E-BUS Digital Room SensorTechnical Guide
TABLE OF CONTENTS
OVERVIEW ....................................................................................................................................... 3
BASIC OPERATION .......................................................................................................................... 4Sensor Operation ..................................................................................................................................................... 4LED Operation ......................................................................................................................................................... 4
MOUNTING AND WIRING ................................................................................................................ 5Dimensions .............................................................................................................................................................. 5Environmental Requirements ................................................................................................................................... 5Important Wiring Considerations .............................................................................................................................. 5Mounting .................................................................................................................................................................. 5
SENSOR OPERATION ...................................................................................................................... 6 Main Sensor Display Screens.................................................................................................... 6
Temperature and Humidity Status Screen .......................................................................................................... 6Outside Air Temperature Humidity Status Screen............................................................................................... 6Unit Information Screen ...................................................................................................................................... 6Setpoint Adjust Screen ....................................................................................................................................... 7Operation Modes ................................................................................................................................................ 7
TROUBLESHOOTING ....................................................................................................................... 8Temperature Sensor Testing for the OE217-02 Temperature Only Sensor .............................................................. 8
APPENDIX ..................................................................................................................................... 10Sensor Confi guration and Test Screens ................................................................................................................ 10Connecting the E-BUS Digital Room Sensor to the HVAC Unit Controller ............................................................ 12Connecting a Wall Mounted E-BUS CO2 Sensor to the HVAC Unit Controller ...................................................... 13Connecting the E-BUS Digital Room Sensor to the VAV/Zone Controller ............................................................. 14Connecting a Remote Sensor ................................................................................................................................ 15Mounting Plate Dimensions ................................................................................................................................... 18
AAON Controls8500 NW River Park Drive · Parkville, MO 64152Toll Free Phone: 866-918-1100PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: [email protected] our web site at www.orioncontrols.com
Form: OR-EBUS-DRS-TGD-01M All rights reserved. © August 2018 AAON, Inc. AAON assumes no responsibility for errors or omissions.This document is subject to change without notice.
www.orioncontrols.com
PART NUMBER CROSS REFERENCE TABLE
PART DESCRIPTION ORION
E-BUS LCD Digital Room Sensor Temp Only OE217-02E-BUS LCD Room Sensor Temp & Humidity OE217-03E-BUS Digital Room Sensor Temp & Humidity OE217-04E-BUS CO2 Sensor (Wall-Mounted) OE256-05Mounting Plate BK000081Return Air Temperature Sensor OE231VCCX2 Controller OE338-26B-VCCX2VCB-X Controller OE335-26B-VCBXVAV/Zone Controller OE326-23D-OR / OE326-23I-OR
E-BUS Digital Room Sensor Technical Guide 3
OVERVIEW
Overview
The OE217 series of E-BUS Digital Room Sensors are used to sense Space Temperature only or Space Temperature & Space Humidity. See Figures 1 & 2.
The OE217-02 model is the Space Temperature Sensor only model and the OE217-03 & OE217-04 models are a combination Space Tempera-ture & Space Humidity Sensor model. The OE217-04 model includes an enclosure without LCD display, front LEDs, and buttons.
All of the OE217 series of sensors can be used with the VCCX2 Control-ler (OE338-26B-VCCX2) and VCB-X Controller (OE335-26B-VCBX) and connect to the controller using various lengths of EBC E-BUS cables connected between the controller and the sensor. The EBC E-BUS cables should not run in conduit with other AC line voltage wiring or with any conductors carrying highly inductive loads.
The OE217-02 model can be used with the VAV/Zone Controller (OE326-23D-OR / OE326-23I-OR). It is either hard-wired or connected via EBC E-BUS cable.
The OE217-02 & OE217-03 sensors provide the following useful functions:
• Provides 112 x 64 monochrome Graphical LCD display with LED backlight
• Displays the Current Space Temperature
Features
Figure 1: OE217-02 & OE217-03 E-BUS Digital Room Sensor
Display Override
OVERRIDE ALARM
• Displays Outdoor Air Temperature (if controller is confi gured with an OA Temperature Sensor)
• Displays the Current Space Humidity (OE217-03 Model Only)
• Displays Outdoor Air Relative Humidity (OE217-03 Model if controller is confi gured with an OA Humidity Sensor)
• Displays the Current Zone Setpoint Temperature when slide adjust is entered
• Equipped with Push Buttons for changing the Zone Setpoint Temperature
• Equipped with an Override Button for forcing the VAV/Zone Controller or VCCX2 / VCB-X Controller into Occupied Operation from Unoccupied Operation
• Provides graphics to indicate the Mode of Operation
• Allows connection of a remote 10K Ohm, Type III thermistor temperature sensor (or 4 sensor averaging array). See Connecting a Remote Sensor section in the Appendix on page 15 for details.
• Provides LEDs to indicate Schedule Override, Button Push, Alarms, and Communications
• Can display Temperature reading from a Remote Temperature Sensor (see Figures 21 & 22, pages 15 & 16 for instructions)
Figure 2: OE217-04 E-BUS Digital Room Sensor
BASIC OPERATION
E-BUS Digital Room Sensor Technical Guide 4
Figure 3: E-BUS Digital Room Sensor Components
Alarm LED
SenseLED
OverrideLED
OverrideButtonDisplay
Button
UpButton
DownButton
LCDDisplay
Cover SetScrew
MIC
RO
CH
IP
PIC
24H
J
25
6G
P2
06
Back View
Remote ThermistorSensor Connector
Front View
E-BUS CableConnection
+12Vdc
GND
-COM
SHLD
Comm LED(Not visiblewith backcover on)
Display Override
OVERRIDE ALARM
Sensor Operation
When power is fi rst applied to the OE217-02 E-BUS Digital Room Sensor, the sensor will display the Current Room Temperature and the current setting of the slide off set. The OE217-03 model will also display Relative Humidity.
NOTE: The sensor readings are not accurate until the controller that the sensor is connected to is done calibrating.
The sensor has 4 buttons—<Display>, <Override>, <Up>, and <Down>. You can also access certain functions by touching the area below the <Display> and <Override> buttons. The sensor has 4 LEDs—one to indicate an Override, one to indicate an Alarm, one to indicate Communications, and one to indicate that a button has been pressed. See Figure 3 for LED and Button Descriptions.
An icon for the current mode of operation will appear in the sensor display. The operation mode icons are a Snowfl ake for Cooling Mode, a Flame for Heating Mode, a Fan in motion for Vent Mode, and a Moon for Unoccupied Mode. When the unit is in Unoccupied Mode, the screen’s background will turn dark. See Figure 9, page 7 for examples of operation modes.
Buttons and LEDs
LED Operation
Refer to Figure 3 for LED locations.
Alarm LED: The Alarm LED will blink when there is an alarm from the Controller.
Sense LED: The Sense LED will blink when the sensor gets a valid touch.
Override LED: The Override LED is inoperable when in Occupied Mode. In Unoccupied Mode, if you touch the <Override> button, the Override LED will blink, indicating an override request. The Control-ler will respond by sending the unit into override. The Override LED will then stay on for the duration of the Override. Any time the Unit is in Override, you can request to cancel the override by touching the <Override> button, and the Override LED will blink. The Unit will then cancel the override. The Override LED will then turn off .
Comm LED: The Comm LED located on the back of the sensor blinks on whenever communications are sensed.
E-BUS Digital Room Sensor Technical Guide
MOUNTING AND WIRING
5
Mounting
CAUTION: Do not touch the front face of the sensor while you are plugging in the modular sensor cable. Touching the front face of the sensor while plugging in the cable may prevent proper initial-ization and keep the buttons on the sensor from working properly.
The E-BUS Digital Room Sensor is designed to be mounted to a vertical 2” x 4” electrical box recessed in the wall. If the wall cannot be pen-etrated, a plastic surface mount box such as those made by WiremoldTM may be used to mount the sensor to the wall surface. The Sensor should be mounted at least 5 feet above the fl oor.
The Sensor is mounted by removing the front cover and fastening the housing base to the electrical box using the supplied (2) 6/32” x 1” machine screws. The modular cable is then plugged into the phone jack located on the circuit board that is mounted on the cover. The cover is then placed onto the housing base, and the Allen Screw on the bottom of the base is adjusted to hold the cover in place. A locking screw secures the sensor to the wall. See Figure 4 for E-BUS Digital Room Sensor dimensions.
