DX-2 Series - 4” Tube Heater Installation, Operation, Maintenance and Parts Manual*
DX-2 SeriesTable of Contents
Page
Models
Warnings
Clearances to Combustibles
Product Summary
Product Instructions
Heater Requirements
Theory of Operation
Wiring Diagrams
Flowchart
Parts Listing
Series Kit Contents
Models
1
2
2
3
3
4
4
5-7
8-9
10-11
12
Project: _______________________________ Date: ____________________
Location: _______________________________________________________
City:___________________________ State: _________ Zip: _____________
Contractor: ______________________________________________________
Engineer: _______________________________________________________
Local Representative: _____________________________________________
Customer Name: _________________________________________________
Address: ________________________________________________________
City:____________________________ State: _________ Zip: ____________
Serial #: ______________________________ Phone#:__________________
Date of Installation: _______________________________________________
Notes: __________________________________________________________
* For complete installation instructions, see Generic IOM this piece was inserted within. Also available at www.reverberray.com.
1. Register online at www.reverberray.com/warranty2. Complete the information above and fax to Detroit Radiant Products Co.3. Complete the information above and mail to Detroit Radiant Products Co.
Printed in U.S.A.© Detroit Radiant Products
21400 Hoover Rd., Warren, MI 48089T. (586) 756-0950 F. (586) 756-2626
Form# LIODX2-2M-9/02 (ID)
WarrantyRegistration
Options:
Model #Gas Type (circle one) BTU's Length Weight
Typical Mount Height
Combustion Chamber
Radiant Emitter Tube
"Type" Tube Pkg #1
"Type" Tube Pkg. #2
Baffle Pieces
DX-2 20-50 N or LP 50,000 21'-7' 120 # 10' - 15' Aluminized 4" Aluminized 20-4 Alum N/A 5DX-2 20-60 N or LP 60,000 21'-7' 120 # 11' - 16' Aluminized 4" Aluminized 20-4 Alum N/A 5DX-2 20-75 N or LP 75,000 21'-7' 120 # 12' - 18' Aluminized 4" Aluminized 20-4 Alum N/A 5DX-2 20-100 N or LP 100,000 21'-7' 120 # 13' - 20' Aluminized 4" Aluminized 20-4 Alum N/A 5DX-2 30-50 N or LP 50,000 31'-3' 160 # 10' - 15' Aluminized 4" Aluminized 30-4 Alum N/A 4DX-2 30-60 N or LP 60,000 31'-3' 160 # 11' - 16' Aluminized 4" Aluminized 30-4 Alum N/A 4DX-2 30-75 N or LP 75,000 31'-3' 160 # 12' - 18' Aluminized 4" Aluminized 30-4 Alum N/A 4DX-2 30-100 N or LP 100,000 31'-3' 160 # 13' - 20' Aluminized 4" Aluminized 30-4 Alum N/A 5DX-2 30-125 N or LP 125,000 31'-3' 160 # 15' - 25' Aluminized 4" Aluminized 30-4 Alum N/A 5DX-2 40-50 N or LP 50,000 40'-11' 190 # 10' - 15' Aluminized 4" Aluminized 40-4 Alum N/A 2DX-2 40-60 N or LP 60,000 40'-11' 190 # 11' - 16' Aluminized 4" Aluminized 40-4 Alum N/A 2DX-2 40-75 N or LP 75,000 40'-11' 190 # 12' - 18' Aluminized 4" Aluminized 40-4 Alum N/A 2DX-2 40-100 N or LP 100,000 40'-11' 190 # 13' - 20' Aluminized 4" Aluminized 40-4 Alum N/A 4DX-2 40-125 N or LP 125,000 40'-11' 190 # 15' - 25' Aluminized 4" Aluminized 40-4 Alum N/A 4DX-2 40-150 N or LP 150,000 