Eco Commercial Fans Installation Instructions
Original Instructions
2 3
Greenwood Airvac Technical Services Tel: 01903 777135
ContentsGeneral Description and Physical Specification 2-3
Wall Mounting Installation 4
Window Mounting Installation 5
Ceiling/Panel Mounting Installation 6
Pitched Roof Installation 7
Flat Roof Installation 8
Refurbishment Installation 9
Wiring Instructions 10
Integral Sensor and Remote Sensor/Remote Switch Installation 11
Superduct Fan Installation 12-13
Cleaning and Maintenance 14
CE Declaration 15
General Description and Physical Specification•Warning: The appliance is not intended for use by young children or infirm persons unless they have been adequately
supervised by a responsible person to ensure that they can use the appliance safely. Young children should be supervised to ensure they do not play with the appliance.
•Observe appropriate safety precautions if working on steps or ladders. Wear eye protection when breaking out wall or window materials etc.
•When installing wall mounted fans, ensure that there are no buried cables or pipes in the way. It is recommended that this fan is mounted 2.3m above floor level.
•A clearance of 75mm to be allowed on at least one side of the fan for the removal of the internal grille.
•Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel burning appliances (for duct and partition fans).
•This fan shall not be mounted above or closer than 1 metre to a cooker of other heat source where it could be affected by excessive heat or moisture or sited where it would be suject to a direct source of heat in excess of 40˚C.
•After the fan is installed, its control system shall be in accordance with EN60335-2-80.
3
Technical Services Tel: 01903 777135 Greenwood Airvac
413mm
206.5mm*
420mm
214.5mm*
Surface cable entry
* To centre of duct
Recessed cable entry
169. 4mm
420mm
Front
Rear
Side342mm
171mm*
342mm
175mm*
130mm
342mm
* To centre of duct
Front
Side
Surface cable entry
Recessedcable entry
Rear
269mm
134.5mm*
269mm
137.5mm*
128mm
272mm
Surface cable entry
* To centre of duct
Recessed cable entry
Front
Rear
Side
Dimensions
Spigot Sizes for Ducted Applications
12” Fan 6” Fan9” Fan
Ck SA Sp iDk Ceiling Adaptor Single Spigot Adaptor Single Spigot Induct Kit
CD12 350mm 350mm 350mm 350mm
CD9 250mm 250mm 250mm 250mm
CD6 200mm 200mm 200mm 200mm
Fan Specifications
220-240 ~ 50Hz / 1Ph
IPX4: CD12: 100 watts CD9: 50 watts CD6: 38 Watts
Cable size required: 3 core 1.5mm2 / 4 core 1.5mm2.
Supply should be fused at 3 Amp.
The sound pressure of the Eco Commercial Fan is less than 70 dB(A).
4 5
Greenwood Airvac Technical Services Tel: 01903 777135
54
Wall Mounting
1
2 6
7
8
9
10
11
12
13
3
4
5
Eco 12” D = 410 x 410 mm
Eco 9” D = 330 x 330 mm
Eco 6” D = 260 x 260 mm
D
Wiring – Page 10
CD12 l CD9 l CD6
Complete kits CD12WA l CD9WA l CD6WA
EG12 l
EG9 l
EG6
ED12 l ED9 l ED6
Min. duct length 200mm
individual Units
5
Technical Services Tel: 01903 777135 Greenwood Airvac
5
CD12 l CD9 l CD6
Complete kits CD12WA l CD9WA l CD6WA
ED12 l ED9 l ED6
11 Wiring – Page 10
6
7
8
9
10
12
13
1
2
4
5
Eco 12” D = 337 mm
Eco 9” D = 260 mm
Eco 6” D = 184 mm
D
3
Window Mounting
individual Units
6 7
Greenwood Airvac Technical Services Tel: 01903 777135
76
10 Wiring – Page 10
9
11
1
2
3
Ceiling/Panel Mounting
Eco 12” D = 430 x 430 mm
Eco 9” D = 340 x 340 mm
Eco 6” D = 270 x 270 mm
D
4
5
6
7
8
CD12 l CD9 l CD6
CK12 l CK9 l CK6
individual Units
Complete kits CD12CK l CD9CK l CD6CK
7
Technical Services Tel: 01903 777135 Greenwood Airvac
7
WT12: 506 x 506mmWT9: 425 x 425mmWT6: 360 x 360mm
WT12: 185mmWT9: 180mmWT6: 170mm
Side
Plan
WFP12: 550 x 550mmWFP9: 475 x 475mmWFP6: 400 x 400mm
WFP12: 337mm dia.WFP9: 260mm dia.WFP6: 185mm dia.
