dynaciat lg lgp

Upload: valentin-malihin

Post on 08-Jan-2016

577 views

Category:

Documents


13 download

TRANSCRIPT

  • DYN

    AC

    IAT

    LG

    Water-cooled chillers

    1AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    USEThe water-cooled packaged LG DYNACIAT series of chillers-heaters are especially designed to supply chilled or hotwater with a middle capacity for air conditioning application systems encountered in collective and commercial buildings, as well as industrial premises and processes.These packaged units are designed to beimplanted as standard indoors in a technical plant, shelteredagainst adverse weather and frost.

    To operate in COOLING mode, these units must be cooledby a water circulation coming from an external source, suchas underground water or city water if using a water flowcontrol valve, or connected to an external water drycooler ora cooling tower.

    On a water supply, the LGP series can be used as a heatpump during winter time.

    Connected to a heating or cooling floor, fan coil units or anair handling unit, a LGP series heat pump allows the heating and the air conditioning of buildings thanks to a setof valves located on the water circuit (not supplied).Each unit is assembled, internally wired (logic and startingbox), charged with refrigerant, and is subject to a operationtest in the factory.

    The installation work is simple, and the only operations required on site are electrical wiring and water pipingconnections.

    DYNACIAT LG series units are supplied as standard with thefollowing components:- water cooled condenser,- chiller evaporator,- capacity control system on outlet chilled or hot water,- logic, control and starting electric box :. Power supply : 3~50Hz 400V (+6%/-10%) + earth. Logic circuit : 1~50Hz 230V (+6%/-10%)(transformers are mounted on the unit as standard feature),- cabinet for indoor installation.

    Conformity with the EC European directives- "LOW VOLTAGE" directive (LVD),- Machines 98 / 37 CEE- Electromagnetic EMC 89 / 336 CEE- Pressure vessels DESP 97 / 23 CEE

    category 2 (LG-LGP-ILG)DESP is not applicable (LGN) unit not complete

    Conforms to standards- EN 60-204 and EN 378-2

    SPECIFICATIONS

    DYNACIAT LG - LGP seriesWater-cooled chillers or heat pump models

    DYNACIAT ILG seriesWater to Water reversible heat pumps models

    DYNACIAT LGN seriesChiller models without condenser (for split system)

    RANGE

    Cooling capacity : 35 to 350 kWHeating capacity : 40 to 415 kW

    High power efficiencyCompact and quietScroll compressorsBrazed plate heat exchangersElectronic control system

    HFC R407C

    EN

    VIRONM

    ENTALLY FRIENDLY

    PROTECTION DE L'ENVIRONNE

    MENTCooling or heating

    HFC R410A

    EN

    VIRONM

    ENTALLY FRIENDLY

    PROTECTION DE L'ENVIRONNE

    MENT

  • 2DYNACIAT LG

    2

    Water-cooled chillers

    AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    DynaCiat LG - LGP 120V 150V 200V 240V 300V 350V 400V 500V 540V 600V 753Z 900Z 1000Z 1100Z 1200ZCooling capacity kW 34.7 45.6 61.5 69.0 91.3 105.1 119.3 147.8 159.6 182.4 208.0 249.0 272.0 315.2 347.0Power input kW 7.5 9.6 13.0 15.2 19.2 22.3 25.4 32.0 34.4 38.4 55.0 67.0 74.0 78.35 85.5Efficiency EER 4.62 4.75 4.73 4.53 4.75 4.71 4.69 4.62 4.63 4.75 3.78 3.72 3.67 4.02 4.06Heating capacity kW 39.9 52.7 70.4 79.4 105.3 120.6 137.7 163.9 184.1 205.0 250.0 301.0 330.0 374.15 413.10Power input kW 9.3 11.9 16.4 18.8 23.9 27.4 31.3 39.1 42.6 48.2 68.0 83.0 92.0 96,5 105.0COP 4.29 4.42 4.29 4.22 4.40 4.40 4.39 4.19 4.32 4.25 3.67 3.62 3.58 3.87 3.93Sound power level dB(A) 67.0 70.0 69.0 70.0 73.0 74.0 75.0 76.0 75.0 76.0 78.0 79.0 79.0 81.0 82.0Compressor Hermetic SCROLL 2900 rpmStarting mode Direct in line in seriesQuantity 1 2 4 3 4Oil quality POE 3MAF (32 cst). POE ISO32-160SZ

    Oil volumel (cir1) 3.25 4.14 6.50 6.50 8.28 8.84 9.76 11.24 8.28 8.28 16.0 16.0 16.0 16.4 16.8 l (cir2) - - - - - - - - 6.50 8.28 8.0 16.0 16.0 16.4 16.8

    Refrig. circuit no. 1 2Refrigerant type R410A R407C

    Refrigerant weightkg (cir1) 3.1 4 6 6.7 9.5 11 12.5 16.3 6.7 9.6 7.7 12.3 13.3 14.2 16.8kg (cir2) - - - - - - - - 9.3 9.6 13.3 13.3 13.3 14.2 16.8

    Electric supply ph/Hz/V 3~50Hz 400V (+6%/-10%) + EarthMaxi rated current A 23.0 28.0 41.0 46.0 56.0 64.0 73.5 91.0 102.0 112.0 142.6 172.4 190.0 208.0 224.0 Starting current A 118.0 198.0 139.0 141.0 226.0 253.0 300.0 318.0 272.0 282.0 366.0 395.0 413.0 473.0 489 .0Starting currentSoft Start option A 81.0 118 90.0 104.0 146.0 163.0 191.0 209.0 192.0 202.0 254.0 284.0 300.0 339.0 357.0

    Breaking capacity kA 50 100Electric box protection IP22Maxi wires section mm2 50 50 50 50 50 95 95 95 95 95 185 185 185 185 185 Control voltage ph/Hz/V 1~50Hz 230V (+6%/-10%) transformer mountedCapacity control % 100-0 100-0 100-50-0

    100-50-0

    100-50-0

    10043-0

    10037-0

    100-50-0

    100-72-50-22-0

    100-75-50-25-0

    100-66-33-0

    100-72-50-22-0

    100-75-50-25-0

    100-78-50-22-0

    100-75-50-25-0

    Evaporator Brazed plate heat exchanger typeWater content l 2.7 3.6 4.8 5.3 9.9 11.3 12.8 15.7 15.2 19.8 15.8 15.8 15.8 18.0 20.3 Outlet water mini Maxi C -10C / +18C -8C / +12CMinimum water flow m3/h 3.5 4.8 6.2 7.0 9.5 10.9 12.4 15.2 16.4 19.1 23.1 27.5 30.1 35.0 39.0 Maximum water flow m3/h 11.2 14.6 19.8 22.2 29.2 34.0 38.4 47.5 51.1 58.4 45.0 54.6 60.0 68.0 77.0 Water connections G 1"1/4 G 1"1/2 G 2" G 2"1/2 DN80 PN16 DN100 PN16 DN125 PN16Design pressure bar 10 bars WATER sideCondenser Brazed plate heat exchanger typeWater content l 3.0 4.1 5.1 5.8 8.0 9.4 11.1 15.2 13.8 16.0 15.8 15.8 15.8 20.3 27.0Outlet water mini Maxi C +30C / +55C +30C / +50CMinimum water flow m3/h 3.1 4.1 5.4 6.1 8.2 9.4 10.7 13.1 14.3 16.3 20.0 24.0 26.3 29.0 32.0Maximum water flow m3/h 8.5 11.1 15.1 17.0 22.3 26.0 29.4 35.0 39.1 44.6 45.0 54.6 60.0 68.0 77.0Water connections G 1"1/2 G 2" G 2"1/2 DN80 PN16 DN100 PN16 DN125 PN16Design pressure bar 10 bars WATER sideStorage mini Maxi C -20C / +50CMini water pipe content l 226 299 197 222 292 286 279 454 217 274 457 364 457 451 565 Operating height mm 1201 1201 1201 1201 1201 1201 1201 1201 1201 1201 1681 1681 1681 1681 1681 Length mm 798 798 1492 1492 1492 1492 1492 1492 2380 2380 2200 2200 2200 2200 2200 Width mm 883 883 883 883 883 883 883 883 883 883 880 880 880 880 880 Weight empty kg 230 300 385 390 590 620 665 735 930 1125 1045 1223 1223 1321 1413Weight in operation kg 240 312 400 406 617 650 703 780 990 1190 1128 1315 1315 1408 1509

    TECHNICAL AND ELECTRICAL CHARACTERISTICS

    Capacities based on: / COOLING mode : +12C/+7C and +30C/+35C / HEATING mode : +40C/+45C and +12C/+7C

    EER and COP are gross values Height without lifting accessories

  • DYN

    AC

    IAT

    LG

    Water-cooled chillers

    3AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    DynaCiat ILG 120V 150V 200V 240V 300VCooling capacity kW 29,2 38,0 50,8 59,1 77,0Power input kW 8,0 10,2 13,9 15,8 20,2Efficiency EER 3,65 3,72 3,65 3,74 3,81Heating capacity kW 38,9 50,8 67,9 78,6 101,5Power input kW 9,1 11,7 16,1 18,1 23,3COP 4,27 4,34 4,22 4,34 4,35

    Sound power level dB(A) 67 70 69 70 73Compressor Hermetic SCROLL 2900 rpmStarting mode Direct in line in seriesQuantity 1 2Oil quality POE 3MAF (32 cst).Oil volume l (cir1) 3.25 3.6 5.5 8.1 9.2Refrig. circuit no. 1Refrigerant type R410ARefrigerant weight kg (cir1) 3.9 4 6.5 7.8 9.7Electric supply ph/Hz/V 3~50Hz 400V (+6%/-10%) + EarthMaxi rated current A 23.0 28.0 41.0 46.0 56.0Starting current A 118.0 198.0 139.0 141.0 226.0Starting currentSoft Start option A 81.0 118 90.0 104.0 146.0

    Breaking capacity kA 50Electric box protection IP22Maxi wires section mm2 50 50 50 50 50Control voltage ph/Hz/V 1~50Hz 230V (+6%/-10%) transformer mounted

    Capacity control % 100-0 100-0 100-50-0 100-50-0 100-50-0

    Internal circuit Brazed plate heat exchanger typeWater content l 2.7 3.6 4.8 5.3 9.9Minimum water flow m3/h 5 6,5 9 10 13,5Maximum water flow m3/h 14 18 25 28 36Water connections G 1"1/2 G 2"Design pressure bar 10 bars WATER sideExternal circuit Brazed plate heat exchanger typeWater content l 2.7 3.6 4.8 5.8 9.9Minimum water flow m3/h 5 6,5 9 10 13,5Maximum water flow m3/h 14 18 25 28 36Water connections G 1"1/2 G 2"Design pressure bar 10 bars WATER side