40'-11' 190 # 16' - 30' Titanium 4" Aluminized 40-4 Titan N/A 4DX-2 40-175 N or LP 175,000 40'-11' 190 # 17' - 35' Titanium 4" Aluminized 40-4 Titan N/A 4DX-2 50-100 N or LP 100,000 50'-7' 235 # 13' - 20' Aluminized 4" Aluminized 40-4 Alum 10-4-Alum 2DX-2 50-125 N or LP 125,000 50'-7' 235 # 15' - 25' Aluminized 4" Aluminized 40-4 Alum 10-4-Alum 4DX-2 50-150 N or LP 150,000 50'-7' 235 # 16' - 30' Titanium 4" Aluminized 40-4 Titan 10-4-Titan 4DX-2 50-175 N or LP 175,000 50'-7' 235 # 17' - 35' Titanium 4" Aluminized 40-4 Titan 10-4-Titan 2DX-2 50-200 N or LP 200,000 50'-7' 235 # 18' - 40' Titanium 4" Aluminized 40-4 Titan 10-4-Titan 2DX-2 60-125 N or LP 125,000 60'-3' 265 # 15' - 25' Aluminized 4" Aluminized 40-4 Alum 20-4-Alum 2DX-2 60-150 N or LP 150,000 60'-3' 265 # 16' - 30' Titanium 4" Aluminized 40-4 Titan 20-4-Titan 2DX-2 60-175 N or LP 175,000 60'-3' 265 # 17' - 35' Titanium 4" Aluminized 40-4 Titan 20-4-Titan 2DX-2 60-200 N or LP 200,000 60'-3' 265 # 18' - 40' Titanium 4" Aluminized 40-4 Titan 20-4-Titan 2DX-2 70-175 N or LP 175,000 69'-11" 300 # 17' - 35' Titanium 4" Aluminized 40-4 Titan 30-4-Titan 2DX-2 70-200 N or LP 200,000 69'-11" 300 # 18' - 40' Titanium 4" Aluminized 40-4 Titan 30-4-Titan 2DX-2 80-200 N or LP 200,000 79'-7" 330 # 18' - 40' Titanium 4" Aluminized 40-4 Titan 40-4-Titan 2
This heater must be installed and serviced by trained gas installation and service personnel only!Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death.Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.Protect yourself and others by observing all safety information. Retain instructions for future reference.
! WARNING:
-
0 MOUNTING ANGLE
TOP
BELOW
SIDE SIDE
0 W/1 SIDE SHIELD
BELOW
TOP
FRONT BEHIND
TOP
BELOW
TOP
BELOW
0 W/2 SIDE SHIELDS
45 MOUNTING ANGLE
SIDE
FRONT
SIDE
BEHIND
DX-2 Series - 4” Tube Heater Installation, Operation, Maintenance and Parts Manual
DX-2 Series
2
SIDEFRONT BEHIND
DX-2 (20,30,40)-50 [N,P] 0º 9 9 6 4745º 39 8 10 47
W/1 side shield 0º 29 8 6 47W/2 side shields 0º 9 9 6 4720 ft from burner 0º 7 7 6 30
DX-2 (20,30,40)-60 [N,P] 0º 9 9 6 4745º 39 8 10 47
W/1 side shield 0º 29 8 6 47W/2 side shields 0º 9 9 6 4720 ft from burner 0º 7 7 6 30
DX-2 (20,30,40)-75 [N,P] 0º 9 9 6 6045º 39 8 10 60
W/1 side shield 0º 29 8 6 60W/2 side shields 0º 9 9 6 6020 ft from burner 0º 7 7 6 30
DX-2 (20,30,40,50)-100 [N,P] 0º 14 14 6 6645º 39 8 10 66
W/1 side shield 0º 29 8 6 66W/2 side shields 0º 16 16 6 6620 ft from burner 0º 7 7 6 30
DX-2 (30,40,50,60)-125 [N,P] 0º 20 20 6 7645º 58 8 10 76
W/1 side shield 0º 42 8 6 76W/2 side shields 0º 20 20 6 7620 ft from burner 0º 7 7 6 30
DX-2 (40,50,60)-150 [N,P] 0º 24 24 6 8145º 58 8 10 81
W/1 side shield 0º 42 8 6 81W/2 side shields 0º 23 23 6 8120 ft from burner 0º 11 11 6 44
DX-2 (40,50,60,70)-175 [N,P] 0º 34 34 6 9245º 63 8 10 92
W/1 side shield 0º 50 8 6 92W/2 side shields 0º 30 30 6 9220 ft from burner 0º 11 11 6 44
DX-2 (50,60,70,80)-200 [N,P] 0º 41 41 6 9445º 63 8 10 94
W/1 side shield 0º 54 8 6 94W/2 side shields 0º 30 30 6 9420 ft from burner 0º 11 11 6 44
CLEARANCES TO COMBUSTIBLES (IN.)
