e-Tracker Portable Energy Monitor Operating & maintenance manual e-TRacKER Portable Energy Monitor

Upload: others

Post on 06-Aug-2020

23 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

e-Tracker Portable Energy Monitor

Operating & maintenance manual

e-TRacKER Portable Energy Monitor

Page 2: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

Marshall-Tufflex Energy Management manufacture a range of products to helporganisations save energy, reduce costs and lower carbon emissions.

The Sinergy range of fixed and portable metering units identify exactly where and howyour energy is being used which then helps pinpoint potential waste and ultimatelycost saving.

Sinergy is a well established in the sub metering market and was brought into theMarshall-Tufflex Energy Management group in 2010.

Marshall-Tufflex Ltd is a market leader in the electrical industry and has been tradingfor over 70 years and includes a wide portfolio of Cable Management and EnergyManagement product solutions.

The group is a BS EN ISO 9001:2008 assessed company and also holds BS EN ISO14001:2004 environmental standard and also we received an excellent rating on ourenergy management from The Carbon Trust in 2007.

Introduction to Marshall-Tufflex Energy Management

PageWhat is e-Tracker? 3Kit contents 3What does e-Tracker measure? 3Installation and set up 4e-Tracker set up prompts and controls 6-7Error messages 8-9 e-Tracker operational specification 10Memory span 10CT selection 11Deltrax5 software guidelines 11-17Trouble shooting 17-18

Ensure that safe working conditions are in place in all potentially hazardousenvironments. The e-tracker unit must be installed by a competent person using the e-tracker installation instructions or Operating & Maintenance Manual.

Contents

Safety information

Welcome to your Sinergy Meters e-TRacKER

Sinergy Meters manufacture a range of products aimed at energy monitoring to suit a wide range of use cases in both portable and fi xed solutions.

Sinergy metering units identify exactly where and how your energy is being used which then helps pinpoint waste and ultimately aids in cost saving endeavours.

Sinergy Meters is a well established company with over 20 years experience in the energy monitoring and sub-metering industry. Sinergy Meters manufacture powerful but easy-to-use products to suit a wide range of requirements in both portable and fixed solutions.

Sinergy joined AU Engineering Ltd in 2015, returning to its roots with a focus on quality products and first class customer service and support.

Sinergy Meters gives you the tools and knowledge you need to reduce energy usage, saving costs and reducing your carbon footprint.

e-TRacKER

e-TRacKER measure?

e-TRacKER set up prompts and controls

e-TRacKER operational specificatione-TRacKER CT selection 10Deltrax5 software guidelines 10-16Troubleshooting 17e-TRacKER operational specification 18

Page 3: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

e-Tracker portable energy monitor operating and maintenance manual 3

Features:Mains or 16 day battery operation*Magnetic back for easy mountingMultiple memory locationsPulse inputOptional voltage connectionsCT amps range indicator

Clip-on CTs for fast safe instalationEV-Trac electrostatic phase identifier

Optical or magnetic gas meter reader available

Deltrax5 software is Windows 7 compatible

The e-Tracker also displays average and peak demand to enable the calculation of loadfactor. Deltrax5 software highlights demand excursions and potential unauthorisedconsumption.

*In battery only operation the e-Tracker will only give accurate current measurements, all other readings will be assumed.

e-Tracker is a portable kWh meter which monitors the incoming powersupply to show the pattern of demand over an hour, day, week or month.As e-Tracker is portable you have the flexibility to use it for measuringsub-circuits and other specific equipment without the need to have afixed sub-metering solution.

What is e-Tracker?

Sold as a full kit comprising:e-Tracker with integral EV-Trac 1Ø -3Ø voltage reference converter

Set of 3 F30-1000 dual range Flexeclamp CTs 30cm - 1000Amps /200Amps

How is data collected?e-Tracker records and stores all data, which is then downloadable via USB memory stickinto our Deltrax5 software. This data is graphically displayed on a monthly, weekly ordaily basis or alternatively processed in Excel format.

