drawing index...server room hvac retrofit inyo annex building 168 n edwards st. independence, ca...

12
SERVER ROOM HVAC RETROFIT INYO ANNEX BUILDING 168 N EDWARDS ST. INDEPENDENCE, CA DRAWING INDEX VICINITY MAP SCOPE OF WORK MECHANICAL ENGINEER BRANDON ETCHEMENDY PE ETCHEMENDY ENGINEERING INC. 10597 DOUBLE R BOULEVARD RENO, NV 89521 775-853-1131 EXT. 221 [email protected] ELECTRICAL ENGINEER JAMES SOLARO PE JP ENGINEERING 10597 DOUBLE R BLVD. STE. 1 RENO, NV 89521 775-852-2337 [email protected] job number drawn checked 19030 01/10/20 DRAWING TITLE REVISIONS SERVER ROOM HVAC RETROFIT INYO ANNEX BUILDING 168 N EDWARDS ST. INDEPENDENCE, CALIFORNIA E T C H E M E N D Y E N G I N E E R I N G I N C 10597 DOUBLE R BLVD RENO, NV 89521 P. 775-853-1131 F. 775-852-2352 [email protected] date PERMIT SET 01/10/20 BAE T0.1IT TITLE PAGE SME BAE 2-19-2020

Upload: others

Post on 10-Mar-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DRAWING INDEX...SERVER ROOM HVAC RETROFIT INYO ANNEX BUILDING 168 N EDWARDS ST. INDEPENDENCE, CA DRAWING INDEX VICINITY MAP SCOPE OF WORK MECHANICAL ENGINEER BRANDON ETCHEMENDY PE

SERVER ROOM HVAC RETROFITINYO ANNEX BUILDING

168 N EDWARDS ST.INDEPENDENCE, CA

DRAWING INDEX

VICINITY MAP SCOPE OF WORKMECHANICAL ENGINEERBRANDON ETCHEMENDY PEETCHEMENDY ENGINEERING INC.10597 DOUBLE R BOULEVARD

RENO, NV 89521775-853-1131 EXT. [email protected]

ELECTRICAL ENGINEERJAMES SOLARO PEJP ENGINEERING10597 DOUBLE R BLVD. STE. 1RENO, NV [email protected]

job number

drawn

checked

19030

01/10/20

DRAWING TITLE

REVISIONS

SERVER R

OO

M H

VAC R

ETR

OFIT

INYO

AN

NEX B

UIL

DIN

G16

8 N

ED

WARD

S S

T.IN

DEPEN

DEN

CE, CALIF

ORN

IA

E T C H E M E N D YE N G I N E E R I N GI N C

10597 DOUBLE R BLVD RENO, NV 89521P. 775-853-1131 F. 775-852-2352

[email protected]

date

P

E

R

M

I

T

S

E

T

0

1

/

1

0

/

2

0

BAE

T0.1IT

TITLE PAGE

SME

BAE

2-19-2020

AutoCAD SHX Text
T0.1IT
AutoCAD SHX Text
TITLE PAGE
AutoCAD SHX Text
APPLICABLE CODES: CALIFORNIA MECHANICAL CODE 2016 CALIFORNIA MECHANICAL CODE 2016 CALIFORNIA PLUMBING CODE 2016 CALIFORNIA BUILDING CODE 2016 CALIFORNIA ELECTRICAL CODE 2016
AutoCAD SHX Text
WORK UNDER THIS CONTRACT: includes but is not limited to, all material, : includes but is not limited to, all material, labor, tools, expendable equipment, utility and transportation service, and all incidental items necessary to perform and complete the required Scope of Work in a workmanlike manner, complete and on schedule. A. The Work shall be performed in areas as shown on the attached drawings at The Work shall be performed in areas as shown on the attached drawings at Inyo Annex Server IT located at 168 N Edwards St. Independence, CA. B. The Scope of Work includes the following: The Scope of Work includes the following: 1. Demolition of diffusers and grilles in the Server Room. Demolition of diffusers and grilles in the Server Room. 2. Demolition of existing condenser and refrigerant piping located in Demolition of existing condenser and refrigerant piping located in outdoor mechanical patio. 3. Salvation of existing AC units located in Server. Salvation of existing AC units located in Server. 4. Demolition of an existing air handler (AC-2) Demolition of an existing air handler (AC-2) 5. Add alternate #1: Add alternate #1: a. Replacement of existing condenser in landscape area near mechanical patio. 6. Provide complete electrical demolition of existing equipment to be Provide complete electrical demolition of existing equipment to be removed. 7. Maintain circuit continuity of any branch circuit that is connected to Maintain circuit continuity of any branch circuit that is connected to equipment being removed. 8. Installation of new heat pumps, new air handlers and the install and Installation of new heat pumps, new air handlers and the install and routing of the refrigerant piping system. 9. Installation of new ductwork, supply air diffusers and return air grilles Installation of new ductwork, supply air diffusers and return air grilles for existing air handler. 10. Provide new Panel and feed from existing Panel. Provide new Panel and feed from existing Panel. 11. Provide new feeds for existing Panel. Provide new feeds for existing Panel. 12. Provide new electrical connections for new HVAC equipment Provide new electrical connections for new HVAC equipment 13. Provide new manual transfer switch Provide new manual transfer switch 14. Provide new temporary generator landing lugs. Provide new temporary generator landing lugs.
AutoCAD SHX Text
M0.1IT
AutoCAD SHX Text
MECHANICAL NOTES & SCHEDULES
AutoCAD SHX Text
M1.1IT
AutoCAD SHX Text
DEMOLITION MECHANICAL PLAN
AutoCAD SHX Text
M2.1IT
AutoCAD SHX Text
MECHANICAL PLAN
AutoCAD SHX Text
M3.1IT
AutoCAD SHX Text
MECHANICAL DETAILS
AutoCAD SHX Text
P1.1IT
AutoCAD SHX Text
P2.1IT
AutoCAD SHX Text
E0.1IT
AutoCAD SHX Text
SYMBOL LIST AND SPECIFICATIONS
AutoCAD SHX Text
E0.2IT
AutoCAD SHX Text
SINGLE LINE DIAGRAM
AutoCAD SHX Text
E1.1IT
AutoCAD SHX Text
ELECTRICAL DEMOLITION PLAN
AutoCAD SHX Text
E2.1IT
AutoCAD SHX Text
DEMOLITION PLUMBING PLAN
AutoCAD SHX Text
PLUMBING PLAN
AutoCAD SHX Text
ELECTRICAL PLAN
AutoCAD SHX Text
P0.1IT
AutoCAD SHX Text
PLUMBING NOTES & DETAILS
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
P
AutoCAD SHX Text
R
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
E
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
I
AutoCAD SHX Text
O
AutoCAD SHX Text
N
AutoCAD SHX Text
A
AutoCAD SHX Text
L
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
V
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
A
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
I
AutoCAD SHX Text
T
AutoCAD SHX Text
A
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
R
AutoCAD SHX Text
-
AutoCAD SHX Text
T
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
9
AutoCAD SHX Text
2
AutoCAD SHX Text
8
AutoCAD SHX Text
1
AutoCAD SHX Text
.
AutoCAD SHX Text
o
AutoCAD SHX Text
N
AutoCAD SHX Text
Exp 12-31-20
AutoCAD SHX Text
ETCHEMENDY
AutoCAD SHX Text
BRANDON A.
Page 2: DRAWING INDEX...SERVER ROOM HVAC RETROFIT INYO ANNEX BUILDING 168 N EDWARDS ST. INDEPENDENCE, CA DRAWING INDEX VICINITY MAP SCOPE OF WORK MECHANICAL ENGINEER BRANDON ETCHEMENDY PE

“ ”

M0.1IT

MECHANICALNOTES &

SCHEDULES

SME

job number

drawn

checked

19030

01/10/20

DRAWING TITLE

REVISIONS

SERVER R

OO

M H

VAC R

ETR

OFIT

INYO

AN

NEX B

UIL

DIN

G16

8 N

ED

WARD

S S

T.IN

DEPEN

DEN

CE, CALIF

ORN

IA

E T C H E M E N D YE N G I N E E R I N GI N C

10597 DOUBLE R BLVD RENO, NV 89521P. 775-853-1131 F. 775-852-2352

[email protected]

date

P

E

R

M

I

T

S

E

T

0

1

/

1

0

/

2

0

BAE

AutoCAD SHX Text
STANDARDS AND CODES: LATEST EDITION OF THE CALIFORNIA MECHANICAL CODE (CMC), AS WELL AS ALL APPLICABLE STATE AND LOCAL CODES AND ORDINANCES. THIS DOES NOT RELIEVE THE CONTRACTOR FROM FURNISHING AND INSTALLING WORK SHOWN OR SPECIFIED WHICH MAY EXCEED THE REQUIREMENTS OF SUCH ORDINANCES, LAWS, REGULATIONS AND CODES. COMPLETE INSTALLATION: PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, TOOLS, ACCESSORIES, ETC., NECESSARY TO ACCOMPLISH A COMPLETE MECHANICAL SYSTEM IN ACCORDANCE WITH THE PLANS TOGETHER WITH THE SPECIFICATIONS. PERMITS: OBTAIN AND PAY FOR ALL BUILDING AND WORKING PERMITS AND INSPECTION FEES REQUIRED FOR THIS PROJECT. DRAWINGS: DATA PRESENTED ON THESE DRAWINGS SHALL BE FIELD VERIFIED SINCE ALL DIMENSIONS, LOCATIONS, AND LEVELS ARE GOVERNED BY ACTUAL FIELD CONDITIONS. REVIEW ALL ARCHITECTURAL, STRUCTURAL, CIVIL, ELECTRICAL AND SPECIALTY SYSTEMS DRAWINGS AND ADJUST ALL WORK TO MEET THE REQUIREMENTS ON CONDITIONS SHOWN THEREON, DO NOT SCALE MECHANICAL PLANS FOR EQUIPMENT, DUCTING ,PIPING, APPLIANCE ETC. LOCATIONS. USE CONFIGURED DIMENSIONS IF GIVEN OR CHECK ARCHITECTURAL DRAWINGS. COPYRIGHT: THESE PLANS, SPECIFICATIONS AND ALL RELATED ADDENDA AND DOCUMENTS CONSTITUTE COPYRIGHT MATERIALS OF ETCHEMENDY ENGINEERING INC. ALL RIGHTS CONFERRED BY THE COPYRIGHT AND SIMILAR LAWS ARE RESERVED TO ETCHEMENDY ENGINEERING INC. THESE MATERIALS SHALL REMAIN THE SOLE PROPERTY OF ETCHEMENDY ENGINEERING INC. AND MAY NOT BE REPRODUCED, DISTRIBUTED TO OTHERS OR USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE PRIOR WRITTEN CONSENT OF ETCHEMENDY ENGINEERING INC. LOCATIONS: INDICATED LOCATIONS OF ALL EQUIPMENT, DUCTING ,PIPING ETC. ARE SUBJECT TO CHANGE. SHIFT/RELOCATE/RECONFIGURE ANY OR CONNECTION POINT UP TO 10' AS DIRECTED BY ENGINEER, AT NO ADDED COST. RECORD DRAWINGS: CONTRACTOR SHALL PROVIDE, PRIOR TO FINAL ACCEPTANCE AND OBSERVATION, ONE SET OF REVISED RECORD MECHANICAL CONSTRUCTION DOCUMENTS ON REPRODUCIBLE MEDIUM. INDICATING THE FOLLOWING ADDITIONAL INFORMATION: RECORD NOTATIONS SHALL BE CLEARLY DRAWN AT A DRAFTING APPEARANCE EQUAL TO THE ORIGINAL DRAWINGS. CONTRACTOR SHALL ALSO PROVIDE ALL OPERATING AND MAINTENANCE MANUALS PRIOR TO FINAL PAYMENT. EXAMINATION OF SITE AND EXISTING CONDITIONS: BEFORE SUBMITTING A PROPOSAL, CONTRACTOR SHALL EXAMINE THE SITE AND FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND LIMITATIONS. NO EXTRAS WILL BE ALLOWED BECAUSE OF THE CONTRACTOR'S MISUNDERSTANDING OF THE AMOUNT OF WORK INVOLVED OR HIS LACK OF KNOWLEDGE OF ANY SITE CONDITIONS WHICH MAY AFFECT HIS WORK. ANY APPARENT VARIANCE OF THE DRAWINGS OR SPECIFICATIONS FROM THE EXISTING CONDITIONS AT THE SITE SHALL BE CALLED TO THE ATTENTION OF THE ENGINEER BEFORE SUBMITTING A PROPOSAL. SEISMIC RESTRAINT: ALL BUILDING HVAC SYSTEMS, INCLUDING DUCTWORK, IS TO BE SEISMICALLY RESTRAINED PER THE UNIFORM MECHANICAL CODES, INTERNATIONAL BUILDING CODE, AMERICAN SOCIETY OF CIVIL ENGINEERS AND STRUCTURAL ENGINEERING INSTITUTE. RESTRAINT SYSTEMS ARE TO BE COMPLETED IN A “DESIGN BUILD” FASHION BY THE DESIGN BUILD” FASHION BY THE FASHION BY THE AWARDED CONTRACTOR AND ARE TO BE INCLUDED IN THE PROJECT BID. THE CONTRACTOR IS TO ENLIST A QUALIFIED LICENSED PROFESSIONAL TO PROVIDE COMPREHENSIVE DESIGN CALCULATIONS AND SHOP DRAWINGS FOR SAID SYSTEMS. ALL DESIGN DATA AND DETAILED DRAWINGS ARE TO BE PROVIDED TO THE ENGINEER AND AUTHORITY HAVING JURISDICTION FOR REVIEW AND APPROVAL DURING THE SUBMITTAL PROCESS. EXISTING CONDITIONS: ALL (E) SIZES AND LOCATIONS ARE APPROXIMATIONS AND ARE TO BE FIELD VERIFIED BY THE CONTRACTOR PRIOR COMMENCEMENT OF ANY WORK. NO ADDITIONAL FEES WILL BE ALLOWED DUE TO DUE LACK OF FIELD VERIFICATION. EQUIPMENT: ALL HVAC AND REFRIGERATION EQUIPMENT SHALL NOT CONTAIN CFC OR HALONS. DUCT LEAKAGE & VERIFICATION: ALL DUCT CONSTRUCTION SHALL COMPLY WITH TITLE 24 SECTION 120.4 & 141.0(B)2D FOR ALTERED SYSTEMS. DUCT LEAKAGE FOR ENTIRELY NEW OR REPLACEMENT DUCT SYSTEMS SHALL BE EQUAL TO OR LESS THN 6 PERCENT OF THE SYSTEM AIR HANDLER AIRFLOW. THIS IS TO BE CONFIRMED BY FIELD VERIFICATION AND DIAGNOSTIC TESTING BY THE AIR BALANCE CONTRACTOR. TESTING SHALL BE PER THE PROJECT SPECIFICATIONS (AABC CONTRACTOR) AND THE TITLE 24 NONRESIDENTIAL APPENDIX SECTION NA2.1.4.2.1 LISTINGS: ALL MECHANICAL EQUIPMENT AND DUCTWORK SHALL BE LISTED AND LABELED BY AN APPROVED AGENCY. INSTALLATION SHALL BE IN ACCORDANCE WITH APPROVED LISTING
AutoCAD SHX Text
GENERAL NOTES:
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
MODEL
AutoCAD SHX Text
CAPACITY
AutoCAD SHX Text
AIRFLOW
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
SPLIT SYSTEM INDOOR HEAT PUMP SCHEDULE
AutoCAD SHX Text
MIN OSA
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
WT (LBS)
AutoCAD SHX Text
MULTI-ZONE CEILING SUSPENDED HEAT PUMP AIR HANDLER
AutoCAD SHX Text
MITSUBISHI MODEL PCFY-P30NKMU-ER1.TH
AutoCAD SHX Text
208V, 1 , 1.22MCA, 15 MOCP
AutoCAD SHX Text
100
AutoCAD SHX Text
-
AutoCAD SHX Text
880 CFM
AutoCAD SHX Text
1, 2, 3
AutoCAD SHX Text
CLG: 20.3 MBH HTG: 27.4 MBH
AutoCAD SHX Text
AHU
AutoCAD SHX Text
1-3
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
MODEL
AutoCAD SHX Text
AIR COOLED VRF HEAT PUMP FOR AHUs 1-2
AutoCAD SHX Text
SPLIT SYSTEM OUTDOOR VRF HEAT PUMP WITH HEAT RECOVERY SCHEDULE
AutoCAD SHX Text
MITSUBISHI MODEL PUMY-P60NKMU2
AutoCAD SHX Text
208V, 1 36 MCA,45 MOCP
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
WEIGHT
AutoCAD SHX Text
370
AutoCAD SHX Text
CAPACITY
AutoCAD SHX Text
CLG: 40.5 MBH HTG: 38.2 MBH
AutoCAD SHX Text
SEER
AutoCAD SHX Text
20
AutoCAD SHX Text
SUCTION
AutoCAD SHX Text
LIQUID
AutoCAD SHX Text
34
AutoCAD SHX Text
38
AutoCAD SHX Text
HP
AutoCAD SHX Text
1
AutoCAD SHX Text
REMARKS: 1. LOW AMBIENT WITH WIND BAFFLE LOW AMBIENT WITH WIND BAFFLE 2. 4-PIPE HEADER, CMY-Y104C-G 4-PIPE HEADER, CMY-Y104C-G 3. JOINT PIPE, CMY-Y62-G-EJOINT PIPE, CMY-Y62-G-E
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
1, 3
AutoCAD SHX Text
REMARKS: 1. INTEGRAL CONDENSATE PUMP WITH OVERFLOW AND ALARM INTEGRAL CONDENSATE PUMP WITH OVERFLOW AND ALARM 2. WIRED THERMOSTAT WIRED THERMOSTAT 3. BV-BB BALL VALVESBV-BB BALL VALVES
AutoCAD SHX Text
HP
AutoCAD SHX Text
2
AutoCAD SHX Text
1, 2
AutoCAD SHX Text
MULTI-ZONE WALL MOUNT HEAT PUMP AIR HANDLER
AutoCAD SHX Text
MITSUBISHI MODEL PKFY-P12NHMU-E2
AutoCAD SHX Text
208V, 1 , 0.38MCA, 15 MOCP
AutoCAD SHX Text
40
AutoCAD SHX Text
-
AutoCAD SHX Text
370 CFM
AutoCAD SHX Text
1, 2, 3
AutoCAD SHX Text
CLG: 8.1 MBH HTG: 10.8 MBH
AutoCAD SHX Text
AHU
AutoCAD SHX Text
4
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
MODEL
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
ACCESSORIES
AutoCAD SHX Text
STEEL MODULAR CORE SUPPLY AIR DIFFUSER
AutoCAD SHX Text
AIR DISTRIBUTION SCHEDULE
AutoCAD SHX Text
-
AutoCAD SHX Text
20''x20''
AutoCAD SHX Text
KRUEGER MODEL S580P
AutoCAD SHX Text
FRAME
AutoCAD SHX Text
F23
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
24''x24''
AutoCAD SHX Text
FINISH
AutoCAD SHX Text
BRITISH WHITE
AutoCAD SHX Text
D
AutoCAD SHX Text
1
AutoCAD SHX Text
ABBREVIATION
AutoCAD SHX Text
DIFFUSER/GRILLE SYMBOL LEGEND
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
XXX
AutoCAD SHX Text
X
AutoCAD SHX Text
AIRFLOW QUANTITY-TYP
AutoCAD SHX Text
DISTRIBUTION PATTERN-TYP
AutoCAD SHX Text
TAG. SEE EQUIP. SCHEDULE-TYP
AutoCAD SHX Text
NUMBER -TYP
AutoCAD SHX Text
X
AutoCAD SHX Text
X
AutoCAD SHX Text
XXX
AutoCAD SHX Text
XXX
AutoCAD SHX Text
NOTE -TYP
AutoCAD SHX Text
NOTE-TYP (R) - RELOCATE (E) - EXISTING TO REMAIN (X) - DEMOLISH COMPLETE
AutoCAD SHX Text
EQUIPMENT SYMBOL LEGEND
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
INTENT
AutoCAD SHX Text
D
AutoCAD SHX Text
G
AutoCAD SHX Text
EXH
AutoCAD SHX Text
MVD
AutoCAD SHX Text
FLEX
AutoCAD SHX Text
RIGID DUCT
AutoCAD SHX Text
SUPPLY AIR
AutoCAD SHX Text
RETURN AIR
AutoCAD SHX Text
EXHAUST AIR
AutoCAD SHX Text
MANUAL VOLUME DAMPER
AutoCAD SHX Text
FLEXIBLE DUCTWORK
AutoCAD SHX Text
VERTICAL BRANCH WITH DAMPER
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
UP
AutoCAD SHX Text
PIPE DOWN
AutoCAD SHX Text
PIPE UP
AutoCAD SHX Text
AutoCAD SHX Text
(N)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
AFF
AutoCAD SHX Text
BFF
AutoCAD SHX Text
TYP
AutoCAD SHX Text
MIN
AutoCAD SHX Text
DIAMETER ROUND
AutoCAD SHX Text
NEW
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
BELOW FINISHED FLOOR
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
MINIMUM
AutoCAD SHX Text
BTU, BTUH
AutoCAD SHX Text
MBH
AutoCAD SHX Text
CFM
AutoCAD SHX Text
CLG
AutoCAD SHX Text
CAP
AutoCAD SHX Text
SENS
AutoCAD SHX Text
BRITISH THERMAL UNIT PER HOUR
AutoCAD SHX Text
THOUSAND BTU
AutoCAD SHX Text
CUBIC FEET PER MINUTE
AutoCAD SHX Text
COOLING
AutoCAD SHX Text
CAPACITY
AutoCAD SHX Text
SENSIBLE
AutoCAD SHX Text
LTNT
AutoCAD SHX Text
LATENT
AutoCAD SHX Text
INTERNALLY LINED DUCTWORK
AutoCAD SHX Text
RIGID EXHAUST DUCT
AutoCAD SHX Text
OSA
AutoCAD SHX Text
OUTSIDE AIR
AutoCAD SHX Text
POINT OF CONNECTION
AutoCAD SHX Text
POINT OF DISCONNECT
AutoCAD SHX Text
MECHANICAL LEGEND
AutoCAD SHX Text
ESP
AutoCAD SHX Text
EXTERNAL STATIC PRESSURE
AutoCAD SHX Text
C
AutoCAD SHX Text
CONDENSATE DRAIN
AutoCAD SHX Text
RLL
AutoCAD SHX Text
REFRIGERATION LIQUID LINE
AutoCAD SHX Text
C
AutoCAD SHX Text
RLL
AutoCAD SHX Text
RSL
AutoCAD SHX Text
RSL
AutoCAD SHX Text
REFRIGERATION SUCTION LINE
AutoCAD SHX Text
BALL VALVE
AutoCAD SHX Text
BALANCING VALVE
AutoCAD SHX Text
BUTTERFLY VALVE
AutoCAD SHX Text
AUTOMATIC CONTROL VALVE (2-WAY)
AutoCAD SHX Text
AUTOMATIC CONTROL VALVE (3-WAY)
AutoCAD SHX Text
MOTORIZED VALVE
AutoCAD SHX Text
PRESSURE REDUCING VALVE
AutoCAD SHX Text
AD
AutoCAD SHX Text
AUTOMATIC DAMPER (MOTORIZED)
AutoCAD SHX Text
DUCT DOWN
AutoCAD SHX Text
DUCT UP
AutoCAD SHX Text
D
AutoCAD SHX Text
G
AutoCAD SHX Text
SUPPLY AIR
AutoCAD SHX Text
RETURN AIR
AutoCAD SHX Text
AFG
AutoCAD SHX Text
ABOVE FINISHED GRADE
AutoCAD SHX Text
HTG
AutoCAD SHX Text
HEATING
AutoCAD SHX Text
TAG. SEE EQUIP. SCHEDULE-TYP
AutoCAD SHX Text
NUMBER -TYP
AutoCAD SHX Text
TURNING VANES
AutoCAD SHX Text
TAG
AutoCAD SHX Text
THERMOSTAT SCHEDULE
AutoCAD SHX Text
T
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
MODEL
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
24V
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
MOUNT HEIGHT
AutoCAD SHX Text
48''
AutoCAD SHX Text
REMARKS 1. ALL MOUNTING HARDWAREALL MOUNTING HARDWARE
AutoCAD SHX Text
1
AutoCAD SHX Text
NOTES 1.
AutoCAD SHX Text
PROGRAMMABLE COMMERCIAL THERMOSTAT
AutoCAD SHX Text
NOTES: 1. MECHANICAL CONTRACTOR TO COORDINATE WITH SYSTEM PIPING TREES AND MECHANICAL CONTRACTOR TO COORDINATE WITH SYSTEM PIPING TREES AND SYSTEM WIRING DIAGRAMS, SEE DETAIL 6/M3.1 2. WHEN CONDENSATE PUMP ALARM IS ENERGIZED ASSOCIATED AIR HANDLER IS WHEN CONDENSATE PUMP ALARM IS ENERGIZED ASSOCIATED AIR HANDLER IS TO DE-ENERGIZE.
AutoCAD SHX Text
MITSUBISHI
AutoCAD SHX Text
AIR COOLED VRF HEAT PUMP FOR AHUs 3-4
AutoCAD SHX Text
MITSUBISHI MODEL PUMY-P60NKMU2
AutoCAD SHX Text
CLG: 28.4 MBH HTG: 38.2 MBH
AutoCAD SHX Text
20
AutoCAD SHX Text
34
AutoCAD SHX Text
38
AutoCAD SHX Text
370
AutoCAD SHX Text
208V, 1 36 MCA,45 MOCP
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
MODEL
AutoCAD SHX Text
AIR COOLED CONDENSING UNIT
AutoCAD SHX Text
CONDENSING UNIT SCHEDULE
AutoCAD SHX Text
RHEEM MODEL RA1660AJ1NA
AutoCAD SHX Text
208V, 1 34 MCA,60 MOCP
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
WEIGHT
AutoCAD SHX Text
310
AutoCAD SHX Text
CAPACITY
AutoCAD SHX Text
56.0 MBH TOTAL CAP 41.2 MBH SENS CAP
AutoCAD SHX Text
SEER
AutoCAD SHX Text
15.1
AutoCAD SHX Text
SUCTION
AutoCAD SHX Text
LIQUID
AutoCAD SHX Text
78
AutoCAD SHX Text
38
AutoCAD SHX Text
CU
AutoCAD SHX Text
1
AutoCAD SHX Text
REMARKS: 1. LOW AMBIENT LOW AMBIENT 2. SUCTION LINE TRAP SUCTION LINE TRAP 3. SOLENOID LIQUID LINE VALVE SOLENOID LIQUID LINE VALVE 4. SIGHT GLASS SIGHT GLASS 5. COMPRESSOR ISOLATION VALVESCOMPRESSOR ISOLATION VALVES
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
1, 2, 3, 4, 5
AutoCAD SHX Text
ADD ALTERNATE #1
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
P
AutoCAD SHX Text
R
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
E
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
I
AutoCAD SHX Text
O
AutoCAD SHX Text
N
AutoCAD SHX Text
A
AutoCAD SHX Text
L
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
V
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
A
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
I
AutoCAD SHX Text
T
AutoCAD SHX Text
A
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
R
AutoCAD SHX Text
-
AutoCAD SHX Text
T
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
9
AutoCAD SHX Text
2
AutoCAD SHX Text
8
AutoCAD SHX Text
1
AutoCAD SHX Text
.
AutoCAD SHX Text
o
AutoCAD SHX Text
N
AutoCAD SHX Text
Exp 12-31-20
AutoCAD SHX Text
ETCHEMENDY
AutoCAD SHX Text
BRANDON A.
Page 3: DRAWING INDEX...SERVER ROOM HVAC RETROFIT INYO ANNEX BUILDING 168 N EDWARDS ST. INDEPENDENCE, CA DRAWING INDEX VICINITY MAP SCOPE OF WORK MECHANICAL ENGINEER BRANDON ETCHEMENDY PE

RL

LR

LL

RS

LR

SL

CH

R

CHR

CHS

HWS

HWR

DEMOLITION MECHANICAL PLANSCALE: 1/4" = 1'-0"

M1.1IT

DEMOLITIONMECHANICAL

PLAN

SME

job number

drawn

checked

19030

01/10/20

DRAWING TITLE

REVISIONS

SERVER R

OO

M H

VAC R

ETR

OFIT

INYO

AN

NEX B

UIL

DIN

G16

8 N

ED

WARD

S S

T.IN

DEPEN

DEN

CE, CALIF

ORN

IA

E T C H E M E N D YE N G I N E E R I N GI N C

10597 DOUBLE R BLVD RENO, NV 89521P. 775-853-1131 F. 775-852-2352

[email protected]

date

P

E

R

M

I

T

S

E

T

0

1

/

1

0

/

2

0

BAE

AutoCAD SHX Text
BOILER/BUILDING CONTROLS
AutoCAD SHX Text
COPY ROOM
AutoCAD SHX Text
INFORMATION SERVICES
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
SERVER ROOM
AutoCAD SHX Text
UTILITY
AutoCAD SHX Text
TELEPHONE SERVICE
AutoCAD SHX Text
SHULTS
AutoCAD SHX Text
T
AutoCAD SHX Text
T
AutoCAD SHX Text
(E) MECHANICAL PIPING TO REMAIN - TYP
AutoCAD SHX Text
(E) CHILLER TO REMAIN - TYP
AutoCAD SHX Text
(E) AIR HANDLER TO REMAIN
AutoCAD SHX Text
(E) IT EQUIPMENT - TYP OF 9
AutoCAD SHX Text
(E) OSA LOUVER TO REMAIN
AutoCAD SHX Text
GENERAL NOTES: 1. ASBESTOS HAS BEEN FOUND TO BE PRESENT IN THE ASBESTOS HAS BEEN FOUND TO BE PRESENT IN THE MECHANICAL ROOM VIA TESTING. COORDINATE ALL ASBESTOS CONTAINING MATERIALS WITH THE COUNTY AND COUNTIES TESTING REPORT. ALL ABATEMENT REQUIRED TO PERFORM WORK IN QUESTION TO BE LISTED AS A SEPARATE LINE ITEM.
AutoCAD SHX Text
(E) REFRIGERANT PIPING TO REMAIN - TYP
AutoCAD SHX Text
(E) DUCTWORK ROUTING UNKNOWN. FIELD VERIFY
AutoCAD SHX Text
(E) AC UNIT TO REMAIN - TYP OF 2
AutoCAD SHX Text
(E) BOILER TO REMAIN
AutoCAD SHX Text
(E) AIR HANDLER AND RETURN PLENUM DUCTWORK TO REMAIN
AutoCAD SHX Text
(E) SUPPLY AIR DIFFUSER AND ASSOCIATED DUCTWORK TO REMAIN - TYP
AutoCAD SHX Text
(E) DUCTWORK TO REMAIN - TYP
AutoCAD SHX Text
(E) MECHANICAL PIPING TO REMAIN. DO NOT TO DISTURB INSULATION DUE TO ASBESTOS - TYP
AutoCAD SHX Text
(E) PUMP TO REMAIN - TYP
AutoCAD SHX Text
DEMOLITION KEYED NOTES: (E) SUPPLY AIR DIFFUSER TO BE REMOVED COMPLETE (E) RETURN AIR GRILLE TO BE REMOVED COMPLETE (E) DUCTWORK TO BE DISCONNECT AND REMAIN FOR RECONNECTION (E) DUCTWORK TO BE REMOVED COMPLETE. EXACT ROUTING UNKNOWN, FIELD VERIFY (E) AC UNIT TO BE REMOVED AND SALVAGED BACK TO THE OWNER (E) THERMOSTAT TO BE REMOVED COMPLETE (E) SUPPLY AIR DIFFUSER TO BE REMOVED COMPLETE, REMOVE ANY FLEX DUCT AND PERMANENTLY CAP THE (E) DUCT ABOVE THE CEILING ADD ALTERNATE #1: (E) CONDENSING UNIT TO BE REMOVED COMPLETE ADD ALTERNATE #1: DISCONNECT (E) REFRIGERANT PIPING AND REMAIN FOR RECONNECTION. (E) REFRIGERANT PIPING TO BE REMOVED COMPLETE (E) OSA HOOD TO REMAIN. DISCONNECT AND REMOVE DUCTWORK (E) DUCTWORK TO BE REMOVED COMPLETE (E) FIRE DAMPERS, HIGH AND/OR LOW TO BE LOCKED CLOSED (E) AC TO BE REMOVED COMPLETE IF ADD ALTERNATE #1 IS NOT TAKEN, (E) CONDENSING UNIT TO REMAIN
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
5
AutoCAD SHX Text
6
AutoCAD SHX Text
7
AutoCAD SHX Text
8
AutoCAD SHX Text
9
AutoCAD SHX Text
10
AutoCAD SHX Text
12
AutoCAD SHX Text
11
AutoCAD SHX Text
13
AutoCAD SHX Text
18
AutoCAD SHX Text
14
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
P
AutoCAD SHX Text
R
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
E
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
I
AutoCAD SHX Text
O
AutoCAD SHX Text
N
AutoCAD SHX Text
A
AutoCAD SHX Text
L
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
V
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
A
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
I
AutoCAD SHX Text
T
AutoCAD SHX Text
A
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
R
AutoCAD SHX Text
-
AutoCAD SHX Text
T
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
9
AutoCAD SHX Text
2
AutoCAD SHX Text
8
AutoCAD SHX Text
1
AutoCAD SHX Text
.
AutoCAD SHX Text
o
AutoCAD SHX Text
N
AutoCAD SHX Text
Exp 12-31-20
AutoCAD SHX Text
ETCHEMENDY
AutoCAD SHX Text
BRANDON A.
Page 4: DRAWING INDEX...SERVER ROOM HVAC RETROFIT INYO ANNEX BUILDING 168 N EDWARDS ST. INDEPENDENCE, CA DRAWING INDEX VICINITY MAP SCOPE OF WORK MECHANICAL ENGINEER BRANDON ETCHEMENDY PE