    Storage mini Maxi C -20C / +50C

    Mini water pipe content l 226 299 197 222 292

    Operating height mm 1201 1201 1201 1201 1201Length mm 798 798 1492 1492 1492Width mm 883 883 883 883 883

    Weight empty kg 226 289 379 452 595Weight in operation kg 237 301 394 468 622Capacities based on: / COOLING mode : +12C/+7C and +30C/+35C / HEATING mode : +40C/+45C and +12C/+7C

    EER and COP are gross values Height without lifting accessories

    TECHNICAL AND ELECTRICAL CHARACTERISTICS

  • DYNACIAT LG

    4

    Water-cooled chillers

    AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    Capacities based on : COOLING mode: +12C/+7C and condensing +45C EER is gross value Height without lifting accessories

    DynaCiat LGN 120Z 150Z 200Z 240Z 300Z 350Z 400Z 500Z 540Z 600Z 753Z 900Z 1000Z 1100Z 1200ZCooling capacity kW 28.0 41.0 55.0 67.0 81.0 95.0 110.0 134.0 150.0 162.0 204.0 245.0 268.0 296.0 327.2Power input kW 7.0 11.0 15.0 19.0 22.0 27.0 30.0 37.0 41.0 45.0 55.0 67.0 73.0 81.7 90.0Discharge capacity kW 35.0 52.0 70.0 86.0 103.0 122.0 140.0 171.0 191.0 207.0 259.0 312.0 341.0 377.7 417.2Efficiency EER 4.00 3.72 3.66 3.52 3.68 3.51 3.66 3.62 3.65 3.60 3.70 3.65 3.67 3.62 3.63

    Sound power level dB(A) 67 70 69 70 73 74 75 76 75 76 78 79 79 81 82Compressor Hermetic SCROLL 2900 rpmStarting mode Direct in line in series Quantity 1 2 4 3 4Oil quality POE ISO32-160SZ POE ISO32-160SZ

    Oil volumel (cir1) 3.8 6.2 7.6 10.0 12.4 14.2 16.0 16.0 12.4 12.4 16.0 16.0 16.0 16.4 16.8 l (cir2) - - - - - - - - 10.0 12.4 8.0 16.0 16.0 16.4 16.8

    Refrig. circuit no. 1 2Refrigerant type R407CRefrigerant weight Refrigerant not supplied (nitrogen charge)Electric supply ph/Hz/V 3~50Hz 400V (+6%/-10%) + EarthMaxi rated current A 19.5 30.0 39.0 49.0 59.0 68.0 77.0 95.0 108.0 118.0 142.6 172.4 190.0 208.0 224.0 Starting current A 120.0 175.0 140.0 195.0 205.0 245.0 254.0 318.0 254.0 264.0 366.0 395.0 413.0 473.0 489.0Starting currentSoft Start option A 72.0 104.0 84.0 118.0 124.0 148.0 161.0 208.0 160.0 166.0 254.0 284.0 300.0 339.0 357.0

    Breaking capacity kA 50 50 50 50 50 50 50 50 50 50 100 100 100 100 100 Maxi wires section mm2 50 50 50 50 50 95 95 95 95 95 185 185 185 185 185Electric box protection IP22Control voltage ph/Hz/V 1~50Hz 230V (+6%/-10%) - transformer mounted Capacity control % 100-0 100-0 100-50-0

    100-40-0

    100-50-0

    100-43-0

    100-50-0

    100-50-0

    100-72-45-18-0

    100-75-50-25-0

    100-66-33-0

    100-72-50-22-0

    100-75-50-25-0

    100-78-50-22-0

    100-75-50-25-0

    Evaporator Brazed plate heat exchanger typeWater content l 2.3 2.3 4.5 5.7 5.7 6.8 6.8 7.9 11.3 11.3 15.8 15.8 15.8 18.0 20.3 Outlet water mini Maxi C -10C / +12C -8C / +12CMinimum water flow m3/h 3.5 4.8 6.2 7.0 9.5 10.9 12.4 15.2 16.4 19.1 23.1 27.5 30.1 35.0 39.0Maximum water flow m3/h 11.2 14.6 19.8 22.2 29.2 34.0 38.4 47.5 51.1 58.4 45.0 54.6 60.0 68.0 77.0Water connections G 1"1/4 G 1"1/2 G 2" G 2"1/2 DN80 PN16 DN100 PN16 DN125 PN16Design pressure bar 10 bars WATER sideDischarge circuit Without condenserBalance circuit 1 / circuit 2 % 100 54/46 50/50 67/33 56/44 50/50 50/50 50/50Evaporator (cir1) 1"1/8 1"1/8 1"3/8 1"3/8 1"5/8 1"5/8 2"1/8 2"1/8 1"3/8 1"5/8 2"1/8 2"1/8 2"1/8 2"1/8 2"1/8Water content (cir2) - - - - - - - - 1"5/8 1"5/8 1"3/8 2"1/8 2"1/8 2"1/8 2"1/8Outlet water mini Maxi (cir1) 7/8 7/8 7/8 1"1/8 1"1/8 1"1/8 1"3/8 1"3/8 1"1/8 1"1/8 1"3/8 1"1/8 1"1/8 1"5/8 1"5/8 Minimum water flow (cir2) - - - - - - - - 1"1/8 1"1/8 1"1/8 1"3/8 1"3/8 1"5/8 1"5/8 Maximum water flow bar 29.5 bar HPWater connections C -20C / +50CDesign pressure l 158 233 153 148 227 227 309 376 144 221 370 293 368 353 442Operating height mm 1201 1201 1201 1201 1201 1201 1201 1202 1201 1201 1681 1681 1681 1681 1681 Length mm 788 788 1482 1482 1482 1482 1482 1482 2370 2370 2200 2200 2200 2200 2200 Width mm 873 873 873 873 873 873 873 873 873 873 880 880 880 880 880Weight empty kg 223 284 375 436 518 548 586 591 835 954 975 1135 1135 1161 1229Weight in operation kg 232 296 390 452 543 577 621 636 883 1008 1017 1177 1177 1203 1273

    TECHNICAL AND ELECTRICAL CHARACTERISTICS

  • DYN

    AC

    IAT

    LG

    Water-cooled chillers

    5AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    MAIN COMPONENTS Framework- casing with removable sheets in galvanized steel,- enamelled paint colors RAL 7024 and RAL 7035

    Hermetic SCROLL compressors- Integral motor cooled by suction gas- Motor protection by a winding internal thermostat- Mounting on antivibration mounts

    Evaporator- Brazed plate heat exchanger(s) type- End plates and internal plates in AISI 316 stainless steel- High performance optimized plates profile- Thermal insulation

    CondenserLG - LGP - ILG Series- Brazed plate heat exchanger(s) type- End plates and internal plates in AISI 316 stainless steel- High performance optimized plates profile- Thermal insulationLGN Series - Chiller without condenser- Possibility of connection on a removed air cooled condenserEUROPA 2C or AIRIAL series- Refrigeration sleeves for LGN (without condenser).

    Control and safety devices- Thermostatic expansion valve- High and low refrigerant pressure switch- Safety relief valves on refrigerant circuit- Temperature sensors and pressure transducers- Chilled water flow switch- Unit starting sequence

    Electrical boxThe entire assembly electric box, containing all the electriccomponents and control process unit (CPU), allows completecontrol of the functions of the machine, operation monitoring,adjustment of the water temperature settings, or interface withan external managing system.

    The electric box includes:- Power circuit and remote control circuit- Wiring numbering- Main safety switch breaker on front panel with handle- Control circuit transformer- Circuit breaker protections on power and control circuits- Compressor(s) motor(s) contactor(s)- General earth connection- Microprocessor electronic system

    Micro Connect ILGConnect for LG - LGP - LGN

    - Free contacts for field wiring signals report.

    Connect electronic control systemA CIAT microprocessor electronic control system, with CPU,with centralization of controls and monitoring of internaloperating.Including:- Selector for Run, Stop, Reset or Remote,- Running mode selector, COOLING or HEATING,- Output. RS485 output for BMS control (ModBus-JBus),. Output adapter for additional potential-free contact board,. Output adapter for remote control (optional).- LCD screen for output or internal operation and LED sightglasses

    Functions:- Monitoring of operating information by :. direct display of clear text messages in different languages. direct display of temperatures and pressures- Global compressors control with starting sequence, countingand equalization of compressors running times- Anti-short cycle protection- Auto-adaptative functions with adjustment of the controlsystem on the running parameters deviation- Capacity stage control system on each compressor (multicompressors) in accordance with the cooling or heatingrequirements controlled by the water temperatures- Control of the internal operating parameters- Second setting point control- Direct display of water temperatures- Diagnosis of operating status and faults :

    HP/LP, water flow, compressor(s) motor(s), anti-frost- Remote management and remote control

    OPTIONAL EQUIPMENT (KITTO BE MOUNTED ON-SITE) Optional equipment (delivered separately)- Remote control box, (Except ILG)- Additional potential-free contact board, (Except ILG)- Evaporator and condenser flexible connectors,- 800 microns water filter, evaporator and condenser,- For city water use (LG 120 - 500), condenser 2-way control valve,- For starting with low water temperature (LG 120 - 500) condenser

    3-way control valve,- Phase rotation detecter (rotation, phase failure, over voltage,under voltage),- Soft starter,

  • 7 -4-4-3

    OPERATING RANGE

    Adm

    issib

    le w

    ate

    r inl

    et/o

    utle

    t diffe

    rence

    C

    Water outlet temperature (C)

    Difference of temperature for performances calculation tables

    Brazed plateevaporator

    EVAPORATOR LIMITSThe curves represent the minimum and maximun allowable temperature difference of chilled water (or glycol) in accordance with the outlet temperature.

    Water glycol

    Example:For a water outlet: + 5 Cmini difference: 2,6 C Water temp.: 7,6 / 5 CMax. difference: 6 C Water temp.: 11 / 5 CFor temperature differences not included between the 2 curves, consult us.

    WATER GLYCOL COEFFICIENTS

    30 % concentration of glycol weight

    Freezing point of the solution: -17,5 C.

    K: Correction cfficients

    Reading valves in the brochurePf: Refrigeration power according to selection tables

    Pa: Compressor absorbed power according to selection tables

    DP: Water pressure drop according to curves for the corresponding corrected flow rate value (Qc).

