Flow Factors

    43/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    Procedure: 1. LocateAlnor6070Pprobeagainsttheoutletasshown.Takereadingswhereshown. 2. Averagevelocityreadings.

    3.TheFlowRateinCFM=FlowFactorxAverageVelocity

    RVDC Supply Air Applications

    24x24CleanroomCellingDiuser

    Alnor Probe 6070P Location

    Alnor 6070P Flow Factor

    0.435

    E-4

    Sept. 15, 1998

    Initial

    24

    1

    Air Flow

    31 3/4

  • 8/3/2019 Eh Price Flow Factors

    44/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    HORDHospital Operating Room 8' Diuser

    Procedure: 1.WithAlnor6070Pprobeconnected,obtainvelocityreadingsasindicatedondiagrambelow. 2.Averagevelocityreadings.

    3.TheFlowRateinCFM=FlowFactorxAverageVelocity

    Alnor 6070P Flow Factor

    0.462

    Alnor Probe 6070P Location

    21 3 4

    65 7 8

    E-5

    Sept. 15, 1998

    Initial

  • 8/3/2019 Eh Price Flow Factors

    45/46

    Page No.

    Date:

    Supercedes:

    Flow Factor Sheet

    HORDHospital Operating Room 12' Diuser

    Procedure: 1.WithAlnor6070Pprobeconnected,obtainvelocityreadingsasindicatedondiagrambelow. 2. Averagevelocityreadings.

    3.TheFlowRateinCFM=FlowFactorxAverageVelocity

    Alnor 6070P Flow Factor

    0.678

    Alnor Probe 6070P Location

    21 3 4

    65 7 8

    E-6

    Sept. 15, 1998

    Initial

  • 8/3/2019 Eh Price Flow Factors

    46/46

    2975 Shawnee Ridge Court

    Suwanee, Georgia USA 30024

    Ph: 770.623.8050 Fax: 770.623.6404

    IN THE UNITED STATES

    US Head Ofce, Laboratory & Testing

    Facilities, Manuacturing Facilities &

    Distribution Warehouse in Atlanta, Georgia

    US Representatives in most major cities

    999 North Thornton Road

    Casa Grande, Arizona USA 85222-3809

    Fax: 520.423.0517

    IN THE UNITED STATES

    Manuacturing Facilities & Distribution Ware-

    house in Casa Grande, Arizona

    US Representatives in most major cities

    638 Raleigh Street

    Winnipeg, Manitoba Canada R2K 3Z9

    Ph: 204.669.4220 Fax: 204.663.2715

    IN CANADA

    Head Ofce, Export Sales Ofce,

    Laboratory & Testing Facilities,

    Manuacturing Facilities & Distribution

    Warehouse in Winnipeg, Manitoba

    Canadian Sales Ofces in most major cities

    The ounding principles o our company have never changed business integrity, frst class service and a commitment to people.

    Price manuacturing endeavours arose rom our belie that we could supply superior products and services at a reasonable price.

    Our mission is to become the worldwide supplier o preerence or air distribution products and services.

    You can rely on Price our products and services with confdence.

    Product Improvementis a continuing endeavour at Price. Thereore, specifcations are subject to change without notice.Consult your Price sales representative or current specifcations or more detailed inormation.

    Warranty: The Company warrants and guarantees that all goods within this catalog that have been manuactured by the Company have been manuactured in accordance with thespecifcations published herein and will be ree rom deects in material and workmanship or a period o twelve (12) months rom the date o Bill o Lading issued by the Company.The Company will replace deective product at its option, but will not be responsible or labor or material charges in replacing product or consequential damages. Any installation

    not conorming with the Company's specifcations, manuals, bulletins or instructions or any misuse or any modifcation not authorized by the Company voids this warranty. Thiswarranty is in lieu o all Provincial, State, and Federal statutory warranties and the conditions herein are in substitution and replacement o such warranties, statutory or otherwise.

    Price is a registered trademark o E.H. Price Limited. 2008. Lithographed in Canada 01/08

    Your Local Price Represntative: