e61d - fire alarm plan first floor sec-d - medic air systems wellington crossing... · any...

1
105 3 vC .A MC A2 MC-Al MC-A2 MC-A DFC-R143 DFC-R142 DFC-R141 DFC-R140 DFC-R139 DFC-R138 MDA2 MC Al DFC-R137 DFC-R136 \ A57 WP DFC-R145 M CO COJNTRY CFCHEN DFC - E1M-Ö MC AS -9F€)- R 1 46 E DFC- R146W p d-R147 M VC-A4 R148 DFC R148- DFC-R149 MC-A5 R144 M o 01 50 L V N OOM DFC-R156 DFC-R157 DFC-'R1 159 DIRECTOR A5 AHU-1.02 FSD-AUB E1M-17 LAJNDR A63 15cd 15cd 15 O L A 65 ¯J SC LTI._.I JTIL TY A167 L . . _I CARE ER LIV N COM DFC-R}S.A4 RIB M MC A4 L-- R52 C R152 DFC-R153 MC-AB R53 4C-R154 M -- vC-A4 DFC 155 ACTIVI GORRIDOR DFC- vC A R60 FC 161 C-A2 Rlbl E1M-17 DFC 1 C 163 DFC FC\-A -1.01A ' MC-A ST GD MC-AIA R163 BAR c A24 TOI._.ET RESIDEN- LOUNGE . A123 COvML,NITY COM . Am D BI-FOLDING PARTITION NALL DI ( LIVING R FSD-0A1 E1M-17 0 AHt|-1 03R Gm FSD-A138 E1M-17--- R R LNING ROOP All2 FSD-A138 E1M-17 SMOKE COMPARTMENT SEPARATION ---- GENERAL NOTES ARCMTECTURAL CONCEPTS A. ALL FIRE ALARM DEVICE LOCATIONS AND DETAILS ARE FOR REFERENCE ONLY. LOCAL GOVERNING CODES AND REQUIREMENTS SHALL TAKE PREFERENCE OVER ALL DETAILS FOR LOCATIONS AND MOUNTING HEIGHTS. VERIFY LOCAL GOVERNING CODES AND REQUIREMENTS WITH LOCAL INSPECTION DEPARTMENT PRIOR TO BID. COMPLETE FIRE ALARM SYSTEM, INSTALLATION AND OPERATION SHALL MEET THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION. B. THE CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND RELATED ITEMS WITH THE ARCHITECTURAL REFECTED CEILING PLANS C. ALL CONDUlT, CABLES, AND DEVICES LOCATED IN FIRE RATED WALLS SHALL BE INSTALLED IN ACCORDANCE WITH N.E.C. SECTION 300.2 I . REFER TO ARCHITECTURALDRAWINGS FOR FINAL RATED WALL LOCATIONS. D. ETCTRICAL CONTRACTOR SHALL NOT LOCATE SMOKE DETECTORS CLOSER THAN 3 FEET FROM ANY MECHANICAL AIR SUPPLY OR RETURN DIFFUSER, GRILLE, OR REGISTER PER NFPA. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OTHER TRADES FOR LOCATION OF DETECTOR. E. THE ELECTRICAL ADDRESS OF THE FIRE ALARM DEVICE SHALL BE SHOWN ON THE BASE OF EACH AND EVERY DEVICE FOR EASE OF IDENTIFICATION. F. ALL SIGNAL AND INITIATING DEVlCE CIRCUITS SHALL BE CLASS "B". G. AUDIO DEVICES SHALL MEET OR F_XCEED THE REQUIRED DECIBEL LEVELS IN NFPA 72. H. WHERE CEILING-MOUNTED SMOKE DETECTORS ARE TO BE INSTALTD FOR DOOR HOLDER CONTROL ON A SMOOTH CEILING FOR A SINGLE OR DOUBE DOORWAY, THEY SHALL BE LOCATED AS FOLLOWS: A) ON THE CENTERLINE OF THE DOORWAY, AND B) NO MORE THAT 5 FT. MEASURED ALONG THE CEILING PERPENDICULAR TO THE DOORWAY. l. DO NOT INSTALL SMOKE DETECTOR HEADS UNTIL ALL MAJOR CONSTRUCTION AND CLEANING IS COMPLETE. CLEANING OF DETECTOR HEADS CONTAMINATED BY CONSTRUCTION DUST IS MANDATORY. J. CONTRACTOR SHALL TEST THE SENSITIVITY OF ALL CEILING AND DUCT SMOKE DETECTORS INSTALTD IN THE FACILITYAND PREPARE A TEST REPORT FOR INCLUSION IN CLOSE OUT DOCUMENTS. CONTRACTOR SHALL PROVIDE A "RECORD OF COMPETlON" FOR THE FIRE