dv/dt filters dv sentry - westek · ld harmonic filters ... enclosed -40c to 50c open -40c to 60c...

8
Product Selector Power quality. Solved. mtecorp.com dV Sentry dV/dt Filters The dV Sentry™ is like nothing you’ve seen before. Our latest patented* technological innovation has made the dV Sentry the revolutionary solution for motor protection. With its patented design, the dV Sentry is the first proven filter that provides common mode reduction, peak voltage protection and rise time reduction – all in one unit. This gives greater motor protection over time. It features a small footprint and easy terminations to make installation faster and easier. Plus, it runs quietly and radiates less heat than previous filters. The dV Sentry is unique, and when it comes to motor protection, there is nothing better. The future is here. Line Side Ln Load Side Ld Harmonic Filters Matrix ® AP Line Reactors SineWave Guardian Filters dV Sentry Filters Load Reactors Motor Protection Utility Power Motor VFD US. Patent # 7,768,373

Upload: others

Post on 10-Sep-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: dV/dt Filters dV Sentry - Westek · Ld Harmonic Filters ... Enclosed -40C to 50C Open -40C to 60C Warranty THREE years from the date of shipment Common Mode Reduction Rise Time Reduction

Product Selector

Power quality. Solved.

mtecorp.com

dV Sentry™

dV/dt Filters

The dV Sentry™ is like nothing you’ve seen before. Our latest patented* technological innovation has made the dV Sentry the revolutionary solution for motor protection. With its patented design, the dV Sentry is the first proven filter that provides common mode reduction, peak voltage protection and rise time reduction – all in one unit. This gives greater motor protection over time. It features a small footprint and easy terminations to make installation faster and easier. Plus, it runs quietly and radiates less heat than previous filters. The dV Sentry is unique, and when it comes to motor protection, there is nothing better.

The future is here.

Line Side

LnLoad Side

LdHarmonic Filters

Matrix® AP

Line Reactors

SineWave Guardian™ Filters

dV Sentry™ Filters

Load Reactors

Motor Protection

Utility Power Motor

VFD

US. Patent # 7,768,373

Page 2: dV/dt Filters dV Sentry - Westek · Ld Harmonic Filters ... Enclosed -40C to 50C Open -40C to 60C Warranty THREE years from the date of shipment Common Mode Reduction Rise Time Reduction

The unique design of the dV Sentry allows for greater load side protection from voltage spikes and common mode voltage for your AC motors, cable and VFDs.

Patented design provides over 50% common mode reduction, peak voltage protection, and rise time reduction - all in one filter.

Low watts loss reduces heating in systems.

Small footprint, with a unique flat design, allows filter to be easily integrated.

Strong robust design allows the filter to withstand installation and other difficult environments.

Runs quieter, comparable to a normal conversation.

dV Sentry™

dV/dt Filters

With the patented dV Sentry™, you get the most advanced motor protection in its class.

mtecorp.com

We know power quality, because

power quality is all we do.

Altitude Derating Curve

Altitude (feet)

Cur

rent

Der

atin

g Fa

ctor

dV Sentry Filter Current Derating

For Drive Output Frequency

Output Drive Frequency Hertz

Cur

rent

Der

atin

g Fa

ctor

Panel Design

Page 3: dV/dt Filters dV Sentry - Westek · Ld Harmonic Filters ... Enclosed -40C to 50C Open -40C to 60C Warranty THREE years from the date of shipment Common Mode Reduction Rise Time Reduction

dV Sentry™

Common Mode Reduction:

With dV Sentry

Without dV Sentry

Peak Rise Protection:

With dV Sentry

Without dV Sentry

Rise Time Reduction:

With dV Sentry

Without dV Sentry

Performance Specifications:Input Voltage 380V - 600V, 50/60Hz

Current Range 3A - 600A

Available Form FactorsPanelNEMA 1/2NEMA 3R

Max Peak motor Voltage150% of DC bus voltage at 1000 feet

Rise Time Less than 0.1uS

Insertion LossNo more than 1.7% at 60HzNo more than 2.6% at 90Hz

Intermittent Current Ratings150% continuous RMS (1 minute)200% continuous RMS (10 seconds)

Carrier Frequency Range3A - 110A: 900Hz -10kHz (up to 14kHz with derating)130A - 600A: 900Hz - 5kHz

Motor FrequencyUp to 90Hz without de-ratingUp to 120Hz with de-rating

Agency Approvals UL, cUL, CE, and RoHS

Motor Audible Noise Less than 65dB

Service TemperaturesEnclosed -40C to 50COpen -40C to 60C

WarrantyTHREE years from the date of shipment

CommonMode

Reduction

Rise Time Reduction

PeakVoltage

Protection Modular Design

Page 4: dV/dt Filters dV Sentry - Westek · Ld Harmonic Filters ... Enclosed -40C to 50C Open -40C to 60C Warranty THREE years from the date of shipment Common Mode Reduction Rise Time Reduction

mtecorp.com

380VMotor

KW

480VMotor

HP

550-600VMotor

HP

Amps Ratting

OPEN Resistors

Part NumberWeight (lbs.)

Open (in.) (H X W X D)

Ref. Fig.

Watts Loss

ResistorResistor Size

(in.) (H X W X D)Ref. Fig.

0.5-1.1 0.5-1.5 0.5-2 3 DVSP0003E 7 9.1 x 6.7 x 7.7 2 227 - - -

1.5 2 3 4 DVSP0004E 7 9.1 x 6.7 x 7.7 2 227 - - -

2.2-3 3 5 7 DVSP0007E 7 9.1 x 6.7 x 7.7 2 227 - - -

4 5 7.5 9 DVSP0009E 7 9.1 x 6.7 x 7.7 2 227 - - -

5.5 7.5 10 12 DVSP0012E 7 9.1 x 6.7 x 7.7 2 227 - - -

7.5 10 15 17 DVSP0017E 8 9.1 x 6.7 x 7.5 2 334 - - -

11 15 20 22 DVSP0022E 11 9.1 x 6.7 x 8.2 2 278 - - -

- 20 25 27 DVSP0027E 11 9.1 x 6.7 x 8.2 2 267 - - -

15 25 30 35 DVSP0035E 15 12.0 x 9.0 x 7.9 3 260 - - -

18.5-22 30 40 45 DVSP0045E 15 12.0 x 9.0 x 7.9 3 219 - - -

- 40 50 55 DVSP0055E 22 12.0 x 9.0 x 8.2 3 297 - - -

30 50 60 65 DVSP0065E 31 12.0 x 9.0 x 11.0 3 376 - - -

37 60 75 80 DVSP0080E 30 12.0 x 9.0 x 11.0 3 336 - - -

45-55 75 100 110 DVSP0110E 32 12.0 x 9.0 x 11.0 3 363 - - -

- 100 125 130 DVSP0130E 51 13.5 x 13.6 x 7.9 4 393 RESPANEL-012 18.4 x 5.0 x 7.0 1A

75-90 125 150 160 DVSP0160E 69 13.5 x 13.6 x 9.0 4 412 RESPANEL-012 18.4 x 5.0 x 7.0 1A

110 150 200 200 DVSP0200E 69 13.5 x 13.6 x 9.0 4 449 RESPANEL-012 18.4 x 5.0 x 7.0 1A

132 200 250 250 DVSP0250E 89 15.0 x 15.1 x 10.3 4 550 RESPANEL-013 18.4 x 5.0 x 7.0 1A

160 250 300 305 DVSP0305E 94 15.2 x 15.1 x 10.4 4 616 RESPANEL-013 18.4 x 5.0 x 7.0 1A

185-200 300 350 365 DVSP0365E 124 15.1 x 15.1 x 11.8 5 703 RESPANEL-013 18.4 x 5.0 x 7.0 1A

- 350 450 415 DVSP0415E 124 15.1 x 15.1 x 11.8 5 703 RESPANEL-013 18.4 x 5.0 x 7.0 1A

250 400-450 500-550 515 DVSP0515E 157 14.9 x 15.1 x 13.3 5 1027 RESPANEL-014 18.4 x 5.0 x 7.0 1B

315 500 600 600 DVSP0600E 164 15.1 x 15.1 x 13.4 5 1062 RESPANEL-014 18.4 x 5.0 x 7.0 1B

Selection Tables: Select filters based on Full Load Amps (FLA) of the motor. If the FLA is greater than the current rating of the filter, use the next larger filter. Note: Resistors always included with purchase. No need to purchase separately.

