Page 1: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

BACnet Gateway V0CTRL86P

Lennox VRF, Mini-VRF and Mini-Split

©2017 Lennox Industries Inc. Dallas, Texas, USA

Installation and Application Guide

CONTROLS 507594-0403/2017

Page 2: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

2

Equipment List

GeneralThe Lennox VRF, Mini-VRF and Mini-Split BACnet Gateway allows connection of those systems to a building management system (BMS) using BACnet protocols.

Package 1 of 1 consists of:1 - BACnet gateway1 - Instruction and Application Guide

THIS MANUAL MUST BE LEFT WITH THE OWNER FOR FUTURE REFERENCE

Network SettingThere is an Ethernet interface in the device (Eth0). The factory-set device address is 192.168.1.8.

SecurityDefault Admin User Name: adminDefault Admin Password: 12345

ContentsEquipment List . . . . . . . . . . . . . . . . . 2General . . . . . . . . . . . . . . . . . . . . . 2Network Setting . . . . . . . . . . . . . . . . . 2Security . . . . . . . . . . . . . . . . . . . . . 2Specifi cations . . . . . . . . . . . . . . . . . . 2System Connections . . . . . . . . . . . . . . 3BACnet Object Points List . . . . . . . . . . . 14Indoor Unit Instance Number Description. . . . 15Indoor Unit Points . . . . . . . . . . . . . . . . 16Outdoor Unit Instance Number Description . . . 21Outdoor Unit Points . . . . . . . . . . . . . . . 23Appendix A. BACnet Protocol Observed . . . . 27Appendix B. Indoor Unit Detailed Points . . . . 28Appendix C. Outdoor Unit Detailed Points . . . 38

Function DescriptionInput Supply Power 24VAC

BACnet Connection BACnet/IP

I/O 4 port 485 interfaceOperating Temperature Range

32°F ~ 122°F(0°C ~ 50°C)

Operating Humidity Range (Rh)

25% ~ 90%

Dimensions10-1/2 in. X 10 in. X 2-3/8 in. (26 cm X 25 cm X 6 cm)

Specifi cations

WARNINGImproper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.

CAUTIONBefore attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.

IMPORTANTThese instructions are intended as a general guide and do not supersede local codes in any way. Consult au-thorities having jurisdiction before installation. Read all of the information in this manual before operating this equipment.

WARNINGDo not operate device with wet hands.

CAUTIONDo not install device in areas where heavy oil, vapor, or gases containing sulfur may exist or the controller may be damaged.

CAUTIONClean device using a clean, damp cloth. Do not spray cleanser on or around device.

NOTE - Outdoor unit control & monitoring points are not available for Mini-Split systems. -1P Mini-VRF systems require the Mini-VRF Control Interface V0CTRL00P-1.

Page 3: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

3

The BACnet instance number is a four-digit number that identifi es the BACnet gateway bus (port), the type of unit (indoor unit or outdoor unit) and the unit’s address. Device ID = XXXX

X X X XBACnet Bus (Port) Number Unit Type Unit Address

(0-3)0 Indoor Unit (Indoor Unit 0-63)

(Outdoor Unit 0-31)1 Outdoor UnitExample - 0001 indicates BACnet device number 0, indoor unit type, indoor unit number 01.

System Connections

EthernetConnection Bus 0 Bus 1 Bus 2 Bus 3

Figure 1. VRF BACnet Gateway Connection Points

Page 4: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

4

BAC

net

Gat

eway BA

Cne

t/IP

Net

wor

k

VRF

Hea

t Pum

pSy

stem

BMS

VRF

Hea

t Pum

pSy

stem

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

K1K2

E O

utdo

or U

nit

Info

rmat

ion

(Poi

nts)

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

K1K2

E O

utdo

or U

nit

Info

rmat

ion

(Poi

nts)

PQE

PQE

NOTE

- Fi

eld-

supp

lied

com

mun

icat

ion

wiri

ng -

18 G

A., s

trand

ed, 3

-con

duct

or, s

hiel

ded

cont

rol w

ire (p

olar

ity s

ensi

tive)

. All

shie

lds

of s

hiel

ded

cabl

e co

nnec

t to

GR

OU

ND

term

inal

, not

to E

.

NOTE

- M

axim

um 9

6 ou

tdoo

r uni

ts p

er d

evic

e. U

p to

24

OD

Us

(K1K

2E c

onne

ctio

n re

quire

d) p

er b

us. (

VRF

& M

ini-V

RF

Syst

ems

only

) M

axim

um 2

56 in

door

uni

ts p

er d

evic

e. U

p to

64

IDU

s pe

r bus

. (Al

l Sys

tem

s)

NOTE

- VR

F H

eat P

ump

PQE

wiri

ng c

onfig

urat

ion

show

n. X

YE w

iring

con

figur

atio

n is

sam

e fo

r VR

F H

eat P

ump

and

VRF

Hea

t Rec

over

y sy

stem

s.

No

mon

itorin

g po

ints

are

ava

ilabl

e fo

r MS

Boxe

s.NO

TE -

Each

VR

F R

efrig

eran

t sys

tem

is li

mite

d to

63

IDU

s.

Figure 2. VRF System Indoor and Outdoor Unit Monitoring

Page 5: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

5

BAC

net

Gat

eway

BAC

net/I

P N

etw

ork

VRF

Hea

t Pum

pSy

stem

BMS

VRF

Hea

t Pum

pSy

stem

VRF

Hea

t Pum

pSy

stem

VRF

Hea

t Pum

pSy

stem

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

XYE XY

E

XYE

PQE

PQE

PQE

PQE

NO

TE -

Fiel

d-su

pplie

d co

mm

unic

atio

n w

iring

- 18

GA.

, stra

nded

, 3-c

ondu

ctor

, shi

elde

d co

ntro

l wire

(pol

arity

sen

sitiv

e). A

ll sh

ield

s of

shi

elde

d ca

ble

conn

ect t

o G

RO

UN

D te

rmin

al, n

ot to

E.

NO

TE -

Max

imum

96

outd

oor u

nits

per

dev

ice.

Up

to 2

4 O

DU

s (K

1K2E

con

nect

ion

requ

ired)

per

bus

. (V

RF

& M

ini-V

RF

Sys

tem

s on

ly)

Max

imum

256

indo

or u

nits

per

dev

ice.

Up

to 6

4 ID

Us

per b

us. (

All

Sys

tem

s)

NO

TE -

VR

F H

eat P

ump

PQ

E w

iring

con

figur

atio

n sh

own.

XY

E w

iring

con

figur

atio

n is

sam

e fo

r VR

F H

eat P

ump

and

VR

F H

eat R

ecov

ery

syst

ems.

N

o m

onito

ring

poin

ts a

re a

vaila

ble

for M

S B

oxes

.N

OTE

- E

ach

VR

F R

efrig

eran

t sys

tem

is li

mite

d to

63

IDU

s.

Figure 3. VRF System Indoor Unit Only Monitoring

Page 6: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

6

PQE

PQE

PQE

PQE

PQE

PQE

PQE

PQEPQ

E

PQE

PQE

PQE

PQE

PQE

BAC

net

Gat

eway BA

Cne

t/IP

Net

wor

k

VRF

Hea

t Rec

over

ySy

stem

BMS

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

K1K2

E O

utdo

or U

nit

Info

rmat

ion

(Poi

nts)

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

K1K2

E O

utdo

or U

nit

Info

rmat

ion

(Poi

nts)

PQE

VRF

Hea

t Rec

over

ySy

stem

PQE

PQE

PQE

NOTE

- Fi

eld-

supp

lied

com

mun

icat

ion

wiri

ng -

18 G

A., s

trand

ed, 3

-con

duct

or, s

hiel

ded

cont

rol w

ire (p

olar

ity s

ensi

tive)

. All

shie

lds

of s

hiel

ded

cabl

e co

nnec

t to

GR

OU

ND

term

inal

, not

to E

.

NOTE

- M

axim

um 9

6 ou

tdoo

r uni

ts p

er d

evic

e. U

p to

24

OD

Us

(K1K

2E c

onne

ctio

n re

quire

d) p

er b

us. (

VRF

& M

ini-V

RF

Syst

ems

only

) M

axim

um 2

56 in

door

uni

ts p

er d

evic

e. U

p to

64

IDU

s pe

r bus

. (Al

l Sys

tem

s)

NOTE

- VR

F H

eat R

ecov

ery

PQE

wiri

ng c

onfig

urat

ion

show

n. X

YE w

iring

con

figur

atio

n is

sam

e fo

r VR

F H

eat P

ump

and

VRF

Hea

t Rec

over

y sy

stem

s. N

o m

onito

ring

poin

ts a

re a

vaila

ble

for M

S Bo

xes.

NOTE

- Ea

ch V

RF

Ref

riger

ant s

yste

m is

lim

ited

to 6

3 ID

Us.

PQE

PQE

Figure 4. VRF Heat Recovery System Indoor and Outdoor Unit Monitoring

Page 7: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

7

BAC

net

Gat

eway BA

Cne

t/IP

Net

wor

k

-1P

Min

i-VR

F Sy

stem

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

-1P

Min

i-VR

F Sy

stem

-1P

Min

i-VR

F Sy

stem

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

-1P

Min

i-VR

F Sy

stem

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

PQE

PQE

PQE

PQE

NOTE

- O

utdo

or u

nit c

ontro

l & m

onito

ring

poin

ts fo

r -1P

Min

i-VRF

sys

tem

s re

quire

the

Min

i-VRF

Con

trol

Inte

rface

V0C

TRL0

0P-1

.

NOTE

- Fi

eld-

supp

lied

com

mun

icatio

n wi

ring

- 18

GA.

, stra

nded

, 3-c

ondu

ctor

, shi

elde

d co

ntro

l wire

(pol

arity

sen

sitive

). Al

l shi

elds

of s

hiel

ded

cabl

e co

nnec

t to

GRO

UND

term

inal

, not

to E

.

NOTE

- M

axim

um 9

6 ou

tdoo

r uni

ts p

er d

evice

. Up

to 2

4 O

DUs

(K1K

2E c

onne

ctio

n re

quire

d) p

er b

us. (

VRF

& M

ini-V

RF S

yste

ms

only)

M

axim

um 2

56 in

door

uni

ts p

er d

evice

. Up

to 6

4 ID

Us p

er b

us. (

All S

yste

ms)

Figure 5. -1P or -2P Mini-VRF System Indoor Unit Only Monitoring

Page 8: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

8

BAC

net

Gat

eway BA

Cne

t/IP

Net

wor

k

-2P

Min

i-VR

F Sy

stem

BMS

-2P

Min

i-VR

F Sy

stem

PQE

PQE

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

K1K2

E O

utdo

or U

nit

Info

rmat

ion

(Poi

nts)

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

K1K2

E O

utdo

or U

nit

Info

rmat

ion

(Poi

nts)

NO

TE -

Fiel

d-su

pplie

d co

mm

unic

atio

n w

iring

- 18

GA.

, stra

nded

, 3-c

ondu

ctor

, shi

elde

d co

ntro

l wire

(pol

arity

sen

sitiv

e). A

ll sh

ield

s of

shi

elde

d ca

ble

conn

ect t

o G

RO

UN

D te

rmin

al, n

ot to

E.

NO

TE -

Max

imum

96

outd

oor u

nits

per

dev

ice.

Up

to 2

4 O

DU

s (K

1K2E

con

nect

ion

requ

ired)

per

bus

. (V

RF

& M

ini-V

RF

Sys

tem

s on

ly)

Max

imum

256

indo

or u

nits

per

dev

ice.

Up

to 6

4 ID

Us

per b

us. (

All

Sys

tem

s)

NO

TE -

Out

door

uni

t con

trol &

mon

itorin

g po

ints

for -

1P M

ini-V

RF

syst

ems

requ

ire th

e M

ini-V

RF

Con

trol

Inte

rface

V0C

TRL0

0P-1

.

Figure 6. -2P Mini-VRF System Indoor and Outdoor Unit Monitoring

Page 9: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

9

Figure 6. Mini-Split Single Zone System Indoor Unit Only Monitoring

Lenn

ox M

ini-S

plit

Sing

le Z

one

Syst

em

Lenn

ox M

ini-S

plit

Sing

le Z

one

Syst

em

Lenn

ox M

ini-S

plit

Sing

le Z

one

Syst

em

BAC

net

Gat

eway BA

Cne

t/IP

Net

wor

k

BMS

Cat

. 5Et

hern

etC

able

Fiel

d Su

pplie

d to

de

sire

d lo

catio

n

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

Lenn

ox M

ini-S

plit

Sing

le Z

one

Syst

em

NOTE

- M

WM

A M

ini-s

plit w

all-m

ount

ed in

door

unit

s are

shipp

ed w

ith a

cable

for u

se w

ith co

nnec

ting

to X

YE te

rmina

l. Do

not d

iscar

d ca

ble.

NOTE

- Ou

tdoo

r unit

cont

rol &

mon

itorin

g po

ints a

re n

ot a

vaila

ble fo

r Mini

-Spli

t sys

tem

s.

NOTE

- Fi

eld-s

uppli

ed co

mm

unica

tion

wirin

g - 1

8 GA

., str

ande

d, 3

-con

ducto

r, sh

ielde

d co

ntro

l wire

(pola

rity s

ensit

ive).

All s

hields

of s

hielde

d ca

ble

conn

ect t

o GR

OUND

term

inal, n

ot to

E.

NOTE

- M

axim

um 9

6 ou

tdoo

r unit

s per

dev

ice. U

p to

24

ODUs

(K1K

2E co

nnec

tion

requ

ired)

per

bus

. (VR

F &

Mini

-VRF

Sys

tem

s only

) M

axim

um 2

56 in

door

unit

s per

dev

ice. U

p to

64

IDUs

per

bus

. (Al

l Sys

tem

s)

Page 10: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

10

BAC

net

Gat

eway BA

Cne

t/IP

Net

wor

k

Min

i-Spl

it M

ulti-

Zone

Sys

tem

Four

-zon

e sy

stem

sho

wn

BMS

Cat

. 5Et

hern

etC

able

Fiel

d Su

pplie

d to

de

sire

d lo

catio

n

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

Min

i-Spl

it M

ulti-

Zone

Sys

tem

Four

-zon

e sy

stem

sho

wn

Min

i-Spl

it M

ulti-

Zone

Sys

tem

Four

-zon

e sy

stem

sho

wn

Min

i-Spl

it M

ulti-

Zone

Sys

tem

Four

-zon

e sy

stem

sho

wn

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts) NO

TE -

MW

MA

Mini

-spli

t wall

-mou

nted

indo

or u

nits a

re sh

ipped

with

a ca

ble fo

r use

with

co

nnec

ting

to X

YE te

rmina

l. Do

not d

iscar

d ca

ble.

NOTE

- Fi

eld-s

uppli

ed co

mm

unica

tion

wirin

g - 1

8 GA

., str

ande

d, 3

-con

ducto

r, sh

ielde

d co

ntro

l wi

re (p

olarit

y sen

sitive

). Al

l shie

lds o

f shie

lded

cable

conn

ect t

o GR

OUND

term

inal, n

ot to

E.

NOTE

- M

axim

um 9

6 ou

tdoo

r unit

s per

dev

ice. U

p to

24

ODUs

(K1K

2E co

nnec

tion

requ

ired)

per

bu

s. (V

RF &

Mini

-VRF

Sys

tem

s only

) M

axim

um 2

56 in

door

unit

s per

dev

ice. U

p to

64

IDUs

per

bus

. (Al

l Sys

tem

s)

NOTE

- Ou

tdoo

r unit

cont

rol &

mon

itorin

g po

ints a

re n

ot a

vaila

ble fo

r Mini

-Spli

t sys

tem

s.

Figure 7. Mini-Split Multi-Zone System Indoor Unit Only Monitoring

Page 11: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

11

Figure 8. Multiple Lennox System Types Using One BACnet Gateway Device

BAC

net

Gat

eway BA

Cne

t/IP

Net

wor

k

VRF

Syst

em

BMS

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

K1K2

E O

utdo

or U

nit

Info

rmat

ion

(Poi

nts)

-1P

Min

i-VR

F Sy

stem

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

PQE

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

Min

i-Spl

it Si

ngle

-Zon

e Sy

stem

PQE

NO

TE -

MW

MA

Min

i-spl

it w

all-m

ount

ed in

door

uni

ts a

re s

hipp

ed w

ith a

cab

le fo

r use

with

con

nect

ing

to X

YE

term

inal

. Do

not d

isca

rd c

able

.N

OTE

- O

utdo

or u

nit c

ontro

l & m

onito

ring

poin

ts a

re n

ot a

vaila

ble

for M

ini-S

plit

syst

ems.

-1P

Min

i-VR

F sy

stem

s re

quire

the

Min

i-VR

F C

ontro

l In

terfa

ce V

0CTR

L00P

-1.

NO

TE -

Fiel

d-su

pplie

d co

mm

unic

atio

n w

iring

- 18

GA.

, stra

nded

, 3-c

ondu

ctor

, shi

elde

d co

ntro

l wire

(pol

arity

sen

sitiv

e). A

ll sh

ield

s of

shi

elde

d ca

ble

conn

ect t

o G

RO

UN

D te

rmin

al, n

ot to

E.

NO

TE -

Max

imum

96

outd

oor u

nits

per

dev

ice.

Up

to 2

4 O

DU

s (K

1K2E

con

nect

ion

requ

ired)

per

bus

. (V

RF

& M

ini-V

RF

Sys

tem

s on

ly)

Max

imum

256

indo

or u

nits

per

dev

ice.

Up

to 6

4 ID

Us

per b

us. (

All

Sys

tem

s)

NO

TE -

VR

F H

eat P

ump

PQ

E w

iring

con

figur

atio

n sh

own.

XY

E w

iring

con

figur

atio

n is

sam

e fo

r VR

F H

eat P

ump

and

VR

F H

eat R

ecov

ery

syst

ems.

N

o m

onito

ring

poin

ts a

re a

vaila

ble

for M

S B

oxes

.N

OTE

- E

ach

VR

F R

efrig

eran

t sys

tem

is li

mite

d to

63

IDU

s.

Page 12: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

12

Figure 9. Multiple Lennox System Types Daisy Chained Together (Two Bus Used)

NO

TE -

MW

MA

Min

i-spl

it w

all-m

ount

ed in

door

uni

ts a

re s

hipp

ed w

ith a

cab

le fo

r use

with

con

nect

ing

to X

YE

term

inal

. Do

not d

isca

rd c

able

.N

OTE

- O

utdo

or u

nit c

ontro

l & m

onito

ring

poin

ts a

re n

ot a

vaila

ble

for M

ini-S

plit

syst

ems.

-1P

Min

i-VR

F sy

stem

s re

quire

the

Min

i-VR

F C

ontro

l Int

erfa

ce V

0CTR

L00P

-1.

NO

TE -

Fiel

d-su

pplie

d co

mm

unic

atio

n w

iring

- 18

GA.

, stra

nded

, 3-c

ondu

ctor

, shi

elde

d co

ntro

l wire

(pol

arity

sen

sitiv

e). A

ll sh

ield

s of

shi

elde

d ca

ble

conn

ect t

o G

RO

UN

D te

rmin

al, n

ot to

E.

NO

TE -

Max

imum

96

outd

oor u

nits

per

dev

ice.

Up

to 2

4 O

DU

s (K

1K2E

con

nect

ion

requ

ired)

per

bus

. (V

RF

& M

ini-V

RF

Sys

tem

s on

ly)

Max

imum

256

indo

or u

nits

per

dev

ice.

Up

to 6

4 ID

Us

per b

us. (

All

Sys

tem

s)

NO

TE -

VR

F H

eat P

ump

PQ

E w

iring

con

figur

atio

n sh

own.

XY

E w

iring

con

figur

atio

n is

sam

e fo

r VR

F H

eat P

ump

and

VR

F H

eat R

ecov

ery

syst

ems.

N

o m

onito

ring

poin

ts a

re a

vaila

ble

for M

S B

oxes

.

BAC

net

Gat

eway

BAC

net/I

P N

etw

ork

VRF

Syst

em

BMS

XYE

Indo

or U

nit

Info

rmat

ion

(Poi

nts)

K1K2

E O

utdo

or U

nit

Info

rmat

ion

(Poi

nts)

-1P

Min

i-VR

F Sy

stemPQ

E

Min

i-Spl

it Si

ngle

-Zon

e Sy

stem

PQE

-2P

Min

i-VR

F Sy

stemPQ

E

Min

i-Spl

it M

ulti-

Zone

Sys

tem

Four

-zon

e sy

stem

sho

wn

NO

TE -

Eac

h V

RF

Ref

riger

ant s

yste

m is

lim

ited

to 6

3 ID

Us.