Kit contents

Voltage Current kW

kVAPower factor kVAR

kWh KVArHAverage and peak demand

What does e-Tracker measure?

Set of 3 fused volt clips

Single phase lead, EV-Trac phase identity probe

Deltrax5 data analysis software

1 USB memory stick

Carry case

, 8, 8.1and 10 compatible

e-TRacKER?e-TRacKER

e-TRacKER

e-TRacKER

e-TRacKER

e-TRacKER

Set of 3 dual range Flexeclamp CTs, 300mm - 1000/200Amps

e-TRacKER measure?

e-TRacKER

e-TRacKER

Page 4: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

e-Tracker portable energy monitor operating and maintenance manual4

Isolate any accessible un-insulated conductors during installation. ClipCTs to all appropriate cables/conductors with all arrows facing the load.All transducers including voltage reference inputs (if used) should befitted and connected to e-Tracker before e-Tracker is switched on.

Installation and set up

Practical and accurate connection options for single and 3 phase use:

Follow standardsafety procedure

Diagram 1

Diagram 2 Finger held probeincluded to identifyphase on low load

Battery onpermanentcharge via

socket

For single phase use CT1 and 13A plug

Use e-Tracker with its fused voltage clipsfor maximum accuracy on all parameters

3Ø direct voltage measurement

The set of colour coded fused voltage crocodileclips must be securely attached to pick up thephase voltages with the colours matching theattached CTs.

Red/Brown = Line 1

Yellow/Black = Line 2

Blue/Grey = Line 3

No neutral connection is required although e-Trackercan be earthed Green/Yellow lead. Direct voltageconnection ensures high accuracy recording.

EV-Trac 3 phase volt reference conversion from a single phase socket outlet

3Ø EV-Trac voltage pickup

e-Tracker’s internal 1Ø- 3Ø converter is automaticallyapplied when three CTs are connected to cables withvoltage reference taken from a 1Ø source all suppliedfrom the same distribution transformer.

(The CTs require sufficient primary current to be able todetect zero crossover see diagram 7 on page 9)

Should automatic identification fail the EV-Tracelectrostatic probe may be used. Please note this canonly be effective on un-armoured phase cables.

e-Tracker calculates the three equivalent Line-Linevoltage vectors and assigns them to the correctphases.

EV-Trac offers a safe alternative when direct voltageconnection is not practical, kW/kWh accuracy is goodparticularly when phase voltage amplitudes are similar.

e-TRacKER e-TRacKER

e-TRacKER

e-TRacKER

e-TRacKER’s internal 1O-3O converter is automtically

e-TRacKER calculates the three equivalent Line-Line

e-TRacKER portable energy monitor operating and maintenance manual

Always follow standard safety procedures when setting up e-TRacKER

Battery on permanent charge via

socket

Ø Ø

Page 5: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

e-Tracker portable energy monitor operating and maintenance manual 5

Diagram 3 Basic recordings of demandprofiles and phase balance

2+ weeks battery life

Diagram 4

Diagram 5

Battery only operation measuring currentand calculated kVA demand profiles

3Ø current recording

This simple method is often very adequate fordetermining day/night consumptions patterns,demand peaks, phase balance and calculatingkVAh totals. In this mode e-Tracker operatestotally from its battery only and has an adjustablenominal voltage (default setting 415V).

e-Tracker will produce line current profiles andderive kVA profiles.

Single phase recording

Single phase with the voltage reference derivedfrom a wall socket etc. Alternatively Tracker willrecord current for up to 2 weeks on battery only.In battery mode Tracker has an adjustablenominal voltage (default setting 240v.)

Pulse count input (minimum integration period 1 min)

When using the optional pulse input interface,Tracker can accept a volt free contact closurefrom any suitable gas, water or electric metre.Alternatively the Magpeye optical metre readermay be connected. Normal analogue inputs areusable at the same time as pulse input.

e-TRacKER operates

e-TRacKER will produce line current profiles and

e-TRacKER portable energy monitor operating and maintenance manual

e-TRacKER will

e-TRacKER has an adjustable

e-TRacKER can accept a volt free contact closure

metermeter.