    Corrected values according to calculations above:Pfc: Corrected cooling capacity

    Qc: Corrected chilled or hot water flow rate

    DPc: Corrected water pressure drop, evaporator orcondenser.

    Chilled water outlet C Chilled water outlet C Chilled water outlet C

    Cond

    ense

    r wate

    r out

    let

    C

    Cond

    ense

    r wate

    r out

    let

    C

    Cond

    ensa

    tion

    tem

    pera

    ture

    C

    Necessary Glycol Necessary Glycol Necessary Glycol

    DYNACIAT LG

    6

    Water-cooled chillers

    AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    LG-LGP 120V - 600V LG-LGP 753 - 1200 LGN 120Z - 1200Z

    CORRECTION POSITIVE TEMPERATURE NEGATIVE TEMPERATUREK Calculation K Calculation

    Evap

    orato

    r Cooling capacity 0,98 Pfc = Pf x 0,98 1,00 see selection tableChilled water

    flow 1,05Pcf x 0.86

    Qc = x 1,05T 1,10Pcf x 0.86

    Qc = x 1,10TPressure drop 1,15 Pc = P x 1,15 1,30 Pc = P x 1,30Average temp. 12 / 7 C see operating limits

    Cond

    ense

    r

    Cooling capacity 0,97 Pfc = Pf x 0,97Chilled water

    flow 1,05(Pcf+Pa) x 0.86

    Qc = x 1,05TPressure drop 1,10 Pc = P x 1,10Average temp. 35 / 40 C

    Evap

    orato

    r + co

    nden

    ser Cooling capacity 0,95 Pfc = Pf x 0,95 0,97 Pfc = Pf x 0,97

    Chilled waterflow 1,05

    Pcf x 0.86Qc = x 1,05T 1,10

    Pcf x 0.86Qc = x 1,10T

    Pressure drop 1,15 Pc = P x 1,15 1,30 Pc = P x 1,30Hot water flow 1,05

    (Pcf+Pa) x 0.86Qc = x 1,05T 1,05

    (Pcf+Pa) x 0.86Qc = x 1,05T

    Condenserpressure drop 1,10 Pc = P x 1,10 1,10 Pc = P x 1,10

  • DYN

    AC

    IAT

    LG

    Water-cooled chillers

    7AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    MINIMUM WATER PIPES VOLUMEThe Connect controller is equipped with an anticipation logic allowing high flexibility in adjusting the set points according to theparameters drifting, in particular for low water volume hydraulic installations.An adapted management of the compressors operating periods avoids therefore the start of anti-short cycle functions, and inmost cases, the requirement of a buffer tank.

    NOTES:Industrial processes which require a high stability of water temperatures or installations with high thermal load variation can privilege the installation of a water buffer tank.

    Models LG - LGP - ILG 120V 150V 200V 240V 300V 350V 400V 500V 540V 600V 753Z 900Z 1000Z 1100Z 1200ZMinimum installation volume (liters) 226 299 197 222 292 286 279 454 217 274 457 364 457 451 565

    NOISE LEVELSThe DYNACIAT LG - LGP - LGN - ILG range is a must by its design integrating the "noiseless" assembly process for attenuationof vibrations and sound power sources : Scroll compressor(s) mounted on antivibration mounts Anti-vibratil assembly of several compressors on structure isolated from the frame (120 to 600) Piping dissociated from the unit structure Double skin paneling with mineral wool insulation 25 mm (753 to 1200) Antivibration mounts to be positioned between the ground and the unit as standard (753 to 1200) Sound power levels ref 2x10-12 Pa 3 dB

    Sound pressure levels ref 2x10-5 Pa 3 dBMeasuring point: in free field 10 meters from the unit, 1.50 meters from the ground directivity 2

    Sizes POWER LEVEL SPECTRUM (dB) Global level LwdB(A)63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz120 77 65 65 59 59 61 59 67150 78 74 72 67 60 64 57 70200 78 60 60 62 62 64 62 69240 78 68 68 62 62 64 62 70300 81 77 75 70 63 67 60 73350 82 75 75 68 64 69 63 74400 83 76 76 69 67 70 64 75500 84 74 77 67 69 72 66 76540 83 78 76 70 66 69 64 75600 84 80 78 73 66 70 63 76753 89 68 70 75 73 69 69 78900 89 69 71 76 74 70 70 791000 89 69 71 76 74 70 70 791100 90 71 72 76 74 74 74 811200 90 73 72 77 75 76 76 82

    Sizes PRESSURE LEVEL SPECTRUM (dB) Global level LpdB(A))63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz120 46 34 34 28 28 29 28 35150 47 43 41 35 29 33 25 39200 47 28 29 31 31 33 30 38240 47 37 37 31 31 32 31 38300 50 46 44 38 32 36 28 42350 51 43 43 37 33 38 31 42400 52 44 45 37 36 39 32 44500 53 43 45 36 38 40 34 45540 51 46 44 39 34 37 33 43600 52 48 47 41 35 39 31 45753 57 36 38 43 41 37 37 46900 57 37 39 44 42 38 38 471000 57 37 39 44 42 38 38 471100 58 39 40 44 42 42 42 491200 58 41 40 45 43 44 44 50

    NOTES: Acoustic pressure levels depend on installation conditions, and consequently are only indicative. Reminder: only thesound power levels are comparable and certified.Compliance with ISO 3744 standard Lp = Lw - 10 log S

  • COOLING AND HEATING CAPACITIESDYNACIAT LG - LGP

    HFC R410A

    EN

    VIRONM

    ENTALLY FRIENDLY

    PROTECTION DE L'ENVIRONNE

    MENT

    DYNACIAT LG

    8

    Water-cooled chillers

    AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    R41

    0A

    LGLGP

    CONDENSER WATER OUTLET TEMPERATURE CEvaporator wateroutlet temperature

    C

    30 35 40 45 50 55Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa PckW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW

    120V

    Glycol water-10 19.0 6.7 25.4 17.9 7.5 25 16.5 8.4 24.5 15.2 9.4 24.1-4 24.0 6.7 30.5 22.6 7.5 29.9 21.1 8.4 29.1 19.4 9.4 28.3 17.8 10.6 27.82 30.1 6.7 36.6 28.6 7.5 35.8 27.0 8.3 35 25.2 9.3 34.1 23.2 10.5 33.2 21.1 11.8 32.3

    Pure water

    5 34.2 6.8 40.8 32.6 7.5 39.9 30.8 8.4 38.8 28.9 9.3 37.9 26.8 10.5 36.8 24.5 11.7 35.77 36.4 6.8 43.0 34.7 7.5 42.0 33.0 8.4 41.1 30.9 9.3 39.9 28.6 10.5 38.7 26.3 11.7 37.512 42.8 6.9 49.5 41.0 7.6 48.4 39.0 8.4 47.1 36.7 9.4 45.8 34.3 10.4 44.4 31.6 11.7 42.815 46,1 6,9 52,8 44,3 7,6 51,7 42,3 8,3 50,4 40,0 9,2 49,0 37,4 10,2 47,3 34,6 11,5 45,618 50,2 7,0 57,1 48,2 7,7 55,7 46,0 8,4 54,2 43,7 9,2 52,6 40,9 10,3 50,9 37,9 11,4 48,9

    150V

    Glycol water-10 25.5 8.4 33.6 24.2 9.3 33.1 22.8 10.4 32.7 21.3 11.5 32.1-4 31.6 8.5 39.8 30.2 9.5 39.3 28.6 10.5 38.7 26.9 11.7 38.1 24.8 13.1 37.22 39.3 8.6 47.6 37.7 9.5 46.9 35.9 10.6 46.1 33.8 11.8 45.2 31.5 13.2 44.2 29,0 14.8 43.0

    Pure water

    5 44.6 8.7 53.1 42.9 9.6 52.1 40.8 10.7 51.1 38.6 11.9 50.0 36.0 13.3 48.8 33.3 14.8 47.57 47.5 8.7 56.0 45.6 9.6 55.0 43.5 10.7 53.8 41.2 11.9 52.7 38.6 13.3 51.4 35.7 14.9 49.912 55.9 9.0 64.7 53.8 9.8 63.3 51.4 10.8 61.9 48.7 12.0 60.4 45.8 13.4 58.7 42.6 15.0 56.915 60,5 9,0 69,3 58,3 9,8 67,8 55,8 10,7 66,2 52,9 11,8 64,4 49,6 13,2 62,4 46,3 14,7 60,518 65,9 9,3 75,0 63,6 10,0 73,4 60,6 10,8 71,2 57,8 11,9 69,4 54,4 13,2 67,2 50,9 14,6 65,1

    200V

    Glycol water-10 33.5 11.4 44.5 31.4 12.9 43.7 29.1 14.6 42.9 26.6 16.5 42.1-4 42.5 11.4 53.5 40.1 12.9 52.5 37.5 14.6 51.4 34.6 16.5 50.2 31.5 18.7 49.22 53.2 11.5 64.3 50.5 12.9 62.9 47.6 14.5 61.6 44.4 16.4 60.1 41.0 18.5 58.6 37.2 21 57.1

    Pure water

    5 60.5 11.6 71.7 57.7 13.0 70.2 54.5 14.6 68.6 51.0 16.4 66.8 47.2 18.5 64.9 43.1 20.9 63.07 64.4 11.7 75.7 61.5 13.0 74.1 58.2 14.6 72.3 54.6 16.4 70.4 50.6 18.5 68.4 46.4 20.9 66.312 76.0 11.8 87.5 73.0 13.1 85.7 69.5 14.5 83.6 65.4 16.3 81.2 61.1 18.3 78.7 56.4 20.5 76.215 81,8 11,9 93,4 78,5 13,1 91,3 75,0 14,5 89,2 70,8 16,1 86,4 66,4 18,0 83,7 60,9 20,4 80,518 89,0 12,1 100,9 85,5 13,3 98,6 81,6 14,7 96,0 77,8 16,2 93,5 72,5 18,2 90,1 67,0 20,3 86,6

    240V

    Glycol water-10 37.8 13.4 50.6 35.6 15.0 49.8 32.8 16.8 48.8 30.1 18.9 47.8-4 47.9 13.4 60.9 45.3 15.0 59.7 42.3 16.8 58.3 39.2 18.9 57.1 35.7 21.2 55.82 59.7 13.5 72.9 56.8 15.0 71.3 53.6 16.8 69.7 50.0 18.8 68.0 46.1 21.1 66.2 41.9 23.7 64.4