MODEL NO.MOUNTING
ANGLETOP BELOW
Failure to comply with the stated clearancesto combustibles could result in personal injury,death and/or property damage.
This heater should be installed so that theminimum clearances to vehicles, as markedon the heater, will be maintained. If vehiclelifts are present, ensure that these clearanceswill be maintained from the highest raisedvehicle.
! ��������
! ��������
! ��������
! ��������
! ��������
NOT FOR RESIDENTIAL USE!Do not use in the home, sleeping quarters,
attached garages, etc.
This heater must be installed and serviced bytrained gas installation and service personnelonly. Read and understand these instructionsthoroughly before attempting to install, operateor service this heater. Failure to comply couldresult in personal injury, asphyxiation, death,fire, and/or property damage. Retain theseinstructions for future reference.
This is not an explosion-proof heater. Wherethere is the possibility of exposure to flammablevapors, consult the local fire marshal, the fireinsurance carrier and other authorities forapproval of the proposed installation.
In locations used for the storage of combustiblematerials, signs must be posted to specify themaximum permissible stacking height tomaintain the required clearances from theheater to the combustibles. Signs must eitherbe posted adjacent to the heater thermostatsor in the absence of such thermostats in aconspicuous location.
! ��������
-
3
DX-2 Series - 4” Tube Heater Installation, Operation, Maintenance and Parts Manual
DX-2 Series Mechanical Instructions
This supplement is designed to address the specifics of the DX-2 Series - See page 12 for specific product features.
Aluminized
Aluminized
Aluminized or Titanium
Aluminized or Titanium
Aluminized or Titanium
Aluminized
Aluminized
Aluminized
Aluminized
Aluminized
Aluminized
Aluminized
Aluminized
Aluminized Aluminized
Aluminized
Aluminized Aluminized
Aluminized
Aluminized
B
B
B
B
B
*
*
*
*
*
(50-100 MBTU/H)
(50-125 MBTU/H)
(50-125 MBTU/H) (150-200 MBTU/H)
(50-125 MBTU/H) (150-200 MBTU/H)
(50-125 MBTU/H) (150-200 MBTU/H) Aluminized or Titanium
B
Aluminized Aluminized Aluminized Aluminized Aluminized Aluminized
*
(50-125 MBTU/H) (150-175 MBTU/H)
Product Summary
DX-2 Series heaters are available from 20 to 80 foot, 50,000 to 200,000 BTU’s, natural or propane gas. DX-2 Series are positivepressure, single stage heaters and feature coated aluminized steel for it’s radiant pipes. DX-2 Series may also be upgraded tostainless steel for harsh environment applications.
Operational Features
DX-2 Series heaters include a gas cock, flex connector and all hanging accessories. Most importantly, these heaters featurecoated aluminized heat exchangers covered by highly polished aluminum reflectors for maximum efficiency. These heaters alsofeature operational indicator lights, potted circuit boards, hot surface ignition and turbulator baffles (for improved efficiencies).
Specific Mechanical Instructions
Be sure to indentify the titanium (150-200 MBTU/H) combustion chamber and place as the first tube section directly followingthe burner box. The identification sticker found on the swagged end of the tubing will identify the titanium combustion tube.
175,000 and 200,000 BTU/H models must be installed with a stainless steel tube clamp at the second joint of the exchangerbetween the first and second radiant tubes.
Note baffle quantities for your model and place baffles in the last tubes (farthest from the burner) as shown below and on pages13-14 of the generic IOM.
Tube Installation Sequence
B = Burner Location Baffle Location*
-
4
DX-2 Series - 4” Tube Heater Installation, Operation, Maintenance and Parts Manual
DX-2 Series
Theory of OperationElectrical Requirements
♦ 120 Volt - 60 HZ♦ Starting Current 4.8 Amps♦ Running Current 1.1 Amps
Gas Requirements
♦ Manifold Pressure • Nat. 3.5’’ • LP. 10.0’’♦ Minimum Inlet Pressure • Nat. 5.0’’ • LP. 11.0’’♦ Maximum Inlet • Nat. 14.0’’ • LP. 14.0’’
Ventilation Requirements
♦ Consult the generic supplement for ventinginstructions.
♦ For unvented operation, there must be a positiveair displacement of at least 4.0 CFM per 1000BTU/H for natural gas or 4.5 CFM per 1000BTU/H for LP gas. WVE-4 termination cap mustalso be used.
· Starting Circuit
When voltage is applied to L1 and L2 (see diagramon right), a circuit is completed from L1 via theblower motor to L2. The blower fan is mounted inthe control box and rated to supply sufficient air forcombustion.
Air pressure generated by the blower will causethe normally open burner pressure switch No. 1 toclose. Another circuit is completed from L1 to thehot surface ignition control and back to L2. Thereis a five second delay, then the glo-bar is pow-ered. After the glo-bar has been powered for 45seconds, the control causes the gas valve to openand initiates the ignition trial.
Power to the glo-bar is shut off during the last twoor three seconds of the ignition trial.
· Running Circuit
After ignition, the flame rod monitors the flame. Aslong as a flame is present, the valve is held open.If the flame is lost, the control acts to close the valvewithin one second, and a new trial sequenceidentical to that at start-up is initiated. If proof offlame is not established within 8.5 seconds, theunit will lock out. If lockout occurs, the control canbe reset by briefly interrupting the power source.
-
A B
C D
FLAME
W R W
BK
BK
BK
L2
BLOWER W
120VAC
L1
BK
BK
BK
2C
GAS VALVE
OFF
NO
P
C
M
3
1
2
3P BK
SWITCHESPRESSURE
LIGHTSINDICATOR
M 1
BK W
MARK 17DU-117
MODULEIGNITION
BR
NEUT
GNDG
VALVENEUTTHLINE1SIC1PROBE
IGNITOR
BK
ROD
BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105 C.IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST
LADDER DIAGRAM - MARK17DU-117 WITH LIGHTS
BLOCK DIAGRAM - MARK17DU-117 WITH LIGHTS
R
W
BKTERMINAL BLOCK
IGNITOR
BK
BK O
LIN
E1
IGNITION MODULE
PR
OB
EBR
SIC
1BK
NE
UT
NE
UT
VA
LV
E
TH GN
D
W
PRESSURE SWITCHES
BK
120VACL1
BK
BK
O
BLOWER
BURNER
G
W
L2
BK
INDICATOR LIGHTS
GAS VALVE
BK
BK
BK
5
DX-2 Series - 4” Tube Heater Installation, Operation, Maintenance and Parts Manual
Internal Wiring Diagrams
Standard Diagrams
-
6
DX-2 Series - 4” Tube Heater Installation, Operation, Maintenance and Parts Manual
DX-2 SeriesField Wiring Diagrams
L2
L1
HEATER BURNER BOX
HEATER BURNER BOX
HEATER BURNER BOX
Common required for thermostats that require constant power.
BY OTHERS
B
RG
NOTE: This transformer relay will handle up to 3 tube heaters per branch (6 tube heaters total).
TO HEATER BRANCH #2
TO HEATER BRANCH #1
POLE #2
POLE #1
24V 24V
115V
115V
115V
W
L1
L2
WHITE
WHITE
VIOLET
BLACK
RED
RED/YELLOW
COIL
W
G
Y C
R
W
R 8285 Transformer Relay - Used in conjunction with any low voltage T-stat (i.e. XL411, T8600) when wiring tube heaters.
NOTE: Brown and Yellow wires are normally not used.
24V T-Stat & Connection for Single/Multiple Heaters - Relay Transformer Required
For multiple heater connection
FIELD WIRING INSTRUCTIONS
HEATER BURNER BOX
HEATER BURNER BOX
HEATER BURNER BOXT-stat
L2
L1
GRD
NC
COM
115V
NOTE: Up to 4 line voltage tube heaters can be wired to most T-stats (consult amp ratings of t-stat). Heaters on same vent must share the same t-stat.