ALARM SYSTEM AT FINAL SURVEY. K. PROVIDE DEDICATED I 2OVAC CIRCUlTS TO FIRE ALARM PANEL AND NAC PANELS. LABEL DEDICATED CIRCUIT "FIRE ALARM SYSTEM" AND PLACE LOCK OUT IN CIRCUIT AT ELECTRICAL PANEL. L. AUDIBLF/VISUALS AND VISUAL ONLY DEVICES SHALL BE PLACED 80", TO THE BOTTOM OF THE DEVICE, ABOVETHE HIGHEST FLOOR LEVEL WITHIN THE SPACE OR 6" BELOW THE CEILING, WHICHEVER l$ LOWER. TO BE IN ACCORDANCE WITH NFPA 72, AUDIBLE/VISUAL AND VISUAL ONLY DEVICES SHALL BE MOUNTED WITH THE ENTIRE LENS BETWEEN 80" AND 96" ABOVETHE FINISHED FLOOR (NFPA 72-7.5.4). REFER TO EQUIPMENT DATA SHEET FOR EXACT BACKBOX MOUNTING HEIGHTS. M. DUCT DETECTORS SHALL BE READILY ACCESSIBLE FOR SERVICING AND TESTING, PER NFPA 72 5-1 I .6.3. DETECTORS SHALL BE MOUNTED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATION. N. ANNUNCIATORS SHALL PROVIDE DEVICE TYPE, LOCATION, AND SMOKE COMPARTMENT FOR ALARM DEVICES. A SMOKE COMPARTMENT FLOOR PLAN SHALL DE LOCATED AT EACH ANNUNCIATOR. O. THE APPLICABC FIRE ALARM CODE FOR THl3 PROJECT IS THE FLORIDA FIRE PROTECTION CODE 20 I O VERSION. P. FIRE ALARM SYSTEM SHALL BE A FULLY ADDRESSABLE CLASS B, STYLE 4 SYSTEM. o KEYED NOTES SOME NOTES MAY NOT APPLY TO THIS SHEET HEAT DETECTORS LOCATED IN THE HOISTWAY SHALL HAVE AUXILLIARY CONTACTS TIED INTO THE SHUNT TRIP BREAKERS AND ARE REQUIRED TO AUTOMATICALLY DISCONNECT THE MAIN POWER TO THE ELEVATOR CONTROLS PRIOR TO APPLICATION OF WATER BY THE SPRINKER SYSTEM. THl3 METHOD OF POWER DISCONNECT SHALL NOT BE SELF-RESETTING. HEAT DETECTORS MUST BE INSTALTD WITHIN 24" OF SPRINKERS. 2 SMOKE DETECTOR SHALL HAVE AUXILLIARY CONTACTS IN ORDER TO WIRE INTO THE ELEVATOR CONTROLLER FOR ELEVATOR RECALL FUNCTION. 3 CONTRACTOR SHALL PROVIDE A RELAY IN THE ANSUL SYSTEM WIRED TO THE FIRE ALARM CONTROL FOR COMMUNICATION AND CONTROL. 4 PROVIDE RELAY WIRED INTO DOOR LOCKING MECHANISM FOR RELEASE DURING BUILDING ALARM. 5 SEE MECHANICAL CONNECTION SCHEDULE ON SHEET E-0.3 FOR ELECTRICAL REQUIREMENTS OF ALL MECHANICAL EQUIPMENT. 6. FAN COlL UNIT IS FED FROM CORRESPONDING CONDENSING UNIT ON ROOF TOP. REFER TO ROOF PLAN, PANEL, AND MECHANICAL SCHEDULES FOR FURTHER REQUIREMENTS. PROVIDE 2-POW I 5 AMP SWITCH AT AlR HANDER. 7. RESIDENT UNIT CONDENSlNG UNIT SHOULD BE FED FROM CORRESPONDING UNIT'S PANEL. ONE TON UNITS SHALL HAVE I5 AMP PROTECTION AND 1.5 TON UNITS SHALL HAVE 20 AMP. OUTSIDE UNIT FEEDS INSIDE AIR MOVING UNIT WITH I 5 AMP WIRlNG AND PROTECTION. COORDINATE WITH UNIT PLANS, MECHANICAL PLANS, AND INSTALLATION INSTRUCTIONS PRIOR TO COMMENCING WORK. V SILVERSTONE 3710 Rawlins St, Suite 800 Dallas, Texas 75219 PROPOSED: Harbor Chase Assisted Living of Wellington Crossing 136 Units 152 Beds Wellington, Florida FIRE ALARM EQUIPMENT SYMBOL DESCRIPTION MOUNTING FACP UL LISTED ADDRESSABLETYPE FIRE ALARM CONTROL PANEL AND ANUNCIATOR FFTOTOP FAA UL LISTED FIRE ALARM ANNUNCIATOR PANEL. R N DOP KNOX BOX. COORDINATE FINAL LOCATION WITH ARCHITECTURALPLANS AND FAFFOR KNOX FIRE MARSHAL. PROVIDE A 3200 SERIES WITH HINGED DOOR AVAILABLEAT AS NOTED KNOXBOX.COM. FIRE ALARM CHIME/STROBESIGNAL DEVICE. 