Page 13: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

13

Figure 10. Outdoor Unit Addressing ENC Setting Example

Ref

rig

eran

t S

yste

m 1

EN

C4

0E

NC

10

EN

C4

0E

NC

11

EN

C4

0E

NC

12

Ref

rig

eran

t S

yste

m 2

EN

C4

1E

NC

10

EN

C4

1E

NC

11

EN

C4

1E

NC

12

Ref

rig

eran

t S

yste

m 3

EN

C4

2E

NC

10

EN

C4

2E

NC

11

EN

C4

2E

NC

12

Ref

rig

eran

t S

yste

m 4

EN

C4

3E

NC

10

EN

C4

3E

NC

11

EN

C4

3E

NC

12

XYE

K1K2E

K1K2E

PQE

K1K2E

PQE

K1K2E

PQE

K1K2E

PQE

BAC

net

Gat

eway

BAC

net/I

P N

etw

ork

BMS

Up

to 8

Sys

tem

s

Out

door

uni

t ad

dres

s se

tting

un

der o

ne E

XE/

K1K

2E p

ort

Ref

riger

ant S

yste

m

1R

efrig

eran

t Sys

tem

2R

efrig

eran

t Sys

tem

3R

efrig

eran

t Sys

tem

4

ENC

1 (N

UM

_S)

Valid

rang

e - 0

- 2

01

20

12

01

20

12

ENC

4 (N

ET_A

D-

DR

ESS)

Valid

rang

e - 0

- 7

00

01

11

22

23

33

The

actu

al n

et-

wor

k ad

dres

s of

ou

tdoo

r uni

t in

LVM

/BAC

net*

0*4+

0=0

0*4+

1=1

0*4+

2=2

0*4+

4=4

0*4+

5=5

0*4+

6=6

0*4+

8=8

0*4+

9=9

0*4+

10=1

00*

4+12

=12

0*4+

13=1

30*

4+14

=14

*The

act

ual n

etw

ork

addr

ess

of th

e ou

tdoo

r uni

t in

LVM

/BAC

net =

EN

C4*

4 +

ENC

1.

Page 14: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

14

BACnet Object Points List

Indoor Unit Point List

Item Function Identifi er Object Name Object

Type Possible Options

1 Mode AC_OModeSetting MO Heating Cooling Dehumidify (Dry)

Fan only OFF

2 Mode Status AC_QueryMode MI Heating Cooling Dehumidify (Dry)

Fan only OFF

3 Fan Speed AC_OFANSpeed MO High Medium Low Stop ---

4 Fan Speed Status AC_QueryFANSpeed MI High Medium Low Stop OFF

5 Setpoint AC_OTempSetting AO °F --- --- --- ---6 Setpoint Status AC_QueryTempSetting AI °F --- --- --- ---

7 Room Temperature AC_ITempIndoor AI °F --- --- --- ---

8 Swing AC_OSwing BO Inactive Active

9 Error Code AC_IMalfunction MI See "Indoor Unit Table 9. Error Code" on page 18

10 Protection Code AC_IProtect MI See "Indoor Unit Table 10. Protection Code" on page 19

11 Remote Control Lock Remote_Control_lock BO Inactive Active

12 Turn Indoor Unit ON/OFF AC_TurnOnOff BO Inactive Active

13 Turn All Indoor Units ON/OFF ALL_AC_OnOff BO --- Active

Outdoor Unit Point List

Item Function Identifi er Object Name Object

Type Possible Options

1 Operation Mode AC_IOperationMode MI Heating Cooling Stop --- ---

2 Condenser Fan Speed AC_IFANSpeed MI High Medium Low --- ---

3 Ambient Temperature AC_ITempOutdoor AI °F --- --- --- ---

4 Indoor Quantity AC_ITotalACs AI Number of indoor units 5 Compressor 1 AC_ICom1Current AI Current in Amps6 Compressor 2 AC_ICom2Current AI Current in Amps7 Compressor 3 AC_ICom3Current AI Current in Amps

8 Error Code AC_IMalfunction MI See "Outdoor Unit Table 8. Error Code" on page 25

9 Protection Code AC_IProtect MI See "Outdoor Unit Table 9. Protection Code" on page 26

NOTE - Outdoor unit control & monitoring points are not available for Mini-Split systems. -1P Mini-VRF systems require the Mini-VRF Control Interface V0CTRL00P-1.

Page 15: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

15

Indoor Unit Instance Number Description

Port

N

o.

Indo

or

unit

addr

ess

Pare

nt

Obj

ect

Sub

Ojb

ects

Dev

ice*

anal

og-

inpu

t,1an

alog

-in

put,2

anal

og-

inpu

t,3an

alog

-inpu

t,4an

alog

-ou

tput

,1bi

nary

-ou

tput

,1bi

nary

-ou

tput

,2m

ulti-

stat

e-in

put,1

mul

ti-st

ate-

inpu

t,2

mul

ti-st

ate-

inpu

t,3m

ulti-

stat

e-in

put,4

mul

ti-st

ate-

outp

ut,1

mul

ti-st

ate-

outp

ut,2

Port

1

00in

door

_0_0

1900

00

AC_

ITem

pInd

oor

AC_

IOnT

ime

AC_

IOffT

ime

AC_

Que

ryTe

mpS

ettin

gAC

_O

Tem

pSet

ting

AC_

Osw

ing

AC_

OEl

ecH

eat

AC_

Imal

func

tion

AC_I

prot

ect

AC_

Que

ryM

ode

AC_

Que

ryFa

nSpe

edAC

_O

Mod

eSet

ting

AC_

OFa

nSpe

ed

01in

door

_0_1

1900

01

……

63in

door

_1_6

319

0063

Port

2

00in

door

_1_0

1910

00

AC_

ITem

pInd

oor

AC_

IOnT

ime

AC_

IOffT

ime

AC_

Que

ryTe

mpS

ettin

gAC

_O

Tem

pSet

ting

AC_

Osw

ing

AC_

OEl

ecH

eat

AC_

Imal

func

tion

AC_I

prot

ect

AC_

Que

ryM

ode

AC_

Que

ryFa

nSpe

edAC

_O

Mod

eSet

ting

AC_

OFa

nSpe

ed

01in

door

_1_1

1910

01

……

63in

door

_1_6

319

1063

Port

3

00in

door

_2_0

1920

00

AC_

ITem

pInd

oor

AC_

IOnT

ime

AC_

IOffT

ime

AC_

Que

ryTe

mpS

ettin

gAC

_O

Tem

pSet

ting

AC_

Osw

ing

AC_

OEl

ecH

eat

AC_

Imal

func

tion

AC_I

prot

ect

AC_

Que

ryM

ode

AC_

Que

ryFa

nSpe

edAC

_O

Mod

eSet

ting

AC_

OFa

nSpe

ed

01in

door

_2_1

1920

01

……

63in

door

_2_6

319

2063

Port

4

00in

door

_3_0

1930

00

AC_

ITem

pInd

oor

AC_

IOnT

ime

AC_

IOffT

ime

AC_

Que

ryTe

mpS

ettin

gAC

_O

Tem

pSet

ting

AC_

Osw

ing

AC_

OEl

ecH

eat

AC_

Imal

func

tion

AC_I

prot

ect

AC_

Que

ryM

ode

AC_

Que

ryFa

nSpe

edAC

_O

Mod

eSet

ting

AC_

OFa

nSpe

ed

01in

door

_3_1

1930

01

……

63in

door

_3_6

319

3063

"* -

Left

two

digi

tsVi

rtual

BAC

net N

etw

ork

num

ber

= 19

(def

ault)

, can

be

chan

ged

on c

onfi g

urat

ion

web

pag

e.R

ight

four

dig

its

Dev

ice

ID="

"BTX

X"";.