WFP12: 2mmWFP9: 2mmWFP6: 2mm
Side
Plan
Dimensions
Weather Terminal
Wall Fixing Plate
SA12: 430 x 430mmSA9: 345 x 345mmSA6: 275 x 275mm
SA12: 350mm dia.SA9: 250mm dia.SA6: 200mm dia.
SA12: 70mmSA9: 70mmSA6: 70mm
Side
Plan
Single Spigot Adaptor
Weather Terminal
WS12: 425 x 425mmWS9: 341 x 341mmWS6: 271 x 271mm
WS12: 137mmWS9: 123mmWS6: 126mm
Side
Plan
Spacer
Pitched Roof InstallationComplete kits CD12PR l CD9PR l CD6PR
Weather Terminal (WT12/WT9/WT6)
Wall Fixing Plate (WFP12/WFP9/WFP6)
Spacer (WS12/WS9/WS6)
Single Spigot Adapter (SA12/SA9/SA6)
Flexible Ducting
Worm Drive Fixing Clips
Lead Flashing
EXPLODED VIEW
The Installation is made by screwing (8. off 5 mm dia. screws not provided) a Wall Fixing Plate (WFP6/9/12) to suitably spaced purlins/ trimmers and weather-sealing this to the structure with a lead or zinc apron.
The trimmed opening size is:–
l 6” Fan = 320 x 320 mm
l 9” Fan = 385 x 385 mm
l 12” Fan = 450 x 450 mm
To complete the water-tightness of the installation, drill out the 4 dimpled hole positions (6 mm dia.) in the base of the Weather Terminal (WT6/9/12), place this centrally on the Fixing Plate, with its lower
edge sealed by silicon mastic, and then, using the M5 screws, washers and seals provided, attach the Weather Terminal to the Spacer Moulding (WS6/9/12).
With the installation now weather-tight, the Fan may be fitted into the Spacer as convenient.
Once the Fan is fitted, the Spigot Adaptor (SA6/9/12) may be screwed to its lower face and ducting attached as required.
On 6” Fans, the Spigot Adaptor may be replaced by a Multi-Spigot Adaptor (MS6) which will accept up to 4 – 100 mm dia. individual ducts.
8 9
Greenwood Airvac Technical Services Tel: 01903 777135
Dimensions
Weather Terminal Spacer
98
Roof Felt
RoofSlab
CeilingPanel
RoofFelt
RoofSlab
CeilingPanel
Spacer WS6 / WS9 / WS12
Fan
Grille
Roof Terminal RT6 / RT9 / RT12
EXPLODED VIEW
RoofFelt
RoofSlab
CeilingPanel
A x B
O/all Finished Curb
C x D
Ceiling Opening
15
0m
m
A B C D (max.) (max.) (max.) (max.)
CD6 610mm 610mm 300mm 300mm
CD9 610mm 610mm 450mm 450mm
CD12 695mm 695mm 450mm 450mm
The Installation is made by constructing a timber or builders-work curb to the dimensions shown below:-
centrally and squarely over the curb and screw the Terminal to the curb using 6mm Wood Screws and Sealing Washers.
Offer the Spacer (WS6, WS9 or WS12) to the underside of the secured Terminal and attach using the 4.off M5 screws provided.
Attach the fan to the Spacer, again using the screws provided, and complete the electrical wiring as required.