120V Field Wiring For Single/Multiple Line Voltage Heaters
For multiple heater connection
-
�
����
���������
� �
�
��
�
�
��
��
��
��
�������������
�����
��������
���
����
����
����
��
����
���
�����
�
�������������������������������������
��������������
�� ������
���
���
�� �
�� ��
���
����
������
�������
��
������
�������
���
����
�����������
���������������������������������������������
��
��
��
�������
�
������
�
��
�������
��
���
��������������
��������������������������������������
�
���
����������
�������
��
��
��
��������������
��
��
�
��
��
���
��
��
��
��
��
�
�
��
��
�
�
�
�
��
�������
��
��
�����
�
�
�
�������
��
��
��
��
������
�������
���
7
DX-2 Series - 4” Tube Heater Installation, Operation, Maintenance and Parts Manual
Alternative Wiring Diagrams
For 24VAO (Internal Relay Option)
DX-2 Series Ladder Diagram (with optional 24VAO relay installed)
DX-2 Series Block Diagram (with optional 24VAO relay installed)
-
8
DX
-2 Series - 4” Tube H
eater Installation, Operation, M
aintenance and Parts M
anual
Is the inlet or the outletof the unit obstructed
(i.e. ice, birds nest, dirt)?
NO Check for loose wiring orresistance in hose connection topressure switch. Are they ok?
NO
Remove obstruction.
The heater is equipped with 2 safety pressureswitches. The burner switch in the blower
compartment is a normally open switch and theexhaust switch in the gas valve compartment is
a normally closed switch. Temporarily placejumpers across the terminals of each switch,one at a time. (Be sure to reinstall the cover.)
Does the light energize?
YES
YES
Replace burned out light.
NO
YES
Replace the appropriate switch afterverifying the following:
* Baffle(s) is in the tube(s) farthest from the burner.* Heater, fan blower, squirrel cage, intake and exhaust are clean and free from dirt and obstructions.* The 4” air intake pipe does not exceed 20 feet and/or 2 elbows.* There is not a negative pressure experienced at the area of air intake (i.e. attic space, high-winds, very tight building).
If any of the previous were occurring,please address the problem.
Turn up thermostat
Does the fanturn on?
YES
YES
DX-2 Troubleshooting Flow Chart (models with indicator lights)NO
*
Does the ignitor warmup and glow red?
NO Is the ignitor physicallydamaged?
Check voltage at ignitorduring ignition sequence(usually 30-45 seconds
after power to the heater).Is it 120V?
NO
Replace circuit board.
NOReplace ignitor.
YES
Is resistance through theignitor 45-400S.
YES
Replace ignitor.
NO
Does valve lightcome on?
YES
NO Does burner ignite atall?
Replace faulty light.
NO The circuit board and/or wiring harnessmay be faulty and need to be replaced.
Does valve open?
YES
YES
NOCheck to make sure pressure is within
min. & max. inputs as indicated onAGA burner rating label. Are both ok?
NO Correct problem.
Replace valve.YES
WARNING: By-passing any switchis for testing purposes only. Do notleave switch by-passed during normaloperation or heater’s built-in safetymechanisms will be compromised.
Is the power at theheater 120V?
Is the blowerobstructed?
Is there 120Vcoming to the fan?
Find the source of theelectrical problem.
NOYES
NO
Correct wiring.
The fan is faulty andmust be replaced.
YES
NO
Remove obstruction& lubricate fan.
YES
NO Is the lightburnt out? Ifso, replace.
Does the switchlight energize?
Repair wiring.
YES
*
-
DX
-2 Series - 4” Tube H
eater Installation, Operation, M
aintenance and Parts M
anual
After ignitor iswarmed up, does gas
valve open?
YES
NO
Test for 120V at valveduring valve openingperiod (usually 30-45
seconds after power tothe heater). Is there
120V to valve?
NO
Possibly, the circuitboard and/or wiring
harness is faulty.These should be
replaced.
Check to make sure gas pressure iswithin minimum and maximum inputs,as indicated on AGA burner rating
label. Is gas pressure ok?
YES
Correctproblem.
NO
Replacegas valve.
YES
YES
Does the burnerignite?
NO Is the gas cock inthe ON position?
YESCheck to make sure gas pressure is
within minimum and maximum inputs,as indicated on AGA burner rating
label. Is gas pressure ok?
Correctproblem.
NO
Make sure gas lines werepurged of air.
YESYES
Does the burnerstay on?
NO Does the burner stay on forapprox. 8 seconds and then
shut off?
YES Is the heater properly grounded?Is the heater’s polarity correct?
YES With microammeter, check amperage at flamerod. Is it greater than 0.7 microamps?
YES
Check to make sureflame sensor wire isok and then replace
circuit board.
NO
Sensing rod is faulty or flame isweak. Check to make sure heater
is operating at proper gaspressure as indicated on AGA
burner rating label and thenreplace sensing rod if needed.
NO
Correct problem.