    Pure water

    5 67.7 13.6 80.9 64.6 15.1 79.2 61.1 16.8 77.4 57.3 18.8 75.3 53.1 21.0 73.2 48.6 23.6 71.07 72.2 13.7 85.6 69.0 15.2 83.7 65.3 16.8 81.6 61.3 18.8 79.4 56.9 21.0 77.1 52.2 23.5 74.612 84.9 13.9 98.5 81.4 15.3 96.4 77.3 17.0 93.8 73.0 18.8 91.2 68.1 21.0 88.3 62.8 23.5 85.415 91,9 14,0 105,5 87,7 15,2 102,5 84,3 16,7 100,6 79,5 18,5 97,5 74,4 20,5 94,2 68,3 23,0 90,418 99,7 14,2 113,6 96,0 15,5 111,1 91,8 16,9 108,2 86,7 18,7 104,8 81,3 20,6 101,3 75,3 23,0 97,5

    300V

    Glycol water-10 50.1 16.8 66.2 47.6 18.7 65.4 44.7 20.7 64.4 41.8 22.9 63.4-4 62.8 16.9 79.1 59.9 18.9 78.0 56.8 21.0 76.9 53.3 23.4 75.6 49.3 26.0 74.02 78.1 17.1 94.7 74.9 19.0 93.3 71.2 21.2 91.7 67.2 23.7 90.0 62.7 26.5 88.0 57.6 29.5 85.7

    Pure water

    5 89.1 17.3 105.9 85.5 19.2 104.0 81.4 21.3 102.0 76.9 23.8 99.8 72.0 26.6 97.5 66.6 29.7 94.97 95.1 17.4 112.0 91.3 19.2 109.9 86.9 21.4 107.6 82.3 23.9 105.3 77.1 26.6 102.7 71.4 29.8 99.812 112. 17.9 129.5 107. 19.6 126.7 102.9 21.6 123.9 97.8 24.0 121.0 91.7 26.8 117.6 85.3 29.9 114.115 121,5 18,1 139,2 116,9 19,5 136,0 111,9 21,4 132,7 106,6 23,6 129,5 100,4 26,2 125,7 92,6 29,5 121,018 132,3 18,6 150,5 127,6 20,0 147,2 122,2 21,7 143,3 116,4 23,8 139,5 109,1 26,4 134,7 102,5 29,3 130,8

    350V

    Glycol water-10 57.0 19.3 75.5 53.7 21.4 74.1 50.5 23.8 73.1 47.0 26.4 71.9-4 71.9 19.5 90.7 68.1 21.6 88.9 64.3 24.0 87.3 60.4 26.8 85.9 56.0 29.9 84.32 90.0 19.8 109.3 85.7 21.9 106.6 81.5 24.3 104.9 76.5 27.1 102.5 71.4 30.3 100.3 65.6 33.9 97.8

    Pure water

    5 103.0 20.1 122.6 98.4 22.2 119.9 93.3 24.5 117.0 88.0 27.3 114.3 82.3 30.4 111.5 76.1 34.1 108.67 110.2 20.3 129.9 105.1 22.3 126.8 99.9 24.6 123.7 94.2 27.4 120.6 88.2 30.5 117.5 81.7 34.2 114.412 130.3 20.8 150.7 124.6 22.7 146.8 118.8 25.0 143.1 112.3 27.7 139.1 105.3 30.8 135.1 98.1 34.5 131.315 142,5 21,0 163,1 135,9 22,8 158,2 129,9 24,9 154,2 122,7 27,4 149,4 115,4 30,4 144,8 107,2 34,2 140,118 156,1 21,6 177,2 149,0 23,3 171,7 141,8 25,3 166,5 134,7 27,8 161,8 126,3 30,8 156,1 116,8 34,3 150,0

    400V

    Glycol water-10 64.2 22.0 85.3 60.9 24.5 84.3 57.2 27.3 83.0 52.9 30.2 81.5-4 81.4 22.3 102.8 77.6 24.7 101.3 73.5 27.6 99.8 68.6 30.7 97.8 63.3 34.2 95.72 101.9 22.6 123.9 97.5 25.0 121.7 92.7 27.8 119.5 87.5 31.0 117.2 81.4 34.6 114.4 74.8 38.5 111.4

    Pure water

    5 116.6 22.9 138.9 111.6 25.3 136.1 106.2 28.0 133.3 100.3 31.2 130.4 93.8 34.8 127.1 86.6 38.8 123.67 124.3 23.1 146.8 119.3 25.4 144.0 113.7 28.1 141.0 107.6 31.3 137.7 100.6 34.8 134.0 93.0 38.9 130.112 147.4 23.7 170.5 141.3 25.9 166.5 135.1 28.5 162.7 128.0 31.5 158.5 120.2 35.1 154.1 111.4 39.1 149.015 162,9 23,6 186,0 156,1 25,7 181,2 150,2 28,1 177,6 141,5 30,8 171,5 132,4 34,2 165,5 122,2 38,3 159,118 177,7 24,1 201,4 171,1 26,1 196,7 162,0 28,6 189,9 154,8 31,2 185,1 145,5 34,4 178,9 134,2 38,3 171,2

    Pf: Cooling output Zone where use of water / glycol is compulsoryPa: Compressor power input Calculation fouling 0.00005 m2 C/WPc: Heating capacity Eurovent conditions

  • COOLING AND HEATING CAPACITIESDYNACIAT LG - LGP

    DYN

    AC

    IAT

    LG

    Water-cooled chillers

    9AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    HFC R410A

    EN

    VIRONM

    ENTALLY FRIENDLY

    PROTECTION DE L'ENVIRONNE

    MENT

    HFC R407C

    EN

    VIRONM

    ENTALLY FRIENDLY

    PROTECTION DE L'ENVIRONNE

    MENT

    R41

    0A

    LGLGP

    CONDENSER WATER OUTLET TEMPERATURE CEvaporator wateroutlet temperature

    C

    30 35 40 45 50 55Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa PckW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW

    500V

    Glycol water-10 78.8 27.3 105.0 74.4 30.3 103.4 69.9 33.7 101.9 64.5 37.5 99.9-4 99.6 27.6 126.2 94.8 30.7 124.3 89.6 34.1 122.3 83.7 38.0 119.9 77.0 42.3 117.12 125.2 28.1 152.4 119.8 31.1 149.8 113.8 34.5 147.0 107.3 38.4 144.1 99.9 42.8 140.7 91.3 47.7 136.5

    Pure water

    5 143.6 28.5 171.3 137.2 31.4 167.6 130.9 34.8 164.5 123.5 38.6 160.7 115.4 43.0 156.7 106.1 47.9 151.87 153.3 28.7 181.3 147.0 31.6 177.7 139.9 35.0 173.7 132.2 38.7 169.6 123.8 43.1 165.2 114.2 48.1 160.212 182.1 29.4 210.8 174.5 32.3 205.9 166.5 35.5 201.0 157.5 39.2 195.4 148.1 43.5 190.0 137.3 48.4 183.715 203,3 29,2 231,9 195,2 31,9 226,3 186,8 35,0 220,9 175,5 38,3 212,7 164,1 42,3 205,0 150,2 47,5 195,918 222,8 29,7 252,0 212,7 32,3 244,4 203,4 35,3 237,9 192,2 38,7 229,9 179,9 42,7 221,4 166,1 47,7 212,2

    540V

    Glycol water-10 87.5 30.2 116.5 82.6 33.7 114.7 77.3 37.5 112.9 71.7 41.8 111.1 -4 110.4 30.4 139.6 104.9 33.8 137.4 98.7 37.8 134.9 92.2 42.3 132.4 84.8 47.2 129.5 2 137.4 30.6 167.1 131.2 34.0 164.1 124.3 38.0 160.9 116.8 42.5 157.5 108.5 47.5 153.8 99.2 53.3 149.7

    Pure water

    5 156.2 30.9 186.3 149.5 34.3 182.7 142.1 38.1 179.0 133.7 42.6 174.7 124.5 47.6 170.1 114.6 53.3 165.4 7 166.6 31.1 196.8 159.6 34.4 192.9 151.6 38.2 188.6 143.0 42.6 184.1 133.4 47.7 179.2 123.1 53.3 174.1 12 196.0 31.9 227.1 188.1 35.0 222.2 179.4 38.6 216.8 170.2 42.8 211.6 159.1 47.7 205.2 147.4 53.4 198.7 15 212,4 32,1 243,8 203,5 34,8 237,5 194,9 38,2 232,0 184,2 42,2 225,1 173,5 46,8 218,7 160,1 52,2 210,318 230,5 32,9 262,7 223,4 35,6 258,2 212,6 38,7 249,9 201,6 42,5 242,9 189,5 47,2 235,2 174,4 52,8 225,4

    600V

    Glycol water-10 100.1 33.6 132.3 95.1 37.3 130.7 89.5 41.4 128.8 83.5 45.8 126.8 -4 125.6 33.9 158.3 119.8 37.7 156.1 113.5 42.1 153.7 106.4 46.8 151.0 98.7 52.0 148.0 2 156.3 34.2 189.4 149.8 38.0 186.6 142.5 42.5 183.4 134.5 47.4 179.9 125.4 52.9 175.9 115.4 59.0 171.5

    Pure water

    5 177.9 34.6 211.6 170.9 38.3 208.1 163.0 42.6 204.2 154.0 47.6 199.8 144.0 53.2 195.1 133.1 59.3 189.7 7 190.1 34.8 224.0 182.4 38.4 219.7 173.9 42.8 215.3 164.5 47.7 210.5 154.1 53.3 205.3 142.7 59.5 199.6 12 223.9 35.8 258.9 215.4 39.2 253.6 206.0 43.2 248.0 195.4 48.0 241.9 183.7 53.5 235.3 170.8 59.8 228.2 15 242,8 36,3 278,4 234,0 39,2 272,3 223,9 42,9 265,8 212,6 47,2 258,4 199,5 52,7 250,5 184,7 59,2 241,818 264,6 37,2 301,1 254,0 40,1 293,2 244,0 43,4 286,3 231,4 47,9 277,9 218,6 53,0 270,0 203,7 59,3 261,0

    R40

    7C

    753Z

    Glycol water-8 117 44 160 112 49 159 107 54 158 101 60 157 2 177 47 223 168 53 220 160 59 216 151 65 213 140 72 209

    Pure water 5 202 49 250 193 54 246 183 61 241 172 67 236 161 74 232 7 217 49 265 208 55 261 197 61 256 185 68 250 172 75 245 12 260 51 310 248 57 303 235 63 296 221 70 289 206 78 281