Optional Mounting PlateIncluded with the Digital Room Sensor is a mounting plate that can be used, if necessary, to cover the sensor sheet rock opening. This mounting plate screws onto the back of the housing base. The mounting plate is then mounted and covers the recessed space in the wall. A locking screw secures the sensor to the wall. See Figure 25, page 18 for dimensions.
Environmental Requirements
The E-BUS Digital Room Sensor needs to be installed in an environment that does not exceed a temperature greater than 150°F or less than -30°F and does not exceed 90% relative humidity levels (non-condensing).
Indoor Reading Range
The E-BUS Digital Room Sensor’s Indoor Reading Range is 40°F to 120°F and 0-100% RH (RH is available on the OE217-03 & OE217-04 models). Its temperature reading accuracy is +/- .8°F, and its RH reading accuracy is +/- 3%. Its sensor element is the integral communicating digital sensing device or external Type III Thermistor 10K Ohm @ 77°F.
Outdoor Reading Range
If your E-BUS Digital Room Sensor is set up to read an Outdoor Air Temperature Sensor, any outdoor air temperature below -40°F will not appear on the E-BUS Digital Room Sensor’s display.
Important Wiring Considerations
The E-BUS Digital Room Sensors connect to the VCCX2 or VCB-X Controller using various lengths of EBC E-BUS cable connected between the controller and the sensor. The EBC E-BUS cables should not run in conduit with other AC line voltage wiring or with any conductors carrying highly inductive loads. See Figure 18, page 12 for wiring.
Dimensions and Mounting
Figure 4: E-BUS Digital Room Sensor Dimensions
MIC
RO
CH
IP
PIC
24H
J
25
6G
P2
06
4.5
5”
2.80
Front View Side View Back View
0.69
1.1
1.81
1.8
7
0.49
Remote ThermistorSensor Connector
0.8
1
+12Vdc
GND
-COM
SHLD
Display Override
OVERRIDE ALARM
SENSOR SCREENS
E-BUS Digital Room Sensor Technical Guide 6
LCD Display Screens
Main Sensor Display Screens
There are 3 Main Sensor Display Screens. The fi rst screen displays the Current Room Temperature, Operation Mode, Slide Off set, and RH (RH is available on the OE217-03 Model). The second screen displays the Outside Air Temperature and/or Humidity if Outdoor Air Temperature and/or Outdoor Air Humidity that is being monitored. The third screen displays the unit information for the controller that the Digital Room Sensor is connected to.
Temperature and Humidity Status Screen
The Main Display Screen dis-plays the current room tem-perature, the humidity in the room (RH is available on the OE217-03 Model), the current setting of the slide off set, and an icon for the current mode of operation once the controller it is connected to is done calibrating.
The diff erent icons shown are a Snowfl ake for cooling mode, a Flame for heating mode, a Fan in
motion for vent mode, and a Moon for unoccupied mode. When the unit is in unoccupied mode, the screen’s background will turn dark. Refer to Figure 9, page 7 for operation mode screen examples.
Figure 5: Main Display Screen
Figure 6: Outdoor Status Screen
Figure 7: Unit Information Screen
Outside Air Temperature Humidity Status Screen
If the connected controller is receiving an outdoor air tempera-ture and/or humidity broadcast, touching <Display> will fi rst bring up the Outdoor Status Screen.
Unit Information Screen
Touching <Display> again will bring up the Unit Information Screen which contains the con-troller’s address or ID number, screen ID, and software version of the controller connected to the sensor.
E-BUS Digital Room Sensor Technical Guide
SENSOR SCREENS
7
Setpoint Adjust Screen
Touching <> or <> will dis-play the Setpoint Adjust Screen. You can adjust the cooling and heating setpoints from this screen based on the VAV/Zone, VCCX2, or VCB-X Controller slide off set setpoint. For example, if the con-nected controller’s Max Slide Off set Setpoint is set for fi ve, you can adjust the setpoint up fi ve degrees and down fi ve degrees.
NOTE: If the VAV/Zone or Unit Controller’s slide off set setpoint is set to Zero, this screen will not appear when you touch <> or <>.