Load Side

Ld

Note: Information is for reference only. Consult www.mtecorp.com for detailed information.

Page 5: dV/dt Filters dV Sentry - Westek · Ld Harmonic Filters ... Enclosed -40C to 50C Open -40C to 60C Warranty THREE years from the date of shipment Common Mode Reduction Rise Time Reduction

dV Sentry™

Load Side

LdSelection Tables: Select filters based on Full Load Amps (FLA) of the motor. If the FLA is greater than the current rating of the filter, use the next larger filter. Note: Resistors always included with purchase. No need to purchase separately.

Note: Information is for reference only. Consult www.mtecorp.com for detailed information.

Amps Ratting

NEMA 1/2

Part NumberWeight (lbs.)

Size (In.)(H X W X D)

EnclosureRef.Fig.

3 DVSG0003E 18 13.2 x 13.0 x 13.0 CAB-13V 6

4 DVSG0004E 18 13.2 x 13.0 x 13.0 CAB-13V 6

7 DVSG0007E 18 13.2 x 13.0 x 13.0 CAB-13V 6

9 DVSG0009E 18 13.2 x 13.0 x 13.0 CAB-13V 6

12 DVSG0012E 18 13.2 x 13.0 x 13.0 CAB-13V 6

17 DVSG0017E 19 13.2 x 13.0 x 13.0 CAB-13V 6

22 DVSG0022E 22 13.2 x 13.0 x 13.0 CAB-13V 6

27 DVSG0027E 22 13.2 x 13.0 x 13.0 CAB-13V 6

35 DVSG0035E 24 13.2 x 13.0 x 13.0 CAB-13V 6

45 DVSG0045E 24 13.2 x 13.0 x 13.0 CAB-13V 6

55 DVSG0055E 32 13.2 x 13.0 x 13.0 CAB-13V 6

65 DVSG0065E 40 13.2 x 13.0 x 13.0 CAB-13V 6

80 DVSG0080E 40 13.2 x 13.0 x 13.0 CAB-13V 6

110 DVSG0110E 43 13.2 x 13.0 x 13.0 CAB-13V 6

130 DVSG0130E 96 24.0 x 17.1 x 17.1 CAB-17V 7

160 DVSG0160E 112 24.0 x 17.1 x 17.1 CAB-17V 7

200 DVSG0200E 115 24.0 x 17.1 x 17.1 CAB-17V 7

250 DVSG0250E 164 33.9 x 18.3 x 20.9 CAB-17AP2 7

305 DVSG0305E 169 33.9 x 18.3 x 20.9 CAB-17AP2 7

365 DVSG0365E 199 33.9 x 18.3 x 20.9 CAB-17AP2 7

415 DVSG0415E 199 33.9 x 18.3 x 20.9 CAB-17AP2 7

515 DVSG0515E 323 51.3 x 27.7 x 24.9 CAB-26AP2 7

600 DVSG0600E 330 51.3 x 27.7 x 24.9 CAB-26AP2 7

NEMA 3R

Part NumberWeight (lbs.)

Size (In.)(H X W X D)

EnclosureRef.Fig.

