ecp extinguishing control panel. extinguishing control panel general overview technical overview
TRANSCRIPT
ECP
Extinguishing Control Panel
Extinguishing Control Panel
• General overview
• Technical overview
Extinguishing Control Panel
Extinguishing Control Panel
Applications
• Computer Suites
• Communication Centres
• Telecom Shelters
• Archives
• Document Stores
Extinguishing Control Panel
• Designed to EN54: 2 & 4 for detection and alarm
• Designed to BS7273: Pt1 for extinguishing control
• Designed, manufactured and tested to ISO9001
• Over 25 years experience in extinguishing control
• EMC and LV compliance
Extinguishing Control Panel
• Fixed format 2 +1, 4 + 1 & 4 + 2
• Self contained with integral PSU
• Fully programmable from the membrane fascia
• Slider text inserts for translations
• All critical I/O circuits are monitored
• Clear precise information via LED indications
• Flush mounting bezel available
Extinguishing Control Panel
Membrane Fascia
Three main areas
• Panel status LED’s section
• Extinguishing control & indications section(s)
• Panel function controls section
Extinguishing Control Panel
Designation Colour
Common Alarm Red
Common Disablement YellowSystem Fault YellowCommon Fault YellowEarth Fault YellowPSU Fault YellowSounder Fault YellowPower On GreenPanel Enabled Yellow
Membrane Fascia
Panel Status LED Indications
Extinguishing Control Panel
Membrane Fascia
Extinguishing Control LED Indications Area #1
Designation Colour 2 + 1 4 + 1 4 + 2
Zone A Fire Red
Zone A Fault YellowZone B Fire RedZone B Fault YellowDischarged RedDisabled YellowHold YellowAbort Yellow
Extinguishing Control Panel
Membrane Fascia
Extinguishing Control LED Indications Area #1
Designation Colour 2 + 1 4 + 1 4 + 2
Auto/Manual Yellow
Manual Only Green
Extinguishing Control Panel
Membrane Fascia
Extinguishing Control LED Indications Area #2
Designation Colour 2 + 1 4 + 1 4 + 2
Zone A Fire Red X
Zone A Fault Yellow XZone B Fire Red XZone B Fault Yellow XDischarged Red X XDisabled Yellow X XHold Yellow X XAbort Yellow X X
Extinguishing Control Panel
Membrane Fascia
Extinguishing Control LED Indications Area #2
Designation Colour 2 + 1 4 + 1 4 + 2
Auto/Manual Yellow X X
Manual Only Green X X
Extinguishing Control Panel
Membrane Fascia
Control Panel Functions
Designation Access Level
Silence Buzzer 1Silence Alarms 2Reset 2Evacuate 2Isolate 2Test 2/4Spare N/A
Extinguishing Control Panel
Membrane Fascia
Control Panel Functions
Designation Access Level
Programme 4Numeric 0-9 1Cancel 2Enter 2
Extinguishing Control Panel
Membrane Fascia
Controls - Extinguishing Areas
Ext Area Designation Access Level 2 + 1 4 + 1 4 + 2
#1 Auto/Manual Keyswitch 1
Manual Release 1#2 Auto/Manual Keyswitch 1 X X
Manual Release 1 X X
Extinguishing Control Panel
Monitored Input Circuits
Designation 2 + 1 4 + 1 4 + 2
Detection Zone A area 1
Detection Zone B area 1Detection Zone A area 2 XDetection Zone B area 2 XHold Area 1Hold Area 2 X XAbort Area 1Abort Area 2 X X
Extinguishing Control Panel
Monitored Input Circuits
Designation 2 + 1 4 + 1 4 + 2
Manual Release Area 1
Manual Release Area 2 X XLow Pressure Area 1Low Pressure Area 2 X XAuto/Manual Area 1Auto/Manual Area 2 X X
Extinguishing Control Panel
Monitored Output Circuits
Designation 2 + 1 4 + 1 4 + 2
Common Sounder Circuit
1st Stage Sounder Circuit (2)2nd Stage Sounder Circuit (2)Actuator (2)
Extinguishing Control Panel
Monitored Outputs
Designation 2 + 1 4 + 1 4 + 2
1st Stage VFCO (2)2nd Stage VFCO (2)Fail Safe Fault VFCO1 Stage Open Collector (2)2nd Stage Open Collector (2)
Extinguishing Control Panel
Access Levels
• Reference EN54:2 restrictions
• Level 1 - Front Fascia
• Level 2 - Via a programmable 4 digit pass code providing limited controls
Extinguishing Control Panel
Access Levels
• Level 3 - Via a fixed 4 digit pass code providing additional controls
• Level 4 - Via a camlock enabling access inside the control panel & programming switch
