duct testing quickie set-up guide. retrotec blower door duct tester dm-2 meter
TRANSCRIPT
Duct TestingQuickie Set-Up Guide
RetroTec Blower DoorDuct Tester
DM-2 Meter
Color CodedConnections
Retrotec DM-2 will work with all of these devices
Input B
Ref B
Ref A
Input A
Program your DM2 forDuct Tester (or Blower Door)
Turn Manometer ONPress On/Off button
Press Exit button
Set Up ManometerPress Setup buttonArrow up or down to Device Setup, then press Enter
Enable/disable DevicesHighlight with up down arrows, right arrow clicks yes/noDu 200 and/or 1000
can eliminate duct tester DU 200 for a dedicated blower door metercan eliminate blower door 1000 for a dedicated duct test meter
Hit EXIT once set up
Scroll and select Mode Set Up press EnterEnable/Disable different tests
Flow cfm @ 50 Pa should be active: to change scroll to test pressure then press Enter. Change to
desired pressure, then press Enter again.For Duct Tester change to 25 pa
Exit, Exit to get to the main screen
N = .60 ( located in Setup )
Time = 1 second ( toggle Time Avg button)
Zero = On ( toggle Auto Zero button)
• Meter always wants to go back to default screen, always just press Exit to return to previous screen
• You can change the Full Screen Timeout duration by pressing Setup and scroll down to Full Screen Timeout (15 seconds is a good start)
Check Devices Enabled• Toggle Device to see what is enabled
– Should display only the devices you want to use
• For Duct Test – Press Setup– Arrow up/down to Device Setup– Press Enter– Highlight Du 200 and click YES with right arrow– Press Exit – Select Mode Set UP– Press Enter– Set to 25 Pascals– Press Range/Config to select the plate install on fan
• Hint: to start your tests with a good guess at the correct Plate • use the “Mid” plate
Duct Testing
Enable the flow @ 25pa for Total Leakage duct test
Turn Off the @25 when doing Leakage to Exterior
Click @Pressure button to turn this function on and off
Retrotec Duct TestSet up for Duct Test
Press ONPress Exit (to continue)Pressure and Flow @ 25
Set Pressure (to 25 Pascals)Punch Buttons 2 and 5
Press Enter
Press Exit Twice (to Stop Test)
Yes for Duct Tester
NO for Blower Door
Makes your meter much easier to use
Press Mode• Shows two channels A&B• Toggle through Mode again to look at fields:– Channels A & B– Pressure / Flow– Air Changes/Hour + volume ft3
• Press @Pressure to get meter to convert and display CFM @25 for Ducts
• Reminder: Use actual 25 Pascal for Leakage to Exterior Test (Do Not use the @25 setting)
Automatic Run Recommended
Once equipment is set up and meter settings are correct, it is recommended to run the fan speed through manometer
Press Set PressureDuct Tester: Set to @25 Pa
Press EnterThe fan will respond automatically Be prepared!
Retrotec Duct TesterPlease confirm contents:
Meter Case DM-2 Meter Power Supply/Charger “Umbilical” Cord Useful Forms + Handouts Manual
Retrotec Duct TesterPlease confirm contents:
Large Case Fan + Duct Plates o Lowo Mid
Power Cord Tubing: Red, Green, Blue (and extras) Static Pressure Tap Bungee Cords Tube Fittings Duct Mask / Masking Tape
On-Site Equipment List Smoke Tube TEC Exhaust Flow Meter Pressure Pan Foam Blocks Flashlight / Headlight Cordless Drill + Bits + Extra Battery Screw Drivers Vise Grips/Wrench “Duct” Tape Leatherman/Knife + Cardboard Ladder / Stool Calculator + Camera Booties + Tyvek Suit Trash Bags + Paper Towels