Figure 9: Operation Mode Screens
Cooling Modewith Snowfl ake Icon
Heating Modewith Flame Icon
Vent Modewith Fan in Motion Icon
Figure 8: Setpoint Adjust Screen
Unoccupied Modewith Moon Icon
Operation ModesRefer to Figure 9 for operation mode screen examples. The diff erent icons shown are a Snowfl ake for cooling mode, a Flame for heating mode, a Fan in motion for vent mode, and a Moon for unoccupied mode. When the unit is in unoccupied mode, the screen’s background will turn dark.
LCD Display Screens
TROUBLESHOOTING
E-BUS Digital Room Sensor Technical Guide 8
Troubleshooting the OE217-02 Temperature Only Sensor
Figure 10: Temperature/Resistance Testing for OE217-02 - Temperature Only Sensor
+ -
T
9302
NOTE: ,
Table 1
For This Test The Sensor Must Be Disconnected From Its E-BUSCable As Shown. The Meter Must Be Set To Measure Resistance In Ohms.Use To Determine If The Sensor Is Reading The Correct ResistanceValue For The Ambient Temperature. This Resistance Value Should MatchThe Temperature Value Listed Next To The Resistance Value In The Table.The Temperature Should Be Measured With A Separate AccurateTemperature Measuring Device Located In The Area Where The Sensor IsCurrently Located.
Measuring Digital Sensor ResistanceOE217-02 - Temperature Only Sensor
E-BUS Cable
From SensorDisconnected
MA
DE
IN U
SA
YS
10
23
70
R1
Mo
dB
us L
CD
Sp
ace
Se
nso
r
Wa
ttMa
ste
r Co
ntro
ls, In
c
PR
OG
RA
M
COMM
LED1
EX
TE
RN
TH
ER
M
+1
2V
dc
GN
D
-CO
M
+C
OM
M
SH
LD
P1
R1
F3
U4
C1
8
R36C30
D1
L1
C17
R3
8
R37C19
C3
1
C2
1
TB
1
X2
J3
C3
C24
C2
3
C1
C8
C12
C13 C14
C1
6
C2
5
C26
J2
Q2
R3R4
R6
R8
R9
R1
0
R11
R1
2
R1
4
R1
3
R1
5
TH1
U3
X1
C2
7
R1
8
C2
0D
4R
17
D6
D7
R32
R33
D5
1
J1
DIS
P1
C15
D2
R2
R5
R7
R1
6
R1
9
R2
0
U6
U2
TB
2
R3
5
2.2uF
R1
8
10
02
10
01
13
30
47
51
47
51
1001
1001
.1u
F
9.21Mhz
47
51
47
51
LTC3502
.1u
F
15pF6.8uF
.1uF
10
uF
31621502
6.8
uH
10
02
24F
C1025
6.8
uF
6.8
uF
10
01
47
51
.1u
F
.1uF
1000 1002
47
51
.1u
F
47
51
AD
M3
483
.1uF
.1uF
RS
1G
X05
MICROCHIP
PIC32MX440F
512H-80IPT
.1uF
10
RO
10
RO
47
0p
F
X05
OE217-02 E-BUS DigitalRoom Sensor
Back View
+
-
E-BUS Digital Room Sensor Technical Guide
TROUBLESHOOTING
9
Temperature/Resistance Chart
Table 1: Temperature/Resistance for Type III 10K Ohm Thermistor Sensors
Temperature – Resis-tance –for Type III 10K
Ohm Thermistor SensorsTemp(ºF)
Resistance(Ohms)
-10 93333-5 805310 698225 6055210 5250015 4590220 4014725 3516530 3080535 2714040 2387445 2109450 1865552 1779954 1695656 1616458 1538560 1468162 1401464 1338266 1275868 1219169 1190670 11652
Temperature – Resis-tance – for Type III 10K Ohm Thermistor Sensors
Temp(ºF)
Resistance(Ohms)
71 1137972 1113673 1087874 1062575 1039876 1015878 971180 930282 889384 851486 815388 780590 747295 6716
100 6047105 5453110 4923115 4449120 4030125 3656130 3317135 3015140 2743145 2502150 2288
APPENDIX
E-BUS Digital Room Sensor Technical Guide 10
Pixel Test Screen
To select the first option—Pixels—touch <> while at the Sensor Configuration & Test Screen (Figure 12). The Pixel Test Screen tests the pixels of the LCD display, allowing you to make the screen white with black characters, black with white characters, or a black or white screen. To exit this screen, touch <Display>.