The ceiling opening should be closed using a suitable 300 x 300mm grille (CD6 fan) or 450 x 450mm grille (CD9 or CD12 fans).
To complete the installation, drill out the 8.off dimpled holes in the base of the Roof Terminal (RT6, RT9 or RT12), position the Terminal
Side
Plan
RT12: 506 x 506mmRT9: 425 x 425mmRT6: 360 x 360mm
RT12: 742 x 742mmRT9: 657 x 657mmRT6: 657 x 657mm
RT12: 185mmRT9: 180mmRT6: 170mm
Flat Roof InstallationComplete kits CD12FR l CD9FR l CD6FR
WS12: 425 x 425mmWS9: 341 x 341mmWS6: 271 x 271mm
WS12: 137mmWS9: 123mmWS6: 126mm
Side
Plan
9
Technical Services Tel: 01903 777135 Greenwood Airvac
9
Refurbishment InstallationComplete kits CD12RE l CD9RE l CD6RE
Replacing existing Greenwood Eco FansThe fan is fixed as the previous fan into the existing channels on the wall liner. The picture frame can be used if desired, however the metal brackets are not required.
Replacing existing T series FansThe brackets supplied with the kit can be aligned with the screw fixing holes of the previous fan. This then positions the receiving nut on the bracket in the correct location to allow fixing of the Greenwood refurbishment fan.
Wiring details – Greenwood Eco FansWhen replacing Greenwood fans in many cases the wiring will remain the same, however if the existing controller is of the RC1 or RC2 type installed with CX fans, then the switch functionally changes. The RC1 switch becomes an intake/off/extract switch operating the fan on high speed only. The RC2 switch maintains the on/off/auto functions, but at installation the direction is selected.
Wiring details – T series FansA Greenwood CD fan can be used to replace a Vent Axia ‘T’ Series fan, retaining the original controller, providing the controller is of the ‘Ecotronic 130’, ‘Rangemaster’ or ‘T’ Series Controller type.
This arrangement will give the following operating features:• Adjustable speed
• Adjustable minimum speed
• Extract/intake
• Fan off – shutter open
• Fan off – shutter closed.
Limitations are:• Control of single fan only
• Integral sensors not possible
• Automatic ECO setting not available.
This arrangement will give the following operating features:• Single speed
• Extract/intake
• On/off.
Limitations are:• Control of single fan only
• Integral sensors not possible
• Automatic ECO setting not available.
NB. All electrical products must be wired and installed by a qualified electrician in accordance with IEE and local regulations which apply. The fans must be connected to mains power by using a fused double pole isolating switch having a contact separation of at least 3mm.
Replacing existing Greenwood Eco fan
Replacing existing T series fan
L
L
L
L3 L1 L2
L5
L4
L3
L2
L1
N
N
N
N N1Max
5 ampDouble-Pole
Isolator
Vent Axia Ecotronic 130 or Rangemaster Controller Greenwood Eco Type CD
Reversible Fan
230v
~ 5
0hz
L
L3
L1
L2
L5
L4
L3
L2
L1
N
N
N
Max5 amp
Double-PoleIsolator
Vent Axia T-Sereis Controller Greenwood Eco Type CD
Reversible Fan
230v
~ 5
0hz
L
L
L
L3 L1 L2
L5
L4
L3
L2
L1
N
N
N
N N1Max
5 ampDouble-Pole
Isolator
Vent Axia Ecotronic 130 or Rangemaster Controller Greenwood Eco Type CD
Reversible Fan
230v
~ 5
0hz
L
L3
L1
L2
L5
L4
L3
L2
L1
N
N
N
Max5 amp
Double-PoleIsolator
Vent Axia T-Sereis Controller Greenwood Eco Type CD
Reversible Fan
230v
~ 5
0hz
NB. The ‘T’ Series controller speed capacitor must be removed from the controller before use with a Greenwood ECO fan.