RL

LR

LL

RS

LR

SL

CH

R

CHR

CHS

HWS

HWR

RL

L

RS

L

RLL

RSL

MECHANICAL PLANSCALE: 1/4" = 1'-0"

M2.1IT

MECHANICALPLAN

SME

job number

drawn

checked

19030

01/10/20

DRAWING TITLE

REVISIONS

SERVER R

OO

M H

VAC R

ETR

OFIT

INYO

AN

NEX B

UIL

DIN

G16

8 N

ED

WARD

S S

T.IN

DEPEN

DEN

CE, CALIF

ORN

IA

E T C H E M E N D YE N G I N E E R I N GI N C

10597 DOUBLE R BLVD RENO, NV 89521P. 775-853-1131 F. 775-852-2352

[email protected]

date

P

E

R

M

I

T

S

E

T

0

1

/

1

0

/

2

0

BAE

AutoCAD SHX Text
BOILER/BUILDING CONTROLS
AutoCAD SHX Text
COPY ROOM
AutoCAD SHX Text
INFORMATION SERVICES
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
SERVER ROOM
AutoCAD SHX Text
UTILITY
AutoCAD SHX Text
TELEPHONE SERVICE
AutoCAD SHX Text
SHULTS
AutoCAD SHX Text
T
AutoCAD SHX Text
T
AutoCAD SHX Text
T
AutoCAD SHX Text
(2) ''RLL & (2) 38''RLL & (2) 34''RSL UP ON LOUVERED WALL, SEE DETAIL 3/M0.1
AutoCAD SHX Text
(2) ''RLL & (2) 38''RLL & (2) 34''RSL ROUTED TIGHT TO CEILING
AutoCAD SHX Text
(E) MECHANICAL PIPING - TYP
AutoCAD SHX Text
(E) CHILLER
AutoCAD SHX Text
(E) HWS, HWR, CHS AND CHR PIPING - TYP
AutoCAD SHX Text
(E) AIR HANDLER
AutoCAD SHX Text
(E) DUCTWORK - TYP
AutoCAD SHX Text
SERVICE CLEARANCE, SEE DETAIL 1/M0.1 FOR AHU INSTALLATION - TYP
AutoCAD SHX Text
(E) IT EQUIPMENT - TYP OF 9
AutoCAD SHX Text
THERMOSTAT FOR AHU 4
AutoCAD SHX Text
THERMOSTAT FOR AHUs 1-3
AutoCAD SHX Text
38''RLL & ''RSL34''RSL
AutoCAD SHX Text
TYP OF 4
AutoCAD SHX Text
FIELD VERIFY HPs 1-2 LOCATIONS WILL NOT CONFLICT WITH ANY SERVICE OR MAINTENANCE CLEARANCES REQUIRED FOR THE (E) CHILLER
AutoCAD SHX Text
(E) 10''
AutoCAD SHX Text
CONNECT (N) 10'' SUPPLY DUCT TO (E) 10'' SUPPLY DUCT
AutoCAD SHX Text
38''RLL & ''RSL34''RSL
AutoCAD SHX Text
38''RLL & ''RSL58''RSL
AutoCAD SHX Text
38''RLL & ''RSL58''RSL
AutoCAD SHX Text
38''RLL & ''RSL58''RSL
AutoCAD SHX Text
FIELD VERIFY REFRIGERANT PIPING ROUTING WILL NOT CONFLICT WITH ANY SERVICE OR MAINTENANCE CLEARANCES REQUIRED FOR THE (E) CHILLER
AutoCAD SHX Text
4-BRANCH PIPE HEADER. PROVIDE FACTORY BALL VALVES AT EACH BRANCH - TYP
AutoCAD SHX Text
FACTORY BALL VALVES - TYP
AutoCAD SHX Text
10''
AutoCAD SHX Text
10''
AutoCAD SHX Text
10''
AutoCAD SHX Text
CONNECT (N) ''RLL & 38''RLL & 78''RSL TO (E) REFRIGERANT PIPING. FIELD VERIFY EXACT SIZE
AutoCAD SHX Text
10''
AutoCAD SHX Text
(E) 10''
AutoCAD SHX Text
CONNECT (N) 10'' SUPPLY DUCT TO (E) 10'' SUPPLY DUCT
AutoCAD SHX Text
GENERAL NOTES: 1. ASBESTOS HAS BEEN FOUND TO BE PRESENT IN THE ASBESTOS HAS BEEN FOUND TO BE PRESENT IN THE MECHANICAL ROOM VIA TESTING. COORDINATE ALL ASBESTOS CONTAINING MATERIALS WITH THE COUNTY AND COUNTIES TESTING REPORT. ALL ABATEMENT REQUIRED TO PERFORM WORK IN QUESTION TO BE LISTED AS A SEPARATE LINE ITEM.
AutoCAD SHX Text
KEYED NOTES: IF ADD ALTERNATE #1 IS NOT TAKEN, NO WORK HERE
AutoCAD SHX Text
1
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
P
AutoCAD SHX Text
R
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
E
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
I
AutoCAD SHX Text
O
AutoCAD SHX Text
N
AutoCAD SHX Text
A
AutoCAD SHX Text
L
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
V
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
A
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
I
AutoCAD SHX Text
T
AutoCAD SHX Text
A
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
R
AutoCAD SHX Text
-
AutoCAD SHX Text
T
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
9
AutoCAD SHX Text
2
AutoCAD SHX Text
8
AutoCAD SHX Text
1
AutoCAD SHX Text
.
AutoCAD SHX Text
o
AutoCAD SHX Text
N
AutoCAD SHX Text
Exp 12-31-20
AutoCAD SHX Text
ETCHEMENDY
AutoCAD SHX Text
BRANDON A.
Page 5: DRAWING INDEX...SERVER ROOM HVAC RETROFIT INYO ANNEX BUILDING 168 N EDWARDS ST. INDEPENDENCE, CA DRAWING INDEX VICINITY MAP SCOPE OF WORK MECHANICAL ENGINEER BRANDON ETCHEMENDY PE

SCALE: NOT TO SCALE

DUCT SUPPORT DETAIL 2

SCALE: NOT TO SCALE

UNIT MOUNTING CEILING SUSPENDED DETAIL 1

SCALE: NOT TO SCALE

PIPING SUPPORT DETAIL 4

SCALE: NOT TO SCALE 3PIPING WALL SUPPORT DETAIL

SCALE: NOT TO SCALE

HEAT PUMP MOUNTING DETAIL 5

SCALE: NOT TO SCALE

HEAT PUMP WIRING/PIPING DETAIL 6

SCALE: NOT TO SCALE

PIPING GROUND SUPPORT DETAIL 7

J1

P1

PCFY-

P30NKMU-ER1

001

Gp14

16-2 AWG(S)

PCFY-

P30NKMU-ER1

002

Gp15

P2 P2

DIP SWITCH 7-3 OFF

HP-1

PUMY-

P60NKMU2

051

TB7

H1

PKFY-

P12NHMU-E2

003

Gp16

P3

16-2 AWG(S)

PCFY-

P30NKMU-ER1

004

Gp17

P2

P1

DIP SWITCH 7-3 OFF

HP-2

PUMY-

P60NKMU2

053

TB7

PIPING AND CONTROLS

SYMBOL BRANCH PIPE MODEL NAME

J1 CMY-Y62-G-E

H1 CMY-Y64-G-E

SYMBOL LIQUID PIPE/GAS PIPE SIZE

P1 3/8 / 3/4

P2 3/8 / 5/8

P3 1/4 / 1/2

SYMBOL MODEL NUMBER

MA PAR-33MAA-J

SCALE: NOT TO SCALE

WALL AIR HANDLER MOUNTING DETAIL 8

M3.1IT

MECHANICALDETAILS

SME

job number

drawn

checked

19030

01/10/20

DRAWING TITLE

REVISIONS

SERVER R

OO

M H

VAC R

ETR

OFIT

INYO

AN

NEX B

UIL

DIN

G16

8 N

ED

WARD

S S

T.IN

DEPEN

DEN

CE, CALIF

ORN

IA

E T C H E M E N D YE N G I N E E R I N GI N C

10597 DOUBLE R BLVD RENO, NV 89521P. 775-853-1131 F. 775-852-2352

[email protected]

date

P

E

R

M

I

T

S

E

T

0

1

/

1

0

/

2

0

BAE

AutoCAD SHX Text
3/8'' ALL THREAD ROD
AutoCAD SHX Text
ATTACH 18ga HANGER STRAP TO B-LINE ROD ADAPTER WITH 3/8'' MACHINE BOLT FENDER WASHER, LOCK WASHER AND NUT.
AutoCAD SHX Text
20ga HANGER STRAP
AutoCAD SHX Text
SECURE UNISTRUT TO STRUCTURE WITH CONCRETE ANCORS
AutoCAD SHX Text
38'' ALL THREAD ROD - TYP
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
SUPPORT UNIT FROM FACTORY CEILING BRACKET
AutoCAD SHX Text
PIPING WITH INSULATION
AutoCAD SHX Text
UNISTRUT PIPE CLAMP
AutoCAD SHX Text
ALL-THREAD ROD
AutoCAD SHX Text
UNISTRUT
AutoCAD SHX Text
RAPID ROD CONCRETE ANCHOR
AutoCAD SHX Text
METAL/LOUVERED WALL
AutoCAD SHX Text
PIPE CLAMP
AutoCAD SHX Text
ATTACH TO WALL
AutoCAD SHX Text
(E) SUPPORTS
AutoCAD SHX Text
8' MAX
AutoCAD SHX Text
CONCRETE SLAB WITH STEEL DECKING
AutoCAD SHX Text
CONCRETE SLAB WITH STEEL DECKING
AutoCAD SHX Text
AS TIGHT AS POSSIBLE
AutoCAD SHX Text
RAPID ROD CONCRETE ANCHOR
AutoCAD SHX Text
CONCRETE SLAB WITH STEEL DECKING
AutoCAD SHX Text
UNISTRUT
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
SECURE TO CONCRETE
AutoCAD SHX Text
UNISTRUT PIPE CLAMP - TYP
AutoCAD SHX Text
INSULATED REFRIGERANT PIPING
AutoCAD SHX Text
T
AutoCAD SHX Text
B
AutoCAD SHX Text
5
AutoCAD SHX Text
T
AutoCAD SHX Text
B
AutoCAD SHX Text
1
AutoCAD SHX Text
5
AutoCAD SHX Text
L1L2
AutoCAD SHX Text
G
AutoCAD SHX Text
F
AutoCAD SHX Text
U
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
~
AutoCAD SHX Text
208-230V
AutoCAD SHX Text
B
AutoCAD SHX Text
1
AutoCAD SHX Text
5
AutoCAD SHX Text
T
AutoCAD SHX Text
5
AutoCAD SHX Text
B
AutoCAD SHX Text
T
AutoCAD SHX Text
L1L2
AutoCAD SHX Text
G
AutoCAD SHX Text
F
AutoCAD SHX Text
U
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
~
AutoCAD SHX Text
208-230V
AutoCAD SHX Text
3
AutoCAD SHX Text
T
AutoCAD SHX Text
B
AutoCAD SHX Text
L1L2
AutoCAD SHX Text
S
AutoCAD SHX Text
)
AutoCAD SHX Text
(
AutoCAD SHX Text
G
AutoCAD SHX Text
208-230V/60Hz
AutoCAD SHX Text
1~
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
MA
AutoCAD SHX Text
22~16-2 AWG(S)
AutoCAD SHX Text
MA
AutoCAD SHX Text
22~16-2 AWG(S)
AutoCAD SHX Text
T
AutoCAD SHX Text
B
AutoCAD SHX Text
5
AutoCAD SHX Text
T
AutoCAD SHX Text
B
AutoCAD SHX Text
1
AutoCAD SHX Text
5
AutoCAD SHX Text
L1L2
AutoCAD SHX Text
G
AutoCAD SHX Text
F
AutoCAD SHX Text
U
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
~
AutoCAD SHX Text
208-230V
AutoCAD SHX Text
B
AutoCAD SHX Text
1
AutoCAD SHX Text
5
AutoCAD SHX Text
T
AutoCAD SHX Text
5
AutoCAD SHX Text
B
AutoCAD SHX Text
T
AutoCAD SHX Text
L1L2
AutoCAD SHX Text
G
AutoCAD SHX Text
F
AutoCAD SHX Text
U
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
~
AutoCAD SHX Text
208-230V
AutoCAD SHX Text
3
AutoCAD SHX Text
T
AutoCAD SHX Text
B
AutoCAD SHX Text
L1L2
AutoCAD SHX Text
S
AutoCAD SHX Text
)
AutoCAD SHX Text
(
AutoCAD SHX Text
G
AutoCAD SHX Text
208-230V/60Hz
AutoCAD SHX Text
1~
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
MA
AutoCAD SHX Text
22~16-2 AWG(S)
AutoCAD SHX Text
MA
AutoCAD SHX Text
22~16-2 AWG(S)
AutoCAD SHX Text
the data book.
AutoCAD SHX Text
Please refer the amount of pre-charge and the formula of calculation which is mentioned on
AutoCAD SHX Text
Additional refrigerant charge is needed depending on the size and length of extended piping.
AutoCAD SHX Text
CITY MULTI
AutoCAD SHX Text
SYSTEM SCHEMATIC DWG.
AutoCAD SHX Text
PAGE
AutoCAD SHX Text
CONT.No
AutoCAD SHX Text
REF. PIPE
AutoCAD SHX Text
DISPLAY
AutoCAD SHX Text
DIAGRAM SYMBOL LEGEND
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
CONTROL WIRE
AutoCAD SHX Text
POWER WIRE
AutoCAD SHX Text
0.75mm(20 AWG) : between 0.5mm(24 AWG) and 0.75mm(20 AWG).
AutoCAD SHX Text
1.25mm(16 AWG) : 1.25mm(16 AWG) or more.
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
ATTACHE FLOOR MOUNTS TO CONCRETE PAD
AutoCAD SHX Text
EXISTING CONCRETE HOUSING KEEPING PAD
AutoCAD SHX Text
PROVIDE RUBBER-IN-SHEAR FLOOR MOUNTS - TYP
AutoCAD SHX Text
ALL-THREAD ROD OR STRAP
AutoCAD SHX Text
RAPID ROD CONCRETE ANCHOR
AutoCAD SHX Text
CONCRETE SLAB WITH STEEL DECKING
AutoCAD SHX Text
UNISTRUT
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
TIGHT AS POSSIBLE
AutoCAD SHX Text
FASTEN TO WALL PER SEISMIC CALCULATION
AutoCAD SHX Text
NOTE: 1. THIS DETAIL IS FOR REFERENCE ONLY, SEE MANUFACTURES INSTRUCTION FOR EXACT INSTALLATION 2. ALL UNIT CONNECTIONS ARE TO BE IN WALL AND NOT VISIBLE (I.E. ELECTRICAL, REFRIGERANT, CONDENSATE ETC.) 3. REFRIGERANT PIPING TO BE INSULATED PER MANUFACTURES SPECIFICATIONS
AutoCAD SHX Text
12''MIN
AutoCAD SHX Text
REFRIGERANT SUCTION AND LIQUID LINE PIPING ROUTED IN WALL TO BACK OF UNIT, SIZE VARIES
AutoCAD SHX Text
DOOR
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
PIPING CONTINUED ABOVE CEILING
AutoCAD SHX Text
UNIT SLIDES INTO CEILING BRACKET
AutoCAD SHX Text
UNISTRUT IF REQUIRED FOR ANCHORING TO FLUTES
AutoCAD SHX Text
PIPING AND ELECTRICAL CONNECTIONS TO BE MADE AT THE BACK OF THE UNIT
AutoCAD SHX Text
6'' MAX
AutoCAD SHX Text
UNISTRUT AS NECESSARY
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
P
AutoCAD SHX Text
R
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
E
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
I
AutoCAD SHX Text
O
AutoCAD SHX Text
N
AutoCAD SHX Text
A
AutoCAD SHX Text
L
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
V
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
A
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
I
AutoCAD SHX Text
T
AutoCAD SHX Text
A
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
R
AutoCAD SHX Text
-
AutoCAD SHX Text
T
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
9
AutoCAD SHX Text
2
AutoCAD SHX Text
8
AutoCAD SHX Text
1
AutoCAD SHX Text
.
AutoCAD SHX Text
o
AutoCAD SHX Text
N
AutoCAD SHX Text
Exp 12-31-20
AutoCAD SHX Text
ETCHEMENDY
AutoCAD SHX Text
BRANDON A.
Page 6: DRAWING INDEX...SERVER ROOM HVAC RETROFIT INYO ANNEX BUILDING 168 N EDWARDS ST. INDEPENDENCE, CA DRAWING INDEX VICINITY MAP SCOPE OF WORK MECHANICAL ENGINEER BRANDON ETCHEMENDY PE