NO
Does the burnercome on and then
turn off immediately(1 or 2 seconds).
YES
Check to make sure that the pressure iswithin minimum and maximum inputs asindicated on the AGA burner ratinglabel. Is gas pressure ok?
Correctproblem.
NO
Exhaust pressureswitch may be
faulty or there is arestriction in the
exhaust.
YES
YES
NO
The following can cause theheater to shut down:
* Improper grounding* High winds
* Taking combustion air fromthe attic
* Dirty environment* Baffle not located properly* Fluctuating gas pressure
Does heater stay onuntil call for heat ends?
YES
Troubleshooting ends.
WARNING: By-passing any switchis for testing purposes only. Do notleave switch by-passed during normaloperation or heater’s built-in safetymechanisms will be compromised.
9
*
-
26E
17
329
Com
bust
ion
Cha
mbe
r
351A
209P
209
65I
303
328
302
352A
56C
70
221
202
60F
61B
218
220
304
12
19B
20C
33B
26B
26A
57A
56C
201
21B
222
205
11
223
7621
2
31B
83
217
50
301
5
55A
208
204
200A
31B
68A
122
4466
67
9
10
1
106
105
82
26D
26A
60G
20D
61C
61D
220
Emitt
er T
ube(
s)
DX-2 Series - 4” Tube Heater Installation, Operation, Maintenance and Parts Manual
DX-2 Series
10
Parts Breakdown
-
11
DX
-2 Series - 4” Tube H
eater Installation, Operation, M
aintenance and Parts M
anual
Basic P
arts List
DX-2 SERIES PARTS LISTING
TP-1 CONTROL BOX COVER TP-82 REFLECTOR CENTER SUPPORTTP-5 FLANGE GASKET TP-83 STAINLESS STEEL FLEX CONNECTORTP-9 CONDUIT COUPLING TP-105 REFLECTOR END CAP TP-10 CONDUIT 4" X 1/2" TP-106 REFLECTOR CLIP TP-11 GLO-BAR IGNITOR BOX TP-108 5' AL-TI TUBE, PAINTED WITH ONE CLAMPTP-12 GLO-BAR IGNITOR BOX COVER TP-111 5' ALUM. TUBE, PAINTED WITH ONE CLAMPTP-17 SIGHT GLASS KIT TP-112 5' REFLECTORTP-19B WIRE HANGER W/ SPRING CLIP TP-122 GASKET FOR AIR ORIFICE & AIR COLLARTP-20C 120" ALUMINUM REFLECTOR TP-200A BURNER (50 TO 100 MBTU/H)TP-20D 120" STAINLESS STEEL REFLECTOR TP-201 BURNER (125 TO 200 MBTU/H)TP-21B TUBE CLAMP TP-202 16'' BURNER TUBE WITH FLANGETP-26A 10 FT. ALUM. RADIANT/COMBUSTION TUBE TP-204 GAS ORIFICE - CONSULT FACTORYTP-26B 10 FT. TITANIUM COMBUSTION TUBE TP-205 GLO-BAR HOLDER TP-26D 10 FT. 304 STAINLESS RADIANT TUBE TP-208 "Z" MOUNTING BRACKET TP-26E 10 FT. 409 STAINLESS STEEL COMBUSTION TUBE TP-209 36E36A-246 GAS VALVE - NAT GAS ASSYTP-31B CONTROL BOX BRACKET TP-209P 36E36A-240 GAS VALVE - LP GAS ASSYTP-33B 1/2" GAS COCK TP-212 1/2" X 3" PIPE NIPPLE TP-44 AIR ORIFICE W/SCREEN - CONSULT FACTORY TP-217 PRESSURE BARB FITTING TP-50 GLO-BAR IGNITOR TP-218 EXHAUST PRESSURE TUBE (VINYL)TP-55A FAN BLOWER TP-220 STAIN. STL. TUBE CLAMP (175 & 200 MBTU/H)TP-56C 1/4" ATMOSPHERIC TUBE (VINYL) TP-221 GLO-BAR HOLDER GASKET TP-57C 1/4" PRESSURE SENSING TUBE (VINYL) TP-222 FLAME RODTP-60F EXHAUST P.S. (50 TO 150 MBH) #PPS 10070-2553 TP-223 GAS MANIFOLDTP-60G EXHAUST P.S. (175 & 200 MBH) #PPS 10070-2554 TP-301 DIVIDER PANEL W/ P.S. MOUNTING TABSTP-61B BURNER P.S. (50 TO 100MBH) #PPS 10069--2550 TP-302 LEFT END PANEL