""B"

" is

the

bus

Num

ber 0

-3;

""T"

" mea

ns ty

pe 0

-indo

or u

nit,1

-out

door

uni

t;""

XX""

is th

e in

door

uni

t Num

ber 0

-63

or O

utdo

or u

nit a

ctua

l net

wor

k ad

dres

s 0-

31(o

utdo

or u

nit a

ddre

ss +

out

door

uni

t net

wor

k ad

dres

s * 4

);"

Page 16: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

16

Indoor Unit Table 2. Mode Status

Attribute identifi er Data type Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er MultiState-input 3 RObject Name CharacterString AC_QueryMode RObject Type BACnetObjectType MultiState-input RDescription CharacterString QueryMode O

Status TextBACnet ARRAY[N]CharacterString

{“Heat”,”Cool”,”Dry”, “Fan only”, Stop”} O

Indoor Unit Table 4. Fan Speed StatusAttribute identifi er Data type Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er MultiState-input 4 RObject Name CharacterString AC_QueryFanSpeed RObject Type BACnetObjectType MultiState-input RDescription CharacterString QueryFanSpeed O

Status TextBACnet ARRAY[N]CharacterString

{"High","Middle","Low", “Stop”} O

Indoor Unit Points

Indoor Unit Table 1. ModeAttribute Identifi er Data Type Attribute value Meaning Read/WriteObject Identifi er BACnetObjectIdentifi er MultiState-output 1 - RObject Name CharacterString AC_OModeSetting - RObject Type BACnetObjectType MultiState-output - R/WDescription CharacterString Operation mode setting - O

Options Integer

1234

HeatCoolDryFan

O

Indoor Unit Table 3. Fan Speed

Attribute Identifi er Data type Attribute value Meaning Read/Write

Object Identifi er BACnetObjectIdentifi er MultiState-output 2 - RObject Name CharacterString AC_OFanSpeed - RObject Type BACnetObjectType MultiState-output - R/WDescription CharacterString Fan Speed Setting - O

Options Integer123

HighMedium

LowO

Page 17: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

17

Indoor Unit Table 7. Room TemperatureAttribute Identifi er Data Mode Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Analog-input 1 RObject Name CharacterString AC_ITempIndoor RObject Type BACnetObjectType Analog-input RDescription CharacterString Indoor Temperature OUnit BACnetEngineering Units Degree-Fahrenheit R

NOTE - The received value is degrees Fahrenheit (°F).

Indoor Unit Table 6. Setpoint StatusAttribute identifi er Data type Attribute value Read/WriteObject identifi er BACnetObjectIdentifi er Analog-input 4 RObject name CharacterString AC_QueryTempSetting RObject type BACnetObjectType Analog-input RCurrent value REAL 0 RDescription CharacterString QueryTempsetting OUnit BACnetEngineering Units Degree-Fahrenheit R

NOTE - The sent value is degrees Fahrenheit (°F).

Indoor Unit Table 5. SetpointAttribute Identifi er Data type Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Analog-output 1 RObject Name CharacterString AC_OTempSetting RObject Type BACnetObjectType Analog-output R/WDescription CharacterString Setpoint OUnit BACnetEngineering Units Degree-Fahrenheit R

NOTE - All values are degrees Fahrenheit (°F). You must send degrees Fahrenheit (°F) values and you will receive degrees Fahrenheit (°F). Range: 61°F - 90°F (16°C - 32°C).

Indoor Unit Table 8. SwingAttribute Identifi er Data type Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Binary-output 1 RObject Name CharacterString AC_OSwing RObject Type BACnetObjectType Binary-output R/WDescription CharacterString Swing Setting OInactive Text CharacterString Turn off OActive Text CharacterString Turn on ONOTE - inactive means swing OFF, active means swing ON.

Page 18: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

18

Indoor Unit Table 9. Error Code

Attribute Identifi er Data Mode Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er MultiState-input 1 RObject Name CharacterString AC_IMalfunction RObject Type BACnetObjectType MultiState-input RDescription CharacterString Malfunction Status O

Status TextBACnet ARRAY[N]CharacterString

E0

O

E1 E2E3 E4 E5 E6 E7 E8 E9 EA EB ECEDEEEFNo

NOTE - Refer to the Lennox VRF Mobile App for error code descriptions.

Page 19: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

19

Indoor Unit Table 10. Protection Code

Attribute Identifi er Data Mode Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er MultiState-input 2 RObject Name CharacterString AC_IProtect RObject Type BACnetObjectType MultiState-input RDescription CharacterString Protection Status O

Status textBACnet ARRAY[N]CharacterString

P0

O

P1 P2 P3 P4 P5 P6 P7 P8 PF No

NOTE - Refer to the Lennox VRF Mobile App for error code descriptions.

Page 20: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

20

Indoor Unit Table 11. Remote Control Lock

Attribute Identifi er Data Mode Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er Binary-output 4 R/WObject Name CharacterString Remote_Control_lock RObject Type BACnetObjectType Binary-output R

Description CharacterString Lock/Unlock remote control O

Inactive text CharacterString unlock remote control OActive text CharacterString lock remote control O

NOTE - Refer to the Lennox VRF Mobile App for error code descriptions.NOTE - Lock All Functions of Wireless Remote Controller V0STAT52P-1.

Indoor Unit Table 12. Turn Indoor Unit ON/OFF

Attribute Identifi er Data Mode Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er Binary-output 3 R/WObject Name CharacterString AC_TurnOnOff RObject Type BACnetObjectType Binary-output RDescription CharacterString Turn On/Off the AC OInactive text CharacterString Turn off OActive text CharacterString Turn on O

NOTE - Refer to the Lennox VRF Mobile App for error code descriptions.

Indoor Unit Table 13. Turn All Indoor Units ON/OFF

Attribute Identifi er Data Mode Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er Binary-output 5 R/WObject Name CharacterString ALL_AC_OnOff RObject Type BACnetObjectType Binary-output R

Description CharacterString turn on/turn off ac all the bus O

Inactive text CharacterString OActive text CharacterString turn off ac all the bus O

NOTE - Refer to the Lennox VRF Mobile App for error code descriptions.

Page 21: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

21

Outdoor Unit Instance Number DescriptionPort No.

Refrigerant system

Outdoor unit address (Dip switch on outdoor unit board)

Outdoor unit network address(Dip switch on outdoor unit board)

