DUAL POWER SUPPLY MODULE ATL DPS1
![Page 2: DUAL POWER SUPPLY MODULE ATL DPS1. P OWER SUPPLY SOLUTIONS FOR ATS CONTROLLER M72GB07_15 AUTOMATIC TRANSFER SWITCH CONTOLLER SOURCE 2 DIGITAL INPUT -](https://reader036.vdocuments.mx/reader036/viewer/2022082518/56649e7e5503460f94b81f02/html5/thumbnails/2.jpg)
POWER SUPPLY SOLUTIONS FOR ATS CONTROLLER
M72GB07_15
AUTOMATIC
TRANSFER
SWITCH
CONTOLLER
SO
UR
CE
2
DIG
ITAL IN
PU
T - O
UP
UT
AC
SUPPLY
SO
UR
CE
1
DC SUPPLY
ATL610 – ATL800 – ATL900
DUAL POWER SUPPLY MODULE
GG
BATTERY
THE PROBLEM:During the transfer from the source 1 to the source 2 and vice versa the auxiliary power supply must be selected from the most reliable source available.
DUAL POWER SUPPLY MODULE
THE SOLUTIONS:
• “Traditional”: a wired logic with two or more relays to select the available source
• DC supply: available with ATL610, ATL800, ATL900. The battery or the UPS connected provides safe and continuous control during the changeover from source 1 to source 2. The automatic transfer switch controller does not switch off in the event of instability both sources
• Dual power supply module ATLDPS1: a single and very compact device select, with a digital control, the best source to use.
2
![Page 3: DUAL POWER SUPPLY MODULE ATL DPS1. P OWER SUPPLY SOLUTIONS FOR ATS CONTROLLER M72GB07_15 AUTOMATIC TRANSFER SWITCH CONTOLLER SOURCE 2 DIGITAL INPUT -](https://reader036.vdocuments.mx/reader036/viewer/2022082518/56649e7e5503460f94b81f02/html5/thumbnails/3.jpg)
K1
K2 K1 K3
L
LLINE 2
N
LINE 1N
A1
14
K1
K3
K2
K3A2 K2 K2
1112
TRMS
K1
N
LOUT
Dual power supply controlled by voltage monitoring relay(two relays with electrical and mechanical interlock and a voltage monitoring relay )
Non-controlled dual power supply(two relays with electrical and mechanical interlock )
• Dedicated wiring• Additional relays• Dedicated space for devices and wiring• Low level of security
M72GB07_15
K1
K1K2
K2
K1 K1 K2 K2
L1 N1
N
L
L2 N2
OUT
POWER SUPPLY SOLUTIONS FOR ATS CONTROLLER – “TRADITIONAL” SOLUTION
DUAL POWER SUPPLY
3
DUAL POWER SUPPLY MODULE
![Page 4: DUAL POWER SUPPLY MODULE ATL DPS1. P OWER SUPPLY SOLUTIONS FOR ATS CONTROLLER M72GB07_15 AUTOMATIC TRANSFER SWITCH CONTOLLER SOURCE 2 DIGITAL INPUT -](https://reader036.vdocuments.mx/reader036/viewer/2022082518/56649e7e5503460f94b81f02/html5/thumbnails/4.jpg)
Dual power supply controlled by voltage monitoring relay
Non-controlled dual power supply
Control of motorised changeover switches
Control of motorised circuit breakers
M72GB07_15 4
DUAL POWER SUPPLY MODULE
![Page 5: DUAL POWER SUPPLY MODULE ATL DPS1. P OWER SUPPLY SOLUTIONS FOR ATS CONTROLLER M72GB07_15 AUTOMATIC TRANSFER SWITCH CONTOLLER SOURCE 2 DIGITAL INPUT -](https://reader036.vdocuments.mx/reader036/viewer/2022082518/56649e7e5503460f94b81f02/html5/thumbnails/5.jpg)
• Reduced wiring costs• Reduction of the components used• Reduction of the space used• Voltage inputs independent and isolated from each other• Secure transfer between the lines• Input and output lines constantly monitored• Two independent measuring circuits• Min and max thresholds managed by microcontroller • Digital thresholds independent from the supply voltage.