10 11
Greenwood Airvac Technical Services Tel: 01903 777135
1110
LL
L4L3L2L1N
L5L4L3L2L1N
NN
Max3 amp
Double-PoleIsolator
SwitchRC3
CD Fan Unit
230v
~ 5
0hz
LL
L4L3L2L1N
L5L4L3L2L1N
NN
Max3 amp
Double-PoleIsolator
SwitchRC4
CD Fan Unit
230v
~ 5
0hz
LL
L1 L2 N
L4L3L2L1N
L5L4L3L2L1N
NN
Max3 amp
Double-PoleIsolator
SwitchRC4
Remote Sensor CD Fan Unit
230v
~ 5
0hz
SWL Only required if Fan unit is to be fitted with integral ‘TA’ Timer
LL
L4L3L2L1N
L5L4L3L2L1N
NN
Max3 amp
Double-PoleIsolator
SwitchRC3
CD Fan Unit
230v
~ 5
0hz
LL
L4L3L2L1N
L5L4L3L2L1N
NN
Max3 amp
Double-PoleIsolator
SwitchRC4
CD Fan Unit
230v
~ 5
0hz
LL
L1 L2 N
L4L3L2L1N
L5L4L3L2L1N
NN
Max3 amp
Double-PoleIsolator
SwitchRC4
Remote Sensor CD Fan Unit
230v
~ 5
0hz
SWL Only required if Fan unit is to be fitted with integral ‘TA’ Timer
LL
L4L2L3N
L5L4L3L2L1N
NN
Max3 amp
Double-PoleIsolator
SwitchRC1
CX Fan Unit
230v
~ 5
0hz
L LN N
Max3 amp
Double-PoleIsolator
CXPC Fan Unit
230v
~ 5
0hz
L
L1 L2 N L5
L4
L3
L2
L1
N
L5
L4
L3
L2
L1
NN
Max3 amp
Double-PoleIsolator
Remote Sensor CD Fan Unit CD Fan Unit
230v
~ 5
0hz
SWL
Link L2 – L4for Extract
Link L2 – L3for Intake
L1 L2 N
Remote Sensor
SWL
L
L5
L4
L3
L2
L1
N
L5
L4
L3
L2
L1
NN
Max3 amp
Double-PoleIsolator
CD Fan Unit CD Fan Unit
230v
~ 5
0hz
Link L2 – L4for Extract
Link L2 – L3for Intake
Only required if Fan unit is to be
L
L5
L4
L3
L2
L1
N
L5
L4
L3
L2
L1
NN
Max3 amp
Double-PoleIsolator
CD Fan Unit CD Fan Unit
230v
~ 5
0hz
Link L2 – L4for Extract
Link L2 – L3for Intake
Only required if Fan unit is to be
LL
L4L2L3N
L5L4L3L2L1N
NN
Max3 amp
Double-PoleIsolator
SwitchRC1
CX Fan Unit
230v
~ 5
0hz
L LN N
Max3 amp
Double-PoleIsolator
CXPC Fan Unit
230v
~ 5
0hz
L
L1 L2 N L5
L4
L3
L2
L1
N
L5
L4
L3
L2
L1
NN
Max3 amp
Double-PoleIsolator
Remote Sensor CD Fan Unit CD Fan Unit
230v
~ 5
0hz
SWL
Link L2 – L4for Extract
Link L2 – L3for Intake
L1 L2 N
Remote Sensor
SWL
L
L5
L4
L3
L2
L1
N
L5
L4
L3
L2
L1
NN
Max3 amp
Double-PoleIsolator
CD Fan Unit CD Fan Unit
230v
~ 5
0hz
Link L2 – L4for Extract
Link L2 – L3for Intake
Only required if Fan unit is to be
L
L5
L4
L3
L2
L1
N
L5
L4
L3
L2
L1
NN
Max3 amp
Double-PoleIsolator
CD Fan Unit CD Fan Unit
230v
~ 5
0hz
Link L2 – L4for Extract
Link L2 – L3for Intake
Only required if Fan unit is to be
LL
L5L4L3L2L1N
NN
Max3 amp
Double-PoleIsolator
CD Fan Unit
230v
~ 5
0hz
At Installation, set link on Terminal Block Coverto L3 to give intake or
L4 to give extract.