    900Z

    Glycol water-8 137 56 191 130 62 189 123 69 189 116 76 187 2 211 58 268 201 65 264 191 72 259 179 80 255 167 88 251

    Pure water 5 244 60 302 232 66 297 219 74 290 206 82 285 192 91 279 7 262 60 321 249 67 315 235 75 307 221 83 301 206 92 294 12 314 62 375 299 69 366 282 77 357 265 86 348 247 95 339

    1000Z

    Glycol water-8 153 59 210 146 66 209 139 73 208 131 81 207 2 230 64 292 220 72 289 208 80 284 196 88 280 182 98 276

    Pure water 5 265 66 328 253 74 324 239 82 318 224 91 311 210 101 306 7 285 67 350 272 74 344 257 83 337 241 92 330 225 102 322 12 341 69 408 324 77 399 307 86 390 288 95 380 269 106 370

    1100Z

    Glycol water-8 168 65 234 161 72 233 152 80 232 143 88 231 134 98 2312 260 69 329 249 77 325 236 85 321 222 94 316 208 104 312

    Pure water 5 302 70 371 292 78 369 276 86 363 261 96 356 244 106 3507 329 70 399 315 78 394 298 87 385 281 96 378 263 107 37012 401 72 473 384 80 464 364 89 453 344 99 442 322 110 431

    1200Z

    Glycol water-8 186 71 258 176 79 255 168 87 255 159 96 255 149 106 2542 293 76 368 277 84 360 261 93 353 248 103 350 233 113 347

    Pure water 5 333 77 409 319 85 404 301 94 395 283 104 387 266 115 3817 364 78 442 347 86 433 328 95 423 308 105 413 291 116 40712 444 80 523 422 88 510 402 97 499 379 107 486 354 119 473

    Pf: Cooling output Zone where use of water / glycol is compulsoryPa: Compressor power input Calculation fouling 0.00005 m2 C/WPc: Heating capacity Eurovent conditions

  • DYNACIAT LG

    10

    Water-cooled chillers

    AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    COOLING CAPACITIES - COOLING MODEDYNACIAT ILG

    HFC R410A

    EN

    VIRONM

    ENTALLY FRIENDLY

    PROTECTION DE L'ENVIRONNE

    MENT

    Pf : Cooling output Zone where use of chilled water is compulsory.Pa : Compressor power input Calculation fouling 0,00005 m2 C/W

    Eurovent conditions

    R41

    0A

    ILG

    CONDENSER WATER OUTLET TEMPERATURE C

    Evaporatorwater outlet

    temperature C

    30 35 40 45 50 55

    Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa

    kW kW kW kW kW kW kW kW kW kW kW kW

    120V Pure water

    5 28,9 7,1 27,3 7,9 25,6 8,8 23,8 9,9 21,8 11,1 19,8 12,3

    7 31,0 7,1 29,2 8,0 27,4 8,9 25,5 9,9 23,4 11,1 21,4 12,3

    12 36,5 7,2 34,5 8,0 32,5 8,9 30,5 9,9 28,2 11,1 25,9 12,3

    15 40,0 7,3 38,0 8,0 36,0 8,9 33,5 9,9 31,0 11,1 28,7 12,3

    18 43,5 7,3 41,5 8,1 39,5 8,9 37,0 9,9 34,5 11,1 32,0 12,3

    150V Pure water

    5 37,0 9,2 35,5 10,1 33,5 11,3 31,5 12,6 29,3 14,0 27,0 15,4

    7 40,0 9,2 38,0 10,2 35,9 11,4 33,8 12,7 31,5 14,1 29,0 15,5

    12 47,0 9,3 45,0 10,3 42,6 11,4 40,0 12,8 37,5 14,3 34,8 15,7

    15 51,5 9,4 49,0 10,3 46,5 11,5 44,0 12,8 41,0 14,3 38,5 15,8

    18 56,5 9,5 54,0 10,4 51,0 11,5 48,3 12,8 45,0 14,3 42,0 15,8

    200V Pure water

    5 50,2 12,3 47,4 13,8 44,2 15,6 41,0 17,6 37,4 19,9 33,8 22,2

    7 53,6 12,4 50,8 13,9 47,4 15,6 44,0 17,6 40,4 19,9 36,8 22,2

    12 63,7 12,5 60,2 13,9 56,8 15,6 52,8 17,6 48,6 19,9 44,6 22,2

    15 70,0 12,5 66,0 14,0 62,5 15,6 58,4 17,6 54,0 19,9 49,6 22,2

    18 76,0 12,6 72,0 14,0 68,0 15,7 64,0 17,7 59,6 19,9 55,0 22,2

    240V Pure water

    5 58,6 14,2 55,4 15,8 51,9 17,6 48,2 19,8 44,2 22,2 40,4 24,6

    7 62,0 14,2 59,1 15,8 55,6 17,6 51,8 19,8 47,6 22,2 43,4 24,6

    12 73,6 14,4 70,0 16,0 66,0 17,8 62,0 19,8 57,2 22,2 52,4 24,6

    15 81,0 14,4 77,0 16,0 73,0 17,8 68,3 19,8 63,0 22,2 58,2 24,4

    18 88,0 14,6 84,0 16,0 80,0 17,8 75,2 19,8 69,6 22,2 64,0 24,4

    300V Pure water

    5 76,0 18,2 72,0 20,2 68,0 22,4 64,0 25,0 59,4 28,0 55,0 30,6

    7 80,7 18,2 77,0 20,2 73,0 22,6 68,7 25,2 64,0 28,0 59,0 30,8

    12 95,0 18,6 91,0 20,4 86,0 22,8 81,0 25,4 75,6 28,4 70,7 31,2

    15 104,0 18,8 100,0 20,6 95,0 22,8 89,2 25,4 83,7 28,4 78,0 31,4

    18 113,5 19,0 109,0 20,8 104,0 23,0 98,0 25,6 92,0 28,6 86,0 31,4

  • DYN

    AC

    IAT

    LG

    Water-cooled chillers

    11AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    HEATING CAPACITIES - HEATING MODEDYNACIAT ILG

    HFC R410A

    EN

    VIRONM

    ENTALLY FRIENDLY

    PROTECTION DE L'ENVIRONNE

    MENT

    Pf : Cooling output Zone where use of chilled water is compulsory.Pa : Compressor power input Calculation fouling 0,00005 m2 C/W

    Eurovent conditions

    R41

    0A

    ILG

    CONDENSER WATER OUTLET TEMPERATURE C

    Evaporator water outlet

    temperature C

    30 35 40 45 50 55

    Pc Pa Pc Pa Pc Pa Pc Pa Pc Pa Pc Pa

    kW kW kW kW kW kW kW kW kW kW kW kW

    120V

    Glycol water

    -8 26,9 6,5 26,4 7,3 25,7 8,3 24,8 9,1-4 30,2 6,5 29,5 7,2 28,8 8,2 28,0 9,1 27,1 10,3

    2 35,9 6,6 35,2 7,3 34,3 8,1 33,4 9,2 32,6 10,3 31,2 11,9

    Pure water

    5 39,9 6,6 38,9 7,3 38,0 8,1 36,9 9,1 35,9 10,2 34,8 11,4

    7 42,2 6,6 41,1 7,3 40,1 8,2 38,9 9,1 37,6 10,2 36,5 11,4

    10 45,6 6,7 44,5 7,4 43,4 8,2 42,1 9,1 40,8 10,1 39,3 11,4

    12 48,5 6,8 47,3 7,5 46,0 8,2 44,6 9,1 43,1 10,1 41,7 11,4

    150V

    Glycol water

    -8 34,6 8,2 34,0 9,2 33,5 10,3 32,7 11,4-4 38,7 8,3 38,0 9,2 37,4 10,4 36,6 11,5 35,9 12,9

    2 46,3 8,4 45,3 9,3 44,5 10,5 43,8 11,7 42,8 13,0 41,5 14,5

    Pure water

    5 51,4 8,5 50,4 9,4 49,4 10,5 48,4 11,7 47,0 13,1 45,9 14,8

    7 54,2 8,6 53,2 9,5 52,2 10,5 50,8 11,7 49,5 13,1 48,5 14,8

    10 58,8 8,7 57,6 9,6 56,3 10,6 54,8 11,8 53,3 13,2 51,7 14,812 62,4 8,9 61,2 9,7 59,7 10,6 58,1 11,8 56,6 13,1 54,8 14,8

    200V

    Glycol water

    -8 46,4 11,1 45,0 12,7 44,1 14,4 43,3 16,3-4 52,3 11,1 50,9 12,6 50,2 14,3 49,1 16,2 47,7 18,2

    2 62,3 11,3 60,9 12,7 59,6 14,3 58,0 16,1 56,1 18,0 54,7 20,6

    Pure water

    5 69,6 11,4 67,9 12,8 66,2 14,3 64,5 16,0 62,8 18,2 61,1 20,2

    7 73,1 11,5 71,3 12,8 69,6 14,3 67,9 16,1 66,0 18,2 64,1 20,1

    10 79,5 11,6 77,8 12,9 75,4 14,4 73,5 16,2 71,0 18,2 68,7 20,012 83,7 11,7 82,2 13,0 80,2 14,4 78,0 16,1 75,4 18,1 73,0 19,9

    240V

    Glycol water

    -8 53,1 13,1 52,3 14,6 51,7 16,6 50,5 18,6-4 59,8 13,0 58,6 14,6 57,8 16,5 56,5 18,6 55,4 20,9

    2 71,3 13,2 69,9 14,7 68,4 16,5 66,8 18,5 65,6 20,8 63,8 23,3

    Pure water

    5 80,8 13,2 78,8 14,6 76,8 16,3 74,3 18,2 72,1 20,4 69,9 22,9

    7 85,0 13,3 83,2 14,7 81,1 16,3 78,6 18,1 76,1 20,4 73,6 22,8

    10 92,4 13,5 89,6 14,9 87,7 16,4 85,5 18,2 82,7 20,3 79,6 22,812 98,2 13,7 96,1 15,0 93,5 16,5 90,9 18,2 87,3 20,3 84,2 22,8

    300V

    Glycol water

    -8 69,1 16,5 67,7 18,3 66,4 20,6 65,1 23,0-4 77,7 16,7 76,6 18,4 75,0 20,7 73,7 23,2 72,2 25,7