Page 6: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

e-Tracker portable energy monitor operating and maintenance manual6

e-Tracker set up prompts and controls

1) Time and date adjustment

If date and time correct press ENTER Alter flashing character(s) using CHANGE and

Press CHANGE to alter any number if required press ENTER to continue and proceed to 2)

2) Memory refresh and/or continue set upIf all data has been downloaded or is redundant press CLEAR &CHANGE to alter ‘NO’ to ‘YES’.

Press ENTER to confirm memory refresh and continue to 3)

3) Voltage range auto set For diagrams 3 & 4 on page 5 (battery only use) press CHANGE toalter default value. Choose a nominal value (default +/-10%). PressENTER to continue to 4).

NB: Recorded kVA(h) accuracy dependent on variance of servicevoltage, PF defaulted to unity.

4) CT HI/LO range selectionPress ENTER to accept the high range (normally 1000Amp) or pressCHANGE to select LO (200Amps i.e. 20% of HI range)

Press ENTER to continue to 5).

5) Integration period adjustPress ENTER to accept displayed value or press CHANGE toselect periods of 60, 30, 20, 15, 10, 5, 2, 1 minutes, 6 seconds (0.1), 1second (HI) integration*

Press ENTER to select and continue to 6)

Memory span (duration related to aggregate total of 5 memory files)

*V1, V2, V3, I1, I2, I3 only recordedfor 1 second integration

Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON.The display will show SELF TEST followed by:

Change or enter mth-day hrs-mins

2007 07.14 10.40

The CHANGE or ENTER procedureis to be used through out the

set up routine

PRESS CLEAR TO CLEAR FILES

OR ENTER TO RUN

CHANGE OR ENTER30 (10) VOLTS NOminal

415 (240) 415 415

SET CT HI - LO1000 (200) 1000 (200) 1000 (200)

Amps 1 Amps 2 Amps 3

DATE ADJUST mth-day hrs-mins

2007 07.14 10.40

Change or enter mth-day hrs-mins

Int per integration period 30

Integration Period Mins. 60

666

30

333

20

222

15

166

10

111

5

55

2

22

1

11

0.1 (6s)

25 hrs

HI (1sec)

9hours*Memory Duration Days

e-TRacKER set up prompts and controlse-TRacKER has been installed slide BATTERY SUPPLY switch ON.

e-TRacKER portable energy monitor operating and maintenance manual

clear

clear and continue to 3)

Page 7: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

e-Tracker portable energy monitor operating and maintenance manual 7

6) Start recordingIf memory is full or all of the 5 files are used, CLEAR is displayed,change NO to YES and press ENTER. Otherwise a FILE ENDmessage will indicate the duration of memory available. If duration isinsufficient for the next test press CHANGE, press CLEAR to revert to2) then refresh memory.

If memory duration is OK press ENTER.

7) Stop recordingPress STOP TEST at the end of a recording exercise and press ENTER to confirm. All data will beretained until a Clear Memory function is performed. e-Tracker will stop automatically when memory isfull, it will not roll on. Recording will stop if the battery supply is switched off. It is alwaysrecommended to use STOP TEST button.

8) Switching offBefore switching the e-Tracker off, ensure that you stop recording, please refer to 7).

Slide battery supply switch to OFF at all times when the unit is not to be used. All recorded dataremains in memory until cleared, please see 2).

NB: Always wait 5 seconds after switching off before switching back on.

9) Downloading e-Tracker to USB memory stickWith USB memory stick fitted and e-Tracker switched on, hold down START button until green LED isilluminated. It will then flash to indicate data processing. 'Serial out' will also appear on display whiledata is buffered prior to loading on USB memory stick.

Only remove USB memory stick when green LED is permanently off.