75 CANDELA UNLESS 80"AFFTO OTHERWISE NOTED. MOF 80" AFF TO FIRE ALARM STROBE SIGNAL DEVICE. 75 CANDELA UNLESS OTHERWISE NOTED. TTOMOF 80" AFF TO M FIRE ALARM UNIT CHIME DEVICE MOF MANUAL PULL STATION AS NO SMOKE DETECTOR. SHALL BE INSTALLED WITHIN 5 FEET OF SMOKf Gl.INGOR COMPARTMENT DOOR. AS NOTED UNIT TYPE SMOKE DETECTOR WITH SOUNDER TYPE BASE ALARMING LOCALLY IN UNIT AND SENDING TROUBE CODE TO MAIN FIRE ALARM CONTROL PANEL. TIE NHNG INTO LOCAL CIRCUIT FOR POWER. UNIT COMBINATION TYPE SMOKf / CARBON MONOXIDE DETECTOR WITH WALL MOUNTED SOUNDER TYPE BASE ALARMING LOCALLY IN UNIT AND SENDING TROUBE CODE 6" BELOWCLNG C0 TO MAIN FIRE ALARM CONTROL PANEL. TIE INTO LOCAL CIRCUlT FOR POWER. BEAM TYPE SMOKE DETECTOR DUCT MOUNTED SMOKE DETECTOR(S) SHALL BE MOUNTED IN RETURN OF THE HVAC SYSTEM (ONE EACH). LOCATION AND EXACT QUANTITY SHALL BE DETERMINED BY THE MECHANICAL ENGINEER AND IN THE FIELD BY THE MECHANICAL CONTRACTOR. THE ELECTRICAL CONTRACTOR SHALL FURNISH, IN HVAC INSTALL, AND WIRE TO THE FIRE ALARM SYSTEM. PROVIDE A REMOTE NcTwm TEST-RESET SWITCH WITH PILOT LIGHT ON ACCESSIBLE ARfA ON CEILING WITHIN THE BUILDING AND LABEL ACCORDINGLY. UPON ACTIVATION THE UNIT SHALL SHUT DOWN AND REPORT TROUBLE SIGNAL TO THE FACP. HEAT DETECTOR NGOTil CARBON MONIXIDE DETECTOR SHALL REPORT A TROUBLE SIGNAL. NGOTIDR FLOW AND TAMPER SWITCHES. CONTRACTOR SHALL VERIFY EXACT QUANITIES AS NOTED AND LOCATIONS WITH FIRE ALARM SPRINKLER PLANS. FS FIRE DUCTWORKSMOKE DAMPER. DEVICES SHALL BE INTERLOCK£D WITH THE ASSOCIATED MECHANICAL EQUIPMENT AS INDICATED IN ORDER TO CLOSE UPON IN HVAC so UNIT SHUT DOWN. I 20 VOLT POWER FROM LIFE SAFETY PANEL AS INDICATED. NCTwm MAGNETIC DOOR HOLDER SHALL BE INTERFACED WITH THE FIRE ALARM CONTROL PANEL IN ORDER TO RELEASE DOORS HOLDING ELECTROMAGNETS IN TIMES OF 0FOR BUILDING ALARM. RELAYS SHALL BE INSTALLED IN THE CONTROL CIRCUIT OF THE ASSOCIATED HVAC EQUIPMENT AND SHALL BE CONNECTED TO THE FIRE ALARM SWTEM SO THAT WHEN THE ALARM SYSTEM GOES IN ALARM, THE HVAC UNITS THROUGHOUT AS NOTED THE BUILDING WILL SHUT DOWN. SEE PLANS FOR ADDITIONAL INFORMATION. C B DO NOT SCALE PRINTS THE DOCUMENTSAND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF ARCHITECTURAL CONCEPTS INC. UNAUTHORIZED REPRODUCTION AND/OR REUSE MAY BE PROSECUTED IN ACCORDANCE WITH THE APPROPRIATE COPYRIGHTAND PATENT LAWS. P CONCEPT: SCHEMATIC DESIGN: PRELIMINARY DESIGN: DESIGN DEVELOPMENT: 04-2 1 - ! 6 PERMIT SET: 06- | 4- ! 6 BID SET: FOR CONSTRUCTION: REVISIONS: 2 3 4 5 6 PLOT DATE: FILE LOCATION: SHEET DESCRIPTION: FIRST FLOOR FIRE ALARM PLAN SEC-D PROJECT NO. SCALE: 1691 DRAWING NO. KEY PLAN NORTH 7/12/2016 10:10:36 AM E:\2150\215156 - Wellington Crossing\Drawings\E61D - FIRE ALARM PLAN FIRST FLOOR SEC-D.dgn