Extinguishing Control Panel
Prog Level Description Default Setting Programming Options
01 Edit user pass code 7179 Any 4 digit pass code except 7134
02 Test mode inhibit Inhibit auxiliary relays Sounders & auxiliary operate
Sounders & auxiliary inhibit
03 Co-incidence Area 1, Zone A & Zone B Zone 1 or 2 & zone 3 or 4. Any 2 zones
04 Area 1 release timer 30 seconds 0-60 seconds
05 Area 2 release timer 30 seconds 0-60 seconds
06 Fault inhibit release No faults inhibit Sounder faults inhibit. Hold faults inhibit.
Sounder or hold faults inhibit.
07 Serial Port Not available Not available
08 Return to default Not applicable Not applicable
09 Set status indicator area Area 1 Area 2
10 Set actuator mode 0.5 second 8 seconds
Programming Options
Extinguishing Control Panel
How to program
• Access level 4 (inside control panel) operate switch 1 leaf 2 to the on position
• Panel enabled LED will pulse rapidly
• Select required menu option 01, 02, 03, etc.
Extinguishing Control Panel
How to program
• Programming details as per the manual
• Confirm selection by “Programme” button
• Return switch 1, leaf 2 to the off position
Extinguishing Control Panel
Description Programming Zone Indication
Code
Z1 & Z2 = 0 Z1 Fire ConstantRelease (Default)Z1 or Z2 or Z3 or Z4 = 1 Z2 Fire ConstantReleaseAny 2 Zones = 2 Z1 & Z2 Fire PulsedRelease
Programming Options
Co-incidence Detection -02 (4+1 Version Only)
Extinguishing Control Panel
Programming Options
Fault Inhibit Release -06
Description Programming Zone Indication
Code
Sounder or hold faults 0 Z1 Fire LED Ondo not inhibit releaseSounder faults 1 Z2 Fire LED Oninhibit releaseHold fault inhibit release 2 Z1 & Z2 Fire LED's OnSounder & hold fault 3 Z1 & Z2 Fire LED'sinhibit release Pulsed
Extinguishing Control Panel
Compatibility
• Detection devices - KFP conventional devices
• Manual release units KFP devices
• Alarm devices - bells, electronic sounders, beacons of KFP manufacture
• KFP manufactured extinguishing equipment
Peripheral equipment
• Status indicators
• Hold switches
• Abort switches
Extinguishing Control Panel
• Status indicators
- SI-1 LED indications only
- SI-2 LED indications & manual release unit
- SI-3 LED indications, manual release unit & auto/manual key switch
Extinguishing Control Panel
Internal O/P's open collector External O/P's LED's External I/P's
Discharged Discharged (red LED) Manual release *(1)
1st stage Auto/Manual keyswitch *(2)
2nd stage
Disabled
Abort
Hold
Auto/Manual Auto/Manual (yellow LED)
Manual only Manual only (green LED)
*(1) SI-2 or 3 only*(2) SI-3 only
Peripheral equipment (cont’d)
Extinguishing Control Panel
Peripheral equipment
• Status indicators
- 6 status indicators up to 1.2km away from the ECP- Flush mounted or surface mounted options- RS 485 communications over 2 core cable- Selectable for area A or area B coverage- Lamp test facility- Surface mounted version 123mm (w) x 123mm
(h) x 64mm (d)- Flush mounted version 143mm (w) x 143mm (h)
Extinguishing Control Panel
Extinguishing Control Panel
• Hold Switch
- Red mushroom button, non-latching
- IP 56 enclosure
- 108mm (w) x 108mm (h) x 85mm (d)
- Out of sequence monitoring by the ECP
Extinguishing Control Panel
• Abort Switch
- Red mushroom button, twist to release
- IP 56 enclosure
- 108mm (w) x 108mm (h) x 85mm (d)
- Out of sequence monitoring by the ECP
Technical Summary
• Quiescent current
ECP 2+1 77mA
ECP 4+1 84mA
ECP 4+2 93mA
• Battery Calculations
Quiescent current x battery degradation factor x 24 hours +