W/ LIGHT HOLESTP-61C BURNER P.S. (200 MBH) #PPS 10069--2552 TP-303 RIGHT END PANELS - NO HOLESTP-61D BURNER P.S. (125, 150, 175 MBH) #PPS 10069--2551 TP-304 CONTROL BOX TP-65I INTERLOCKING 33" BAFFLE SECTION TP-328 120V INDICATOR LIGHTTP-66 2" X 4" OUTLET BOX TP-329 1/4" NEUTRAL TERMINAL BLOCKTP-67 2" X 4" OUTLET BOX COVER TP-330 DIVIDER GROMMETTP-68A STRAIN RELIEF BUSHING TP-331 GREEN SELF TAP GROUND SCREWTP-70 CONTROL BOX COVER GASKET (PER FOOT**) TP-351A MARK 17DU-117 POTTED CIRCUIT BOARDTP-76 RUBBER GROMMET TP-352A LONG WIRING HARNESS FOR 17DU-117
Part # Description Part # Description
**6” TOTAL NEEDED TO COVER OUTER EDGES OF BURNER BOX (TP-70)
-
DX-2 Series - 4” Tube Heater Installation, Operation, Maintenance and Parts Manual
Kit Contents & Product Features
12
Product Features
Kit contents for the DX-2 Series are shown below. Reference the proper column for your particular models length.
4 " H a n g e rTP -1 9 B
Ga s C o ck1 /2 " TP-3 3 B
4 " Bu tt C la m pTP-2 1 B
Generic IOMLIOM-Tube
ANDSeries InsertLIOM-DX-2
Reflector EndCaps TP-105
Notes *One 4” stainless steel butt clamp is provided for each175,000-200,000 BTU model. Place as shown in IOM.
4” Reflector CenterSupport TP-82
APPROVALS• CSA.• Indoor/Outdoor approval.• Commercial/Industrial approval.
BURNER SIGHT GLASS• For burner inspection.
COMBUSTION AIR INLET & VENT• 4” Male duct.
ENAMELED CONTROL BOX• Outside air collar (4”) attached.• Totally enclosed components.
CONTROLS• 100% safety shut off.• Moisture and corrosion resistant
ignition module.• Dual differential pressure switches.• Silicon carbide hot surface igniter.• Flame rod sensing.• Pre-purge controls.
EMMITER & COMBUSTION TUBES• 16ga. 4” O.D. coated aluminized steel.• All tubes coated with high temperature,
corrosion resistant black coating .95emissivity. Slip fit connection.
• Coated, titanium combustion chamber(150-200 MBTU/H models).
GAS CONNECTION• 1/2” gas cock included.• 7/8” flare-2’ S.S. flex included.
WARRANTY *• 1 year - Burner box components.• 5 years - Combustion and radiant tubes.• 10 years - Stainless steel burner.* See cover for warranty registration information.
OTHER• Stainless steel upgrade available for
harsh environments.• One reflector center support per heater.• Turbulator baffle included.• Visit www.reverberray.com• Made in U.S.A.
Bag of ReflectorEnd Cap Clips.
TP-10624" SS Flex
Connect TP-83
FILLED BY: TP# DESCRIPTION 20 FOOT 30 FOOT 40 FOOT 50 FOOT 60 FOOT 70 FOOT 80 FOOT
TP-19B 4" Hangers 3 4 5 6 7 8 9TP-21B 4" Tube Clamps 2 3 4 5* 6* 7* 8*TP-33B 1/2" Gas Cock 1 1 1 1 1 1 1TP-82 4" Refl. Cntr. Sprt. 2 3 4 5 6 7 8TP-83 24" SS Flex Line 1 1 1 1 1 1 1TP-105 Refl. Endcaps 2 2 2 2 2 2 2TP-106 Refl. Endcap Clips 8 8 8 8 8 8 8IOM Install / Op Manual 1 1 1 1 1 1 1SS ADD ON When Applicable
DX-2 SERIES KIT CONTENTS
Stainless Steel upgrades are noted in the bottom row when applicable.*175, 200 Models to have one TP-21B upgraded to Stainless Steel