    2 92,6 16,9 91,1 18,6 89,5 20,8 87,8 23,4 85,5 26,0 83,1 28,9

    Pure water

    5 103,3 17,0 101,4 18,8 99,4 20,9 97,2 23,3 94,5 26,0 91,5 29,7

    7 107,9 17,1 106,3 18,8 104,1 20,9 101,5 23,3 98,9 26,1 95,1 29,8

    10 117,2 17,4 114,6 19,1 112,1 21,1 109,1 23,4 106,2 26,2 101,6 29,912 124,1 17,5 121,3 19,3 118,6 21,3 115,7 23,4 112,5 26,3 107,7 29,9

  • COOLING AND HEATING CAPACITIES REJECTED ON REMOTE CONDENSERDYNACIAT LGN

    R40

    7C

    LGN

    CONDENSING TEMPERATURE CEvaporator wateroutlet temperature

    C

    35 40 45 50 55Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa PckW kW kW kW kW kW kW kW kW kW kW kW kW kW kW

    120Z

    Glycol water-8 15.2 5.9 20.8 14.3 6.6 20.6 13.3 7.4 20.3 12.3 8.3 20.1-4 18.2 5.9 23.9 17.2 6.6 23.6 16.1 7.4 23.2 14.9 8.3 22.8 13.7 9.4 22.52 24.3 5.9 30.0 23.1 6.6 29.4 21.7 7.4 28.8 20.2 8.3 28.2 18.7 9.4 27.6

    Pure water5 28.7 5.9 34.5 27.3 6.6 33.7 25.7 7.4 32.9 24.0 8.3 32.0 22.2 9.4 31.27 30.8 5.9 36.6 29.4 6.6 35.8 27.8 7.4 34.9 26.0 8.3 34.0 24.1 9.3 33.112 38.2 5.9 44.0 36.5 6.6 42.9 34.5 7.4 41.7 32.3 8.3 40.4 30.1 9.3 39.1

    150Z

    Glycol water-8 22.6 8.7 31.0 21.4 9.7 30.7 20.1 10.8 30.4 18.7 12.1 30.2-4 27.1 8.8 35.5 25.7 9.8 35.1 24.2 10.9 34.6 22.6 12.2 34.2 20.9 13.7 33.82 35.4 8.9 44.0 33.7 9.9 43.3 31.9 11.0 42.5 30.0 12.3 41.8 28.0 13.8 41.1

    Pure water5 41.6 8.9 50.3 39.7 9.9 49.3 37.6 11.1 48.3 35.4 12.4 47.3 33.1 13.8 46.47 44.8 8.9 53.5 42.9 9.9 52.5 40.6 11.1 51.3 38.4 12.4 50.3 35.8 13.8 49.112 54.7 9.0 63.5 52.4 10.0 62.1 49.7 11.1 60.5 47.1 12.4 59.1 44.1 13.9 57.5

    200Z

    Glycol water-8 30.0 11.8 41.3 28.0 13.2 40.6 26.0 14.8 40.1 24.0 16.7 39.7-4 35.7 11.8 47.0 33.7 13.2 46.4 31.6 14.8 45.7 29.3 16.7 45.1 26.8 18.9 44.62 47.3 11.9 58.8 45.2 13.3 58.0 42.5 14.9 56.8 39.6 16.7 55.6 36.6 18.8 54.5

    Pure water5 56.1 12.0 67.7 53.3 13.3 66.2 50.2 14.9 64.6 47.0 16.7 63.1 43.5 18.8 61.67 60.5 12.0 72.2 57.8 13.4 70.8 54.5 14.9 69.0 51.0 16.7 67.1 47.3 18.8 65.412 75.0 12.1 86.8 71.5 13.4 84.6 67.6 15.0 82.2 63.5 16.8 79.8 59.2 18.8 77.3

    240Z

    Glycol water-8 36.5 14.7 50.5 34.5 16.4 50.1 32.3 18.3 49.7 30.0 20.5 49.4-4 44.0 14.8 58.3 41.7 16.5 57.6 39.3 18.4 56.8 36.6 20.6 56.2 33.8 23.2 55.62 58.5 15.0 73.1 55.6 16.7 71.7 52.5 18.6 70.4 49.3 20.8 69.2 45.8 23.3 68.0

    Pure water5 68.8 15.1 83.5 65.6 16.8 81.9 62.1 18.7 80.1 58.3 20.9 78.4 54.3 23.4 76.77 74.4 15.2 89.2 71.1 16.9 87.5 67.2 18.8 85.4 63.2 21.0 83.4 59.0 23.5 81.512 91.9 15.4 106.9 87.6 17.1 104.2 83.2 18.9 101.6 78.4 21.1 98.9 73.3 23.6 96.1

    300Z

    Glycol water-8 45.0 17.5 61.7 42.0 19.5 60.5 39.5 21.7 60.1 36.8 24.3 59.7-4 53.3 17.6 70.3 50.7 19.6 69.5 47.7 21.9 68.6 44.8 24.5 68.0 41.5 27.4 67.32 70.4 17.8 87.7 67.1 19.8 86.3 63.5 22.1 84.8 59.7 24.7 83.3 55.7 27.6 82.0

    Pure water5 82.4 18.0 99.9 79.3 20.0 98.7 75.0 22.2 96.5 70.5 24.8 94.4 65.9 27.7 92.57 89.3 18.0 106.8 85.5 20.0 105.0 81.0 22.3 102.6 76.5 24.9 100.4 71.5 27.8 98.212 109.8 18.2 127.6 104.8 20.2 124.5 99.8 22.4 121.6 94.2 25.0 118.4 88.5 27.9 115.5

    350Z

    Glycol water-8 51.8 20.7 71.6 48.9 22.9 70.7 46.0 25.4 70.1 43.0 28.3 69.7-4 62.5 20.9 82.6 59.2 23.1 81.4 55.8 25.7 80.3 52.3 28.5 79.4 48.6 31.8 78.62 82.7 21.3 103.3 78.6 23.5 101.3 74.4 26.1 99.5 70.1 29.0 97.8 65.4 32.2 96.2

    Pure water5 97.8 21.5 118.8 93.0 23.8 116.1 88.0 26.3 113.4 82.8 29.2 111.0 77.4 32.5 108.67 105.3 21.7 126.4 100.5 23.9 123.7 95.3 26.5 120.9 89.8 29.4 118.1 84.0 32.7 115.412 129.5 22.0 151.1 123.8 24.3 147.5 117.5 26.9 143.6 111.0 29.8 139.9 104.1 33.1 136.1

    400Z

    Glycol water-8 60.1 23.8 82.8 56.9 26.2 81.9 53.5 29.1 81.1 50.0 32.2 80.4 46.4 35.9 80.1-4 72.5 24.0 95.6 68.8 26.5 94.2 64.8 29.3 92.7 60.6 32.5 91.5 56.4 36.2 90.62 95.9 24.5 119.6 91.2 27.0 117.3 86.2 29.8 114.9 81.0 33.0 112.7 75.8 36.7 110.8

    Pure water5 113.4 24.8 137.5 107.6 27.3 134.1 101.9 30.2 131.0 96.0 33.4 128.2 89.8 37.1 125.47 122.3 24.9 146.6 116.9 27.5 143.6 110.4 30.4 139.8 104.1 33.6 136.5 97.5 37.3 133.412 151.3 25.4 176.1 143.9 28.0 171.2 136.4 30.9 166.4 128.7 34.2 161.8 120.9 38.0 157.5

    HFC R407C

    EN

    VIRONM

    ENTALLY FRIENDLY

    PROTECTION DE L'ENVIRONNE

    MENT

    DYNACIAT LG

    12

    Water-cooled chillers

    AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    Pf: Cooling output Zone where use of water / glycol is compulsoryPa: Compressor power input Calculation fouling 0.00005 m2 C/WPc: Heating capacity to evacuate Standard conditions

  • COOLING AND HEATING CAPACITIES REJECTED ON REMOTE CONDENSERDYNACIAT LGN

    R40

    7C

    LGN

    CONDENSING TEMPERATURE CEvaporator wateroutlet temperature

    C

    35 40 45 50 55Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa PckW kW kW kW kW kW kW kW kW kW kW kW kW kW kW

    500Z

    Glycol water-8 73.75 27.97 100.6 70.1 31.2 99.9 67.1 34.7 100.1 63.2 38.5 99.7 58.9 42.7 99.12 115.9 28.9 144 110.9 32.4 142.2 105.4 36.1 140.2 99.7 40.2 138.2 93.5 44.6 136

    Pure water5 135.9 29.3 164.4 130.2 32.9 162.0 123.9 36.6 159.3 117.3 40.8 156.6 110.1 45.2 153.57 146.1 29.6 174.9 140.7 33.1 172.9 133.9 36.9 169.7 126.9 41.1 166.4 119.1 45.6 162.912 178.9 30.2 208.4 172.1 33.8 205.1 164.3 37.7 200.9 155.9 41.9 196.5 146.7 46.5 191.6

    540Z

    Glycol water-8 80.3 32.0 110.9 76.1 35.7 110.1 71.7 40.0 109.6 67.4 44.8 109.62 129.2 32.6 160.8 123.3 36.3 158.4 116.5 40.5 155.6 110.0 45.3 153.5 102.5 50.8 150.9

    Pure water5 154.3 32.8 186.3 146.9 36.5 182.3 139.2 40.7 178.5 130.9 45.5 174.8 122.2 51.0 171.07 167.0 32.9 199.1 158.7 36.6 194.2 150.4 40.8 190.0 142.0 45.6 186.0 132.3 51.0 181.312 204.6 33.2 237.0 195.8 36.9 231.7 185.3 41.0 225.2 175.2 45.8 219.6 163.7 51.2 213.2

    600Z

    Glycol water-8 88.0 34.9 121.3 83.3 38.9 120.3 77.8 43.4 119.0 72.9 48.6 118.82 140.8 35.7 175.4 134.4 39.7 172.7 127.2 44.2 169.7 119.2 49.4 166.5 111.1 55.2 163.7

    Pure water5 162.8 35.9 197.7 157.2 39.9 195.9 149.6 44.5 192.6 140.4 49.6 188.2 131.5 55.5 184.77 178.5 36.0 213.6 170.4 40.1 209.3 161.8 44.6 205.0 152.3 49.8 200.3 143.0 55.6 196.412 220.1 36.3 255.6 210.5 40.3 249.8 200.1 44.9 243.8 189.1 50.1 237.6 177.6 55.9 231.5

    753Z

    Glycol water-8 116 42 156 111 47 155 105 52 155 99 58 154 92 64 1532 178 43 220 171 48 218 163 54 215 154 60 212 144 67 208