NB: Loading may take many minutes if recording period is extensive or on short integration.

ERROR INDICATION – Red LED sequences:

1) Slow flash for 10 seconds – an error has been detected

2) Permanently on for 10 seconds – non compatible or no USB memory stick fitted

3) Fast flash – insufficient space remaining on USB memory stick

4) Intermittent flash 3xon – off – 3xon – no recorded data in e-Tracker files.

When therecording/test isstarted the e-Trackerdisplays Pgs 1 – 3 (4).

Page change

Advances the displayto Pg2, 3 (& 4). AUTOscrolls pages untilPage is pressed.

Notes Pg2# Vectorially calculated value ofneutral current A-n*Displayed value of calculatedTHD to 5th harmonic (notrecorded in memory) Pg 2 only

Notes Pg3Peak demand and the time anddate occurred

START YES mth-day

FILE 6. 07 END

Volts(AV) Kw PFAmPs l1 AmPs l2 AmPs l3

KVA KVAr Hz

AmPs A-n# *tHo%

KwH

AVerAge Kw /PeAK DemAnD DAte time

PUlse CoUntACCUmAlAtiVe

(pulse interface connected)

Pg1 Pg2

Pg3 Pg4

1) Permanently on for 10 seconds - error detected2) Fast flash - insufficient space remaining on USB memory stick3) Intermittent flash 3xon - off - no recorded data in e-Tracker files.

e-TRacKER

e-TRacKER will stop automatically when memory is

e-TRacKER off, ensure that you stop recording, please refer to 7).

e-TRacKER to USB memory sticke-TRacKER switched on, hold down START button until green LED is

e-TRacKER files.

e-TRacKER portable energy monitor operating and maintenance manual

up to 30 minutes if recording period is extensive or on short integration.

If memory is full or all of the 5 files are used, CLEAR is displayed, ensure data has been downloaded then change NO to YES and press ENTER to clear memory. Otherwise a FILE END message will indicate the date memory will be full. If duration is insufficient for the next test press CLEAR then see 2). If memory duration is OK press ENTER.

Page 8: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

5)

(2 messages flashing) CTs wrong way round or CTs not in l1 connector when used on single phase

4)

(2 messages flashing) Two CT connected to same phase

e-Tracker portable energy monitor operating and maintenance manual8

Error messages After switch on and during the set up the display will indicate an unacceptable connection.

Check CTs and voltage reference input (if used), correct any error, press ENTER andproceed with set-up.

1)

(3 messages flashing) No CTs connected

--ERROR-- TRANSDUCER --NO CT--MTH-DAY HRS-MINS

2011 07.14 10.40

--ERROR--MTH-DAY HRS-MINS

2011 07.14 10.40

TRANSDUCERMTH-DAY HRS-MINS

2011 07.14 10.40

--CT1-2-3 ODD--MTH-DAY HRS-MINS

2011 07.14 10.40

2)

(3 messages flashing) CTs have different full scale current ratings or only two are connected

--ERROR--MTH-DAY HRS-MINS

2011 07.14 10.40

TRANSDUCERMTH-DAY HRS-MINS

2011 07.14 10.40

VOLTS--CT ODD--MTH-DAY HRS-MINS

2011 07.14 10.40

3)

(3 messages flashing) If three phase volt probes connected but only one CT connected VOLTS CT ODD

--ID ERR 1--MTH-DAY HRS-MINS

2011 07.14 10.40

--NOT 3 PHASE--MTH-DAY HRS-MINS

2011 07.14 10.40

--ID ERR 2--MTH-DAY HRS-MINS

2011 07.14 10.40

--CTS ODD--MTH-DAY HRS-MINS

2011 07.14 10.40

e-TRacKER portable energy monitor operating and maintenance manual

or CTs not in l1 connector when used in single phase’

when used in EV-Trac mode

Page 9: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

7)

(2 messages flashing) Signal from CTs insufficient for automatic phase sensing, proceed to manual setup routine

6)

(2 messages flashing) Non specific connection error

e-Tracker portable energy monitor operating and maintenance manual 9

--ID ERR 3--MTH-DAY HRS-MINS

2011 07.14 10.40

--NOT FOUND--MTH-DAY HRS-MINS

2011 07.14 10.40

LO indicates which channel(s) has insufficient signal. Increase phase current if possible, switch off, switch on (after 5 seconds) and try again.