M72GB07_15
DUAL POWER SUPPLY MODULE
POWER SUPPLY SOLUTIONS FOR ATS CONTROLLER – “NEW” SOLUTION
5
DUAL POWER SUPPLY MODULE
![Page 6: DUAL POWER SUPPLY MODULE ATL DPS1. P OWER SUPPLY SOLUTIONS FOR ATS CONTROLLER M72GB07_15 AUTOMATIC TRANSFER SWITCH CONTOLLER SOURCE 2 DIGITAL INPUT -](https://reader036.vdocuments.mx/reader036/viewer/2022082518/56649e7e5503460f94b81f02/html5/thumbnails/6.jpg)
Control of motorised changeover switches
Control of motorised circuit breakers
M72GB07_15 6
DUAL POWER SUPPLY MODULE
![Page 7: DUAL POWER SUPPLY MODULE ATL DPS1. P OWER SUPPLY SOLUTIONS FOR ATS CONTROLLER M72GB07_15 AUTOMATIC TRANSFER SWITCH CONTOLLER SOURCE 2 DIGITAL INPUT -](https://reader036.vdocuments.mx/reader036/viewer/2022082518/56649e7e5503460f94b81f02/html5/thumbnails/7.jpg)
ATL DPS1
• Module dedicated to the control of the supply voltages of motorised circuit breakers and changeover switches
• The ATL DPS1 is able to measure and control the voltages present at its inputs by identifying the most suitable to be connected to the output
• Constant monitoring of the network status• Microcontroller based.
FEATURES• Voltage value selectable using a terminals bypass• Response thresholds of min and max voltage: 80%
and 120% of the nominal setting• 2 single phase inputs L+N• 1 single phase output L+N• Priority line L1• Using with motor supply at 110VAC or 230VAC• Range of input voltage : 80…264VAC• LED signal: abnormality, state of the inputs and
outputs• Frequency: 50/60Hz• Current output: 4A max• Fixed time delay between switching lines: 0.5s• Din rail mounting or with screw means extractable clip• Modular housing at 3 modules • Protection degree: IP40 on front, IP20 on the back• Temperature range: -30...+70°C• Certification: EAC - cULus pending.
M72GB07_15 7
DUAL POWER SUPPLY MODULE
![Page 8: DUAL POWER SUPPLY MODULE ATL DPS1. P OWER SUPPLY SOLUTIONS FOR ATS CONTROLLER M72GB07_15 AUTOMATIC TRANSFER SWITCH CONTOLLER SOURCE 2 DIGITAL INPUT -](https://reader036.vdocuments.mx/reader036/viewer/2022082518/56649e7e5503460f94b81f02/html5/thumbnails/8.jpg)
M72GB07_15
LOVATO Electric ABB SOCOMEC Characteristics ATLDPS1 ODPS230 ODPSE230C DPS Rated voltage 110VAC / 230VAC 230VAC 230VAC 230VAC Voltage inputs range 80...264VAC max 288VAC 220...240VAC 20% 180..288VAC Voltage inputs L-N L-N L-N L-N Frequency 50-60Hz 50-60Hz 50-60Hz 45-65Hz Rated voltage selection Terminals bypass - - -
Control thresholds applied80% and 120%
of the rated voltage set≥198VAC and ≤154VAC 80% and 120%
of the rated voltage set min voltage 200VAC
Type of control Microcontroller based Analog Analog Analog Priority line L1 L1 L1 L1 Operating transfer time 60ms max 1s ±0.5s 0.5s max ? Current output 4A 3.15A 4A 3.15A Fuse External External Internal replaceable Internal not replaceable Synoptic with led Input, output, alarm Input Input Input Output relay 1 NO 3A 250V~ 3A 30V= - - - Operating temperature -30 ... + 70°C -25…+60°C -25... +60°C ? Housing Modular DIN43880 housing
3-moduleDIN-rail or screw mounted
100x100x64mmDIN-rail or screw mounted
52x90x130mmModular DIN43880 housing
4-module
COMPETITORS
8
DUAL POWER SUPPLY MODULE
![Page 9: DUAL POWER SUPPLY MODULE ATL DPS1. P OWER SUPPLY SOLUTIONS FOR ATS CONTROLLER M72GB07_15 AUTOMATIC TRANSFER SWITCH CONTOLLER SOURCE 2 DIGITAL INPUT -](https://reader036.vdocuments.mx/reader036/viewer/2022082518/56649e7e5503460f94b81f02/html5/thumbnails/9.jpg)
www.LovatoElectric.com