SCALE: NOT TO SCALE

CEILING SUSPENDED UNIT PIPING DETAIL 1

SCALE: NOT TO SCALE

WALL MOUNTED UNIT PIPING DETAIL 2

P0.1IT

PLUMBING NOTES& DETAILS

SME

job number

drawn

checked

19030

01/10/20

DRAWING TITLE

REVISIONS

SERVER R

OO

M H

VAC R

ETR

OFIT

INYO

AN

NEX B

UIL

DIN

G16

8 N

ED

WARD

S S

T.IN

DEPEN

DEN

CE, CALIF

ORN

IA

E T C H E M E N D YE N G I N E E R I N GI N C

10597 DOUBLE R BLVD RENO, NV 89521P. 775-853-1131 F. 775-852-2352

[email protected]

date

P

E

R

M

I

T

S

E

T

0

1

/

1

0

/

2

0

BAE

AutoCAD SHX Text
NOTE: 1. THIS DETAIL IS FOR REFERENCE ONLY, SEE MANUFACTURES INSTRUCTION FOR EXACT INSTALLATION 2. ALL UNIT CONNECTIONS ARE TO BE IN WALL AND NOT VISIBLE (I.E. ELECTRICAL, REFRIGERANT, CONDENSATE ETC.)
AutoCAD SHX Text
34''C ROUTED UP IN WALL
AutoCAD SHX Text
DOOR
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
CONDENSATE PUMP TO BE LOCATED ABOVE CEILING IN ACCESSIBLE LOCATION, INSTALL PER MANUFACTURES RECOMMENDATIONS
AutoCAD SHX Text
PIPING CONNECTIONS TO BE MADE AT THE BACK OF THE UNIT
AutoCAD SHX Text
6'' MAX
AutoCAD SHX Text
GENERAL NOTES:
AutoCAD SHX Text
STANDARDS AND CODES: LATEST EDITION OF THE CALIFORNIA PLUMBING CODE (CPC), AS WELL AS ALL APPLICABLE STATE AND LOCAL CODES AND ORDINANCES. THIS DOES NOT RELIEVE THE CONTRACTOR FROM FURNISHING AND INSTALLING WORK SHOWN OR SPECIFIED WHICH MAY EXCEED THE REQUIREMENTS OF SUCH ORDINANCES, LAWS, REGULATIONS AND CODES. COMPLETE INSTALLATION: PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, TOOLS, ACCESSORIES, ETC., NECESSARY TO ACCOMPLISH A COMPLETE PLUMBING SYSTEM IN ACCORDANCE WITH THE PLANS TOGETHER WITH THE SPECIFICATIONS. PERMITS: OBTAIN AND PAY FOR ALL BUILDING AND WORKING PERMITS AND INSPECTION FEES REQUIRED FOR THIS PROJECT. DRAWINGS: DATA PRESENTED ON THESE DRAWINGS SHALL BE FIELD VERIFIED SINCE ALL DIMENSIONS, LOCATIONS, AND LEVELS ARE GOVERNED BY ACTUAL FIELD CONDITIONS. REVIEW ALL ARCHITECTURAL, STRUCTURAL, CIVIL, ELECTRICAL AND SPECIALTY SYSTEMS DRAWINGS AND ADJUST ALL WORK TO MEET THE REQUIREMENTS ON CONDITIONS SHOWN THEREON, DO NOT SCALE PLUMBING PLANS FOR FIXTURE, PIPING, APPLIANCE ETC. LOCATIONS. USE CONFIGURED DIMENSIONS IF GIVEN OR CHECK ARCHITECTURAL DRAWINGS. COPYRIGHT: THESE PLANS, SPECIFICATIONS AND ALL RELATED ADDENDA AND DOCUMENTS CONSTITUTE COPYRIGHT MATERIALS OF ETCHEMENDY ENGINEERING INC. ALL RIGHTS CONFERRED BY THE COPYRIGHT AND SIMILAR LAWS ARE RESERVED TO ETCHEMENDY ENGINEERING INC. THESE MATERIALS SHALL REMAIN THE SOLE PROPERTY OF ETCHEMENDY ENGINEERING INC. AND MAY NOT BE REPRODUCED, DISTRIBUTED TO OTHERS OR USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE PRIOR WRITTEN CONSENT OF ETCHEMENDY ENGINEERING INC. LOCATIONS: INDICATED LOCATIONS OF ALL FIXTURES, PIPING, EQUIPMENT ETC. ARE SUBJECT TO CHANGE. SHIFT/RELOCATE/RECONFIGURE ANY FIXTURE, PIPE, EQUIPMENT OR CONNECTION POINT UP TO 10' AS DIRECTED BY ENGINEER, AT NO ADDED COST. RECORD DRAWINGS: CONTRACTOR SHALL PROVIDE, PRIOR TO FINAL ACCEPTANCE AND OBSERVATION, ONE SET OF REVISED RECORD PLUMBING CONSTRUCTION DOCUMENTS ON REPRODUCIBLE MEDIUM. INDICATING THE FOLLOWING ADDITIONAL INFORMATION: RECORD NOTATIONS SHALL BE CLEARLY DRAWN AT A DRAFTING APPEARANCE EQUAL TO THE ORIGINAL DRAWINGS. CONTRACTOR SHALL ALSO PROVIDE ALL OPERATING AND MAINTENANCE MANUALS PRIOR TO FINAL PAYMENT. EXAMINATION OF SITE AND EXISTING CONDITIONS: BEFORE SUBMITTING A PROPOSAL, CONTRACTOR SHALL EXAMINE THE SITE AND FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND LIMITATIONS. NO EXTRAS WILL BE ALLOWED BECAUSE OF THE CONTRACTOR'S MISUNDERSTANDING OF THE AMOUNT OF WORK INVOLVED OR HIS LACK OF KNOWLEDGE OF ANY SITE CONDITIONS WHICH MAY AFFECT HIS WORK. ANY APPARENT VARIANCE OF THE DRAWINGS OR SPECIFICATIONS FROM THE EXISTING CONDITIONS AT THE SITE SHALL BE CALLED TO THE ATTENTION OF THE ENGINEER BEFORE SUBMITTING A PROPOSAL. EXISTING CONDITIONS: ALL (E) SIZES AND LOCATIONS ARE APPROXIMATIONS AND ARE TO BE FIELD VERIFIED BY THE CONTRACTOR PRIOR COMMENCEMENT OF ANY WORK. NO ADDITIONAL FEES WILL BE ALLOWED DUE TO DUE LACK OF FIELD VERIFICATION. WATER HEATING TESTING: THE WATER HEATING SYSTEM SHALL BE TESTED AND ADJUSTED TO MAINTAIN A DELIVERY WATER TEMPERATURE AS INDICATED ON THE WATER HEATER PIPING DIAGRAM FOR ALL OPERATING CONDITIONS.
AutoCAD SHX Text
PLUMBING LEGEND
AutoCAD SHX Text
LINETYPE
AutoCAD SHX Text
ABBREVIATION
AutoCAD SHX Text
INTENT
AutoCAD SHX Text
CONDENSATE PIPING
AutoCAD SHX Text
PIPE UP
AutoCAD SHX Text
PIPE DOWN
AutoCAD SHX Text
POINT OF CONNECTION
AutoCAD SHX Text
VENT THRU ROOF
AutoCAD SHX Text
BALANCING VALVE
AutoCAD SHX Text
BALL VALVE
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
UP
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
POC
AutoCAD SHX Text
VTR
AutoCAD SHX Text
(N)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
AFF
AutoCAD SHX Text
AFG
AutoCAD SHX Text
BFF
AutoCAD SHX Text
BFG
AutoCAD SHX Text
MIN
AutoCAD SHX Text
TYP
AutoCAD SHX Text
GPH
AutoCAD SHX Text
GPM
AutoCAD SHX Text
FCO
AutoCAD SHX Text
COTG
AutoCAD SHX Text
WCO
AutoCAD SHX Text
NEW
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
ABOVE FINISHED GRADE
AutoCAD SHX Text
BELOW FINISHED FLOOR
AutoCAD SHX Text
BELOW FINISHED GRADE
AutoCAD SHX Text
MINIMUM
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
GALLONS PER HOUR
AutoCAD SHX Text
GALLON PER MINUTE
AutoCAD SHX Text
FLOOR CLEANOUT
AutoCAD SHX Text
CLEANOUT TO GRADE
AutoCAD SHX Text
WALL CLEAN OUT
AutoCAD SHX Text
GPF
AutoCAD SHX Text
GALLONS PER FLUSH
AutoCAD SHX Text
POINT OF DISCONNECT
AutoCAD SHX Text
POD
AutoCAD SHX Text
TDL
AutoCAD SHX Text
TOTAL DEVELOPED LENGTH
AutoCAD SHX Text
CONDENSATE PUMP TO BE LOCATED ABOVE CEILING IN ACCESSIBLE LOCATION, INSTALL PER MANUFACTURES RECOMMENDATIONS
AutoCAD SHX Text
PIPING CONTINUED TO EXISTING FLOOR SINK
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
PIPING CONTINUED TO EXISTING FLOOR SINK
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
P
AutoCAD SHX Text
R
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
E
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
I
AutoCAD SHX Text
O
AutoCAD SHX Text
N
AutoCAD SHX Text
A
AutoCAD SHX Text
L
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
V
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
A
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
I
AutoCAD SHX Text
T
AutoCAD SHX Text
A
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
R
AutoCAD SHX Text
-
AutoCAD SHX Text
T
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
9
AutoCAD SHX Text
2
AutoCAD SHX Text
8
AutoCAD SHX Text
1
AutoCAD SHX Text
.
AutoCAD SHX Text
o
AutoCAD SHX Text
N
AutoCAD SHX Text
Exp 12-31-20
AutoCAD SHX Text
ETCHEMENDY
AutoCAD SHX Text
BRANDON A.
Page 7: DRAWING INDEX...SERVER ROOM HVAC RETROFIT INYO ANNEX BUILDING 168 N EDWARDS ST. INDEPENDENCE, CA DRAWING INDEX VICINITY MAP SCOPE OF WORK MECHANICAL ENGINEER BRANDON ETCHEMENDY PE

DEMOLITION PLUMBING PLANSCALE: 1/4" = 1'-0"

P1.1IT

DEMOLITIONPLUMBING PLAN

SME

job number

drawn

checked

19030

01/10/20

DRAWING TITLE

REVISIONS

SERVER R

OO

M H

VAC R

ETR

OFIT

INYO

AN

NEX B

UIL

DIN

G16

8 N

ED

WARD

S S

T.IN

DEPEN

DEN

CE, CALIF

ORN

IA

E T C H E M E N D YE N G I N E E R I N GI N C

10597 DOUBLE R BLVD RENO, NV 89521P. 775-853-1131 F. 775-852-2352

[email protected]

date

P

E

R

M

I

T

S

E

T

0

1

/

1

0

/

2

0

BAE

AutoCAD SHX Text
BOILER/BUILDING CONTROLS
AutoCAD SHX Text
COPY ROOM
AutoCAD SHX Text
INFORMATION SERVICES
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
SERVER ROOM
AutoCAD SHX Text
UTILITY
AutoCAD SHX Text
TELEPHONE SERVICE
AutoCAD SHX Text
SHULTS
AutoCAD SHX Text
(E) FLOOR SINK TO REMAIN
AutoCAD SHX Text
AIR HANDLER TO BE REMOVED, SEE MECHANICAL DRAWINGS
AutoCAD SHX Text
AIR HANDLER TO REMAIN
AutoCAD SHX Text
(E) CONDENSATE FROM AIR HANDLER TO REMAIN
AutoCAD SHX Text
(E) CONDENSATE FROM AIR HANDLER TO BE REMOVED COMPLETE
AutoCAD SHX Text
(E) CONDENSATE FROM AIR HANDLER TO REMAIN. FIELD VERIFY EXACT LOCATION AND ROUTING
AutoCAD SHX Text
(E) AIR HANDLER TO REMAIN, SEE MECHANICAL DRAWINGS
AutoCAD SHX Text
(E) IT EQUIPMENT - TYP OF 9
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
P
AutoCAD SHX Text
R
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
E
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
I
AutoCAD SHX Text
O
AutoCAD SHX Text
N
AutoCAD SHX Text
A
AutoCAD SHX Text
L
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
V
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
A
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
I
AutoCAD SHX Text
T
AutoCAD SHX Text
A
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
R
AutoCAD SHX Text
-
AutoCAD SHX Text
T
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
9
AutoCAD SHX Text
2
AutoCAD SHX Text
8
AutoCAD SHX Text
1
AutoCAD SHX Text
.
AutoCAD SHX Text
o
AutoCAD SHX Text
N
AutoCAD SHX Text
Exp 12-31-20
AutoCAD SHX Text
ETCHEMENDY
AutoCAD SHX Text
BRANDON A.
Page 8: DRAWING INDEX...SERVER ROOM HVAC RETROFIT INYO ANNEX BUILDING 168 N EDWARDS ST. INDEPENDENCE, CA DRAWING INDEX VICINITY MAP SCOPE OF WORK MECHANICAL ENGINEER BRANDON ETCHEMENDY PE