Manual set up routine

Switch off e-Tracker, plug in EV-Trac probe and switch on after 5 seconds.

The SELF TEST routine starts.

PROBE SCANMTH-NO SIGNAL2011

07.14 10.40

Followed by:

Place the Probe along the phase cables’ insulation one at a time. Display indicates L1

or L2 or L3, clip-on the appropriate CT as below.

• Red CT on phase indicated as L1 (ignore phase cable colour)

• Yellow CT on phase indicated as L2

• Blue CT on phase indicated as L3.

If 'SIG ERR' displayed move Probe to different location on cable, away from otherphase cables.

Press enter

LO INPUTMTH-LO LO LO2011

07.14 10.40

USE PROBEMTHLO LO LO2012011

07.14 10.40

e-TRacKER portable energy monitor operating and maintenance manual

e-TRacKER plug in EV-Trac probe and switch on after 5 seconds.

e-TRacKER portable energy monitor operating and maintenance manual

Page 10: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

e-Tracker portable energy monitor operating and maintenance manual 11

e-Tracker CT selection CT Style CT Part NOMINAL Size Nominal Ip Accuracy Clip-on Outlines

Number ID OD Amps range PF-0.6 Capacityto unity mm Nomtemp 25’c50/60Hz

Hinged Clip On TC16 16mm 54mm 4-200 1.0% 16x16 16TC32 32mm 72mm 5-500 1.0% 32x18 32TC48 48mm 84mm 6-1000 1.0% 42x25 48TC60 60mm 90mm 8-1500 1.0% 58x25 60

Flexeclamp Clip TF30 300mm length 10-1000 2.0% 20x85 75Round TF40 400mm length 10-1500 2.0% 60x130 120

TF50 500mm length 20-2500 2.0% 70x150 155TF60 600mm length 20-2500 2.0% 70x200 190TF70 700mm length 20-2500 3.0% 70x265 215

Precision Clip On THSSB 15mm 45mm 1-100 1.0% 15

Deltrax5 software guidelinesContents1. The File List 122. The File Menu 12

2.1 Import from USB memory stick (e-Tracker Mk 2B) 122.2 Graph 132.3 Report 142.4 Delete 142.5 Show files 142.6 Manage data 142.7 Manage reports 14

3. The Preference Menu 153.1 Graph preferences 153.2 Change excel location 15

4. The Tariff Menu 164.1 Create tariff 164.2 Edit tariff 17

5. The Window Menu 176. Windows operating systems 17

e-TRacKER CT selection

(e-TRacKER Mk 2B)

e-TRacKER portable energy monitor operating and maintenance manual

CTFL300CTFL400CTFL500CTFL600CTFL700

CTSFEP

1CTSA161CTSA321CTSA481CTSA60

10

Page 11: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

Deltrax5 software guidelines1. The file list

At the bottom of the Deltrax5 screen you will see a table called the ‘File List’. This tablecontains all the data that you have downloaded or imported.

If you do not have data on your system then the table will just contain the words ‘NoData’ in the first row of the table.

To perform any of the key Deltrax5 functions (graph, report, delete) you must haveselected a file in this table first.

Additionally, if you highlight a file and then click the right mouse button, you will get apop-up menu that will you permit you to select the graph, report and delete functions forthat data file.

You can remove the File List at any time by clicking on the red cross in the top right handcorner - to bring it back just select the File - Show Files option from the menu bar.

2. The file menu2.1 Import from USB memory stick (e-Tracker Mk 2B)

If you use the File-Import-Import from USB option from the menu then you will be able toimport e-Tracker MK 2B data.