DVSW0003E 26 15.5 x 10.9 x 12.0 CAB-10 8

DVSW0004E 26 15.5 x 10.9 x 12.0 CAB-10 8

DVSW0007E 26 15.5 x 10.9 x 12.0 CAB-10 8

DVSW0009E 26 15.5 x 10.9 x 12.0 CAB-10 8

DVSW0012E 26 15.5 x 10.9 x 12.0 CAB-10 8

DVSW0017E 27 15.5 x 10.9 x 12.0 CAB-10 8

DVSW0022E 29 15.5 x 10.9 x 12.0 CAB-10 8

DVSW0027E 29 15.5 x 10.9 x 12.0 CAB-10 8

DVSW0035E 32 15.5 x 10.9 x 12.0 CAB-10 8

DVSW0045E 33 15.5 x 10.9 x 12.0 CAB-10 8

DVSW0055E 75 24.0 x 12.5 x 22.9 CAB-12AP3 10

DVSW0065E 84 24.0 x 12.5 x 22.9 CAB-12AP3 10

DVSW0080E 84 24.0 x 12.5 x 22.9 CAB-12AP3 10

DVSW0110E 85 24.0 x 12.5 x 22.9 CAB-12AP3 10

DVSW0130E 138 33.9 x 18.3 x 26.0 CAB-17AP3 10

DVSW0160E 154 33.9 x 18.3 x 26.0 CAB-17AP3 10

DVSW0200E 157 33.9 x 18.3 x 26.0 CAB-17AP3 10

DVSW0250E 172 33.9 x 18.3 x 26.0 CAB-17AP3 10

DVSW0305E 176 33.9 x 18.3 x 26.0 CAB-17AP3 10

DVSW0365E 207 33.9 x 18.3 x 26.0 CAB-17AP3 10

DVSW0415E 207 33.9 x 18.3 x 26.0 CAB-17AP3 10

DVSW0515E 343 51.3 x 27.7 x 30.0 CAB-26AP3 9

DVSW0600E 350 51.3 x 27.7 x 30.0 CAB-26AP3 9

Page 6: dV/dt Filters dV Sentry - Westek · Ld Harmonic Filters ... Enclosed -40C to 50C Open -40C to 60C Warranty THREE years from the date of shipment Common Mode Reduction Rise Time Reduction

mtecorp.com

H

W D

H

WD

D

H

W

D

H

W

OPEN MAGNETICS

RESISTOR PANELFIGURE 1BFIGURE 1A

D

H

W

D

H

W

FIGURE 4

FIGURE 5

FIGURE 2

FIGURE3

Page 7: dV/dt Filters dV Sentry - Westek · Ld Harmonic Filters ... Enclosed -40C to 50C Open -40C to 60C Warranty THREE years from the date of shipment Common Mode Reduction Rise Time Reduction

Note: drawing dimensions are for reference only. See MTECORP.com for detailed information.

ENCLOSURES

dV Sentry™

H

W D

H

W D

FIGURE 10

FIGURE 6

FIGURE 9

FIGURE 7

FIGURE 8

NOTE: HOODS ONLY ON NEMA 3R ENCLOSURES

NOTE: HOODS ONLY ON NEMA 3R ENCLOSURES

HH

DW

W D

H

DW

H

Page 8: dV/dt Filters dV Sentry - Westek · Ld Harmonic Filters ... Enclosed -40C to 50C Open -40C to 60C Warranty THREE years from the date of shipment Common Mode Reduction Rise Time Reduction

MTE CorporationN83 W13330 Leon Road • Menomonee Falls, WI 53051 (800) 455-4MTE • (262) 253-8200 • mtecorp.com

Form DVS-PSL-E 10/14

© 2014 MTE Corporation Printed in U.S.A.

Power quality. Solved.

Simple, robust power quality solutions that are never over engineered.Power quality management requirements vary significantly. By utility. By industry. By application. By country. By site. That is why we offer a variety of power quality and filter products, for both input (line-side) and output (load-side) of Variable Frequency Drives (VFDs) and power conversion equipment. These components represent strategic parameters of power quality. We can provide you with a complete power quality solution.

mtecorp.com

Rl and RlW line/load Reactors help keep your equipment running longer by absorbing many of the power line disturbances which otherwise damage or shut down your inverters, variable speed controllers, or other sensitive equipment.

Line Side

Ln

Load Side

LdLine Side

LnLoad Side

Ld

Load Side

Ld

MATRIX® AP harmonic Filters can help ensure that your system meets the IEEE-519 requirements for harmonic current.

The dV Sentry™, with its patented Triple Defense Core, is our latest technological innovation and the only proven filter that provides commonmode reduction, peak voltage protection, and rise time reduction– all in one unit.

SineWave Filters transform the output of your VFD to a near perfect sinusoidal waveform for the best level of motor protection.

Supersedes DVS-PSL-E 09/14