PLUMBING PLANSCALE: 1/4" = 1'-0"

C

C

P2.1IT

PLUMBING PLAN

SME

job number

drawn

checked

19030

01/10/20

DRAWING TITLE

REVISIONS

SERVER R

OO

M H

VAC R

ETR

OFIT

INYO

AN

NEX B

UIL

DIN

G16

8 N

ED

WARD

S S

T.IN

DEPEN

DEN

CE, CALIF

ORN

IA

E T C H E M E N D YE N G I N E E R I N GI N C

10597 DOUBLE R BLVD RENO, NV 89521P. 775-853-1131 F. 775-852-2352

[email protected]

date

P

E

R

M

I

T

S

E

T

0

1

/

1

0

/

2

0

BAE

AutoCAD SHX Text
BOILER/BUILDING CONTROLS
AutoCAD SHX Text
COPY ROOM
AutoCAD SHX Text
INFORMATION SERVICES
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
SERVER ROOM
AutoCAD SHX Text
UTILITY
AutoCAD SHX Text
TELEPHONE SERVICE
AutoCAD SHX Text
SHULTS
AutoCAD SHX Text
(E) FLOOR SINK
AutoCAD SHX Text
34''C
AutoCAD SHX Text
34''C
AutoCAD SHX Text
34''C
AutoCAD SHX Text
(N) MECHANICAL EQUIPMENT, SEE MECHANICAL DRAWINGS FOR DETAILS - TYP
AutoCAD SHX Text
34''C DOWN ON WALL AND ROUTED TO FLOOR SINK. TERMINATE 1'' ABOVE FLOOD RIM WITH 90° ELBOW DOWN
AutoCAD SHX Text
34''C FROM MECHANICAL UNIT AND ROUTED ABOVE CEILING - TYP OF 4
AutoCAD SHX Text
(E) AIR HANDLER
AutoCAD SHX Text
(E) IT EQUIPMENT - TYP OF 9
AutoCAD SHX Text
34''C
AutoCAD SHX Text
34''C
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
P
AutoCAD SHX Text
R
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
E
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
I
AutoCAD SHX Text
O
AutoCAD SHX Text
N
AutoCAD SHX Text
A
AutoCAD SHX Text
L
AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
V
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
A
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
G
AutoCAD SHX Text
I
AutoCAD SHX Text
T
AutoCAD SHX Text
A
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
R
AutoCAD SHX Text
-
AutoCAD SHX Text
T
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
9
AutoCAD SHX Text
2
AutoCAD SHX Text
8
AutoCAD SHX Text
1
AutoCAD SHX Text
.
AutoCAD SHX Text
o
AutoCAD SHX Text
N
AutoCAD SHX Text
Exp 12-31-20
AutoCAD SHX Text
ETCHEMENDY
AutoCAD SHX Text
BRANDON A.
Page 9: DRAWING INDEX...SERVER ROOM HVAC RETROFIT INYO ANNEX BUILDING 168 N EDWARDS ST. INDEPENDENCE, CA DRAWING INDEX VICINITY MAP SCOPE OF WORK MECHANICAL ENGINEER BRANDON ETCHEMENDY PE

SIGN

·

·

·

job number

drawn

checked

EEI #19030

DRAWING TITLE

REVISIONS

10597 DOUBLE R BLVD RENO, NV 89521P. 775-853-1131 F. 775-852-2352

[email protected]

date

JPS

JPS

10597 Double R Blvd, Ste. 1

Reno, Nevada 89521

P: 775.852.2337

F: 775.852.2352

JP #19070

E T C H E M E N D YE N G I N E E R I N GI N C

*

*

R

E

G

IS

T

E

R

E

D

P

R

O

F

E

S

S

ION

A

L

E

N

G

I

N

E

E

R

S

T

A

T

E

O F

C

A

L

I

F

O

R

N

I

A

JA

M

E

S

P

.

SO

L

A

R

O

E

L

E

CT

R

I

C

A

L

E

x

p

:

1

2

/

3

1

/

2

0

1/10/2020

SERVER R

OO

M H

VAC R

ETR

OFIT

INYO

AN

NEX B

UIL

DIN

G16

8 N

ED

WARD

S S

T.IN

DEPEN

DEN

CE, CALIF

ORN

IA

E0.1IT

SYMBOL LISTAND

SPECIFICATIONS

AutoCAD SHX Text
DIAMOND SYMBOLS INDICATES DEDICATED CIRCUIT.
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text
CEILING SPACE
AutoCAD SHX Text
3/4"C (UON) STUB INTO ACCESSIBLE
AutoCAD SHX Text
METAL CLAD CABLE (MC)
AutoCAD SHX Text
CEILING MOUNTED
AutoCAD SHX Text
MOTION/OCCUPANCY SENSOR SWITCH WITH OFF-AUTO
AutoCAD SHX Text
SELECTOR - WALL MOUNTED AT +48'' TO TOP UON
AutoCAD SHX Text
ULTRASONIC MOTION/OCCUPANCY SENSOR SWITCH
AutoCAD SHX Text
J
AutoCAD SHX Text
L INDICATES PILOT LOCATOR (LIGHTED WHEN OFF)
AutoCAD SHX Text
MISCELLANEOUS
AutoCAD SHX Text
DESIGNATIONS
AutoCAD SHX Text
CIRCUITING
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
SWITCHES
AutoCAD SHX Text
METHODS
AutoCAD SHX Text
MISCELLANEOUS: THESE AND OTHER SYMBOLS AS INDICATED
AutoCAD SHX Text
IN TABLES AND SCHEDULES ON THE PLANS.
AutoCAD SHX Text
REVISION DELTA: NUMBER REPRESENTS REVISION
AutoCAD SHX Text
SHEET NOTE
AutoCAD SHX Text
LIGHT FIXTURE: F1 = TYPE (SEE FIXTURE SCHEDULE)
AutoCAD SHX Text
MECHANICAL AND PLUMBING EQUIPMENT
AutoCAD SHX Text
WALL MOUNT +54'' AFF UON
AutoCAD SHX Text
TELEPHONE: 4S BOX WITH SINGLE GANG MUD RING UON,
AutoCAD SHX Text
SIGNAL OUTLETS
AutoCAD SHX Text
RECEPTACLES
AutoCAD SHX Text
TO BE REMOVED
AutoCAD SHX Text
FINE DASHING INDICATES EXISTING EQUIPMENT AND DEVICES
AutoCAD SHX Text
RECEPTACLE MOUNTED IN CEILING OR CASEWORK
AutoCAD SHX Text
PHOTO ELECTRIC SWITCH: 1600VA UON
AutoCAD SHX Text
COMPARTMENT BOX
AutoCAD SHX Text
FLUSH FLOOR MOUNTED WIRING DEVICES IN SINGLE MULTI-
AutoCAD SHX Text
CONTACTOR (120V COIL, STEP DN XFMR IF REQUIRED, UON)
AutoCAD SHX Text
RELAY (120V COIL , STEP DN XFMR IF REQUIRED, UON)
AutoCAD SHX Text
TRANSFORMER
AutoCAD SHX Text
PANELBOARD: FLUSH MOUNTED
AutoCAD SHX Text
SWITCHBOARD
AutoCAD SHX Text
TELEPOWER POLE
AutoCAD SHX Text
FUSIBLE DISCONNECT SWITCH
AutoCAD SHX Text
SURFACE RACEWAY WITH OR WITHOUT DEVICES
AutoCAD SHX Text
JUNCTION BOX: SIZE AS REQUIRED BY NEC
AutoCAD SHX Text
PULLBOX: SIZE AS REQUIRED BY NEC
AutoCAD SHX Text
NON-FUSIBLE DISCONNECT SWITCH
AutoCAD SHX Text
COMBINATION MAGNETIC STARTER/FUSED DISCONNECT
AutoCAD SHX Text
PANELBOARD: SURFACE MOUNTED
AutoCAD SHX Text
T
AutoCAD SHX Text
TELEPHONE
AutoCAD SHX Text
S
AutoCAD SHX Text
P
AutoCAD SHX Text
PRIMARY
AutoCAD SHX Text
OH
AutoCAD SHX Text
SECONDARY
AutoCAD SHX Text
OVERHEAD SERVICE
AutoCAD SHX Text
CONDUIT IN FLOOR OR BELOW GRADE
AutoCAD SHX Text
CONDUIT IN WALL OR ABOVE CEILING
AutoCAD SHX Text
LOW VOLTAGE AND/OR CONTROL CIRCUITNG
AutoCAD SHX Text
CIRCUITING UP OR DOWN
AutoCAD SHX Text
STUB OUT: MARK AND CAP (SITE)
AutoCAD SHX Text
TV
AutoCAD SHX Text
TELEVISION
AutoCAD SHX Text
DOUBLE DUPLEX: 20A, 125V, NEMA 5-20, +18'' AFF
AutoCAD SHX Text
DUPLEX: 20A, 125V, NEMA 5-20, +18'' AFF
AutoCAD SHX Text
S
AutoCAD SHX Text
X
AutoCAD SHX Text
FLUSH FLOOR MOUNTED WIRING DEVICES
AutoCAD SHX Text
MAXIMUM HEIGHT ON WALLS SHALL BE +48'' TO TOP UON
AutoCAD SHX Text
DEVICES MOUNTED IN OR ABOVE COUNTER/BACKSPLASH:
AutoCAD SHX Text
MAXIMUM HEIGHT ON WALL SHALL BE +48'' TO TOP UON
AutoCAD SHX Text
DEVICE MOUNTED IN MULTIPLE UNDER COMMON COVER
AutoCAD SHX Text
SHADING INDICATES: FIXTURE, OUTLET, EQUIPMENT,
AutoCAD SHX Text
ETC. ON EMERGENCY 'X' OR NIGHT LIGHT 'NL' CIRCUIT
AutoCAD SHX Text
SIGNAGE CONNECTION
AutoCAD SHX Text
CONTROL STATION: AT +48'' TO TOP UON
AutoCAD SHX Text
SHUNT TRIP STATION: +7'-6'' AFF, 12'' RED TRIANGLE, UON
AutoCAD SHX Text
MOTOR: NUMBER = HORSEPOWER
AutoCAD SHX Text
EXHAUST FAN: FRACTIONAL HORSEPOWER
AutoCAD SHX Text
THERMOSTAT: AT +48'' TO TOP UON (OR PER MECH PLANS)
AutoCAD SHX Text
(TOP HALF SWITCHED)
AutoCAD SHX Text
+18'' AFF UON
AutoCAD SHX Text
+18'' AFF UON
AutoCAD SHX Text
+18'' AFF UON
AutoCAD SHX Text
+18'' AFF UON
AutoCAD SHX Text
TELEVISION: 4S BOX WITH SINGLE GANG MUD RING UON,
AutoCAD SHX Text
VOICE/DATA: 4S BOX WITH SINGLE GANG MUD RING UON,
AutoCAD SHX Text
DATA: 4S BOX WITH SINGLE GANG MUD RING UON,
AutoCAD SHX Text
TELEPHONE: 4S BOX WITH SINGLE GANG MUD RING UON,
AutoCAD SHX Text
+18'' AFF (WHITE WITH ORANGE TRIANGLE, UON)
AutoCAD SHX Text
DUPLEX I.G.: 20A, 125V, ISO. GND., NEMA 5-20 IG
AutoCAD SHX Text
DUPLEX GFCI: 20A, 125V, GFCI, NEMA 5-20 GFR, +18'' AFF
AutoCAD SHX Text
HALF SWITCHED DUPLEX: 20A, 125V, NEMA 5-20, +18'' AFF
AutoCAD SHX Text
SPECIAL RECEPTACLE - AS INDICATED ON PLANS, +18'' AFF
AutoCAD SHX Text
+18'' AFF UON
AutoCAD SHX Text
CEILING MOUNTED UON
AutoCAD SHX Text
CEILING MOUNTED UON
AutoCAD SHX Text
SPEAKER: 8'' COAXIAL WITH BACK BOX AND GRILLE,
AutoCAD SHX Text
UON, +48'' TO TOP UON
AutoCAD SHX Text
VOLUME CONTROL: 4S BOX WITH SINGLE GANG MUD RING
AutoCAD SHX Text
MICROPHONE: 4S BOX WITH SINGLE GANG MUD RING UON,
AutoCAD SHX Text
CAMERA: 4S BOX WITH SINGLE GANG MUD RING UON,
AutoCAD SHX Text
X INDICATES EMERGENCY CIRCUIT
AutoCAD SHX Text
FOUR WAY: 20A, 120/277V, +48'' TO TOP UON
AutoCAD SHX Text
THREE WAY: 20A, 120/277V, +48'' TO TOP UON
AutoCAD SHX Text
TWO POLE: 20A, 120/277V, +48'' TO TOP UON
AutoCAD SHX Text
SINGLE POLE: 20A, 120/277V, +48'' TO TOP UON
AutoCAD SHX Text
INDICATE TYPE: FLUOR, INCAND OR LOW-VOLTAGE)
AutoCAD SHX Text
ON/OFF TOGGLE, +48'' TO TOP UON (PLANS SHALL
AutoCAD SHX Text
DIMMER: 600 WATT UON, ELECTRONIC SLIDER, WITH
AutoCAD SHX Text
NORMALLY OFF UON, +48'' TO TOP UON
AutoCAD SHX Text
MOMENTARY CONTACT: 20A, 120/277V, SPDT CENTER
AutoCAD SHX Text
AND HEATERS AS REQUIRED
AutoCAD SHX Text
MANUAL MOTOR STARTER: 20A, 120/277V, POLES
AutoCAD SHX Text
K INDICATES KEY OPERATED SWITCH
AutoCAD SHX Text
P INDICATES PILOT LIGHT (LIGHTED WHEN ON)
AutoCAD SHX Text
MASTER SYMBOL LIST
AutoCAD SHX Text
ABBREVIATIONS
AutoCAD SHX Text
EMERGENCY CIRCUIT
AutoCAD SHX Text
INCANDESCENT
AutoCAD SHX Text
EXISTING TO BE REMOVED
AutoCAD SHX Text
TRANSFORMER
AutoCAD SHX Text
WATERTIGHT
AutoCAD SHX Text
WEATHERPROOF (NEMA 3R)
AutoCAD SHX Text
UNLESS OTHERWISE NOTED
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
TELECOM
AutoCAD SHX Text
SINGLE POLE SINGLE THROW
AutoCAD SHX Text
SINGLE POLE DOUBLE THROW
AutoCAD SHX Text
RIGID STEEL CONDUIT
AutoCAD SHX Text
RIGID ALUMINUM CONDUIT
AutoCAD SHX Text
EXISTING TO BE RELOCATED
AutoCAD SHX Text
POLYVINYL CHLORIDE CONDUIT
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
NIGHT LIGHT
AutoCAD SHX Text
NORMALLY CLOSED
AutoCAD SHX Text
NEW
AutoCAD SHX Text
MOTOR CIRCUIT PROTECTOR
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
GROUND FAULT INTERRUPTER
AutoCAD SHX Text
FURNISHED BY OTHERS
AutoCAD SHX Text
ELECTRICAL METALLIC TUBING
AutoCAD SHX Text
ELEVATOR
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
DOUBLE POLE SINGLE THROW
AutoCAD SHX Text
DOUBLE POLE DOUBLE THROW
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
CENTERLINE
AutoCAD SHX Text
CIRCUIT
AutoCAD SHX Text
BUILDING MANAGEMENT SYSTEM
AutoCAD SHX Text
MULTI-CONDUCTOR CABLE
AutoCAD SHX Text
AMPERES INTERRUPTING CAPACITY
AutoCAD SHX Text
ABOVE FINISH CEILING
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
CIRCUIT BREAKER
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
EMERGENCY POWER OFF SYSTEM
AutoCAD SHX Text
FLUORESCENT
AutoCAD SHX Text
FUSE: DUAL-ELEMENT, TIME DELAY
AutoCAD SHX Text
HAND-OFF-AUTOMATIC
AutoCAD SHX Text
HIGH INTENSITY DISCHARGE
AutoCAD SHX Text
ISOLATED GROUND
AutoCAD SHX Text
kcmil (300K = 300 kcmil)
AutoCAD SHX Text
LIGHTING
AutoCAD SHX Text
LOW VOLTAGE
AutoCAD SHX Text
NEUTRAL
AutoCAD SHX Text
NORMALLY OPEN
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
SEAL OFF
AutoCAD SHX Text
SIZE PER EQUIPMENT NAMEPLATE
AutoCAD SHX Text
UNSWITCHED
AutoCAD SHX Text
EXPLOSION PROOF
AutoCAD SHX Text
UNSW
AutoCAD SHX Text
UON
AutoCAD SHX Text
WP
AutoCAD SHX Text
WT
AutoCAD SHX Text
(X)
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
XP
AutoCAD SHX Text
MCP
AutoCAD SHX Text
(N)
AutoCAD SHX Text
NC
AutoCAD SHX Text
NL
AutoCAD SHX Text
NTS
AutoCAD SHX Text
PVC
AutoCAD SHX Text
(R)
AutoCAD SHX Text
RAC
AutoCAD SHX Text
RSC
AutoCAD SHX Text
SPDT
AutoCAD SHX Text
SPST
AutoCAD SHX Text
TEL
AutoCAD SHX Text
TYP
AutoCAD SHX Text
MC
AutoCAD SHX Text
LV
AutoCAD SHX Text
NEUT
AutoCAD SHX Text
NO
AutoCAD SHX Text
PNL
AutoCAD SHX Text
SO
AutoCAD SHX Text
SPEN
AutoCAD SHX Text
INCAND
AutoCAD SHX Text
DPDT
AutoCAD SHX Text
DPST
AutoCAD SHX Text
(E)
AutoCAD SHX Text
ELEV
AutoCAD SHX Text
EMT
AutoCAD SHX Text
FBO
AutoCAD SHX Text
GFI/GFCI
AutoCAD SHX Text
GND
AutoCAD SHX Text
CIR
AutoCAD SHX Text
CB
AutoCAD SHX Text
CLG
AutoCAD SHX Text
EPO
AutoCAD SHX Text
FLUOR
AutoCAD SHX Text
FU
AutoCAD SHX Text
HOA
AutoCAD SHX Text
HID
AutoCAD SHX Text
IG
AutoCAD SHX Text
LTG
AutoCAD SHX Text
K
AutoCAD SHX Text
AFF
AutoCAD SHX Text
BMS
AutoCAD SHX Text
AIC
AutoCAD SHX Text
AFC
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
L
AutoCAD SHX Text
ARROWS INDICATE DIRECTION AND COVERAGE
AutoCAD SHX Text
PROVIDE WITH POWER PACK PER MANUFACTURERS REQUIREMENTS
AutoCAD SHX Text
%%UNOTE:
AutoCAD SHX Text
THIS IS A MASTER SYMBOL LIST, ALL SYMBOLS SHOWN MAY NOT BE USED WITHIN THIS SET OF PLANS
AutoCAD SHX Text
FPEN
AutoCAD SHX Text
FUSE PER EQUIPMENT NAMEPLATE
AutoCAD SHX Text
DOUBLE DUPLEX I.G.: 20A, 125V, ISO. GND., NEMA 5-20 IG
AutoCAD SHX Text
+18'' AFF (WHITE WITH ORANGE TRIANGLE, UON)
AutoCAD SHX Text
DUAL LEVEL LIGHTING CONTROL
AutoCAD SHX Text
SWITCH 'a' = CENTER (1) LAMP
AutoCAD SHX Text
SWITCH 'b' = OUTER (2) LAMPS
AutoCAD SHX Text
SINGLE LINE DIAGRAM
AutoCAD SHX Text
SLD
AutoCAD SHX Text
= 360
AutoCAD SHX Text
= 180
AutoCAD SHX Text
= 90
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
NEUTRAL CONDUCTOR (ONE PER PHASE CONDUCTOR)
AutoCAD SHX Text
GROUNDING CONDUCTOR
AutoCAD SHX Text
PHASE CONDUCTOR(S)
AutoCAD SHX Text
ISOLATED GROUNDING CONDUCTOR
AutoCAD SHX Text
%%UHOMERUN DESIGNATION
AutoCAD SHX Text
PNL-[H,H,H,N]G,IG
AutoCAD SHX Text
PANEL DESIGNATION
AutoCAD SHX Text
TWO WITHIN CONDUIT OR MC
AutoCAD SHX Text
TICS = NO. OF #12 WIRES (UON) IF MORE THAN
AutoCAD SHX Text
ISOLATED GROUNDING CONDUCTOR
AutoCAD SHX Text
NEUTRAL CONDUCTOR (ONE PER PHASE CONDUCTOR)
AutoCAD SHX Text
PHASE CONDUCTOR(S)
AutoCAD SHX Text
GROUNDING CONDUCTOR
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
2
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
S
AutoCAD SHX Text
4
AutoCAD SHX Text
S
AutoCAD SHX Text
X
AutoCAD SHX Text
S
AutoCAD SHX Text
P
AutoCAD SHX Text
S
AutoCAD SHX Text
L
AutoCAD SHX Text
S
AutoCAD SHX Text
K
AutoCAD SHX Text
S
AutoCAD SHX Text
M
AutoCAD SHX Text
S
AutoCAD SHX Text
MC
AutoCAD SHX Text
D
AutoCAD SHX Text
TV
AutoCAD SHX Text
C
AutoCAD SHX Text
M
AutoCAD SHX Text
V
AutoCAD SHX Text
S
AutoCAD SHX Text
PE
AutoCAD SHX Text
J
AutoCAD SHX Text
J
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
F1
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
AC
AutoCAD SHX Text
1
AutoCAD SHX Text
A
AutoCAD SHX Text
5
AutoCAD SHX Text
T
AutoCAD SHX Text
N
AutoCAD SHX Text
F
AutoCAD SHX Text
TP
AutoCAD SHX Text
T
AutoCAD SHX Text
f
AutoCAD SHX Text
1
AutoCAD SHX Text
a
AutoCAD SHX Text
b
AutoCAD SHX Text
F
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
ITEM
AutoCAD SHX Text
ITEM
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
16.33
AutoCAD SHX Text
SPECIFICATIONS
AutoCAD SHX Text
16.18
AutoCAD SHX Text
16.22
AutoCAD SHX Text
16.24
AutoCAD SHX Text
16.25
AutoCAD SHX Text
16.26
AutoCAD SHX Text
16.27
AutoCAD SHX Text
16.28
AutoCAD SHX Text
16.23
AutoCAD SHX Text
16.32
AutoCAD SHX Text
16.29
AutoCAD SHX Text
16.10
AutoCAD SHX Text
16.11
AutoCAD SHX Text
16.12
AutoCAD SHX Text
16.9
AutoCAD SHX Text
16.7
AutoCAD SHX Text
16.1
AutoCAD SHX Text
16.2
AutoCAD SHX Text
16.3
AutoCAD SHX Text
16.4
AutoCAD SHX Text
16.5
AutoCAD SHX Text
16.6
AutoCAD SHX Text
16.8
AutoCAD SHX Text
16.13
AutoCAD SHX Text
16.14
AutoCAD SHX Text
16.15
AutoCAD SHX Text
16.16
AutoCAD SHX Text
16.17
AutoCAD SHX Text
16.21
AutoCAD SHX Text
16.30
AutoCAD SHX Text
16.31
AutoCAD SHX Text