LL
L4L3L2L1N
L5L4L3L2L1N
NN
Max3 amp
Double-PoleIsolator
SwitchRC3
CD Fan Unit
230v
~ 5
0hz
LL
L4L3L2L1N
L5L4L3L2L1N
NN
Max3 amp
Double-PoleIsolator
SwitchRC4
CD Fan Unit
230v
~ 5
0hz
LL
L1 L2 N
L4L3L2L1N
L5L4L3L2L1N
NN
Max3 amp
Double-PoleIsolator
SwitchRC4
Remote Sensor CD Fan Unit
230v
~ 5
0hz
SWL Only required if Fan unit is to be fitted with integral ‘TA’ Timer
Wiring Instructions
N.B:
All electrical products should be wired and installed by a qualified electrician, in accordance with IEE or local regulations which apply.
The fans must be connected to mains power by using a fused double pole isolating switch having a contact separation of at least 3mm.
For other siting appliances please refer to supplier data sheets available on requested.
Always isolate appliance from the mains before cleaning.
Do not use solvents to clean the fan.
1 2 3
4
Fan with Automatic operation by Remote Sensor
Fan without Controller switched by Integral Sensor
Fan with 2-position Switch
Fan with Remote Switch RC3
Fan with Remote Switch RC4 and Remote Sensor
Fan with Remote Switch RC4 and Integral Sensor
11
Technical Services Tel: 01903 777135 Greenwood Airvac
11
Integral Sensor
Remote Sensor/Remote Switch
1
2
4
3
5
6
7
8
9
1
4 6
53
2
> 200mm> 1.5m
12 13
Greenwood Airvac Technical Services Tel: 01903 777135
1312
Dimensions
242mm
80mm
SD100
80mm
194mm
242mm
44mm
242mm
272mm
80mm
SD150
80mm
198mm
272mm
44mm
272mm
344mm
80mm
SD200
80mm
230mm
344mm
44mm
344mm
344mm
80mm
SD250
80mm
230mm
344mm
44mm
344mm
402mm
80mm
SD315
80mm
257mm
402mm
44mm
402mm
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
242mm
80mm
SD100
80mm
194mm
242mm
44mm
242mm
272mm
80mm
SD150
80mm
198mm
272mm
44mm
272mm
344mm
80mm
SD200
80mm
230mm
344mm
44mm
344mm
344mm
80mm
SD250
80mm
230mm
344mm
44mm
344mm
402mm
80mm
SD315
80mm
257mm
402mm
44mm
402mm
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
242mm
80mm
SD100
80mm
194mm
242mm
44mm
242mm
272mm
80mm
SD150
80mm
198mm
272mm
44mm
272mm
344mm
80mm
SD200
80mm
230mm
344mm
44mm
344mm
344mm
80mm
SD250
80mm
230mm
344mm
44mm
344mm
402mm
80mm
SD315
80mm
257mm
402mm
44mm
402mm
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
242mm
80mm
SD100
80mm
194mm
242mm
44mm
242mm
272mm
80mm
SD150
80mm
198mm
272mm
44mm
272mm
344mm
80mm
SD200
80mm
230mm
344mm
44mm
344mm
344mm
80mm
SD250
80mm
230mm
344mm
44mm
344mm
402mm
80mm
SD315
80mm
257mm
402mm
44mm
402mm
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
242mm
80mm
SD100
80mm
194mm
242mm
44mm
242mm
272mm
80mm
SD150
80mm
198mm
272mm
44mm
272mm
344mm
80mm
SD200
80mm
230mm
344mm
44mm
344mm
344mm
80mm
SD250
80mm
230mm
344mm
44mm
344mm
402mm
80mm
SD315
80mm
257mm
402mm
44mm
402mm
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
Surfacecable entry
Front
Side
SD100
SD150 SD200 SD250 SD315
SD100 l SD150 l SD200
l SD250 l SD315
Superduct Fan
Wiring Instructions
N.B.:
All electrical products should be wired and installed by a qualified electrician, in accordance with IEE or local regulations which apply.