Out

door

un

it ac

tual

ne

twor

k ad

dres

s

Pare

nt O

bjec

tD

evic

e*

Sub

Obj

ects

Mul

tista

te-

inpu

t,1M

ultis

tate

- iu

tput

,2 A

nalo

g-iu

tput

,1A

nalo

g-iu

tput

,2 A

nalo

g-iu

tput

,3A

nalo

g-iu

tput

,4A

nalo

g-iu

tput

,5M

ultis

tate

-in

put,3

Mul

tista

te-

inpu

t,4

Port

1

Sys 1

0000

00+0

0*4=

0ou

tdoo

r_0_

0_0

1901

00

AC_

IOpe

ratio

nMod

e AC

_IF

anSp

eed

AC_

ITem

pOut

oor

AC

_ IT

otal

ACs

AC

_ IC

om1C

urre

ntAC

_ IC

om2C

urre

nt A

C_

ICom

3Cur

rent

AC _

Iout

mal

func

tion

AC _

IOut

prot

ect

0100

01+0

0*4=

1ou

tdoo

r_0_

0_1

1901

01

0200

02+0

0*4=

2ou

tdoo

r_0_

0_2

1901

02

Sys 2

0001

00+0

1*4=

4ou

tdoo

r_0_

1_0

1901

04

0101

01+0

1*4=

5ou

tdoo

r_0_

1_1

1901

05

0201

02+0

1*4=

6ou

tdoo

r_0_

1_2

1901

06

……

……

……

Sys 8

0007

00+0

7*4=

28ou

tdoo

r_0_

7_0

1901

28

0107

01+0

7*4=

28ou

tdoo

r_0_

7_1

1901

29

0207

02+0

7*4=

30ou

tdoo

r_0_

7_2

1901

30

Port

2

Sys 1

0000

00+0

0*4=

0ou

tdoo

r_1_

0_0

1911

00

AC_

IOpe

ratio

nMod

e AC

_IF

anSp

eed

AC_

ITem

pOut

oor

AC

_ IT

otal

ACs

AC

_ IC

om1C

urre

ntAC

_ IC

om2C

urre

nt A

C_

ICom

3Cur

rent

AC _

Iout

mal

func

tion

AC _

IOut

prot

ect

0100

01+0

0*4=

1ou

tdoo

r_1_

0_1

1911

01

0200

02+0

0*4=

2ou

tdoo

r_1_

0_2

1911

02

Sys 2

0001

00+0

1*4=

4ou

tdoo

r_1_

1_0

1911

04

0101

01+0

1*4=

5ou

tdoo

r_1_

1_1

1911

05

0201

02+0

1*4=

6ou

tdoo

r_1_

1_2

1911

06

……

……

……

Sys 8

0007

00+0

7*4=

28ou

tdoo

r_1_

7_0

1911

28

0107

01+0

7*4=

28ou

tdoo

r_1_

7_1

1911

29

0207

02+0

7*4=

30ou

tdoo

r_1_

7_2

1911

30

"* -

Left

two

digi

tsVi

rtual

BAC

net N

etw

ork

num

ber

= 19

(def

ault)

, can

be

chan

ged

on c

onfi g

urat

ion

web

pag

e.R

ight

four

dig

itsD

evic

e ID

=""B

TXX"

";.""

B"" i

s th

e bu

s N

umbe

r 0-3

;""

T"" m

eans

type

0-in

door

uni

t,1-o

utdo

or u

nit;

""XX

"" is

the

indo

or u

nit N

umbe

r 0-6

3 or

Out

door

uni

t act

ual n

etw

ork

addr

ess

0-31

(out

door

uni

t add

ress

+ o

utdo

or u

nit n

etw

ork

addr

ess

* 4);"

Page 22: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

22

Port No.

Refrigerant system

Outdoor unit address (Dip switch on outdoor unit board)

Outdoor unit network address(Dip switch on outdoor unit board)

Out

door

un

it ac

tual

ne

twor

k ad

dres

s

Pare

nt O

bjec

tD

evic

e*

Sub

Obj

ects

Mul

tista

te-

inpu

t,1M

ultis

tate

- iu

tput

,2 A

nalo

g-iu

tput

,1A

nalo

g-iu

tput

,2 A

nalo

g-iu

tput

,3A

nalo

g-iu

tput

,4A

nalo

g-iu

tput

,5M

ultis

tate

-in

put,3

Mul

tista

te-

inpu

t,4

Port

3

Sys 1

0000

00+0

0*4=

0ou

tdoo

r_2_

0_0

1921

00

AC_

IOpe

ratio

nMod

e AC

_IF

anSp

eed

AC_

ITem

pOut

oor

AC

_ IT

otal

ACs

AC

_ IC

om1C

urre

ntAC

_ IC

om2C

urre

nt A

C_

ICom

3Cur

rent

AC _

Iout

mal

func

tion

AC _

IOut

prot

ect

0100

01+0

0*4=

1ou

tdoo

r_2_

0_1

1921

01

0200

02+0

0*4=

2ou

tdoo

r_2_

0_2

1921

02

Sys 2

0001

00+0

1*4=

4ou

tdoo

r_2_

1_0

1921

04

0101

01+0

1*4=

5ou

tdoo

r_2_

1_1

1921

05

0201

02+0

1*4=

6ou

tdoo

r_2_

1_2

1921

06

……

……

……

Sys 8

0007

00+0

7*4=

28ou

tdoo

r_2_

7_0

1921

28

0107

01+0

7*4=

28ou

tdoo

r_2_

7_1

1921

29

0207

02+0

7*4=

30ou

tdoo

r_2_

7_2

1921

30

Port

4

Sys 1

0000

00+0

0*4=

0ou

tdoo

r_3_

0_0

1931

00

AC_

IOpe

ratio

nMod

e AC

_IF

anSp

eed

AC_

ITem

pOut

oor

AC

_ IT

otal

ACs

AC

_ IC

om1C

urre

ntAC

_ IC

om2C

urre

nt A

C_

ICom

3Cur

rent

AC _

Iout

mal

func

tion

AC _

IOut

prot

ect

0100

01+0

0*4=

1ou

tdoo

r_3_

0_1

1931

01

0200

02+0

0*4=

2ou

tdoo

r_3_

0_2

1931

02

Sys 2

0001

00+0

1*4=

4ou

tdoo

r_3_

1_0

1931

04

0101

01+0

1*4=

5ou

tdoo

r_3_

1_1

1931

05

0201

02+0

1*4=

6ou

tdoo

r_3_

1_2

1931

06

……

……

……

Sys 8

0007

00+0

7*4=

28ou

tdoo

r_3_

7_0

1931

28

0107

01+0

7*4=

28ou

tdoo

r_3_

7_1

1931

29

0207

02+0

7*4=

30ou

tdoo

r_3_

7_2

1931

30

"* -

Left

two

digi

tsVi

rtual

BAC

net N

etw

ork

num

ber

= 19

(def

ault)

, can

be

chan

ged

on c

onfi g

urat

ion

web

pag

e.R

ight

four

dig

itsD

evic

e ID

=""B

TXX"

";.""

B"" i

s th

e bu

s N

umbe

r 0-3

;""

T"" m

eans

type

0-in

door

uni

t,1-o

utdo

or u

nit;

""XX

"" is

the

indo

or u

nit N

umbe

r 0-6

3 or

Out

door

uni

t act

ual n

etw

ork

addr

ess

0-31

(out

door

uni

t add

ress

+ o

utdo

or u

nit n

etw

ork

addr

ess

* 4);"

Page 23: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

23

Outdoor Unit Points

Outdoor Unit Table 1. Operation ModeAttribute Identifi er Data Mode Attribute value Meaning Read/WriteObject Identifi er BACnetObjectIdentifi er MultiState-input 1 RObject Name CharacterString AC_IOperationMode RObject Type BACnetObjectType MultiState-input RDescription CharacterString Operation mode O

Status textBACnet ARRAY [N]CharacterString

123

HeatCoolStop

O

Outdoor Unit Table 4. Indoor QuantityAttribute Identifi er Data Mode Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Analog-input 2 RObject Name CharacterString AC_ITotalACs RObject Type BACnetObjectType Analog-input RDescription CharacterString Indoor unit qty O

Operation instruction The CURRENT VALUE attribute of the selected object refl ects the current INDOOR UNIT QUANTITY (Read only).