STANDARDS AND CODES: ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE : ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC), AS WELL AS ALL APPLICABLE STATE AND LOCAL CODES AND ORDINANCES. THIS DOES NOT RELIEVE THE CONTRACTOR FROM FURNISHING AND INSTALLING WORK SHOWN OR SPECIFIED WHICH MAY EXCEED THE REQUIREMENTS OF SUCH ORDINANCES, LAWS, REGULATIONS AND CODES. COMPLETE INSTALLATION: PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, TOOLS, ACCESSORIES, ETC., : PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, TOOLS, ACCESSORIES, ETC., NECESSARY TO ACCOMPLISH A COMPLETE ELECTRICAL SYSTEM IN ACCORDANCE WITH THE PLANS TOGETHER WITH THE SPECIFICATIONS. PERMITS: OBTAIN AND PAY FOR ALL BUILDING AND WORKING PERMITS AND INSPECTION FEES REQUIRED : OBTAIN AND PAY FOR ALL BUILDING AND WORKING PERMITS AND INSPECTION FEES REQUIRED FOR THIS PROJECT. DRAWINGS: DATA PRESENTED ON THESE DRAWINGS SHALL BE FIELD VERIFIED SINCE ALL DIMENSIONS, : DATA PRESENTED ON THESE DRAWINGS SHALL BE FIELD VERIFIED SINCE ALL DIMENSIONS, LOCATIONS, AND LEVELS ARE GOVERNED BY ACTUAL FIELD CONDITIONS. REVIEW ALL ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL AND SPECIALTY SYSTEMS DRAWINGS AND ADJUST ALL WORK TO MEET THE REQUIREMENTS ON CONDITIONS SHOWN THEREON, DO NOT SCALE ELECTRICAL PLANS FOR FIXTURE, DEVICE OR APPLIANCE LOCATIONS. USE CONFIGURED DIMENSIONS IF GIVEN OR CHECK ARCHITECTURAL OR MECHANICAL DRAWINGS. COPYRIGHT: THESE PLANS, SPECIFICATIONS AND ALL RELATED ADDENDA AND DOCUMENTS CONSTITUTE : THESE PLANS, SPECIFICATIONS AND ALL RELATED ADDENDA AND DOCUMENTS CONSTITUTE COPYRIGHT MATERIALS OF JP ENGINEERING. ALL RIGHTS CONFERRED BY THE COPYRIGHT AND SIMILAR LAWS ARE RESERVED TO JP ENGINEERING. THESE MATERIALS SHALL REMAIN THE SOLE PROPERTY OF JP ENGINEERING AND MAY NOT BE REPRODUCED, DISTRIBUTED TO OTHERS OR USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE PRIOR WRITTEN CONSENT OF JP ENGINEERING. LOCATIONS: INDICATED LOCATIONS OF ALL OUTLETS AND EQUIPMENT ARE SUBJECT TO CHANGE. : INDICATED LOCATIONS OF ALL OUTLETS AND EQUIPMENT ARE SUBJECT TO CHANGE. SHIFT/RELOCATE/RECONFIGURE ANY OUTLET, EQUIPMENT OR CONNECTION POINT UP TO 10' AS DIRECTED BY ENGINEER, AT NO ADDED COST. RECORD DRAWINGS: CONTRACTOR SHALL PROVIDE, PRIOR TO FINAL ACCEPTANCE AND OBSERVATION, : CONTRACTOR SHALL PROVIDE, PRIOR TO FINAL ACCEPTANCE AND OBSERVATION, ONE SET OF REVISED RECORD ELECTRICAL CONSTRUCTION DOCUMENTS ON REPRODUCIBLE MEDIUM INDICATING THE FOLLOWING ADDITIONAL INFORMATION: EXACT ROUTING OF ALL CONDUITS LARGER THAN 1'' EXACT LOCATION OF ALL SERVICE GROUNDING/BONDING CONNECTIONS CONTRACTORS NAME, ADDRESS AND TELEPHONE NUMBER RECORD NOTATIONS SHALL BE CLEARLY DRAWN AT A DRAFTING APPEARANCE EQUAL TO THE ORIGINAL DRAWINGS. CONTRACTOR SHALL ALSO PROVIDE ALL OPERATING AND MAINTENANCE MANUALS PRIOR TO FINAL PAYMENT. EXAMINATION OF SITE AND EXISTING CONDITIONS: BEFORE SUBMITTING A PROPOSAL, CONTRACTOR SHALL : BEFORE SUBMITTING A PROPOSAL, CONTRACTOR SHALL EXAMINE THE SITE AND FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND LIMITATIONS. NO EXTRAS WILL BE ALLOWED BECAUSE OF THE CONTRACTOR'S MISUNDERSTANDING OF THE AMOUNT OF WORK INVOLVED OR HIS LACK OF KNOWLEDGE OF ANY SITE CONDITIONS WHICH MAY AFFECT HIS WORK. ANY APPARENT VARIANCE OF THE DRAWINGS OR SPECIFICATIONS FROM THE EXISTING CONDITIONS AT THE SITE SHALL BE CALLED TO THE ATTENTION OF THE ENGINEER BEFORE SUBMITTING A PROPOSAL. EXISTING OUTLETS: EXISTING OUTLETS AND CIRCUITING NOT IN CONFLICT WITH NEW CONDITIONS SHALL : EXISTING OUTLETS AND CIRCUITING NOT IN CONFLICT WITH NEW CONDITIONS SHALL REMAIN. EXTEND OUTLETS TO NEW SURFACES, CAULK AND PROVIDE JUMBO PLATES AS REQUIRED TO PRESENT A SERVICEABLE AND FINISHED APPEARANCE. EXISTING SWITCHGEAR: REUSE EXISTING SWITCHGEAR AND PANELS IN PLACE WHERE SO INDICATED. : REUSE EXISTING SWITCHGEAR AND PANELS IN PLACE WHERE SO INDICATED. MODIFY AS REQUIRED TO ACCOMMODATE NEW WORK. PROVIDE NEW CIRCUIT BREAKERS AND/OR FUSES AS REQUIRED. REARRANGE EXISTING CIRCUITS WITHIN PANELS TO AGREE WITH NEW PANEL SCHEDULES. TRACE AND IDENTIFY ALL EXISTING CIRCUITS ON NEW RECORD PANEL SCHEDULES. DEMOLITION: PROVIDE COMPLETE ELECTRICAL DEMOLITION: REMOVE EXISTING OUTLETS AND EQUIPMENT IN : PROVIDE COMPLETE ELECTRICAL DEMOLITION: REMOVE EXISTING OUTLETS AND EQUIPMENT IN CONFLICT WITH NEW CONDITIONS. EXISTING CONDUITS REMOVED FROM SERVICE MAY BE ABANDONED IN PLACE IF IN A CONCEALED LOCATION. REMOVE ALL WIRE FROM ABANDONED RACEWAYS. CONTRACTOR SHALL INSURE CONTINUITY OF EXISTING CIRCUITING PASSING THROUGH DEMOLITION AREAS. EXTEND AND/OR RELOCATED AS NECESSARY. SHIFT/RELOCATE EXISTING EQUIPMENT AND CIRCUITING AS REQUIRED TO ACCOMMODATE NEW WORK. SALVAGE: ALL EXISTING EQUIPMENT REMOVED DURING THE COURSE OF THIS PROJECT SHALL BE : ALL EXISTING EQUIPMENT REMOVED DURING THE COURSE OF THIS PROJECT SHALL BE OFFERED TO OWNER FOR SALVAGE. ANY EQUIPMENT SELECTED BY OWNER SHALL BE DELIVERED TO OWNER ON SITE. ALL REMAINING EQUIPMENT BECOMES THE PROPERTY OF THIS CONTRACTOR AND SHALL BE REMOVED FROM THE SITE. TESTING: PRIOR TO PLACING IN SERVICE, ALL ELECTRICAL SYSTEMS SHALL BE TESTED FOR OPENS, : PRIOR TO PLACING IN SERVICE, ALL ELECTRICAL SYSTEMS SHALL BE TESTED FOR OPENS, GROUNDS, AND PHASE ROTATION. THE MAIN SERVICE GROUND AND ALL LOCAL TRANSFORMER MADE GROUNDS SHALL BE MEGGER-TESTED. GROUNDING: TEST EXISTING SERVICE NEUTRAL FOR ADEQUACY AND FOR GROUND CONTINUITY. GROUND : TEST EXISTING SERVICE NEUTRAL FOR ADEQUACY AND FOR GROUND CONTINUITY. GROUND ALL EQUIPMENT AND SYSTEM NEUTRAL IN ACCORDANCE WITH ARTICLE 250 OF THE NEC. EQUIPMENT GROUNDS HAVE NOT BEEN SHOWN ON DRAWINGS - WHERE GROUND WIRES HAVE BEEN SHOWN THEY INDICATE AN INSULATED GROUND. EQUIPMENT STANDARDS: ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND OF THE HIGHEST QUALITY : ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND OF THE HIGHEST QUALITY AVAILABLE ("SPECIFICATION GRADE"). SERVICE EQUIPMENT SHALL BE FACTORY-ASSEMBLED COMMERCIAL-GRADE, CONFIGURED PER SERVING UTILITY STANDARDS. WIRING DEVICES SHALL BE SPECIFICATION GRADE WITH NYLON PLATES, WHITE UNLESS OTHERWISE NOTED, RAISED STEEL BOX COVERS MAY BE USED IN UTILITY AREAS. MATCH EXISTING: EXISTING EQUIPMENT AND SYSTEMS SHALL BE CONSIDERED A MINIMUM STANDARD TO : EXISTING EQUIPMENT AND SYSTEMS SHALL BE CONSIDERED A MINIMUM STANDARD TO BE MET, IF NOT OTHERWISE EXCEEDED BY THESE PLANS AND SPECIFICATIONS. NEW MATERIALS AND EQUIPMENT SHALL MATCH EXISTING IN APPEARANCE AND FUNCTION. TAMPER-PROOF: ALL EQUIPMENT AND CIRCUITING ACCESSIBLE BY THE PUBLIC SHALL BE TAMPER- : ALL EQUIPMENT AND CIRCUITING ACCESSIBLE BY THE PUBLIC SHALL BE TAMPER- PROOF AND VANDAL RESISTANT. OPENABLE DEVICES AND EQUIPMENT SHALL BE PADLOCKABLE. DISTRIBUTION EQUIPMENT: DISTRIBUTION EQUIPMENT SHALL BE DEAD-FRONT, PANELBOARD OR : DISTRIBUTION EQUIPMENT SHALL BE DEAD-FRONT, PANELBOARD OR SWITCHBOARD TYPE AS INDICATED, UL-LABELED AND ENCLOSED IN A NEMA HOUSING APPROPRIATE TO ITS LOCATION AND APPLICATION WITH HINGED WIREWAY COVERS. BUSSING, DEVICE FINGERS AND LUGS SHALL BE COPPER UNLESS INDICATED ON DRAWINGS. AIC RATINGS SHOWN ON PLANS ARE MINIMUM RATINGS, CIRCUIT BREAKERS SHALL BE IN EXCESS OF THE AVAILABLE FAULT CURRENT. SERIES-RATING OF UPSTREAM AND DOWNSTREAM CIRCUIT BREAKERS TO ACHIEVE REQUIRED FAULT CURRENT RATINGS IS PROHIBITED UNLESS APPROVED BY ENGINEER IN WRITING. PANELBOARDS: PANELS SHALL HAVE FLUSH MONO-FLAT TRIM, LOCKING DOOR-IN-DOOR HINGED COVERS : PANELS SHALL HAVE FLUSH MONO-FLAT TRIM, LOCKING DOOR-IN-DOOR HINGED COVERS AND BOLT-ON CIRCUIT BREAKERS. FLUSH-MOUNTED PANELS SHALL HAVE EMPTY CONDUITS STUBBED TO ACCESSIBLE ATTIC SPACE: ONE 1'' CONDUIT FOR EACH FOUR SPARE/SPACE CIRCUITS. PROVIDE ONE TYPED AND ONE SPARE PANEL SCHEDULE FOR OWNER'S USE. SCHEDULES SHALL BE TWO COLUMN TYPE WITH ODD CIRCUIT NUMBERS ON THE LEFT AND EVEN NUMBERS ON THE RIGHT.
AutoCAD SHX Text
CODE COMPLIANCE: A. WORKING CLEARANCE: WORKING CLEARANCE: THE CONTRACTOR SHALL VERIFY THAT ALL ELECTRICAL EQUIPMENT MEETS THE CLEARANCE REQUIREMENTS OF NEC 110.26. DRAWINGS REPRESENT CLEARANCES ARE MET AS DESIGNED, ANY DEVIATION SHALL ALSO MEET THIS REQUIREMENT. ELECTRICAL SWITCHBOARDS RATED 1200 AMPS OR GREATER, IN EXCESS OF 6 FEET IN LENGTH, SHALL REQUIRE TWO (2) EXITS FROM THE ELECTRICAL ROOM UNLESS NEC 110.26(C)(2)(a) OR 110.26(C)(2)(6) ARE MET. B. TRANSFORMERS: TRANSFORMERS: TRANSFORMERS RATED GREATER THAN 112.5 KVA SHALL BE PLACED IN ELECTRICAL ROOMS WITH A 1-HOUR FIRE RATING PER NEC 450.21(B) WHERE THEY DO NOT MEET THE TRANSFORMER SECTION. TRANSFORMERS AS SPECIFIED IN THIS SECTION MEET NEC 450.21(B) EXCEPTION #2 AND ARE NOT REQUIRED TO BE PLACED IN A 1-HOUR RATED ROOM. CIRCUITING: ALL WIRING SHALL BE IN CONDUIT, MINIMUM 3/4"C, CONCEALED EXCEPT WHERE NOTED. EMT : ALL WIRING SHALL BE IN CONDUIT, MINIMUM 3/4"C, CONCEALED EXCEPT WHERE NOTED. EMT WITH STEEL SET SCREW INSULATED-THROAT FITTINGS MAY BE USED IN DRY, PROTECTED INTERIOR LOCATIONS. PVC SCHEDULE 40 SHALL BE USED BELOW GRADE AT MINIMUM -24''. WRAPPED RIGID ELBOWS AND RISERS SHALL BE USED FOR ALL THROUGH-GRADE TRANSITIONS AND STUB-UPS. RGS OR IMC CONDUIT WITH THREADED FITTINGS SHALL BE USED IN ALL LOCATIONS WHERE EXPOSED TO THE ELEMENTS OR SUBJECT TO PHYSICAL DAMAGE. METAL-CLAD CABLE (TYPE MC) WILL BE ACCEPTABLE FOR SINGLE CIRCUIT BRANCH CIRCUITING, FLEXIBLE WHIPS FROM JUNCTION BOXES TO LIGHTING FIXTURES (MAXIMUM OF 6'-0''), WITHIN CASEWORK AND ACCESSIBLE AREAS ONLY. TYPE MC CABLE MAY NOT BE USED FOR HOMERUNS. ENT IS NOT ALLOWED. CONNECT RECESSED AND SUSPENDED LIGHTING FIXTURES, MOTORIZED AND VIBRATING EQUIPMENT WITH STEEL FLEX. ALL CONDUIT SHALL HAVE PULL CORD IF OTHERWISE EMPTY. WIRING: WIRE SHALL BE COPPER UNLESS OTHERWISE INDICATED. MINIMUM WIRE SIZE SHALL BE #12 AWG. : WIRE SHALL BE COPPER UNLESS OTHERWISE INDICATED. MINIMUM WIRE SIZE SHALL BE #12 AWG. INSULATION SHALL BE THW, THWN OR THHN. FUSES: FUSES SHALL BE SIZED PER ACTUAL NAMEPLATE OF EQUIPMENT SERVED. FUSES SHALL BE : FUSES SHALL BE SIZED PER ACTUAL NAMEPLATE OF EQUIPMENT SERVED. FUSES SHALL BE DUAL-ELEMENT, CURRENT-LIMITING, AND SHALL BE INTERCHANGEABLE BETWEEN FRAME SIZES WITH STANDARD FACTORY FUSE REDUCERS. FUSES SHALL BE AS FOLLOWS UNLESS OTHERWISE INDICATED: a. CIRCUITS 601 TO 6000 AMPERES SHALL BE PROTECTED BY CURRENT LIMITING BUSSMANN LOW-PEAK TIME-DELAY FUSES KRP-C - UL CLASS L b. CIRCUITS 0 TO 600 AMPERES SHALL BE PROTECTED BY CURRENT LIMITING BUSSMANN LOW-PEAK DUAL-ELEMENT FUSES LPN-RK (250 VOLTS) OR LPS-RK (600 VOLTS) - UL CLASS RK1 c. ALL INDIVIDUAL MOTOR CIRCUITS RATED 480 AMPERES OR LESS SHALL BE PROTECTED BY BUSSMANN LOW-PEAK DUAL-ELEMENT FUSES LPN-RK (250 VOLTS) OR LPS-RK (600 VOLTS) - UL CLASS RK1 OR L d. CIRCUIT BREAKER PANELS SHALL BE PROTECTED BY BUSSMANN LOW-PEAK DUAL-ELEMENT FUSES LPN-RK (250 VOLTS), LPS-RK (600 VOLTS) OR BUSSMANN LOW-PEAK KRP-C TIME-DELAY FUSES - UL CLASS RK1 OR L e. ALL DUAL-ELEMENT FUSES SHALL HAVE SEPARATE OVERLOAD AND SHORT-CIRCUIT ELEMENTS. f. PROVIDE SPARE FUSE CABINET AFTER THE COMPLETION OF THE PROJECT WITH ONE SET OF SPARE FUSES FOR EVERY SIZE USED. UTILITY SERVICES: PROVIDE POWER AND COMMUNICATIONS SYSTEM SERVICES IN ACCORDANCE WITH THE : PROVIDE POWER AND COMMUNICATIONS SYSTEM SERVICES IN ACCORDANCE WITH THE REQUIREMENTS OF THE SERVING UTILITIES. PROVIDE EXCAVATION, RACEWAY, STRUCTURES, GROUNDING, ETC. AS REQUIRED. CONTACT SERVING UTILITIES AND OBTAIN THEIR PROJECT SPECIFIC REQUIREMENTS PRIOR TO BID. UTILITY WORK INDICATED HEREIN IS FOR BIDDING ASSISTANCE ONLY. THESE PLANS DO NOT PURPORT TO INDICATE ALL WORK REQUIRED. (UTILITY SERVICE CHARGES PAID BY OTHERS) TEMPORARY CONSTRUCTION POWER: PROVIDE TEMPORARY ELECTRICAL POWER AND LIGHTING FOR ALL : PROVIDE TEMPORARY ELECTRICAL POWER AND LIGHTING FOR ALL TRADES THAT REQUIRE SERVICE DURING THE COURSE OF THIS PROJECT. PROVIDE TEMPORARY SERVICE AND DISTRIBUTION AS REQUIRED. COMPLY WITH THE NEC AND OSHA REQUIREMENTS. (ENERGY COSTS BY OTHERS). SUBMITTALS: BEFORE ORDERING ANY EQUIPMENT, CONTRACTOR SHALL SUBMIT SIX COPIES OF FACTORY : BEFORE ORDERING ANY EQUIPMENT, CONTRACTOR SHALL SUBMIT SIX COPIES OF FACTORY SHOP DRAWINGS FOR ALL LIGHTING FIXTURES, SWITCHGEAR, PANELS, MOTOR CONTROLLERS, WIRING DEVICES, ETC. PROPOSED FOR THIS PROJECT. SUBSTITUTIONS: PROPOSED SUBSTITUTIONS SHALL BE EQUAL OR SUPERIOR TO SPECIFIED ITEMS IN ALL : PROPOSED SUBSTITUTIONS SHALL BE EQUAL OR SUPERIOR TO SPECIFIED ITEMS IN ALL RESPECTS. DETERMINATION OF EQUALITY RESTS SOLELY WITH ENGINEER. SUBSTITUTIONS MUST BE SUBSTITUTIONS MUST BE SUBMITTED A MINIMUM OF 10 WORKING DAYS PRIOR TO BID FOR CONSIDERATION. PROPOSED PROPOSED SUBSTITUTIONS PROVIDED LATER WILL NOT BE REVIEWED OR ALLOWED. BID SUBSTITUTED MATERIAL WILL ONLY BE ALLOWED IF ACCEPTED IN WRITING BY ENGINEER. IDENTIFICATION: PROVIDE ENGRAVED NAMEPLATES FOR ALL SWITCHBOARDS, PANELS, TRANSFORMERS, : PROVIDE ENGRAVED NAMEPLATES FOR ALL SWITCHBOARDS, PANELS, TRANSFORMERS, DISCONNECTS, MOTOR STARTERS, CONTACTORS, TIME SWITCHES AND CABINETS. NAMEPLATES SHALL INCLUDE THE FOLLOWING INFORMATION AS APPLICABLE: DESIGNATION (i.e. PANEL A) FUNCTION (i.e. AIR HANDLER AH-1) VOLTAGE, PHASE, WIRE (i.e. 480 VOLT, 3 , 4W.)FEEDER SIZE (i.e. 4-#4/0 THWN CU IN 2'' C.) SOURCE (i.e. SWITCHBOARD MSB) NAMEPLATES SHALL BE WHITE LETTERS ON BLACK FOR NORMAL EQUIPMENT AND WHITE LETTERS ON RED FOR EMERGENCY EQUIPMENT. GUARANTEE: THE COMPLETE ELECTRICAL SYSTEM, AND ALL PORTIONS THEREOF, SHALL BE GUARANTEED : THE COMPLETE ELECTRICAL SYSTEM, AND ALL PORTIONS THEREOF, SHALL BE GUARANTEED TO BE FREE FROM DEFECTS IN WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE. PROMPTLY REMEDY SUCH DEFECTS AND ANY SUBSEQUENT DAMAGE CAUSED BY THE DEFECTS OR REPAIR THEREOF AT NO EXPENSE TO THE OWNER. LAMPS ARE EXEMPT FROM THIS GUARANTEE, BUT SHALL BE NEW AT TIME OF FINAL ACCEPTANCE. SUSPENDED CEILING SYSTEMS: ALL LAY-IN FIXTURES SHALL BE INDEPENDENTLY SUPPORTED BY TWO #12 : ALL LAY-IN FIXTURES SHALL BE INDEPENDENTLY SUPPORTED BY TWO #12 SLACK WIRES ATTACHED TO TWO OPPOSITE CORNERS OF THE FIXTURE PER UBC & NEC REQUIREMENTS. THESE WIRES SHALL BE SECURED TO THE STRUCTURAL FRAMING SUCH THAT FAILURE OF THE SUSPENDED CEILING SHALL NOT ALLOW THE FIXTURE TO DROP. COORDINATION: THE CIVIL, ARCHITECTURAL, MECHANICAL, KITCHEN AND INTERIOR DRAWINGS CONTAIN : THE CIVIL, ARCHITECTURAL, MECHANICAL, KITCHEN AND INTERIOR DRAWINGS CONTAIN DETAIL DESCRIPTIONS, CIRCUITING AND CONNECTION REQUIREMENTS WHICH ARE PART OF DIVISION 16 RESPONSIBILITIES. ELECTRICAL CONTRACTOR SHOULD NOT SUBMIT BIDS ON THIS PROJECT BEFORE REVIEWING ALL PROJECT DRAWINGS, SPECIFICATIONS AND ADDENDA. ALL PROJECT DRAWINGS, SPECIFICATIONS AND ADDENDA. PROJECT DRAWINGS, SPECIFICATIONS AND ADDENDA. FIRE ALARM: EXISTING FIRE ALARM SYSTEM TO REMAIN: MAINTAIN IN CONSTANT OPERATION DURING THIS : EXISTING FIRE ALARM SYSTEM TO REMAIN: MAINTAIN IN CONSTANT OPERATION DURING THIS PROJECT. NEW COMPONENTS AND CIRCUITING SHALL BE FACTORY-CERTIFIED AS BEING PROJECT-SPECIFIC COMPATIBLE WITH EXISTING SYSTEM. ALL CONNECTIONS TO EXISTING SYSTEM SHALL BE PERFORMED BY FACTORY-CERTIFIED TECHNICIAN AND SHALL BE ACCEPTED BY OWNER'S SYSTEM- MONITORING AGENCY. PLANS DO NOT INDICATE ALL DEVICES, CONNECTIONS OR CIRCUITING REQUIRED FOR A COMPLETE SYSTEM. SUBMIT PROPOSED DESIGN TO THE FIRE MARSHAL AND RECEIVE APPROVAL PRIOR TO ROUGH-IN. ONGOING OPERATION: CONDUCT WORK TO MINIMIZE DISRUPTION OF OWNER'S ONGOING OPERATIONS. : CONDUCT WORK TO MINIMIZE DISRUPTION OF OWNER'S ONGOING OPERATIONS. PROVIDE BARRICADES, NOISE ABATEMENT AND DUST CONTAINMENT MEASURES TO ENSURE THE SAFETY AND COMFORT OF PATRONS, STAFF AND WORKERS. INTERRUPTIONS OF EXISTING POWER, COMMUNICATIONS OR FIRE ALARM SYSTEMS SHALL BE PERFORMED ONLY AT SUCH TIMES AS DIRECTED BY RESIDENT ENGINEER. OUTAGES SHALL BE MOMENTARY IN NATURE. EACH SUCH OUTAGE (OR OPERATION WHICH MAY POSE RISK OF AN ACCIDENTAL OUTAGE) SHALL BE SCHEDULED 48 HOURS IN ADVANCE.
AutoCAD SHX Text
16.19
AutoCAD SHX Text
16.20
AutoCAD SHX Text
No.E16851
AutoCAD SHX Text
1/8/2020
Page 10: DRAWING INDEX...SERVER ROOM HVAC RETROFIT INYO ANNEX BUILDING 168 N EDWARDS ST. INDEPENDENCE, CA DRAWING INDEX VICINITY MAP SCOPE OF WORK MECHANICAL ENGINEER BRANDON ETCHEMENDY PE