Ensure that the USB memory stick with the data on is connected to your computer.

You will be directed to a standard file selection box where you need to locate the datathat is on your USB memory stick.

All e-Tracker MK 2B data is contained in files with a .dat extension.

e-Tracker portable energy monitor operating and maintenance manual12

(e-TRacKER Mk 2B)

e-TRacKER Mk 2B data.

e-TRacKER Mk 2B data is contained in files with a .dat extension.

11e-TRacKER portable energy monitor operating and maintenance manual

Page 12: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

e-Tracker portable energy monitor operating and maintenance manual 13

2.2 Graph

To show Deltrax5 data on a Graph you first need to select (highlight) a file in the File List box.

If you then use the File – Graph option from the menu, or click on the graphing icon (shownabove) then you will be shown the Date/Data selection options for the data that you want to graph.

Once you have chosen the date/time and type of data that you want to see your graphwill be displayed on the screen.

Once the graph is displayed you have a number of options, you can:

Zoom in and out, draw a rectangle around the data you want to zoom in. Click the mouse down at the top left of the rectangle, and release it at the bottom right. To zoom out, click at the bottom right and release at the top left.

Hover over the line with the mouse pointer to get specific readings

Right click anywhere on the graph for more options, including printing

Use the Preferences – Graph Preferences menu item to customize your graph (pleaserefer to The preferences menu on page 15).

e-TRacKER portable energy monitor operating and maintenance manuale-TRacKER portable energy monitor operating and maintenance manual12

Page 13: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

2.3 Report

To use Deltrax5 reporting facilities you first need to select (highlight) a file in the File Listbox.

If you use then use the File – Report option from the menu, or click on the Reporting icon(shown above) you will be taken to the report selection dialogue box. Depending on thedata that you are looking at you can usually select a Monthly, Weekly, Daily, or Excelreport. The first three of these reports are created on a PDF, and contain both a graphand some tabular data. The Excel report is all the data written straight to an Excelspreadsheet

If you choose a Monthly, Weekly or Daily report and your data spans more than one ofthose time periods then you will be given the choice of which Month, Week or Day thatyou want to view.

2.4 Delete

To use Deltrax5 delete facility you first need to select (highlight) a file in the File List box.

If you use then use the File – Delete option from the menu, or click icon shown abovethen the file that you have selected will be deleted.

2.5 Show files

If you hide or close the File List box then the File – Show Files option will return it backto the screen.

2.6 Manage data

Using the File – Manage Files menu option you can perform the following:

Archive your data; use the 'Move & Zip' option to write your data into a compressed .zip file that can be read by other Deltrax5 systems.Note: The Deltrax5 zip file is not a Win Zip file.

Delete your data, this facility also enables you to delete more than one file at once.

2.7 Manage reports

Once a Deltrax5 Report is created it is within the system and can be viewed again andagain using the File – Manage Reports menu option. When it is no longer needed it canbe deleted from the system, as it is not linked to the data file that it originally came from.

Additionally, reports can be moved. A Deltrax5 report consists of a set of PDF files, or anExcel file. If you want to provide this information to someone then use this facility tosend the report to the file location of your choice.

e-Tracker portable energy monitor operating and maintenance manual14 e-TRacKER portable energy monitor operating and maintenance manual 13e-TRacKER portable energy monitor operating and maintenance manual

Page 14: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

e-Tracker portable energy monitor operating and maintenance manual 15

3. The preferences menu3.1 Graph preferences

Using the Preferences – Graph Preferences option will give you the following options:

Line Colour – either choose industry standard or random colours for your graphdata

Default Shapes – setting Default Shapes ON will place shapes on your graphdata lines to make it easier to distinguish them if you print in black and white

Grid Lines – setting this option ON will apply grid lines to your graph background

Cross Hair – setting this option to ON will permit you to see horizontal andvertical lines, which appear when you click on any part of the graph, enablingyou to read the axis values easier

Line Thickness – this option allows you to control the thickness of the Graphinglines

Tariff to Apply – this option allows you to set which tariff is applied to anygraphs/reports that contain kW data. You have to have created a tariff within thesystem to be able to do this (please refer to The tariff menu on page 16)

3.2 Change excel location

Using Preferences option the Change Excel Location menu item allows you to pinpointwhere on your PC you have Excel installed.

