EARTH FAULT DETECTING
METHODS ON
COMPENSATED
NETWORKS
![Page 2: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/2.jpg)
SUMMARY
Events during normal network condition
Asymmetry on compensated networks
Usage of Petersen coil controller
Events during single earth-fault condition
Prevention of evolving permanent earth faults
Main types of permanent earth faults
Different methods for detecting earth faults
Residual definite time overcurrent protection
Directional residual delayed overcurrent protection
Transient earth fault protection
New method: admittance earth fault protection
09-Nov-17 2
![Page 3: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/3.jpg)
09-Nov-17 3
ASYMMETRY ON
COMPENSATED
NETWORKS
![Page 4: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/4.jpg)
SOURCES OF ASYMMETRY ON
COMPENSATED NETWORKS
09-Nov-17 4
Asymmetrical arrangement of phase conductors
Iron core structure of power transformers
Isolator’s leakage resistance
Asymmetrical elements connected to the network
![Page 5: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/5.jpg)
CONSEQUENCES OF
ASYMMETRY
09-Nov-17 5
Increased phase voltages
Increased risk of earth-faults
It can block the tuning of the Petersen coil (because of high U0)
Petersen coil is not tuned
Earth-fault current is increased
Earth-fault is continuous
Risk of dangerous step voltage is high
Protection trip is needed
![Page 6: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/6.jpg)
SYMMETRIZATION METHODS
09-Nov-17 6
Cyclic transposition of the phase conductors
Needs reconstruction of the network
Mounting on several locations
Long time without power supply
Continuous grounding resistor
Several disadvantages
Added symmetrizing capacitors (provided by Protecta)
Mounting at the substation only
Lower costs
Short time without power supply
![Page 7: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/7.jpg)
09-Nov-17 7
USAGE OF
PETERSEN COIL
CONTROLLER
![Page 8: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/8.jpg)
PRINCIPLE OF COMPENSATION
(PETERSEN COIL)
09-Nov-17 8
![Page 9: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/9.jpg)
PRINCIPLE OF COMPENSATION
(PETERSEN COIL)
09-Nov-17 9
![Page 10: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/10.jpg)
ADVANTAGES OF USING PETERSEN
COIL CONTROLLER
09-Nov-17 10
Why is it important to use an automatical controller for the Petersen coil?
To check the level of compensation whenever it is needed
The network always changes: feeders can be connected or disconnected to the busbar any time
Because the capacity of the zero sequence network can change any time, the Petersen coil
must follow the change of the capacity
It always keeps the Petersen coil in a well-tuned position
![Page 11: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/11.jpg)
RESULT OF THE MEASUREMENT: THE
RESONANT CURVE
09-Nov-17 11
![Page 12: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/12.jpg)
09-Nov-17 12
PREVENTION OF
EVOLVING
PERMANENT
EARTH FAULTS
![Page 13: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/13.jpg)
WHAT CAN INCREASE THE RISK OF
EVOLVING PERMANENT EARTH
FAULTS?
09-Nov-17 13
Use of grounding (shunt) resistor � it increases the fault current, so the fault
becomes stable
The Petersen coil is not well tuned � High under- or overcompensation
Short time for using the Petersen coil alone
![Page 14: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/14.jpg)
AN EFFECTIVE WAY OF PREVENTION
09-Nov-17 14
Well-tuned Petersen coil
Example 1:
Example 2:
Example 3:
![Page 15: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/15.jpg)
WHY ”EXACT” COMPENSATION CAN
CAUSE PROBLEMS?
09-Nov-17 15
The U0 is relatively high:
Increased phase voltages
Problems of Petersen tuning procedure
![Page 16: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/16.jpg)
WHAT CAN BE THE BEST SOLUTION?
(IDEA OF PROTECTA)
09-Nov-17 16
Use of shunt inductance, which is connected parallel to the Petersen coil � in
case of possible earth fault the ”exact” compensation can be approached:
ADAPTIVE COMPENSATION
![Page 17: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/17.jpg)
09-Nov-17 17
MAIN TYPES OF
PERMANENT
EARTH FAULTS
![Page 18: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/18.jpg)
STABLE EARTH FAULTS WITH LOW
FAULT RESISTANCE
09-Nov-17 18
The fault current flows continuously
If the grounding resistance is switched on, the increased fault current is high
enough for overcurrent protections to detect the earth fault
![Page 19: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/19.jpg)
STABLE EARTH FAULTS WITH HIGH
FAULT RESISTANCE
09-Nov-17 19
The fault current flows continuously
If the grounding resistance is switched on, the increased fault current is NOT
enough for overcurrent protections to detect the earth fault
The primary 3I0 is 18A!