480/277V, 3PH, 4W, 1200A

(E) SERVICE ENTRANCE SE

SOLAR

ARRAY

MONITORING

(E) (E)

PANEL

S-B

(E)

LIGHTING

PANEL

(E)

PANEL

CH-HSF

(E)

PANEL

MSB6

(E)

(E)

ELEVATOR

PANEL

X

(E)

PANEL

CC

(E)

PANEL

IS

(E)

job number

drawn

checked

EEI #19030

DRAWING TITLE

REVISIONS

10597 DOUBLE R BLVD RENO, NV 89521P. 775-853-1131 F. 775-852-2352

[email protected]

date

JPS

JPS

10597 Double R Blvd, Ste. 1

Reno, Nevada 89521

P: 775.852.2337

F: 775.852.2352

JP #19070

E T C H E M E N D YE N G I N E E R I N GI N C

*

*

R

E

G

IS

T

E

R

E

D

P

R

O

F

E

S

S

ION

A

L

E

N

G

I

N

E

E

R

S

T

A

T

E

O F

C

A

L

I

F

O

R

N

I

A

JA

M

E

S

P

.

SO

L

A

R

O

E

L

E

CT

R

I

C

A

L

E

x

p

:

1

2

/

3

1

/

2

0

1/10/2020

SERVER R

OO

M H

VAC R

ETR

OFIT

INYO

AN

NEX B

UIL

DIN

G16

8 N

ED

WARD

S S

T.IN

DEPEN

DEN

CE, CALIF

ORN

IA

E0.2IT

SINGLE LINEDIAGRAM

AutoCAD SHX Text
M
AutoCAD SHX Text
800 AT
AutoCAD SHX Text
800 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
150 AT
AutoCAD SHX Text
150 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
60 AT
AutoCAD SHX Text
60 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E) SECONDARY
AutoCAD SHX Text
S
AutoCAD SHX Text
NEUT
AutoCAD SHX Text
GND
AutoCAD SHX Text
(E) PRIMARY
AutoCAD SHX Text
(E) GROUND
AutoCAD SHX Text
P
AutoCAD SHX Text
PAD MOUNTED TRANSFORMER
AutoCAD SHX Text
EXISTING LADWP
AutoCAD SHX Text
(E) TELEPHONE
AutoCAD SHX Text
PRIMARY
AutoCAD SHX Text
BLDG. STEEL
AutoCAD SHX Text
C.W.
AutoCAD SHX Text
(E) GROUND
AutoCAD SHX Text
(E) GROUND
AutoCAD SHX Text
(E) GROUND
AutoCAD SHX Text
COMMUNICATION
AutoCAD SHX Text
BACKBOARD
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
SINGLE LINE DIAGRAM
AutoCAD SHX Text
A
AutoCAD SHX Text
E0.2IT
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
60 AT
AutoCAD SHX Text
60 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
20 AT
AutoCAD SHX Text
20 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
400 AT
AutoCAD SHX Text
400 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
400 AT
AutoCAD SHX Text
400 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
400 AT
AutoCAD SHX Text
400 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
600 AT
AutoCAD SHX Text
600 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
150 AT
AutoCAD SHX Text
150 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
150 AT
AutoCAD SHX Text
150 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
T
AutoCAD SHX Text
(E)
AutoCAD SHX Text
T
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E) TRANSFORMER TX-MB
AutoCAD SHX Text
(E) TRANSFORMER TX-HB
AutoCAD SHX Text
600 AT
AutoCAD SHX Text
600 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
50 AT
AutoCAD SHX Text
50 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
225 AT
AutoCAD SHX Text
225 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
175 AT
AutoCAD SHX Text
175 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
450 AT
AutoCAD SHX Text
450 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
175 AT
AutoCAD SHX Text
175 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
20 AT
AutoCAD SHX Text
20 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
40 AT
AutoCAD SHX Text
40 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
20 AT
AutoCAD SHX Text
20 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
20 AT
AutoCAD SHX Text
20 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
20 AT
AutoCAD SHX Text
20 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
T
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E) TRANSFORMER T-X
AutoCAD SHX Text
300kVA
AutoCAD SHX Text
480V - 208/120V
AutoCAD SHX Text
(E)
AutoCAD SHX Text
CHILLER
AutoCAD SHX Text
F
AutoCAD SHX Text
(E)
AutoCAD SHX Text
CONDENSER
AutoCAD SHX Text
F
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
CW
AutoCAD SHX Text
PUMP
AutoCAD SHX Text
F
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
HW
AutoCAD SHX Text
PUMP
AutoCAD SHX Text
F
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
FAN
AutoCAD SHX Text
F
AutoCAD SHX Text
(E)
AutoCAD SHX Text
ASSESSOR'S
AutoCAD SHX Text
& INFORMATION
AutoCAD SHX Text
SERVICES
AutoCAD SHX Text
25 AT
AutoCAD SHX Text
25 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
AC2
AutoCAD SHX Text
FAN
AutoCAD SHX Text
F
AutoCAD SHX Text
(E)
AutoCAD SHX Text
20 AT
AutoCAD SHX Text
20 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
AC3
AutoCAD SHX Text
FAN
AutoCAD SHX Text
F
AutoCAD SHX Text
(E)
AutoCAD SHX Text
20 AT
AutoCAD SHX Text
20 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
AC5
AutoCAD SHX Text
FAN
AutoCAD SHX Text
F
AutoCAD SHX Text
(E)
AutoCAD SHX Text
20 AT
AutoCAD SHX Text
20 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
AC6
AutoCAD SHX Text
FAN
AutoCAD SHX Text
F
AutoCAD SHX Text
(E)
AutoCAD SHX Text
20 AT
AutoCAD SHX Text
20 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
AC7
AutoCAD SHX Text
FAN
AutoCAD SHX Text
F
AutoCAD SHX Text
(E)
AutoCAD SHX Text
20 AT
AutoCAD SHX Text
20 AF
AutoCAD SHX Text
3P
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
AC8
AutoCAD SHX Text
FAN
AutoCAD SHX Text
F
AutoCAD SHX Text
(E)
AutoCAD SHX Text
(E)
AutoCAD SHX Text
XCR
AutoCAD SHX Text
F
AutoCAD SHX Text
(E)
AutoCAD SHX Text
2 1/2''C. W/
AutoCAD SHX Text
(4) #250K THWN CU
AutoCAD SHX Text
(1) #4 GND
AutoCAD SHX Text
NEW
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
250 A
AutoCAD SHX Text
42 CIR
AutoCAD SHX Text
ANNEX MECHANICAL RM.
AutoCAD SHX Text
EM
AutoCAD SHX Text
(E)
AutoCAD SHX Text
NEW NEMA 3R 225/3
AutoCAD SHX Text
MANUAL TRANSFER SW.
AutoCAD SHX Text
(E)
AutoCAD SHX Text
PROVIDE LANDING LUGS
AutoCAD SHX Text
FOR TEMPORARY GENERATOR
AutoCAD SHX Text
2 1/2''C. W/
AutoCAD SHX Text
(4) #250K THWN CU
AutoCAD SHX Text
(1) #4 GND
AutoCAD SHX Text
No.E16851
AutoCAD SHX Text
1/8/2020
Page 11: DRAWING INDEX...SERVER ROOM HVAC RETROFIT INYO ANNEX BUILDING 168 N EDWARDS ST. INDEPENDENCE, CA DRAWING INDEX VICINITY MAP SCOPE OF WORK MECHANICAL ENGINEER BRANDON ETCHEMENDY PE

job number

drawn

checked

EEI #19030

DRAWING TITLE

REVISIONS

10597 DOUBLE R BLVD RENO, NV 89521P. 775-853-1131 F. 775-852-2352

[email protected]

date

JPS

JPS

10597 Double R Blvd, Ste. 1

Reno, Nevada 89521

P: 775.852.2337

F: 775.852.2352

JP #19070

E T C H E M E N D YE N G I N E E R I N GI N C

*

*

R

E

G

IS

T

E

R

E

D

P

R

O

F

E

S

S

ION

A

L

E

N

G

I

N

E

E

R

S

T

A

T

E

O F

C

A

L

I

F

O

R

N

I

A

JA

M

E

S

P

.

SO

L

A

R

O

E

L

E

CT

R

I

C

A

L

E

x

p

:

1

2

/

3

1

/

2

0

1/10/2020

SERVER R

OO

M H

VAC R

ETR

OFIT

INYO

AN

NEX B

UIL

DIN

G16

8 N

ED

WARD

S S

T.IN

DEPEN

DEN

CE, CALIF

ORN

IA

E1.1IT

ELECTRICALDEMOLITION

PLAN

AutoCAD SHX Text
BOILER/BUILDING CONTROLS
AutoCAD SHX Text
COPY ROOM
AutoCAD SHX Text
INFORMATION SERVICES
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
COMPUTER ROOM
AutoCAD SHX Text
UTILITY
AutoCAD SHX Text
TELEPHONE SERVICE
AutoCAD SHX Text
SHULTS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
ELECTRICAL DEMOLITION PLAN
AutoCAD SHX Text
A
AutoCAD SHX Text
E1.1IT
AutoCAD SHX Text
1/4" = 1'-0"
AutoCAD SHX Text
CU
AutoCAD SHX Text
CU
AutoCAD SHX Text
(X)
AutoCAD SHX Text
(X)
AutoCAD SHX Text
No.E16851
AutoCAD SHX Text
1/8/2020
Page 12: DRAWING INDEX...SERVER ROOM HVAC RETROFIT INYO ANNEX BUILDING 168 N EDWARDS ST. INDEPENDENCE, CA DRAWING INDEX VICINITY MAP SCOPE OF WORK MECHANICAL ENGINEER BRANDON ETCHEMENDY PE

job number

drawn

checked

EEI #19030

DRAWING TITLE

REVISIONS

10597 DOUBLE R BLVD RENO, NV 89521P. 775-853-1131 F. 775-852-2352

[email protected]

date

JPS

JPS

10597 Double R Blvd, Ste. 1

Reno, Nevada 89521

P: 775.852.2337

F: 775.852.2352

JP #19070

E T C H E M E N D YE N G I N E E R I N GI N C

*

*

R

E

G

IS

T

E

R

E

D

P

R

O

F

E

S

S

ION

A

L

E

N

G

I

N

E

E

R

S

T

A

T

E

O F

C

A

L

I

F

O

R

N

I

A

JA

M

E

S

P

.

SO

L

A

R

O

E

L

E

CT

R

I

C

A

L

E

x

p

:

1

2

/

3

1

/

2

0

1/10/2020

SERVER R

OO

M H

VAC R

ETR

OFIT

INYO

AN

NEX B

UIL

DIN

G16

8 N

ED

WARD

S S

T.IN

DEPEN

DEN

CE, CALIF

ORN

IA

E2.1IT

ELECTRICALPLAN

AutoCAD SHX Text
BOILER/BUILDING CONTROLS
AutoCAD SHX Text
COPY ROOM
AutoCAD SHX Text
INFORMATION SERVICES
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
COMPUTER ROOM
AutoCAD SHX Text
UTILITY
AutoCAD SHX Text
TELEPHONE SERVICE
AutoCAD SHX Text
SHULTS
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
ELECTRICAL PLAN
AutoCAD SHX Text
A
AutoCAD SHX Text
E2.1IT
AutoCAD SHX Text
1/4" = 1'-0"
AutoCAD SHX Text
HP
AutoCAD SHX Text
2
AutoCAD SHX Text
HP
AutoCAD SHX Text
1
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
AHU
AutoCAD SHX Text
4
AutoCAD SHX Text
F
AutoCAD SHX Text
T
AutoCAD SHX Text
(E) PANEL X
AutoCAD SHX Text
(E) TRANSFORMER
AutoCAD SHX Text
(E) PANEL CHA-HSP
AutoCAD SHX Text
NEW PANEL EM
AutoCAD SHX Text
30/2
AutoCAD SHX Text
FPEN
AutoCAD SHX Text
EM-[1,3]G
AutoCAD SHX Text
(2) #6 Cu, (1) #10 GND
AutoCAD SHX Text
IN 1''C.
AutoCAD SHX Text
60/2
AutoCAD SHX Text
FPEN
AutoCAD SHX Text
WP
AutoCAD SHX Text
EM-[5,7]G
AutoCAD SHX Text
(2) #6 Cu, (1) #10 GND
AutoCAD SHX Text
IN 1''C.
AutoCAD SHX Text
60/2
AutoCAD SHX Text
FPEN
AutoCAD SHX Text
WP
AutoCAD SHX Text
WITH THE ACCEPTANCE OF ALTERNATE #2, INTERCEPT THE EXISTING FEEDERS TO PANEL CC AT THIS LOCATION. WITH THE ACCEPTANCE OF ALTERNATE #2, PROVIDE A NEW FEEDER PER THE SINGLE LINE DIAGRAM.
AutoCAD SHX Text
SHEET NOTES
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
(E) PANEL CC
AutoCAD SHX Text
J
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
AHU
AutoCAD SHX Text
1
AutoCAD SHX Text
F
AutoCAD SHX Text
30/2
AutoCAD SHX Text
FPEN
AutoCAD SHX Text
AHU
AutoCAD SHX Text
2
AutoCAD SHX Text
F
AutoCAD SHX Text
30/2
AutoCAD SHX Text
FPEN
AutoCAD SHX Text
AHU
AutoCAD SHX Text
3
AutoCAD SHX Text
F
AutoCAD SHX Text
30/2
AutoCAD SHX Text
FPEN
AutoCAD SHX Text
(ON PLATFORM)
AutoCAD SHX Text
(ON PLATFORM)
AutoCAD SHX Text
CU
AutoCAD SHX Text
1
AutoCAD SHX Text
F
AutoCAD SHX Text
EM-[9,11]G
AutoCAD SHX Text
(2) #6 Cu, (1) #10 GND
AutoCAD SHX Text
IN 1''C.
AutoCAD SHX Text
60/2
AutoCAD SHX Text
FPEN
AutoCAD SHX Text
WP
AutoCAD SHX Text
EM-[4,6]G
AutoCAD SHX Text
NEW NEMA 3R MANUAL TRANSFER SW.
AutoCAD SHX Text
No.E16851
AutoCAD SHX Text
1/8/2020