The default location for the installation of Excel is C:\Program Files\MicrosoftOffice\Office, but some users may have this software on another drive or anotherlocation.

More recent versions of Office have seen the Excel software being installed in any of thefollowing locations:

C:\Program Files\Microsoft Office\Office10

C:\Program Files\Microsoft Office\Office11

C:\Program Files\Microsoft Office\Office12

C:\Program Files\Microsoft Office\Office13

etc.

e-TRacKER portable energy monitor operating and maintenance manuale-TRacKER portable energy monitor operating and maintenance manuale-TRacKER portable energy monitor operating and maintenance manual14

Page 15: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

4. The tariff menu4.1 Create tariff

If you use the Tariff – Create Tariff menu option you will be presented with a screensimilar to the one below.

Enter a Tariff Name and the select the Currency that you require from the drop down selection box

Click on the first of the 'day buttons' (e.g. January 1st). You can then enter the 48tariff values for that day (i.e. every half hour). There are 'copy forward' and 'clear'functions to help limit entries.

When you have saved a 'day', you will notice that the 'day button' for that daybecomes bold to indicate that you have completed that day

If you right-click on a 'day button' you will see a number of options appear toassist you with your input. They range from 'Copy Forward to Next Day' to 'Copyforward to all days in Year'

Experimenting with the different 'Copy Forward' options means that you canminimize the amount of keystrokes needed to enter a tariff for the year.

For Tariffs that span more than one year, use the 'Add Year' button

Always Save your Tariffs and the 'Days' within them

Remember – if you have more than one tariff saved, set the one that is used onGraphs and reports using the Preferences – Graph Preferences menu option

e-Tracker portable energy monitor operating and maintenance manual16 e-TRacKER portable energy monitor operating and maintenance manuale-TRacKER portable energy monitor operating and maintenance manual 15e-TRacKER portable energy monitor operating and maintenance manual

Page 16: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

e-Tracker portable energy monitor operating and maintenance manual 17

4.2 Edit tariff

If you use the Tariff – Edit Tariff menu option you will be able to edit or delete the tariffsthat you have created during Create Tariff (previous page).

5. The window menuUse the Window – Arrange and Window – Close menu items to organise the windowsthat you may have open on your screen.

6. Windows operating systemsThe Deltrax5 CD contains software that should automatically install the currentdrivers/software to suit the PC it is being installed on.Deltrax5 included on the memory stick should automatically install current drivers to suit the operating system it is being installed on.

e-TRacKER portable energy monitor operating and maintenance manuale-TRacKER portable energy monitor operating and maintenance manuale-TRacKER portable energy monitor operating and maintenance manuale-TRacKER portable energy monitor operating and maintenance manual16

Page 17: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

Trouble shootingIf you are experiencing difficulties with your e-Tracker, please consult the points below.However if your problem is still not resolved please contact Marshall-Tufflex EnergyManagement on +44 (0)1424 856610.

If the unit will not switch on and has no display try the following:1) Your battery could be flat, please place on charge for at least half a day with on/off

switch in off position, use mains lead to charge (Note ensure 3Amp fuse in 13Amp plug is okay).

2) If charging fails to cure the problem, either the battery is flat or your e-Tracker program could be corrupted. Your unit would need to be returned to factory for reprogramming or to fit a new battery.

3) If charging fails to cure the problem, the internal fuse may have blown. Your unit would need to be returned to the factory for investigation.

Please note: a faulty battery, corrupt program or blown internal fuse can give the samesymptoms.