Sensor Info & LED Test Screen
To select the second option—Info & LEDS—touch <> while at the Sensor Confi gura-tion & Test Screen (Figure 12). The Sensor Info & LED Test Screen shows the version of software that the sensor is run-ning and allows you to test the LEDs that are used on the con-troller. Touching <> will turn the LEDs on and touching <> will turn the LEDs off . To exit this screen, touch <Display>.
Sensor Confi guration and Test Screens
Sensor Confi guration and Test Screens
To access the Sensor Confi guration & Test Screens, you fi rst need to access the Unit Information Screen by touching <Display> while at the Main Display Screen.
NOTE: While in the Sensor Confi guration & Test Screens, the <Display> button functions as an exit key to return to the previous screen or menu. After a few seconds, however, the sensor will automatically revert to the Main Display Screen. Refer to Figure 11 when reading the instructions that follow.
Sensor Confi guration & Test Screen
While the Unit Information Screen is being displayed, you can enter the Sensor Confi gura-tion & Test Screen options by touching simultaneously below the <Display> and <Over-ride> buttons. (See Figure 11 which shows where to touch to access this option.)
OverrideButton
DisplayButton
TouchHere
TouchHere
Display Override
Figure 11: E-BUS Digital Room Sensor Buttons
Figure 12: Sensor Confi guration & Test Screen
Figure 14: Sensor Info & LED Test Screen
Figure 13: Sensor Info & LED Test Screen
E-BUS Digital Room Sensor Technical Guide
APPENDIX
11
LCD Backlight Test Screens
To select the third option—BACKLT—touch <Override> while at the Sensor Confi guration & Test Screen (Figure 12, page 10). This option allows you to control when the LCD backlight turns on and off . You can con-fi gure the backlight to stay on at all times, remain off at all times, or to come on when any button is touched on the sensor.
To exit this screen, touch <Dis-play>.
Sensor Confi guration and Test Screens
Thermistor Averaging Screen
To select the fourth and fi nal op-tion—THRM AVG—, while at the Sensor Confi guration & Test Screen (Figure 12, page 10), touch simultaneously below the <Display> and <Override> buttons. (See Figure 11, page 10 which shows where to touch to access this option.)
This option allows you to set the rate—from 1-15 seconds—at which the sensor takes a new temperature reading. Touch <> to increase the number of seconds and touch <> to decrease the number of seconds.
To exit this screen, touch <Dis-play>.
NOTE: The sensor takes the average of the last 10 readings based on the number that is entered in this screen. For example, if you want a 3-second sample, the sensor will take the average of the last 10 readings every 3 seconds over a 30-second span. Therefore, if you have your sensor next to an outside doorway, you would want to enter a higher number for your sample to give a more accurate read-ing for the room temperature in case the outside door is opened often.
Figure 15: Backlight Test & Confi guration Screen
Figure 16: Temperature Averaging Screen
Address Screen
To access the Address Screen, while at the Thermistor Averag-ing Screen, (Figure 16), touch the <Override> button.
This option allows you to set the address—from 1-10. Touch <> to increase the number and touch <> to decrease the number. The default is 1.
To exit this screen, touch <Display>.
Figure 17: Address Screen
SENSOR
1
COMMADDRESS
APPENDIX
E-BUS Digital Room Sensor Technical Guide 12
E-BUS Digital Room Sensor to HVAC Unit Controller Wiring
E-BUS Digital Room Sensor to HVAC Unit Controller Wiring
The OE217-02, OE217-03, or OE217-04 E-BUS Digital Room Sensor connects to the VCCX2 or VCB-X Controller with the EBC E-BUS expansion cable.
The E-BUS Digital Room Sensor should be mounted at approximately 5 Ft. above the fl oor on the wall in an area that does not have drafts or is exposed to direct sunlight. See Figure 18 for wiring details.
VCCX2 Controller
E-BUS DigitalRoom Sensor
EBC E-BUSCable
NOTE: When Only The E-BUS
Connects Directly To TheController Using A
Of The Appropriate Length.
Digital Room Sensor Is Used, ItUnit
n EBC E-BUSCableMount At Least 5 Feet Above Floor.See on page 13 ForConnection When A Wall-MountedE-BUS C Sensor Is Also Used.