The fans must be connected to mains power by using a fused double pole isolating switch having a contact separation of at least 3mm.
For other siting applications please refer to supplier data sheets, available on request.
Always isolate appliance from the mains before cleaning.
Do not use solvents to clean this fan.
L
N
230
V ~
50
HzGreen/Yellow
Blue
BrownFan
Capacitor
Black
SD150, SD200, SD250 & SD315
L
N
230
V ~
50
HzGreen/Yellow
Blue
Brown
Fan
Capacitor
Black
SD100
13
Technical Services Tel: 01903 777135 Greenwood Airvac
13
1
3
4
5
6
7
8
2
9
11
10
12
15
13
14
14 15
Greenwood Airvac Technical Services Tel: 01903 777135
Cleaning / Maintenance
•Always isolate fan from mains before cleaning.
•For all fan sizes remove grille and clean in warm soapy water with a non-abrasive cloth.
•The impeller can be removed by carefully pulling the fan blades from either side at the same time. These are to be cleaned in the same way as the above.
•The rear shutters can be cleaned but care must be taken when removing and replacing.
•Ensure that the shutter blades pins are correctly seated on the outside rim.
•Remove shutters via the retaining screws (3 will be found on the 6” and 9” models, 7 will be found on the 12” model). Once removed, the shutter assembly can be cleaned in warm soapy water and must be dried thoroughly before replacing.
•When replacing ensure that the shutter assembly blades are fully closed and that the assembly, as a whole, is correctly seated before tightening the screws.
•When the shutter assembly has been replaced, ensure that the shutter blades are free to open by placing a hand on either side of the shutter assembly blades and carefully opening.
•Once the interior grille shutter assembly has been cleaned, the fan’s main housing can be wiped with a clean damp, non-abrasive cloth.
15
Technical Services Tel: 01903 777135 Greenwood Airvac
EC Declaration of Conformity/Incorporation In accordance with EN ISO 17050-1:2004
We Greenwood Air Management Ltd Of Greenwood House, Brookside Avenue, Rustington, West Sussex, BN16 3LF, UK In accordance with the following Directive(s): 2004/108/EC The Electromagnetic Compatibility Directive 2006/42/EC The Machinery Directive hereby declare that: Equipment Ventilation Fan Model Number CD6 / ENERGY 500VE / CD9 / ENERGY 900VE / CD12 / ENERGY 1800VE Is in conformity with the applicable requirements of the following documents Ref. No. Title Edition/date BS EN ISO 12100- Safety of machinery. Basic concepts, general principles for design 2003 =A1:2009 1&2 BS EN 60335-1 Household and similar electrical appliances. Safety. General 2002+A2:2006 requirements BS EN 60335-2-80 Household and similar electrical appliances. Safety. Particular 2003 requirements for fans BS EN 61000-6-1 Electromagnetic compatibility (EMC). Generic standards. 2007 Immunity for residential, commercial and light-industrial environments BS EN 61000-6-3 Electromagnetic compatibility (EMC). Generic standards. Emission 2007 standard for residential, commercial and light-industrial environments
I hereby declare that the equipment named above has been designed to comply with the relevant sections of the above referenced specifications and is in accordance with the requirements of the Directive(s)
Signed by: Name: John Barratt (full name of signatory) Position: Business Process Manager (position) Done at: As above (place) On : 02 February 2012 (date) The technical documentation for the machinery is available from the manufacturer at the above address.
Greenwood Air Management Ltd
Greenwood House, Brookside Avenue, Rustington, West Sussex BN16 3LF
Main Line Tel: +44 (0) 1903 771021 Technical Services: +44 (0) 1903 777135 Main Line Fax: +44 (0) 1903 782398 Web: www.greenwood.co.uk Email: [email protected]
P541/132 Iss H May 2012 MCR708 PN05.10.114