    Pure water5 206 44 248 197 49 245 188 55 241 178 61 237 167 68 2327 222 44 265 214 49 261 204 55 257 193 61 252 181 68 24712 268 45 312 257 50 306 246 56 300 233 62 294 220 69 287

    900Z

    Glycol water-8 137 52 186 130 57 185 123 64 184 116 71 183 108 79 1822 214 53 266 205 59 262 195 66 258 184 73 254 172 81 250

    Pure water5 249 54 301 238 60 296 226 66 291 214 74 285 200 82 2797 270 54 322 258 60 316 245 67 310 231 74 303 217 83 29712 325 55 379 312 61 371 297 68 363 281 75 354 269 84 350

    1000Z

    Glycol water-8 151 56 205 145 62 204 138 69 204 130 77 203 121 86 2022 234 57 290 224 64 287 214 72 283 202 80 279 190 89 275

    Pure water5 271 58 327 260 65 323 248 73 318 235 81 313 220 90 3077 293 58 349 281 66 345 268 73 339 254 82 333 239 91 32612 352 59 410 339 67 404 323 74 396 307 83 387 289 92 378

    1100Z

    Glycol water-8 165 63 227 156 70 226 147 77 225 139 86 225 129 95 2242 257 65 321 246 72 318 233 80 313 220 89 309 206 99 3055 303 66 368 289 73 362 275 81 356 259 90 349 242 100 342

    Pure water 7 326 66 392 312 73 385 296 82 378 280 91 370 263 101 36412 400 67 467 382 75 457 364 83 447 345 92 437 323 102 426

    1200Z

    Glycol water-8 181 70 250 173 77 250 162 85 247 152 95 246 141 105 2462 284 72 356 270 80 350 256 88 345 242 98 340 226 109 335

    Pure water5 334 73 407 318 81 398 302 89 392 285 99 384 267 110 3777 360 74 433 344 81 425 327 90 417 308 100 407 289 111 40012 441 75 514 423 83 503 401 91 489 378 101 476 356 112 464

    HFC R407C

    EN

    VIRONM

    ENTALLY FRIENDLY

    PROTECTION DE L'ENVIRONNE

    MENT

    DYN

    AC

    IAT

    LG

    Water-cooled chillers

    13AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    Pf: Cooling output Zone where use of water / glycol is compulsoryPa: Compressor power input Calculation fouling 0.00005 m2 C/WPc: Heating capacity to evacuate Standard conditions

  • DYNACIAT LG

    14

    Water-cooled chillers

    AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    WATER PRESSURE DROPLG - LGP 120 - 1200Condenser and evaporator

    (prohibited use outside limit applications)

    EVAPORATOR

    3 4 5 6 7 8 9 10 2015 30 40 50 60 70 808

    10

    20

    30

    40

    5060

    80

    100

    160

    Units conversion formulaekPa = bar x 100bar = mH2O x 0.0981kg/cm2 = bar x 1.0197Pi (lbf/in2) = bar x 14.504Inches (in) = mm x 0.0394

    Foot (ft) = mm x 0.0032808Pounds (lb) = kg x 2.205Cubic foot mn (cfm) = m3/h x 0.5885US Gallons = m3 x 264.2UK Gallons = m3 x 220

    CONDENSER

    Water flow m3/h

    Wate

    r pre

    ssur

    e dr

    op in

    kPa

    3 4 5 6 7 8 9 10 2015 30 40 50 60 70 808

    10

    20

    30

    40

    5060

    80

    100

    160

    Water flow m3/h

    Wate

    r pre

    ssur

    e dr

    op in

    kPa

  • DYN

    AC

    IAT

    LG

    Water-cooled chillers

    15AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    WATER PRESSURE DROPLGN 120 - 1200Condenser and evaporator

    (prohibited use outside limit applications)

    EVAPORATOR

    3 4 5 6 7 8 9 10 15 20 30 40 50 60 70 800.1

    0.2

    0.4

    0.6

    0.81

    2

    4

    6

    8

    EVAP

    120 -

    150

    EVAP

    200-24

    0 CON

    D 120-

    150-200

    -24

    0

    EVAP

    300-35

    0 CON

    D 300-

    350

    EVAP

    400-500

    COND

    400-500

    EVAP

    -

    COND

    540-60

    0

    EVAP

    -

    COND

    753-900

    -100

    0

    EVAP

    -

    COND

    1100-1

    200

    Wate

    r pre

    ssur

    e dr

    op in

    mCE

    Filter - LG - LGP - LGN (compulsory)

    109876543 2015 30 40 50 60 70 80

    10

    20

    30

    40

    5060

    80

    100

    160

    120

    150

    200 24

    0 300

    350

    500

    400

    540 60

    0

    753

    1100

    1200

    900 -

    1000

    Water flow m3/h

    Wate

    r pre

    ssur

    e dr

    op in

    kPa

    Water flow m3/h

  • DYNACIAT LG

    16

    Water-cooled chillers

    AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    WATER PRESSURE DROPILG 120 - 300Evaporator (prohibited use outside limit applications)

    INTERNAL CIRCUIT AND EXTERNAL CIRCUIT

    Water flow m3/h

    Wate

    r pre

    ssur

    e dr

    op in

    kPa

    8

    6

    4

    4 5 6 7 8 9 10 15 20 30 40 50 60 703

    2

    10.8

    0.6

    0.4

    0.2

    0.1

    ILG 12

    0 - 15

    0 - 200

    - 240

    ILG 30

    0

    Wate

    r pre

    ssur

    e dr

    op in

    mCE

    Filter - ILG (compulsory)

    Water flow m3/h

    Units conversion formulaekPa = bar x 100bar = mH2O x 0.0981kg/cm2 = bar x 1.0197Pi (lbf/in2) = bar x 14.504Inches (in) = mm x 0.0394

    Foot (ft) = mm x 0.0032808Pounds (lb) = kg x 2.205Cubic foot mn (cfm) = m3/h x 0.5885US Gallons = m3 x 264.2UK Gallons = m3 x 220

  • 17

    DYN

    AC

    IAT

    LG

    Water-cooled chillers

    17AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    DIMENSIONSDYNACIAT LG - LGP 120 - 1200

    AF 3 x D E

    9015

    91

    a : Condenser cooling water outlet (LG) Condenser hot water outlet (LGP)

    b : Condenser cooling water inlet (LG) Condenser hot water inlet (LGP)

    c : Evaporator chilled water outlet

    d : Evaporator chilled water inlet

    e : Electrical supply

    Anti-vibration mounts

    LG-LGP 120 150 200 240 300 350 400 500 540 600 753 900 1000 1100 1200

    Figure 1 2 3 4

    Male connectors Flange PN16a - b G 11/2

    G 11/2 G 2 G 21/2 DN 80 DN 100 DN 125c - d G 11/4

    A 127 126 127 122 125.8B 454 492 494 473 C 446 408 406 427 D 270 270 270 300 300 E 690 690 690 607 607 F 690 690 690 683 683

    Mas

    s K

    g Empty 230 300 385 390 590 620 665 735 930 1125 1045 1223 1223 1321 1413

    In operation 240 312 400 406 617 650 703 780 990 1190 1128 1315 1315 1408 1509

  • DYNACIAT LG

    18

    Water-cooled chillers

    AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    DIMENSIONSDYNACIAT LGN 120 - 1200

    169 150 150 150169 461 140 280 280

    95

    98

    321 585 385 680150 150 150 270

    AF 3 x G D E

    9015

    91

    a : Discharge pipe connection

    b : Liquid return pipe connection

    c : Evaporator chilled water outlet

    d : Evaporator chilled water inlet

    e : Electrical supply

    Anti-vibration mounts

    LGN 120 150 200 240 300 350 400 500 540 600 753 900 1000 1100 1200 Figure 1 2 3 4 4

    Circ

    uit

    1

    a 11/8 13/8 13/8 15/8 21/8 15/8 21/8

    b 7/8 7/8 11/8 11/8 11/8 11/8 13/8 11/8 15/8

    Circ

    uit

    2

    a 13/8 15/8 Tube

    13/8 21/8 21/8b 11/8 11/8 13/8 15/8

    c - d G 11/4 G 11/2 G 2 G 21/2 PN 16 DN 80 PN 16 DN 100 PN 16 DN 125A 127 111 122 125.8B 535 563 563 581 568 C 365 337 337 319 332D 270 270 270 300 300E 690 690 690 607 607F 775 775 775 803 803 G 80 80 80 80 80

    Mas

    sKg

    Empty 223 284 375 436 518 548 586 591 835 954 975 1135 1135 1161 1229In operation 232 296 390 452 543 577 621 636 883 1008 1017 1117 1117 1203 1273

  • ILG 120 150 200 240 300Figure 1 2

    Male connectors

    a - bG 11/2 G 2

    c - d

    A 127 126

    Mas

    s K

    g Empty 226 289 379 452 595

    In operation 237 301 394 468 622

    DYN

    AC

    IAT

    LG

    Water-cooled chillers

    19AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    DIMENSIONSDYNACIAT ILG 120 - 300

    169 150 150 150169 461 140 280 280

    95

    321

    a : Water outlet internal circuit

    c : Water outlet external circuit

    b : Water inlet internal circuit

    d : Water inlet external circuit

    e : Electricity supply

    A

  • DYNACIAT LG

    20

    Water-cooled chillers

    AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    PIPING INSTALLATION EXAMPLE LG - LGP SERIES

    chilled water circuit

    hot water recovery circuit

    water filling

    expansion tank

    balance valve

    drain

    stop valve

    temperature controller

    air purge

    water filter (compulsory)

    flexibles (compulsory)

    thermometer wells

    water discharge

    4 ways water valve

    accessible exchanger

    relief valve

    COOLING installation with water dry-cooler

    NOTE: the above piping diagram examples are indicative only and do not constitute installation details.

  • DYN

    AC

    IAT

    LG

    Water-cooled chillers

    21AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    PIPING INSTALLATION EXAMPLE - ILG SERIESTERMINAL UNITSand / or

    Outdoorsensor

    Indoorsensor

    Flexiblesleeves

    REGULATOR

    HYDRAULIC MODULE

    COOLING / HEATING FLOOR

    Safety valve+ manometer

    Filling

    Pump

    Internalcirculation

    pump

    Screenfilter

    Expansion vessel

    Screenfilter

    Safety valve+ manometer

    Filling

    Expansionvessel

    Buffer tank(option)

    Solenoidevalve

    Strainer valve

    Wallorground water

    Outsidenetwork of water

    (pump with boosteror city water)

    Closed in summerWINTER

    SUMMERDischarge

    VS

    (The screen filter is positioned upstreamfrom the wall pump if this pump does not

    accept the non-filtered water.)