Outdoor Unit Table 2. Condenser Fan SpeedAttribute Identifi er Data Mode Attribute value Meaning Read/WriteObject Identifi er BACnetObjectIdentifi er MultiState-input 2 RObject Name CharacterString AC_IFanSpeed RObject Type BACnetObjectType MultiState-input RDescription CharacterString Fan Speed O

Options Integer

1234

HighMediumLowStop

O

Outdoor Unit Table 3. Ambient TemperatureAttribute Identifi er Data type Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Analog-input 1 RObject Name CharacterString AC_ITempOutoor RObject Type BACnetObjectType Analog-input RDescription CharacterString Outdoor Temperature OUnit BACnetEngineering Units Degree-Fahrenheit RNOTE - The received value is degrees Fahrenheit (°F).

NOTE - Outdoor unit control & monitoring points are not available for Mini-Split systems. -1P Mini-VRF systems require the Mini-VRF Control Interface V0CTRL00P-1.

Page 24: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

24

Outdoor Unit Table 6. Compressor 2Attribute Identifi er Data type Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Analog-input 4 RObject Name CharacterString AC_ICom2Current RObject Type BACnetObjectType Analog-input RCurrent Value REAL 0 RDescription CharacterString Compressor 2 current OUnit BACnetEngineering Units Amperes R

Operation InstructionThe CURRENT VALUE attribute of the selected object refl ects theCOMPRESSOR 2 ELECTRIC CURRENT (Read only).

Outdoor Unit Table 5. Compressor 1Attribute Identifi er Data type Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Analog-input 3 RObject Name CharacterString AC_ICom1Current RObject Type BACnetObjectType Analog-input RCurrent Value REAL 0 RDescription CharacterString Compressor 1 current OUnit BACnetEngineering Units Amperes R

Operation InstructionThe CURRENT VALUE attribute of the selected object refl ects theCOMPRESSOR 1 ELECTRIC CURRENT (Read only).

Outdoor Unit Table 7. Compressor 3Attribute Identifi er Data type Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Analog-input 5 RObject Name CharacterString AC_ICom3Current RObject Type BACnetObjectType Analog-input RDescription CharacterString Compressor 3 current OUnit BACnetEngineering Units Amperes R

Operation InstructionThe CURRENT VALUE attribute of the selected object refl ects theCOMPRESSOR 3 ELECTRIC CURRENT (Read only).

Page 25: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

25

Outdoor Unit Table 8. Error Code

Attribute Identifi er Data type Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er MultiState-input 3 RObject Name CharacterString AC_IMalfunction RObject Type BACnetObjectType MultiState-input RDescription CharacterString Malfunction Status O

Status TextBACnet ARRAY[N]CharacterString

E0

O

E1 E2E3 E4 E5 E6 E7 E8 E9 EA EB ECEDEEEFNo

NOTE - Refer to the Lennox VRF Mobile App for error code descriptions.

Page 26: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

26

Outdoor Unit Table 9. Protection Code

Attribute Identifi er Data Mode Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er MultiState-input 4 RObject Name CharacterString AC_IProtect RObject Type BACnetObjectType MultiState-input RDescription CharacterString Protect Status O

Status TextBACnet ARRAY[N]CharacterString

P0

O

P1 P2 P3 P4 P5 P6 P7 P8 P9 PA PB PC PD PE PF No

NOTE - Refer to the Lennox VRF Mobile App for error code descriptions.

Page 27: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

27

Supportive Object TypeObject Type Supported Dynamic Established or Not Dynamic Deleted or NotAnalog Input Object Type X X XAnalog Output Object Type X X XAnalog Value Object Type X X XBinary Input Object Type X X XBinary Output Object Type X X XBinary Value Object Type X X XDevice Object Type X X XMulti-Status Input Object Type X X XMulti-Status Output Object Type X X X

Application Services of Supplied BACnetApplication Services

Request Start

Request Preformed

Read Property XRead Property Multiple X

Write Property XWrite Property Multiple X

Who-Has X XWho-IsI-Am X

Appendix A. BACnet Protocol Observed

Option of Data Link LayerISO 8802-3,10BASE5ISO 8802-3,10BASE2ISO 8802-3,10BASET

Supportive Character SetANSI X3.4IBMTM/Microsoft TM ISO10646(UCS2)T

Special FunctionYes No

Subsection request support X window

size:1476Subsection respond support X window

size:1476

LegendAbbreviation Meaning

R Read

W WriteR/W Read/Write

I InputO OutputBI Binary InputBO Binary OutputAI Analog InputAO Analog OutputMI Multistate InputMO Multistate Output

Page 28: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

28

Appendix B. Indoor Unit Detailed Points

Indoor Unit Table 2. Mode Status

Attribute identifi er Data type Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er MultiState-input 3 RObject Name CharacterString AC_QueryMode RObject Type BACnetObjectType MultiState-input RDescription CharacterString QueryMode O

Status TextBACnet ARRAY[N]CharacterString

{“Heat”,”Cool”,”Dry”, “Fan only”, Stop”} O

Indoor Unit Table 1. ModeAttribute Identifi er Data type Attribute value Meaning Read/WriteObject Identifi er BACnetObjectIdentifi er MultiState-output 1 RObject Name CharacterString AC_OModeSetting RObject Type BACnetObjectType MultiState-output RDescription CharacterString Operation mode setting OCurrent Value REAL 0 WStatus Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RStatus Number Unsigned 6 R

Options Integer

1234

HeatCoolDryFan

O

Priority Array BACnetPriorityArra NULL RRelease Default Unsigned 0 RPublicly Type Unsigned 1701 OFeedback Value Unsigned 6Event Enable BACnetEventTransitionBits T T T OAffi rm Transform BACnetEventTransitionBits T T T ONotify Type BACnetNotifyType Alarm O

Page 29: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

29

Indoor Unit Table 4. Fan Speed StatusAttribute identifi er Data type Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er MultiState-input 4 RObject Name CharacterString AC_QueryFanSpeed RObject Type BACnetObjectType MultiState-input RDescription CharacterString QueryFanSpeed O

Status TextBACnet ARRAY[N]CharacterString

{"High","Middle","Low", “Stop”} O

Indoor Unit Table 3. Fan Speed

Attribute Identifi er Data type Attribute value Meaning Read/Write

Object Identifi er BACnetObjectIdentifi er MultiState-output 2 RObject Name CharacterString AC_OFanSpeed RObject Type BACnetObjectType MultiState-output RDescription CharacterString Fan Speed Setting OCurrent Value Unsigned 0 WStatus Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RStatus Number Unsigned 6 R

Options Integer123

HighMedium

LowO

Priority Array BACnetPriorityArra NULL RRelease Default Unsigned 0Time Delay Unsigned 1 O

Publicly Type Unsigned 1701 OFeedback Value Unsigned 6Event Enable BACnetEventTransitionBits T T T OAffi rm Transform BACnetEventTransitionBits T T T ONotify Type BACnetNotifyType event O

Page 30: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

30

Indoor Unit Table 6. Setpoint StatusAttribute identifi er Data type Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Analog-input 4 RObject Name CharacterString AC_QueryTempSetting RObject Type BACnetObjectType Analog-input RCurrent Value REAL 0 RDescription CharacterString QueryTempsetting OUnit BACnetEngineering Units Degree-Fahrenheit R

NOTE - The sent value is degrees Fahrenheit (°F).