Upload: duongthuan

Post on 19-Aug-2019

213 views

Category:

Documents


0 download

TRANSCRIPT

105

3 vC .AMC A2

MC-Al MC-A2 MC-A

DFC-R143 DFC-R142 DFC-R141 DFC-R140 DFC-R139 DFC-R138

MDA2 MC Al

DFC-R137 DFC-R136

\ A57

WP

DFC-R145

M CO

COJNTRY CFCHEN

DFC -

E1M-Ö

MC AS

-9F€)- R 1 4 6 E

DFC-R146W

p d-R147

M

VC-A4

R148

DFC R148-

DFC-R149MC-A5

R144

M o

01 50

L V N OOM

DFC-R156 DFC-R157 DFC-'R1 159

DIRECTOR

A5

AHU-1.02 FSD-AUB

E1M-17

LAJNDR

A63

15cd

15cd 15 O L

A 65 ¯J

SC

LTI._.I

JTIL TY

A167

L. .

_I

CARE ER

LIV N COM

DFC-R}S.A4RIB

M

MC A4 L--

R52

C R152

DFC-R153MC-AB

R53

4C-R154

M--

vC-A4

DFC 155

ACTIVI

GORRIDOR

DFC-

vC A

R60

FC 161

C-A2

Rlbl

E1M-17

DFC 1 C 163 DFCFC\-A

-1.01A '

MC-A ST GD

MC-AIA

R163

BAR

c A24

TOI._.ET

RESIDEN-

LOUNGE

.

A123

COvML,NITY

COM

.

Am D

BI-FOLDING

PARTITION NALL

DI

-® (

LIVING R

FSD-0A1

E1M-17

0

AHt|-1 03R

GmFSD-A138 E1M-17---

R RLNING ROOP

All2

FSD-A138 E1M-17

SMOKE COMPARTMENTSEPARATION

- - - -

GENERAL NOTES ARCMTECTURALCONCEPTS

A. ALL FIRE ALARM DEVICE LOCATIONS AND DETAILS ARE FOR REFERENCE ONLY. LOCAL GOVERNINGCODES AND REQUIREMENTS SHALL TAKE PREFERENCE OVER ALL DETAILS FOR LOCATIONS ANDMOUNTING HEIGHTS. VERIFY LOCAL GOVERNING CODES AND REQUIREMENTS WITH LOCALINSPECTION DEPARTMENT PRIOR TO BID. COMPLETE FIRE ALARM SYSTEM, INSTALLATION ANDOPERATION SHALL MEET THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION.