    BA

    B

    C

    A

    C

    Floor

    Isolating valves

    Thermometer bags

    Adjusting valves

    ABC

    NOTE: the above piping diagram examples are indicative only and do not constitute installation details.

  • PIPING INSTALLATION EXAMPLE - ILG SERIES

    Isolating valves

    Thermometer bags

    Adjusting valves

    ABC

    Outdoorsensor

    Indoorsensor

    Floor

    Plancher

    Flexiblesleeves

    Optionalauxiliaryheating

    REGULATOR

    HYDRAULIC MODULE

    Safety valve+ manometer

    Filling

    Pump

    Internalcirculation

    pumpScreen

    filter

    Expansion vessel

    Screenfilter

    Safety valve+ manometer

    Filling

    Expansionvessel

    Buffer tank(option)

    Fillingproduct

    Geothermalsensor

    Return circuit

    Glycol water sensor under ground

    Inlet circuit

    BA

    B

    C

    A

    COOLING / HEATING FLOOR TERMINAL UNITSand / or

    NOTE: the above piping diagram examples are indicative only and do not constitute installation details.

    DYNACIAT LG

    22

    Water-cooled chillers

    AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

  • DYN

    AC

    IAT

    LG

    Water-cooled chillers

    23AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    DYNACIAT LG - LGP - ILG - LGN SERIES

    Installation recommendations

    Instructions for water quality criteriaWARNING: A water filter (800 microns) must be mounted on the unit inlet by the installer.Correct and specified operation along with the assurance of reasonable life expectancy from the chiller-heater is significantlydependent on the water circuits, especially if the water quality is allowed to cause scaling, corrosion, the formation of algae or the growth of micro-organisms.The water quality must be thoroughly analyzed to ensure that it is suitable for use on the machine, and to establish that chemical treatment will be sufficient to maintain water quality at acceptable levels and if it will be necessary to install asoftening/demineralisation process.This water analysis must establish the compatibility of the water used on the site with the following schedule of the different materials existing on the CIAT machine :- copper tubes 99.9% brazed with copper and silver filler,- depending on models, bronze threaded connexions or steal flange couplings,- exchangers with plates and connexions in stainless steal AISI 316 - 1.4401 brazed with copper and silver filler.

    Caution : if these instructions are not respected the warranty of the chiller will be voided.

    Lifting and handling operationsWork with the best safety conditions for people during the lifting and handling operations.Follow the lifting instructions provided on the machine and the Installation, Operating, Commissioning and Maintenanceinstructions manual to the letter.Plan properly to ensure an accessible route to the place of installation before moving the machine.Always lift the unit vertically, under no circumstances must the machine be bent or put in a horizontal position.

    Location of the machineDYNACIAT units are designed to be positioned indoor in a technical plant.Frost protection must be foreseen.Great attention must be paid to leaving necessary space for maintenance access to the unit, including at the top.The machine has to be mounted on a level, non combustible flat and horizontal floor with a foundation capable of supportingthe operation weight.Counter measures against the noise level of the auxiliaries, such as pumps, are recommended.Before installation, prevent, with the help of a sound specialist, the different possible sources of noise transmission, dependingon the machine room and its design.It is NECESSARY to fit the pipework with rubber expansion joints (optional equipment). Venting of technical plantIn accordance with the regulations on the installation site, a fresh air supply system may be installed to avoid dangerous situations or loss of comfort in the case of refrigerant leakage from the circuit of the machine.

    Installation of the accessoriesSeveral optional accessories can be delivered separately, to be mounted on the machine on site.Follow the instructions of the Installation, Operating, Commissioning and Maintenance manual to the letter.

    Field electrical wiringFollow the Installation, Operating, Commissioning and Maintenance instructions manual to the letter.All necessary instructions for electrical connections are detailed on the wiring diagrams attached to the unit.(They must be followed strictly)Connections must conform to good engineering practices and to norms and regulations in force.Field electrical wiring on site:

    . main electric power supply,

    . remote control of the machine (if necessary)

    . free contacts informations (optional).It is important to note that the unit is not protected against lightning transients on the electrical supply.Accordingly, the installation must be fitted with apparatus to give adequate transient protection, and such devices must beincorporated in the field power electric box.

  • 24

    DYNACIAT LG

    24

    Water-cooled chillers

    AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    Piping connections:Follow absolutely the Installation, Operating, Commissioning and Maintenance instructions manual to the letter.All piping shall be properly aligned and graded to a drain valve to permit complete drainage of the system. All pipes must beinstalled and connected to the machine ensuring that complete access for service is provided to all panels, then covered witha thermal insulation.Adequately support and brace the piping independently of the unit to avoid vibrations and strain on the piping connections.

    Isolating valves and manual valves for water flow adjustment must also be installed.- Field water connections required on site :. water supply of the pipes installation check-pressure reducing valve,. evaporator, condenser and water drain,- Provide the accessories necessary for all hydraulic circuits, for example :. a cooling water flow control valve, thermostatic type, mounted on the inlet side or outlet side of the condenser,. water expansion tank,. drain valves on pipes low points to extract all the water,. exchangers stop valves and water filter,. air purge valves on pipes top points,. check that there is a sufficient water volume in the installation (if necessary provide a storage tank),. rubber expansion joints on the exchangers inlet and outlet water side.. thermowells at each inlet and outlet connection for measurement during commissioning and maintenance procedure.Caution :- Water circuit pressure do not exceed 4.0 bar,- Expansion tank mounted before water pump,- Do not install any valve on the expansion tank.- Be sure to install the water circulating pumps immediately on the exchangers water inlet side.- Be sure that the water pressure at the suction of each circulating pump is equal or higher than the minimum pressure NPSHrequired, particularly in case of an "open" type circuit.- Referring to the technical conditions, the water quality criteria must be analyzed.- The frozen protection of the unit and the hydraulic piping is necessary, as is the possibility of a water drain of the circuit.

    In case of use of glycol for protection against freezing, it is absolutely necessary to check the physical properties andconcentration before commissioning.

    - Before making final connection to the chiller-heater, the piping must be flushed with clean water to remove debris in the circuit.

    Start upThe commissioning of DynaCiat machines must be made by CIAT or by a CIAT approved company.Follow the Installation, Operating, Commissioning and Maintenance instructions manual to the letter.Non exhaustive list of operations to be carried out during commissioning:- Check the correct location of the machine- Check the electrical supply protection. Check the phases and correct rotation direction- Check the electrical connections on the unit- Check the correct direction of water circulation on the unit- Check cleanliness of the water circuit- Adjust water flow to the specified value- Check the refrigeration circuit pressures- Check the correct direction of rotation of compressors- Check the water pressure drop and water flow- Complete running parameters check list

    Maintenance operationsThe machine requires specific routine maintenance operations which must be provided by authorized service agents agreed byCIAT.A report of the running parameters must be completed on a special "CHECK LIST" form which may be sent to CIAT.For this operation, refer to and follow the instructions of the Installation, Operating, Commissioning and Maintenanceinstructions manual to the letter.It is necessary to take out a maintenance contract of the unit with a specialist of refrigerating machines agreed by CIAT, including the period of warranty.

    DYNACIAT LGN SERIES Refrigeration connections- Follow the installation, Operating, Commissioning and Maintenance instructions manual to the letter.- The pipes must be in refrigerant quality copper and follow the state of the art.- As these units have been designed for connection to a removed condenser not supplied by CIAT, neither refrigerant

    connections nor commissioning will be carried out.- The pipe runs should be designed carefully and the requirements taken into consideration to facilitate the oil return to the

    compressor and pressure drops which can impair the performances.

  • DRYCOOLERSAIR COOLED CONDENSERS

    The CIAT drycoolers and air cooled condensers seriesEUROPA - AIRIAL are compatible with the DYNACIAT LG units with water cooled condensers orDYNACIAT LGN units without condenser.

    Available in a large choice of sizes and 6 ventilationspeeds, EUROPA and AIRIAL units are adapted to the dimensional or acoustic constraints of the site.

    DYN

    AC

    IAT

    LG

    Water-cooled chillers

    25AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

  • DYNACIAT LG

    26

    Water-cooled chillers

    AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    NOTES

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • DYN

    AC

    IAT

    LG

    Water-cooled chillers

    27AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.538 C

    NOTES

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • DYNACIAT LGWater-cooled chillers

    This document is non-contractual. As part of its policy of continual product improvement, CIAT reserves the right to make any technical modification it feels appropriate without prior notification.

    Head officeAvenue Jean Falconnier - B.P. 1401350 - Culoz - FranceTel: +33 (0)4 79 42 42 42 - Fax: +33 (0)4 79 42 42 10e-mail: [email protected] - www.ciat.com

    CCompagnie IIndustrielle dAApplications TThermiques - S.A. with a registered capital of 26 000 000 - R.C.S. Belley B 545 620 114

    CIAT ServiceTel.: +33 (0)4 79 42 42 90 - Fax: +33 4 79 42 42 13

    CONNECT CONTROL SYSTEM

    - LCD multilingual screen (2 lines of 20 characters)- Pressures and temperatures reading- Pump control- Communication

    Available free contacts :Inputs: - External ON/OFF contact

    - Setting selection- Cooling / heating selection- Compressors load shedding

    Outputs: - General fault of the unit

    MODBUS-JBUS open Protocol (standard)LONWORKS Protocol (option)

    RS 485 OUTPUT IN STANDARD

    F R E E C O N TAC T S R E L AY B O A R D ( O P T I O N )

    REMOTE CONTROL BOX (OPTION)Identical to the ergonomic interface

    Available outputs : - Water flow fault- Antifreeze fault- Pump fault- Fans fault- Low and high pressure fault- Compressors safety fault- Discharge temperature fault- Compressors running status

    ERGONOMIC INTERFACE PANEL

    OPTION FOR MANAGEMENT OF SEVERAL UNITSMULTICONNECT (kit delivered separately)Main available functions :

    - Management up to 8 units on the same water loop

    - Cooling or heating mode management- Management of chilled water or hot water

    pump- Management of safety unit- Load shedding of units- Time programming of the installation- Management of ice storage mode- Faults management of each unit- Balancing of the running time of each unit- MODBUS-JBUS R485 output for BMS connection

    allowing to get running and faults status of each unit