DESCRIPTION
Battery charger DSETRANSCRIPT
053-049 ISSUE 12 DSE9000 Battery Charger Installation Instructions
D E E P S E A E L E C T R O N I C S
DANGER OF DEATH : LIVE PARTS exist within the DSE9000 enclosure. The enclosure cover must not be removed.
Installation The DSE9000 battery charger is designed to be mounted within a control panel, on the panel DIN rail utilising the integral mounts or on a chassis utilising the mounting holes. For dimension and mounting details, see overleaf. The DSE9000 battery charger is fit-and-forget. It can be permanently connected to the supply and the load, with no requirement to disable the charger during times of heavy load (such as engine cranking) or when in parallel with a charging alternator.
Battery suitability The charger is factory set by DSE to suit Lead Acid batteries. However 91XX / 92XX Series can be adjusted at the time of ordering to suit other battery types. Care should be taken to ensure the batteries connected to the charger are of the correct ‘technology’ to suit the setting of the charger.
Indications The DSE9000 Battery Charger features an LED indicator(s) to show Status.(see operators manual 057-085 for further information.)
Boost Mode (Not applicable to DSE9150 12V 2A or DSE9155 30V 2A) (DSE94XX Series Only. Boost feature is controlled automatically, no external connection needed.) Boost mode is operated by connecting the BOOST terminals together (for instance with an external switch or timer circuit. This will raise the battery charger floating voltage by 0.8V DC. Caution:- Boost mode is intended for equalisation of cells in lead acid batteries.
Dimensions and Mounting DSE9150 12V 2A Overall size 108mm x 101mm x 49mm
(4.25” x 3.98” x 1.91”) Weight 0.16kg Mounting type DIN rail or chassis mounting Din rail type EN 50022 35mm type only Mounting holes Suitable for M4 Mounting hole centres 91mm x 89mm (4.25” x 3.51”) Input voltage (nominal) 110V-240V Input voltage (absolute range)
90V-250V
Charge failure relay rating
3A DC resistive, 30V maximum
Operating Temperature -30°C to 55°C (-22°F to 131°F)
Dimensions in mm unless stated
Connection type Screw terminal, rising clamp, no internal spring
Min cable size 0.5mm² (AWG 20) Max cable size 2.5mm² (AWG 14) Recommended AC fuse DSE9130 12V 5A charger DSE9140 12V 10A charger DSE9150 12V 2A charger DSE9155 30V 2A charger DSE9250 24V 3.7A charger DSE9260 24V 10A charger DSE9255 24V 5A charger DSE9470 24V 10A charger DSE9480 12V 10A charger DSE9481 12V 5A charger DSE9472 24V 5A charger
230V AC Input 110V AC Input 1.0A anti-surge 2.0A anti-surge 1.0A anti-surge 1.0A anti-surge 1.0A anti-surge 3.5 A anti-surge 2.0A anti-surge 3.5A anti-surge 2.0A anti-surge 1.0A antisurge 2.0A antisurge
2.0A anti-surge 3.5A anti-surge 1.5A anti-surge 2.5A anti-surge 2.5A anti-surge 6.3A anti-surge 3.5A anti-surge 6.3A anti-surge 3.5A anti-surge 2.5A anti-surge 3.5A anti-surge
Typical Wiring Diagrams
Boost not available on DSE9150 12V 2A DSE9150 30V 2A
CF not available on DSE9150 12V 2A
DSE 94XX Series Battery Chargers
DSE 91XX / 92XX Series Battery Chargers
Automatic boost control on DSE9400 series chargers
Dimensions and Mounting DSE9130 12V 5A DSE9250 24V 3.7A * DSE9155 30V 2A DSE9255 24V 5A * This model is no longer available Overall size 136mm x 140mm x 63mm
(5.37” x 5.53” x 2.5”) Weight 0.5kg Mounting type DIN rail or chassis mounting Din rail type EN 50022 35mm type only Mounting holes Suitable for M4 Mounting hole centres
119.36mm x 128.36mm (4.7” x 5.05”)
Input voltage (nominal)
DSE9250-001 24V 3.7A DSE9250-002 24V 3.7A DSE9130 12V 5A DSE9255 24V 5A
110V-240V 110V-277V 110V-277V 110V-277V
Input voltage (absolute range)
DSE9250-001 24V 3.7A DSE9250-002 24V 3.7A DSE9130 12V 5A DSE9255 24V 5A
90V-265V 90V-305V 90V-305V 90V-305V
Charge failure relay rating
3A DC resistive, 30V maximum
Operating Temperature
-30°C to 55°C (-22°F to 131°F)
Dimensions in mm unless stated
Dimensions and Mounting DSE9140 12V 10DSE9260 24V 10A Overall size
WeightDSE9140 12V 10ADSE9260 24V 10AMounting typeDin rail typeMounting holesMounting hole centres
Input voltage (nominal)Input voltage (absolute range)Charge failure relay ratingOperating Temperature
Deep Sea Electronics Plc. Tel:+44 (0)1723 890099 Fax: +44 (0)1723 893303
Email: [email protected] Web: www.deepseaplc.com
Deep Sea Electronics inc. Phone: +1 (815) 316-8706 Fax: +1 (815) 316- 8708 TOLL FREE (USA only) :
Tel: 1 866 636 9703 Email: [email protected]
Web: www.deepseausa.com
with the terminal strips atwith the terminal strips atwith the terminal strips atwith the terminal strips at
NOTE : NOTE : NOTE : NOTE : This document is intended as a ‘quick start’ guide only.This document is intended as a ‘quick start’ guide only.This document is intended as a ‘quick start’ guide only.This document is intended as a ‘quick start’ guide only.