B. THE CONTRACTORSHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES ANDRELATED ITEMS WITH THE ARCHITECTURALREFECTED CEILING PLANS

C. ALL CONDUlT, CABLES, AND DEVICES LOCATED IN FIRE RATED WALLS SHALL BE INSTALLED INACCORDANCE WITH N.E.C. SECTION 300.2 I

.

REFER TO ARCHITECTURALDRAWINGS FOR FINALRATED WALL LOCATIONS.

D. ETCTRICAL CONTRACTOR SHALL NOT LOCATE SMOKE DETECTORS CLOSER THAN 3 FEET FROMANY MECHANICAL AIR SUPPLY OR RETURN DIFFUSER, GRILLE, OR REGISTER PER NFPA. ELECTRICALCONTRACTOR SHALL COORDINATE WITH OTHER TRADESFOR LOCATION OF DETECTOR.

E. THE ELECTRICAL ADDRESS OF THE FIRE ALARM DEVICE SHALL BE SHOWN ON THE BASE OF EACHAND EVERY DEVICE FOR EASE OF IDENTIFICATION.

F. ALL SIGNAL AND INITIATING DEVlCE CIRCUITS SHALL BE CLASS "B".

G. AUDIO DEVICES SHALL MEET OR F_XCEED THE REQUIRED DECIBEL LEVELS IN NFPA 72.

H. WHERE CEILING-MOUNTED SMOKE DETECTORS ARE TO BE INSTALTD FOR DOOR HOLDERCONTROL ON A SMOOTH CEILING FOR A SINGLE OR DOUBE DOORWAY, THEY SHALL BE LOCATEDAS FOLLOWS:

A) ON THE CENTERLINE OF THE DOORWAY, ANDB) NO MORE THAT 5 FT. MEASURED ALONG THE CEILING PERPENDICULARTO THEDOORWAY.

l. DO NOT INSTALL SMOKE DETECTOR HEADS UNTIL ALL MAJOR CONSTRUCTION AND CLEANING ISCOMPLETE. CLEANING OF DETECTOR HEADS CONTAMINATED BY CONSTRUCTION DUST ISMANDATORY.

J. CONTRACTORSHALL TEST THE SENSITIVITY OF ALL CEILING AND DUCT SMOKE DETECTORSINSTALTD IN THE FACILITYAND PREPARE A TEST REPORT FOR INCLUSION IN CLOSE OUTDOCUMENTS. CONTRACTORSHALL PROVIDE A "RECORD OF COMPETlON" FOR THE FIRE ALARMSYSTEM AT FINAL SURVEY.

K. PROVIDE DEDICATED I 2OVAC CIRCUlTS TO FIRE ALARM PANEL AND NAC PANELS. LABELDEDICATED CIRCUIT "FIRE ALARM SYSTEM" AND PLACE LOCK OUT IN CIRCUIT AT ELECTRICAL PANEL.

L. AUDIBLF/VISUALS AND VISUAL ONLY DEVICES SHALL BE PLACED 80", TO THE BOTTOM OF THE

DEVICE, ABOVETHE HIGHEST FLOOR LEVEL WITHIN THE SPACE OR 6" BELOW THE CEILING,WHICHEVER l$ LOWER. TO BE IN ACCORDANCE WITH NFPA 72, AUDIBLE/VISUAL AND VISUAL ONLYDEVICES SHALL BE MOUNTED WITH THE ENTIRE LENS BETWEEN 80" AND 96" ABOVETHE FINISHEDFLOOR (NFPA 72-7.5.4). REFER TO EQUIPMENT DATA SHEET FOR EXACT BACKBOX MOUNTINGHEIGHTS.

M. DUCT DETECTORS SHALL BE READILY ACCESSIBLE FOR SERVICING AND TESTING, PER NFPA 725-1 I .6.3. DETECTORS SHALL BE MOUNTED IN ACCORDANCE WITH THE MANUFACTURER'SRECOMMENDATION.

N. ANNUNCIATORS SHALL PROVIDE DEVICE TYPE, LOCATION, AND SMOKE COMPARTMENT FOR ALARMDEVICES. A SMOKE COMPARTMENT FLOOR PLAN SHALL DE LOCATED AT EACH ANNUNCIATOR.