Figure 19
O2
Display Override
OVERRIDE ALARM
24 VAC POWERONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
WattMasterOverlay
#S 000079Rev.: 1AW
GN
D
DUCTSTATIC
+2
4V
AC
DUALEBUS
Figure 18: OE217-02, OE217-03 & OE217-04 – E-BUS Digital Room Sensor Wiring
E-BUS Digital Room Sensor Technical Guide
APPENDIX
13
E-BUS DigitalRoom Sensor
Wall-MountedE-BUS CO Sensor2
EBC E-BUS Cable
EBC E-BUS Cable
NOTE: MountBoth Sensors AtLeast 5 Feet AboveFloor. The DigitalRoom SensorConnects To The
Sensor.CO2
VCCX2 Controller
Display Override
OVERRIDE ALARM
24 VAC POWERONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
WattMasterOverlay
#S 000079Rev.: 1AW
GN
D
DUCTSTATIC
+24
VA
C
DUALEBUS
Figure 19: OE256-05 – Wall Mounted E-BUS CO2 Sensor Wiring
E-BUS CO2 Wall Mounted Sensor to HVAC Unit Controller Wiring
The OE256-05 Wall Mounted E-BUS CO2 Sensor is used to monitor CO2 levels in the space served by the HVAC unit. The CO2 Sensor con-nects to the VCCX2 or VCB-X Controller with an EBC E-BUS cable. It can be daisy-chained with the E-BUS Digital Room Sensor ( OE217-02, OE217-03, OE217-04) for applications requiring both a room CO2 sensor and room temperature sensor.
It should be mounted at approximately 5 Ft. above the fl oor on the wall in an area that does not have drafts or is exposed to direct sunlight. See Figure 19 for wiring details and installation notes.
Wall Mounted E-BUS CO2 Sensor Wiring
NOTE: The OE265-07 Duct Mounted E-BUS CO2 Sensor can be used if desired instead of the Wall Mounted E-BUS CO2 Sensor. However, the E-BUS Digital Room Sensor does not directly connect to the Duct Mounted E-BUS CO2 Sensor. See the OE265-07 E-BUS CO2 Sensor Technical Guide for Duct Mounted E-BUS CO2 Sensor wiring details.
APPENDIX
E-BUS Digital Room Sensor Technical Guide 14
E-BUS Digital Room Sensor to VAV/Zone Controller Wiring
E-BUS Digital Room Sensor to VAV/Zone Controller Wiring
The OE217-02 E-BUS Digital Room Sensor connects to the VAV/Zone Controller with an EBC E-BUS expansion cable. It can also be hard-wired to the VAV/Zone Controller.
The E-BUS Digital Room Sensor should be mounted at approximately 5 Ft. above the fl oor on the wall in an area that does not have drafts or is exposed to direct sunlight. See Figure 20 for wiring details.
Figure 20: OE217-02 – VAV/Zone Controller E-BUS Digital Room Sensor Wiring
E-BUS Digital Room Sensor Technical Guide
APPENDIX
15
Connecting a Remote Sensor
Connecting a Remote Sensor
If the job requires this Sensor to be mounted outside of a conditioned space, a remote OE210 Space Sensor or OE231 Return Air Temperature Sensor (or any 2-wire 10K Ohm, Type III thermistor temperature sensor) can be hard-wired to the E-BUS Digital Room Sensor. Other versions of the WattMaster space sensors (OE211, OE212, or OE213) with slide adjust and/or override button should not be used as the remote sensor.
Contact AAON Controls for wiring information if a four sensor averag-ing array will be used as the “remote sensor”.
See Figure 21 for OE231 Return Air Temperature Sensor wiring. See Figure 22, page 16 for OE210 Space Sensor wiring.
OE217-02 - E-BUS Digital Room Temperature Only SensorDisconnect the modular cable from the E-BUS Digital Room Sensor before performing the following modifi cations.
If using the OE217-02 Temperature Only version of the sensor, you must fi rst remove the Digital Sensor’s back cover. You will see a loop of wire hanging off of the sensor circuit board. See Figure 23, page 17. This is the external thermistor loop wire. Clip the external thermistor loop wire so that the sensor will read the remote temperature input. Be sure to cut
Figure 21: OE231 Return Air Temperature Sensor Wiring
MIC
RO
CH
IP
PIC
24H
J
25
6G
P2
06
OE217-02, OE217-03 & OE217-04E-BUS Digital Room Sensor
Back View
Sensor Shown WithBack Cover Removed
Mount Sensor In Return AirDuct As Shown. Route WiresTo Digital Room SensorLocation And Connect ToTerminal Block.