![Page 20: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/20.jpg)
INTERMITTENT EARTH FAULTS
09-Nov-17 20
The fault current does not flow continuously
The exact fault time is around 5-10msec, then the fault is cleared for many
periods
The time between faults can be 100msec – 500msec
![Page 21: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/21.jpg)
09-Nov-17 21
RESIDUAL
DEFINITE TIME
OVERCURRENT
PROTECTION
![Page 22: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/22.jpg)
EARTH FAULT CURRENT-BOOSTER
METHOD
09-Nov-17 22
The symmetrical component network:
![Page 23: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/23.jpg)
EARTH FAULT CURRENT-BOOSTER
METHOD
09-Nov-17 23
The zero sequence voltage and currents during the earth fault:
Healthy feeder: Faulty feeder:
![Page 24: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/24.jpg)
RESIDUAL DEFINITE TIME
OVERCURRENT PROTECTION
09-Nov-17 24
The setting parameters are:
Starting current (Istart)
Definite time delay (Tdelay)
![Page 25: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/25.jpg)
RESIDUAL DEFINITE TIME
OVERCURRENT PROTECTION
09-Nov-17 25
Advantages
Very simple solution
The list of parameters is short
It does not require U0 voltage
Disadvantages
Maintenance of the resistance is expensive
It cannot detect earth faults with high fault resistance
If the resistance is switched on, then the chance of clearing the earth fault by the Petersen coil
is zero
Dangerous step and touching voltage: the IEC-50522 standard does not allow to keep the
increased fault current for a long time (the fault time can be maximum 100-200ms)
![Page 26: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/26.jpg)
09-Nov-17 26
DIRECTIONAL
RESIDUAL DELAYED
OVERCURRENT
PROTECTION
![Page 27: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/27.jpg)
WATTMETRIC METHOD
09-Nov-17 27
The symmetrical component network:
![Page 28: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/28.jpg)
WATTMETRIC METHOD
09-Nov-17 28
The zero sequence voltage and currents during the earth fault:
Healthy feeder: Faulty feeder:
![Page 29: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/29.jpg)
DIRECTIONAL RESIDUAL DELAYED
OVERCURRENT PROTECTION
09-Nov-17 29
The setting parameters are:
Starting current (Istart)
Characteristic angle (RCA)
Operating angle (ROA)
Operating characteristic
![Page 30: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/30.jpg)
09-Nov-17 30
Advantages
It does not require any added primary or secondary element
The earth fault current is not increased
Disadvantages
It cannot detect intermittent earth faults
If the resistance of the Petersen coil is low, then the wattmetric component of the fault current is
too low � it is hard to set the characteristic well
It requires U0 voltage (and of course I0 current)
DIRECTIONAL RESIDUAL DELAYED
OVERCURRENT PROTECTION
![Page 31: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/31.jpg)
09-Nov-17 31
TRANSIENT EARTH
FAULT PROTECTION
![Page 32: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/32.jpg)
TRANSIENT METHOD
09-Nov-17 32
The symmetrical component network at the transient:
![Page 33: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/33.jpg)
TRANSIENT METHOD
09-Nov-17 33
The zero sequence voltage and currents at the faulty moment:
Healthy feeder: Faulty feeder:
![Page 34: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/34.jpg)
TRANSIENT EARTH FAULT
PROTECTION
09-Nov-17 34
The setting parameters are:
Minimal residual voltage (U0,min) and current (I0,min)
Number of the counted peaks
Reset time after the last detected peak (Treset)
![Page 35: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/35.jpg)
09-Nov-17 35
Advantages
It does not require any added primary or secondary element
The earth fault current is not increased
Very simple solution
The list of parameters is short
Disadvantages
It cannot detect the stable earth faults with high fault resistance
It requires U0 voltage (and of course I0 current)
TRANSIENT EARTH FAULT
PROTECTION
![Page 36: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/36.jpg)
09-Nov-17 36
NEW METHOD:
ADMITTANCE EARTH
FAULT PROTECTION
![Page 37: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/37.jpg)
ADMITTANCE CHANGE METHOD
09-Nov-17 37
The symmetrical component network:
![Page 38: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/38.jpg)
09-Nov-17 38
The zero sequence voltage and currents
Healthy feeder:
Faulty feeder:
ADMITTANCE CHANGE METHOD
![Page 39: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/39.jpg)
09-Nov-17 39
The measured zero sequence admittances (3I0/3U0):
∆Y switched OFF ∆Y switched ON Difference
Healthy feeder YC YC 0
Faulty feeder -(YC+YP) -(YC+YP+∆Y) ∆Y
ADMITTANCE CHANGE METHOD
![Page 40: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/40.jpg)
09-Nov-17 40
The application:
ADMITTANCE CHANGE METHOD
![Page 41: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/41.jpg)
09-Nov-17 41
The setting parameters are:
Minimal residual voltage (U0,min) and current (I0,min)
Voltage and current transformer ratios
Admittance value of the added coil
Line parameters (for calculating the fault location only)
ADMITTANCE EARTH FAULT
PROTECTION
![Page 42: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/42.jpg)
09-Nov-17 42
Advantages
It can detect stable faults with high fault resistance
The earth fault current is not increased
It can calculate the exact fault resistance
It can separate the earth faults (all the three types)
It can be used for adaptive compensation (mentioned earlier)
Disadvantages
It cannot detect the intermittent fault: it requires a different method. This different method is built
to the admittance protection
It requires U0 voltage (and of course I0 current)
ADMITTANCE EARTH FAULT
PROTECTION
![Page 43: EARTH FAULT DETECTING METHODS ON COMPENSATED …electro-sistem.com/wp-content/uploads/2017/11/Electro... · 2017-11-09 · RESIDUAL DEFINITE TIME OVERCURRENT PROTECTION 09-Nov-17](https://reader034.vdocuments.mx/reader034/viewer/2022042803/5f4342126dcb096f236956fc/html5/thumbnails/43.jpg)
THANK YOU FOR YOUR ATTENTION!