O. THE APPLICABC FIRE ALARM CODE FOR THl3 PROJECT IS THE FLORIDA FIRE PROTECTION CODE20 I O VERSION.

P. FIRE ALARM SYSTEM SHALL BE A FULLY ADDRESSABLECLASS B, STYLE 4 SYSTEM.

o KEYED NOTESSOME NOTES MAY NOT APPLY TO THIS SHEET

HEAT DETECTORS LOCATED IN THE HOISTWAY SHALL HAVE AUXILLIARYCONTACTSTIED INTO THESHUNT TRIP BREAKERS AND ARE REQUIRED TO AUTOMATICALLY DISCONNECT THE MAIN POWERTO THE ELEVATOR CONTROLS PRIOR TO APPLICATION OF WATERBY THE SPRINKER SYSTEM. THl3METHOD OF POWER DISCONNECT SHALL NOT BE SELF-RESETTING. HEAT DETECTORS MUST BEINSTALTDWITHIN 24" OF SPRINKERS.

2 SMOKE DETECTOR SHALL HAVE AUXILLIARYCONTACTS IN ORDER TO WIRE INTO THE ELEVATORCONTROLLER FOR ELEVATOR RECALL FUNCTION.

3 CONTRACTOR SHALL PROVIDE A RELAY IN THE ANSUL SYSTEM WIRED TO THE FIRE ALARMCONTROL FOR COMMUNICATION AND CONTROL.

4 PROVIDE RELAY WIRED INTO DOOR LOCKING MECHANISM FOR RELEASE DURING BUILDING ALARM.

5 SEE MECHANICAL CONNECTION SCHEDULE ON SHEET E-0.3 FOR ELECTRICAL REQUIREMENTS OFALL MECHANICAL EQUIPMENT.

6. FAN COlL UNIT IS FED FROM CORRESPONDING CONDENSING UNIT ON ROOF TOP. REFER TO ROOF

PLAN, PANEL, AND MECHANICAL SCHEDULES FOR FURTHER REQUIREMENTS. PROVIDE 2-POW I 5AMP SWITCH AT AlR HANDER.

7. RESIDENT UNIT CONDENSlNG UNIT SHOULD BE FED FROM CORRESPONDING UNIT'S PANEL. ONETON UNITS SHALL HAVE I5 AMP PROTECTION AND 1.5 TON UNITS SHALL HAVE 20 AMP. OUTSIDEUNIT FEEDS INSIDE AIR MOVING UNIT WITH I 5 AMP WIRlNG AND PROTECTION. COORDINATE WITHUNIT PLANS, MECHANICAL PLANS, AND INSTALLATION INSTRUCTIONS PRIOR TO COMMENCINGWORK.

V SILVERSTONE

3710 Rawlins St, Suite 800

Dallas, Texas 75219

PROPOSED:

Harbor Chase

Assisted Livingof WellingtonCrossing136 Units

152 Beds

Wellington, Florida

FIRE ALARM EQUIPMENTSYMBOL DESCRIPTION MOUNTING

FACP UL LISTED ADDRESSABLETYPE FIRE ALARM CONTROL PANEL AND ANUNCIATORFFTOTOP

FAA UL LISTED FIRE ALARM ANNUNCIATOR PANEL. R N DOPKNOX BOX. COORDINATE FINAL LOCATION WITH ARCHITECTURALPLANS AND

FAFFORKNOX FIRE MARSHAL. PROVIDE A 3200 SERIES WITH HINGED DOOR AVAILABLEAT AS NOTED

KNOXBOX.COM.

FIRE ALARM CHIME/STROBESIGNAL DEVICE. 75 CANDELA UNLESS 80"AFFTO

OTHERWISE NOTED.MOF

80" AFF TO

FIRE ALARM STROBE SIGNAL DEVICE. 75 CANDELA UNLESS OTHERWISE NOTED. TTOMOF

80" AFF TO

MFIRE ALARM UNIT CHIME DEVICE MOF

MANUAL PULL STATION AS NO

SMOKE DETECTOR. SHALL BE INSTALLED WITHIN 5 FEET OF SMOKf Gl.INGOR

COMPARTMENT DOOR. AS NOTED

UNIT TYPE SMOKE DETECTOR WITH SOUNDER TYPE BASE ALARMING LOCALLY INUNIT AND SENDING TROUBE CODE TO MAIN FIRE ALARM CONTROL PANEL. TIE NHNGINTO LOCAL CIRCUIT FOR POWER.