specifications, refer to operator manual DSE part number 057specifications, refer to operator manual DSE part number 057specifications, refer to operator manual DSE part number 057specifications, refer to operator manual DSE part number 057----085085085085
Dimensions and Mounting DSE9140 12V 10A DSE9260 24V 10A Overall size 152mm x 188mm x 62mm
(6” x 7.4”x 2.44”) Weight DSE9140 12V 10A DSE9260 24V 10A
0.75kg 0.85kg
Mounting type DIN rail or chassis mounting Din rail type EN 50022 35mm type only Mounting holes Suitable for M4 Mounting hole centres 142mm x 128mm
(5.59” x 5.0”) Input voltage (nominal) 110V-277V Input voltage (absolute range)
90V-305V
Charge failure relay rating 3A DC resistive 30V Maximum Operating Temperature -30°C to 55°C
(-22°F to 131°F)
Dimensions in mm unless stated
Dimensions and Mounting Intelligent Battery Chargers
DSE9481 12V 5A DSE9472 24V 5A
Overall size
Weight DSE9470DSE9472/80/81Mounting typeDin rail typeMounting holesMounting hole centres
Input voltage Input voltage (absolute range)Charge failure relay rating
Operating Temperature
Optional Temperature Sensor CommunicationsPC connection (USB)
6in 2.44in
7.4
in
NOTE : NOTE : NOTE : NOTE : DSE9000DSE9000DSE9000DSE9000 series cseries cseries cseries chargerhargerhargerhargers ares ares ares are designed to bedesigned to bedesigned to bedesigned to be mounted with the base to a vemounted with the base to a vemounted with the base to a vemounted with the base to a vewith the terminal strips atwith the terminal strips atwith the terminal strips atwith the terminal strips at the bottom.the bottom.the bottom.the bottom.
This document is intended as a ‘quick start’ guide only.This document is intended as a ‘quick start’ guide only.This document is intended as a ‘quick start’ guide only.This document is intended as a ‘quick start’ guide only. For full operating instructions and For full operating instructions and For full operating instructions and For full operating instructions and
085085085085
Dimensions and Mounting
Intelligent Battery Chargers
DSE9481 12V 5A DSE9472 24V 5A
DSE9480 12V 10A DSE9470 24V 10A
Overall size 205mm x 135mm x 80mm (8.1” x 5.3” x 3.1”)
DSE9470 472/80/81
0.78kg 0.7kg
Mounting type DIN rail or chassis mounting Din rail type EN 50022 35mm type only Mounting holes Suitable for M4 Mounting hole centres 190mm x 120mm
(7.5” x 4.7”) Input voltage (nominal) 110V-277V Input voltage (absolute range)
95V-305V
Charge failure relay rating 3A DC resistive 30V maximum
Operating Temperature -30°C to 85°C with de-rating (-22°F to 185°F)
Optional Temperature NTC connections for connection to PT1000 Sensor
Communications RS485. connection (USB) To enable Configuration Suite
PC Software changes.
Dimensions in mm unless stated
mounted with the base to a vemounted with the base to a vemounted with the base to a vemounted with the base to a verrrrttttiiiical surface cal surface cal surface cal surface