ReturnAir Duct
OE231 Return AirTemperature Sensor
+12Vdc
GND
-COM
SHLD
the ends of the wire close to the circuit board so that the sensor loop wire ends won’t short between each other. The remote sensor then wires to the remote sensor terminal block on the back of the Digital Room Sensor.
If using an OE210 type Space Sensor as the remote sensor, you must clip off the C1 capacitor from the back of the OE210. Be sure to cycle power to begin reading the remote sensor. See Figure 22, page 16.
OE217-03 & OE217-04 E-BUS Digital Room Tempera-ture and Humidity SensorDisconnect the modular cable from the Digital Room Sensor before performing the following modifi cations.
If using the OE217-03 and OE217-04 Temperature and Humidity ver-sions of the Digital Room Sensor, you only need to wire the remote sensor to the remote sensor terminal block on the digital sensor. DO NOT CLIP OFF OR REMOVE the temperature/humidity sensor ele-ment on the Digital Sensor. See Figure 24, page 17. When the remote temperature sensor is wired in, it will override the on-board temperature value of the OE217-03 or OE217-04 sensor, even though the sensor element remains attached.
If using an OE210 type Space Sensor as the remote sensor, you must clip off the C1 capacitor from the back of the OE210. Be sure to cycle power to begin reading the remote sensor. See Figure 22, page 16.
APPENDIX
E-BUS Digital Room Sensor Technical Guide 16
Connecting a Remote Sensor
Figure 22: Attaching the OE210 Space Room Sensor
MIC
RO
CH
IP
PIC
24H
J
25
6G
P2
06
OE217-02, OE217-03 & OE217-04E-BUS Digital Room Sensor
Back View
Sensor Shown WithBack Cover Removed
RemoveC1 Capacitor
OE210 SpaceTemperature Sensor
Back View
TMP
GND
AUXOUT
+12Vdc
GND
-COM
SHLD
E-BUS Digital Room Sensor Technical Guide
APPENDIX
17
Connecting a Remote Sensor
Figure 23: Wire Clipping Instructions For OE217-02 - Digital Room Temperature Only Sensor
MIC
RO
CH
IP
PIC
24H
J
25
6G
P2
06
OE217-02 E-BUS Digital RoomTemperature Sensor Only
Back View
Sensor Shown WithBack Cover Removed
Cut Wire Loop As Shown.Make Sure That The WiresAre Cut Close Enough ToThe Circuit Board So TheyCan’t Touch Each Other.
+12Vdc
GND
-COM
SHLD
Figure 24: Instructions For OE217-03 & OE217-04 - Digital Room Temperature & Humidity Sensor
MIC
RO
CH
IP
PIC
24H
J
25
6G
P2
06
OE217-03 & OE217-04 E-BUS Digital RoomTemperature & Humidity Sensor
Back View
Sensor Shown WithBack Cover Removed
WARNING: DO NOT CLIP OFF OR REMOVE THETEMPERATURE & HUMIDITY SENSING ELEMENT
Sensing Element
+12Vdc
GND
-COM
SHLD
APPENDIX
E-BUS Digital Room Sensor Technical Guide 18
Mounting Plate Dimensions
Figure 25: BK000081 Mounting Plate Dimensions
1.64
3.285
0.060
5.0453.27
Optional Mounting Plate
Included with the Digital Room Sensor is a mounting plate that can be used, if necessary, to cover the sensor sheet rock opening. This mounting plate screws onto the back of the housing base. The mounting plate is then mounted and covers the recessed space in the wall. A locking screw secures the sensor to the wall. See Figure 25 for dimensions.
E-BUS Digital Room Sensor Technical Guide
NOTES
19
Form: OR-EBUS-DRS-TGD-01M Printed in the USA August 2018All rights reserved. © 2018AAON Inc. • 8500 NW River Park Drive • Parkville, MO • 64152Phone: 866-918-1100 www.orioncontrols.com Fax (816) 505-1101