UNIT COMBINATION TYPE SMOKf / CARBON MONOXIDE DETECTOR WITH WALL MOUNTEDSOUNDER TYPE BASE ALARMING LOCALLY IN UNIT AND SENDING TROUBE CODE 6" BELOWCLNG

C0 TO MAIN FIRE ALARM CONTROL PANEL. TIE INTO LOCAL CIRCUlT FOR POWER.

BEAM TYPE SMOKE DETECTOR

DUCT MOUNTED SMOKE DETECTOR(S) SHALL BE MOUNTED IN RETURN OF THEHVAC SYSTEM (ONE EACH). LOCATION AND EXACT QUANTITY SHALL BEDETERMINED BY THE MECHANICAL ENGINEER AND IN THE FIELD BY THEMECHANICAL CONTRACTOR. THE ELECTRICAL CONTRACTORSHALL FURNISH, IN HVAC

INSTALL, AND WIRE TO THE FIRE ALARM SYSTEM. PROVIDE A REMOTE NcTwm

TEST-RESET SWITCH WITH PILOT LIGHT ON ACCESSIBLE ARfA ON CEILING WITHINTHE BUILDING AND LABEL ACCORDINGLY. UPON ACTIVATION THE UNIT SHALLSHUT DOWN AND REPORT TROUBLE SIGNAL TO THE FACP.

HEAT DETECTOR NGOTilCARBON MONIXIDE DETECTOR SHALL REPORT A TROUBLE SIGNAL. NGOTIDRFLOW AND TAMPER SWITCHES. CONTRACTORSHALL VERIFY EXACT QUANITIES AS NOTEDAND LOCATIONS WITH FIRE ALARM SPRINKLER PLANS.

FS FIRE DUCTWORKSMOKE DAMPER. DEVICES SHALL BE INTERLOCK£D WITH THEASSOCIATED MECHANICAL EQUIPMENT AS INDICATED IN ORDER TO CLOSE UPON IN HVAC

so UNIT SHUT DOWN. I 20 VOLT POWER FROM LIFE SAFETY PANEL AS INDICATED.NCTwm

MAGNETIC DOOR HOLDER SHALL BE INTERFACED WITH THE FIRE ALARM CONTROLPANEL IN ORDER TO RELEASE DOORS HOLDING ELECTROMAGNETS IN TIMES OF 0FORBUILDING ALARM.

RELAYS SHALL BE INSTALLED IN THE CONTROL CIRCUIT OF THE ASSOCIATEDHVAC EQUIPMENT AND SHALL BE CONNECTED TO THE FIRE ALARM SWTEM SOTHAT WHEN THE ALARM SYSTEM GOES IN ALARM, THE HVAC UNITS THROUGHOUT AS NOTED

THE BUILDING WILL SHUT DOWN. SEE PLANS FOR ADDITIONAL INFORMATION.

C

B

DO NOT SCALE PRINTS

THE DOCUMENTSAND THE INFORMATION CONTAINED HEREIN

ARE THE SOLE PROPERTYOF ARCHITECTURALCONCEPTS INC.

UNAUTHORIZED REPRODUCTIONAND/OR REUSE MAY BE

PROSECUTED IN ACCORDANCE WITH THE APPROPRIATE

COPYRIGHTAND PATENT LAWS.

P

CONCEPT:

SCHEMATIC DESIGN:

PRELIMINARY DESIGN:

DESIGN DEVELOPMENT: 04-2 1 - ! 6

PERMIT SET: 06- | 4- ! 6

BID SET:

FOR CONSTRUCTION:

REVISIONS:

2

3

4

5

6

PLOT DATE:

FILE LOCATION:

SHEET DESCRIPTION:

FIRST FLOOR FIRE

ALARM PLAN SEC-D

PROJECT NO. SCALE:

1691

DRAWING NO.

KEY PLANNORTH

7/12/2016 10:10:36 AM E:\2150\215156 - Wellington Crossing\Drawings\E61D - FIRE ALARM PLAN FIRST FLOOR SEC-D.dgn