On screen error messages:CT’s odd

At least one of the three CTs does not match, or at least one of the three CT cables isdamaged thus causing the “CTs odd” message. In turn test each of the CTs using CT1input only, the rogue CT can be identified as it will produce a different Amp range to theother CTs (when going through the e-Tracker's set-up procedure).

For further help and information please contact our team on +44 (0)1424 856610 or visit www.marshalltufflexenergy.com

e-Tracker portable energy monitor operating and maintenance manual18

For further help and information please contact our team at [email protected]

Sinergy Meters supporton +44 (0)1625 613764

+44 (0)1625 613764

troubleshooting difficulties with your e-TRacKER, please consult the points below.Troubleshooting

1) Your battery could be flat, please place on charge for at least half a day with on/off switch in off position. Use mains lead to charge (Note ensure 3Amp fuse in 13Amp plug is ok.)

2) If charging fails to cure the problem, either battery is faulty, the internal fuse has blown or the programming could be corrupted. Your unit would need to be returned to the facto-ry for service or to fit a new battery.

When receiving a CT error message refer to page 8. If e-TRacKER is set up correctly then at least one of the three CTs is damaged. In turn test each of the CTs using CT1 input only, the rogue CT can be identified as it will produce a different Amp range to the other CTs (when going through the e-TRacKER’s set-up procedure).

e-TRacKER portable energy monitor operating and maintenance manuale-TRacKER portable energy monitor operating and maintenance manual 17e-TRacKER portable energy monitor operating and maintenance manual

Page 18: e-TRacKER Portable Energy Monitor e-Tracker Portable ...€¦ · Once the e-Tracker has been installed slide BATTERY SUPPLY switch ON. The display will show SELF TEST followed by:

e-Tracker portable energy monitor operating and maintenance manual10

e-Tracker operational specification ElectricalCurrent Input Clip-On or Flexeclamp CTs, 400mV. FS output

Current Range 50Amps full scale - 2500Amps full scale

Voltage Direct 3Ø 450V L-L 50Hz via voltage Clips

Voltage Direct 1Ø 240V 50Hz via 1Ø socket outlet

Voltage Nominal Adjustable 1Ø 220V +/- 10%, 3Ø 400V +/-10%

Pulse Input Volt free contact interface option

Battery Rechargeable cyclon 4V/2.5AH battery

Charge sources Integral charger via voltage connections

Battery life Approx 2 weeks of recorded current and calculated kVA only

Insulation inc CTs 2.5kV for 1min

Connection Leads CT to Plug 1.5m

Accuracy True RMS measurement of voltage & current

Clip-On CTs +/-1% percentage of reading @25°C for PF -0.7 -1

& 10% -100%IP

Flexeclamp CTs +/-2% of reading within conditions as above

ConstructionMaterial ABS case with insulated magnetic mounting panel

Climatic Oper.Temp -10°C-+50°C, 95% RH (NC), IP30 protection

e-Tracker dimensions 177mm(w) x 295mm(h) x 50mm(d) Weight 4kg (full kit)

StandardsCalibration & Safety IEC 1036 and IEC 61010-1

EMC EN55022:1994, EN50082 Pt.1 1992

Memory Spane-Tracker has capacity to store 16,000 lines of all parameters, either on one file or as

an aggregate total on up to five separate recording files. Recording will stop when

the memory is full.

Integration Period Mins. 60 30 20 15 10 5 2 1 0.1(6s) H1(1sec)

Memory Duration Days 666 333 222 166 111 55 22 11 25 hrs 9 hrs*

*V1, V2, V3, I1, I2 & I3 only

e-TRacKER operational specification

e-TRacKER dimensions

e-TRacKER has capacity to store 16,000 lines of all parameters, either on one file or as

e-TRacKER portable energy monitor operating and maintenance manuale-TRacKER portable energy monitor operating and maintenance manuale-TRacKER portable energy monitor operating and maintenance manuale-TRacKER portable energy monitor operating and maintenance manuale-TRacKER portable energy monitor operating and maintenance manual18