half hour alarm time x alarm load x battery degradation factor
Q1 x 1.25 x 24 + 0.5 x Al x 1.25
Extinguishing Control Panel
Extinguishing Control Panel
Technical Summary
• ECP 2+1 Example
0.077mA x 1.25 x 24 + 0.5 x 1.0 x 1.25
2.31 + 0.625
2.935 A/H
Note: 7 A/H battery space available
Extinguishing Control Panel
Technical Summary
• ECP 4+1 Example
0.084mA x 1.25 x 24 + 0.5 x 1.0 x 1.25
2.52 + 0.625
3.145 A/H
Note: 7 A/H battery space available
Extinguishing Control Panel
Technical Summary
• ECP 4+2 Example
0.093mA x 1.25 x 24 + 0.5 x 1.0 x 1.25
2.79 + 0.625
3.415 A/H
Note: 7 A/H battery space available
Extinguishing Control PanelTechnical Summary
• End of line resistors
Sounder circuits 10K
Detection zones 3K9
• Dimensions
ECP 2+1 438 (w) x 128 (d) x 398 (h)
ECP 4+1 438 (w) x 128 (d) x 398 (h)
ECP 4+2 438 (w) x 128 (d) x 398 (h)
• Weight
ECP 2+1, ECP 4+1 & ECP4+2 7.2Kg
Extinguishing Control Panel
Fuse Reference Rating Type
F1 - Common sounders 0.5A Sub minatureF2 - Area A 1st stage sounder 0.5A Sub minatureF3 - Area A 2nd stage sonder 0.5A Sub minatureF4 - Area B 1st stage sounder 0.5A Sub minatureF5 - Area B 2nd stage sounder 0.5A Sub minatureF6 - Battery 1.0A Sub minatureF7 - 28v auxiliary 1.0A Sub minatureF8 - Area B actuator 1.6A Sub minatureF9 - Area A acuator 1.6A Sub minatureMains fuse 1.0A 20mm semi delay
Fuse Details
Note: Sub minature fuses are of the plug in type which have a 5mm pitch and are the F type (quick blow). The leads of the fuses will need to be cut down prior to being mounted in their sockets.
Extinguishing Control Panel
Internal Controls
Switch ref Switch Type Designation
SW2 Momentary push button Restarts the micro-processor, hardware reset
SW3 Momentary push button Resets the micro-processor fault signal
SW1 2 way DIL switch Leaf 1 in the off position will make common sounder circuit operate
in a pulsed mode. Leaf 1 in the position will make the common
sounder circuit operate in a constant mode. Leaf 2 in the on
position will put the panel into programming mode; the off
position will terminate this mode.
LK1 3 position link In the parked position (top pin exposed) the ECP will operate
from the on board power supply. In the made position (bottom pin
exposed) the ECP can be powered from an external 24v-dc supply.
Extinguishing Control Panel
Internal Indications
Area 1 Fault Designation LED LED Area 2 Fault Designation
Hold HoldAbort AbortLow Pressure Low PressureDischarge DischargeManual Release Manual ReleaseActuator ActuatorDisable Disable
Extinguishing Control Panel
Status Indicators
Description Part Number
LED's only SI-1 53836-K178/01LED's & auto/manual keyswitch SI-2 53836-K178/02LED's manual release & auto/manual key switch SI-3 53836-K178/03Semi-flush mounting bezel 35100-132/01RS 485 driver card 44782-K076
SW1 - Momentary push button for micro-processor resetSW2 - Momentary push button for LED test
Extinguishing Control Panel
Jumper Intermeadiate SI Last SI
1 IN OUT2 IN OUT3 OUT IN4 OUT IN5 OUT IN6 OUT IN
The status indicators have a terminating resistor network for the RS485 communications, the jumper selection must be as detailed below. The ECP RS485 driver card for the status indicators has two way DIL switch SW1 located on the board. With leaves 1 & 2 in the ON position the board will drive in both directions. With leaves 1 & 2 in the OFF position the board will drive in one direction only.
Status Indicators
Extinguishing Control Panel
Panel Part Number
ECP 2+1 35100-K165ECP 4+1 35100-K165ECP 4+2 35100-K165Status Indicators 35100-132/01
Flush mounting bezel