DVMFeatures• Built-inselectorswitch
• Easy-to-read,14.2mmdigitdisplay
• DINsizecasing
Technical Data
Auxiliary supply : 198 ~ 265 V AC : 94 ~ 127 V ACVA rating : 3 VAInput frequency : 47 ~ 66 HzMaximum input voltage : 500 VrmsApproximateweight :0.6kg
Digital Power M
eterAux Supply
AC 240 V
DVM360 Series
62 3 4 5
L1
L2
L3
N
7 8 9 10 11 12
1
Typical Application Diagram
Aux SupplyAC 240 V
DVM100 Series
62 3 4 5
7 8 9 10 11 12
1
L
N
Case Dimensions
96 m
m
96 mm
Front
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Panel Cutout
91.5 mm
87 mm
Side
Ordering Information
DVM360-240A Auxiliaryvoltage240VACDVM100-240A Auxiliaryvoltage240VACDVM360-110A Auxiliaryvoltage110VACDVM100-110A Auxiliaryvoltage110VAC
MODEL DESCRIPTION
DVM
DAMFeatures• Built-inselectorswitch
• Easy-to-read,14.2mmdigitdisplay
• DINsizecasing
• Wideselectionofcurrenttransformer(CT) ratio
Technical Data
Auxiliary supply : 198 ~ 265 V AC : 94 ~ 127 V ACVA rating : 3 VAInput frequency : 47 ~ 66 HzMaximum input : 6 A continuousAmmeter CT ratio : .../5 AClass : 1.0Approximateweight :0.7kg
Aux SupplyAC 240 V
DAM330 / 3000 Series
62 3 4 5
L1
L2
L3
7 8 9 10 11 12
1
Typical Application Diagram
Aux SupplyAC 240 V
DAM100 / 1000 Series
62 3 4 5
7 8 9 10 11 12
1
L
N
Case Dimensions
96 m
m
96 mm
Front
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Panel Cutout
91.5 mm
87 mm
Side
Digital Power M
eterDAM
For primary current from 60 A to 500 A
DAM330-XXXXDAM100-XXXX
Order number
Example: ModelDAM330-0060 fordigital ammeter with CT ratio 60 / 5 A.
0060
ORDER NUMBERModel DAM 330 & DAM 100
*CT RATIO
60 / 5 A
0100 100 / 5 A
0150 150 / 5 A
0200
0250
0300
0400
0500
200 / 5 A
250 / 5 A
300 / 5 A
400 / 5 A
500 / 5 A
For primary current from 600 A to 5000 A
DAM3000-XXXXDAM1000-XXXX
Order number
600
ORDER NUMBERModel DAM3000 & DAM1000
*CT RATIO
600 / 5 A
800 800 / 5 A
1000 1000 / 5 A
1200
1500
1600
2000
2400
1200 / 5 A
1500 / 5 A
1600 / 5 A
2000 / 5 A
2400 / 5 A
2500 2500 / 5 A
3000 3000 / 5 A
3200 3200 / 5 A
3500 3500 / 5 A
4000 4000 / 5 A
4500 4500 / 5 A
5000 5000 / 5 A
*CT : Current Transformer For other CT ratio, please contact
the manufacturer.
DAM330-xxxx-240A
MODEL DESCRIPTION
Auxiliary voltage 240 V AC
DAM100-xxxx-240A Auxiliary voltage 240 V AC
DAM330-xxxx-110A Auxiliary voltage 110 V AC
DAM100-xxxx-110A Auxiliary voltage 110 V AC
DAM3000-xxxx-240A Auxiliary voltage 240 V AC
DAM1000-xxxx-240A Auxiliary voltage 240 V AC
DAM3000-xxxx-110A Auxiliary voltage 110 V AC
DAM1000-xxxx-110A Auxiliary voltage 110 V AC
DAM330
MODEL/ SERIES
DAM3000
DAM100
WITHSELECTOR
WITHOUTSELECTOR
A
UNIT
A
A
A
DISPLAYFORMAT
DAM1000
Ordering Information
Digital Power M
eterDAM
DPM680FeaturesMeasurement Parameters: •Phase&LineVoltages(L-N)•PhaseCurrent&NeutralCurrent•BidirectionalkW,kVAR&kVA•BidirectionalkWh,kVARh&kVAh•Frequency•Total&DisplacementPowerFactor•VoltageTotalHarmonicDistortion•CurrentTotalHarmonicDistortion•ThermalCurrentDemand•PowerDemand•CurrentSequenceComponents•VoltageSequenceComponents
TFT Colour LCD Display SerialRS-485ModbusRTUModbus TCP/IPBuilt-inWebserverVoltage & Current Waveform DisplayVoltage & Current Harmonics Display
Digital Power M
eter
Technical Data
WIRING SYSTEMS3-phase4-wiresystem3-phase3-wiresystem
CURRENT MEASUREMENT (TRMS) Nominal current : 5 A Min. measurement : 5 mA Accuracy : 0.2% of full scaleBurden : < 0.05 VA at 5 AMeasurement range : 10 APulsed withstand : 100 A for 1 secCT primary : 5 ~ 50,000 A
VOLTAGE MEASUREMENT (TRMS) Nominal phase voltage : 0 ~ 300 V AC Minimum measurement : 10 V Accuracy : 0.2% at full scalePhase voltage via VT : 60 ~ 50,000 V
POWER MEASUREMENT Real power, apparent power, reactive power Accuracy : 0.5%
POWER FACTOR MEASUREMENT Total and displacement power factor Accuracy : 0.5%
POWER & THERMAL CURRENT DEMANDInterval : 1 ~ 30 mins
VOLTAGE AND CURRENT SEQUENCECOMPONENTSPositive, negative and zero sequence
FREQUENCY MEASUREMENT Measurement range : 45 ~ 65 Hz Accuracy : 0.2%
ENERGY MEASUREMENT ACCURACYActive :IEC62053-22class0.5Reactive :IEC62053-23class2
HARMONICS DISPLAY Fundamental up to 32nd order
VOLTAGE & CURRENT WAVEFORMDISPLAY Simultaneous3-phasevoltageorcurrent waveforms
COMMUNICATIONProtocol : Modbus RTU Interface : Isolated RS485
Protocol : Modbus TCP/IPInterface : Ethernet 10M/100M BaseT
Protocol : HTTP ServerInterface : Ethernet 10M/100M BaseT
AUXILIARY POWER SUPPLY AC voltage : 90 ~ 415 V AC Frequency : 50 / 60 Hz DC voltage : 100 ~ 300 V DC Power consumption : 3W typicalSustained overload : 500 V AC
ENVIRONMENTAL CONDITIONSOvervoltage category : IVPollution degree : 2Operatingtemperature :-10˚C~+55˚CStoragetemperature :-20˚C~+70˚CHumidity : 0 – 95%,
non condensing
MECHANICAL Mounting : according to DIN 43700 /
ANSI C39.1Dimension (mm) : 96(w) x 96(h) x 100(d) Enclosure protection : IP63 at the panel
IP20 at the bodyApproximateweight:0.5kg
DPM 680
Ordering Information
Test Standards
DPM680-415AD AuxiliaryVoltage90~415VACor100 ~ 300 V DC
Safety requirements.
EMC requirements.
MODEL DESCRIPTION
IEC 61010-1
IEC 61326-1
Case DimensionsTypical Application Diagrams
101.6±0.5mm
91±0.5mm
91±0.5mm
Cut-Out Recommendations
Digital Power M
eter
3-PHASE 4-WIRE SYSTEM : 4 CTs, Direct V Input
3-PHASE 3-WIRE SYSTEM : 3 CTs, 3 VTs 3-PHASE 3-WIRE SYSTEM : 3 CTs, Direct V Input
3-PHASE 4-WIRE SYSTEM : 3 CTs, Direct V Input
L3
L2
L1
S2
S1
S2
S1
S2
S1
l3
GND
l2
l1
S2
S1ln
Ln
L3L2L1 Ln90~415 V AC /100~300 V DCAUX
RS 485Modbus-RTU
Ethernet
L3
L2
L1
S2
S1
S2
S1
S2
S1
l3
GND
l2
l1
S2
S1ln
Ln
L3L2L1 Ln90~415 V AC /100~300 V DCAUX
RS 485Modbus-RTU
Ethernet
L3
L2
L1
S2
S1
S2
S1
S2
S1
l3
GND
l2
l1
S2
S1ln
Ln
L3L2L190~415 V AC /100~300 V DCAUX
RS 485Modbus-RTU
GND
Ethernet
L3
L2
L1
S2
S1
S2
S1
S2
S1
l3
l2
l1
S2
S1ln
Ln
L3L2L190~415 V AC /100~300 V DCAUX
RS 485Modbus-RTU
Ethernet
GND
LOAD
LOAD
LOAD
LOAD
Front
Rear
Side
96 mm
83 mm
17 mm
100 m
m
96 mm
90 mm
86 mmea
DPM 680
DPM380DPM380B
FeaturesLCDdisplaywithbacklighting
Modbus-RTUcommunication
(for DPM380 only)
MEASUREMENT PARAMETERS:•PhaseVoltage(L-N)
•LineVoltage(L-L)
•PhaseCurrentandNeutralCurrent
•BidirectionalkW(perphase&total)
•BidirectionalkVAR(perphase&total)
•BidirectionalkVA(perphase&total)
•Frequency
•PowerFactor(perphase&total)
•Energy(+and-)forkWh,kVARhandkVAh
•THDPhaseVoltage(L-N)
•THDPhaseCurrent
•ActivePowerDemand
Technical Data
DISPLAY TYPELCD display
MEASUREMENTS3-phase4-wiresystem3-phase3-wiresystem
CURRENT MEASUREMENT (TRMS)CT primary : 5 ~ 8000 ACT secondary : 5 AMinimum measurement : 5 mAAccuracy : 0.5% from 1A to 6 A (secondary)Burden : < 0.05 VA at 5 ASustained overload : 6 A
VOLTAGE MEASUREMENT (TRMS)Nominal phase voltage : 20 ~ 300 V AC Minimum measurement : 10 V Accuracy : 0.5% at full scalePhase voltage via VT : 60 ~ 33,000 V
POWER MEASUREMENTReal power, apparent power, reactive power measurementMeasuring updating period : 1 sAccuracy : 1.0%
ACTIVE POWER DEMANDInterval : 1 ~ 30 mins
POWER FACTOR MEASUREMENTTotal and displacement power factor Accuracy : 1.0%
FREQUENCY MEASUREMENT Measurement range : 45 ~ 65 HzMeasurement updating period : 1sAccuracy : 0.5%
ENERGY ACCURACYActive(accordingtoIEC62053-21) :class1Reactive(accordingtoIEC62053-23):class2
AUXILIARY POWER SUPPLYAC voltage : 90 ~ 415 V ACFrequency : 50 / 60 HzDC voltage : 100 ~ 300 V DCPower consumption : <3 VA
COMMUNICATIONHardware interface : Isolated RS485Protocol :Modbus-RTUBaud rate : 2400, 4800, 9600, 19200, 38400
ENVIRONMENTAL CONDITIONSOperatingtemperature :-10˚C~+55˚CStoragetemperature :-20˚C~+70˚CHumidity : 0 – 95%,
non condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 100(d) Approximateweight :0.5kg
Digital Power M
eterDPM
380 / 380B
Typical Application Diagram
Ordering Information
Electromagnetic Compatibility (EMC)
DPM380-415AD AuxiliaryVoltage90~415VACor100 ~ 300 V DC, with RS 485DPM380B-415AD AuxiliaryVoltage90~415VACor100 ~ 300 V DC
Immunity for industrial environments.
Emission standard for industrial environments.
MODEL DESCRIPTION
Part 6-2: Generic Standards IEC61000-6-2
Part 6-4: Generic Standards IEC61000-6-4
L3
L2
L1
S2
S1
S2
S1
S2
S1
l3
GND
l2
l1
S2
S1ln
Ln
L3L2L1 Ln90~415 V AC /100~300 V DCAUX
RS 485Modbus-RTU
* For DPM380 only
+
-
GND
3-PHASE 4-WIRE SYSTEM WITH 4 CTs CONNECTION
LOAD
L3
L2
L1
S2
S1
S2
S1
S2
S1
l3
GND
l2
l1
S2
S1ln
Ln
L3L2L1 Ln90~415 V AC /100~300 V DCAUX
3-PHASE 4-WIRE SYSTEM WITH 3 CTs CONNECTION
RS 485Modbus-RTU
* For DPM380 only
+
-
GND
LOAD
Case Dimensions
Front
Rear
Side
96 mm
83 mm
17 mm
100 m
m1
96 mm
90 mm
86 mm
86 mm
ea
101.6±0.5mm
91±0.5mm
91±0.5mm
Cut-Out Recommendations
Digital Power M
eterDPM
380 / 380B
DM38FeaturesLCDdisplaywithbacklighting
Modbus-RTUcommunication
DIN rail type
MEASUREMENT PARAMETERS:•PhaseVoltage(L-N)
•LineVoltage(L-L)
•PhaseCurrent
•BidirectionalkW(perphase&total)
•BidirectionalkVAR(perphase&total)
•BidirectionalkVA(perphase&total)
•Frequency
•PowerFactor(perphase&total)
•Energy(+and-)forkWh,kVARhandkVAh
•THDPhaseVoltage(L-N)
•THDPhaseCurrent
Technical Data
DISPLAY TYPELCD display
MEASUREMENTS3-phase4-wiresystem
CURRENT MEASUREMENT (TRMS)CT primary : 5 ~ 8000 ACT secondary : 5 AMinimum measurement : 10 mAAccuracy : 0.5% from 1A to 6 A (secondary)Burden : < 0.03 VA at 5 ASustained overload : 6 A
VOLTAGE MEASUREMENT (TRMS)Nominal phase voltage : 70 ~ 300 V AC Minimum measurement : 10 V Accuracy : 0.5% at full scale
POWER MEASUREMENTReal power, apparent power, reactive power measurementMeasuring updating period : 1 sAccuracy : 1.0%
POWER FACTOR MEASUREMENTTotal and displacement power factor Accuracy : 1.0%
FREQUENCY MEASUREMENT Measurement range : 45 ~ 65 HzMeasurement updating period : 1sAccuracy : 0.5%
ENERGY ACCURACYActive(accordingtoIEC62053-21) :class1Reactive(accordingtoIEC62053-23):class2
POWER SUPPLYSelf supplied : 100 ~ 240 V ACFrequency : 50 / 60 HzPower consumption : <3 VA
COMMUNICATIONHardware interface : Isolated RS485Protocol :Modbus-RTUBaud rate : 2400, 4800, 9600, 19200, 38400
ENVIRONMENTAL CONDITIONSOperatingtemperature :-10˚C~+55˚CStoragetemperature :-20˚C~+70˚CHumidity : 0 – 95%,
non condensing
MECHANICALMounting : DIN railDimension (mm) : 65(w) x 85(h) x 50(d)Approximateweight : 0.3kg
Digital Power M
eterDM
38
Digital Power M
eter
65 mm
85 mm
45.5 mm
71 mm
Front
15.5 mm
50 mm
Side
Case Dimensions
Typical Application Diagram
1 2 3 4 5 6
S1 S2 S1 S2 S1 S2
7 8 9 10 11
12 13 14 15 16 17 18 19 20 21 22
LnL3L2L1
RS 485Modbus-RTU
NOTE: Current transformer secondaryterminal MUST NOT be earthed.
S1P1
P2S2 DM38
120 Ohm
I1 I2 I3
L3L1 L2 Ln
DM 38 CONNECTION DIAGRAM
!X
+-GN
D
LOAD
Ordering Information
Electromagnetic Compatibility (EMC)
DM38-240A SelfPowered100~240VAC
Immunity for industrial environments.
Emission standard for industrial environments.
MODEL DESCRIPTION
Part 6-2: Generic Standards IEC61000-6-2
Part 6-4: Generic Standards IEC61000-6-4
DM 38