Indoor Unit Table 5. SetpointAttribute Identifi er Data type Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Analog-output 1 RObject Name CharacterString AC_OTempSetting RObject Type BACnetObjectType Analog-output RDescription CharacterString Setpoint OStatus Flags BACnetStatusFlags F F F F RCurrent value REAL Temperature Value WEvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RUnit BACnetEngineering Units Degree-Fahrenheit RMinimum REAL 62°F (17°C) OMaximum REAL 86°F (30°C) ODistinguishability REAL 1 OPriority Array Value BACnetPriorityArra NULL RDefault Release REAL 0 RDistinguishability REAL 1 OCov Increment REAL 1 OLow Valve Value REAL 62°F (17°C) OHigh Valve Value REAL 86°F (30°C) OWidth Valve Value REAL 1 OEnable Valve Value BACnetLimitEnable T T OEvent Enable BACnetEventTransitionBits T T T ONotify Type BACnetNotifyType Alarm OPublicly Type Unsigned 1701 OTime Delay Unsigned 1 OAffi rm Transform BACnetEventTransitionBits T T T O

NOTE - All values are degrees Fahrenheit (°F). You must send degrees Fahrenheit (°F) values and you will receive degrees Fahrenheit (°F). Range: 61°F - 90°F (16°C - 32°C)..

Page 31: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

31

Indoor Unit Table 7. Room TemperatureAttribute Identifi er Data Mode Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Analog-input 1 RObject Name CharacterString AC_ITempIndoor RObject Type BACnetObjectType Analog-input RCurrent Value REAL 0 RDescription CharacterString Indoor Temperature OUnit BACnetEngineering Units Degree-Fahrenheit RStatus Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RReliablity BACnetReliability NO-FAULT-DETECTED RTake Off Service BOOLEAN F RUnit BACnetEngineering Units Degree-Fahrenheit RMinimum REAL 0°F (-18°C) OMaximum REAL 200°F (93°C) ODistinguishability REAL 1 OTime Delay Unsigned 1 OPublicly Type Unsigned 1701 OLow Valve Value REAL 0°F (-18°C) OHigh Valve Value REAL 200°F (93°C) OWidth Valve Value REAL 1 OEnable Valve Value BACnetLimitEnable F T OEvent Enable BACnetEventTransitionBits T T T ONotify Type BACnetNotifyType event O

NOTE - The received value is degrees Fahrenheit (°F).

Page 32: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

32

Indoor Unit Table 8. SwingAttribute Identifi er Data type Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Binary-output 1 RObject Name CharacterString AC_OSwing RObject Type BACnetObjectType Binary-output RCurrent Value BACnetBinaryPV inactive WDescription CharacterString Swing Setting OStatus Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RPolarity BACnetPolarity Normal RInactive Text CharacterString Turn off OActive Text CharacterString Turn on OTime Delay Unsigned 1 OStatus Change Time BACnetDateTime OStatus Change Times Unsigned OChange Time To 0 BACnetDateTime OPublicly Type Unsigned 1701 OFeedback Value BACnetBinaryPV inactive OEvent Enable BACnetEventTransitionBits T T T RAffi rm Transform BACnetEventTransitionBits T T T OPriority Array BACnetPriorityArra NULL RDefault Release BACnetBinaryPV inactive RNotify Type BACnetNotifyType Alarm O

NOTE - Inactive means swing OFF, active means swing ON.

Page 33: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

33

Indoor Unit Table 9. Error CodeAttribute Identifi er Data Mode Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er MultiState-input 1 RObject Name CharacterString AC_IMalfunction RObject Type BACnetObjectType MultiState-input RDescription CharacterString Malfunction Status OCurrent Value Unsigned 0 RStatus Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RStatus Number Unsigned 11 R

Status TextBACnet ARRAY[N]CharacterString

E0

O

E1 E2E3 E4 E5 E6 E7 E8 E9 EA EB ECEDEEEFNo

Time Delay Unsigned 1 OPublicity Type Unsigned 1701 OEvent Enable BACnetEventTransitionBits T T T OAffi rm Transform BACnetEventTransitionBits T T T ONotify Type BACnetNotifyType Alarm O

NOTE - Refer to the Lennox VRF Mobile App for error code descriptions.

Page 34: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

34

Indoor Unit Table 10. Protection Code

Attribute Identifi er Data Mode Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er MultiState-input 2 RObject Name CharacterString AC_IProtect RObject Type BACnetObjectType MultiState-input RDescription CharacterString Protect Status OCurrent Value Unsigned 0 RStatus Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RStatus Number Unsigned 11 R

Status TextBACnet ARRAY[N]CharacterString

P0

O

P1 P2 P3 P4 P5 P6 P7 P8 PF No

Time Delay Unsigned 1 OPublicly Type Unsigned 1701 OEvent Enable BACnetEventTransitionBits T T T OAffi rm Transform BACnetEventTransitionBits T T T ONotify Type BACnetNotifyType Alarm O

NOTE - Refer to the Lennox VRF Mobile App for error code descriptions.

Page 35: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

35

Indoor Unit Table 11. Remote Control Lock

Attribute Identifi er Data Mode Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er Binary-output 4 R/WObject Name CharacterString Remote_Control_lock RObject Type BACnetObjectType Binary-output RCurrent Value BACnetBinaryPV inactive W

Description CharacterString Lock/Unlock remote control O

Status Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RPolarity BACnetPolarity Normal RInactive text CharacterString unlock remote control OActive text CharacterString lock remote control OTime Delay Unsigned 1 OStatus Change Time BACnetDateTime OStatus Change Times Unsigned OChange Time To 0 BACnetDateTime OPublicly Type Unsigned 1701 OFeedback Value BACnetBinaryPV inactive OEvent Enable BACnetEventTransitionBits T T T RAffi rm Transform BACnetEventTransitionBits T T T OPriority Array BACnetPriorityArra NULL RDefault Release BACnetBinaryPV inactive RNotify Type BACnetNotifyType Alarm O

NOTE - Refer to the Lennox VRF Mobile App for error code descriptions.NOTE - Lock All Functions of Wireless Remote Controller V0STAT52P-1.NOTE - Inactive means unlock remote control, active means lock remote control.

Page 36: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

36

Indoor Unit Table 12. Turn Indoor Unit ON/OFF

Attribute Identifi er Data Mode Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er Binary-output 3 R/WObject Name CharacterString AC_TurnOnOff RObject Type BACnetObjectType Binary-output RCurrent Value BACnetBinaryPV inactive WDescription CharacterString Turn On/Off the AC OStatus Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RPolarity BACnetPolarity Normal RInactive text CharacterString Turn off OActive text CharacterString Turn on OTime Delay Unsigned 1 OStatus Change Time BACnetDateTime OStatus Change Times Unsigned OChange Time To 0 BACnetDateTime OPublicly Type Unsigned 1701 OFeedback Value BACnetBinaryPV inactive OEvent Enable BACnetEventTransitionBits T T T RAffi rm Transform BACnetEventTransitionBits T T T OPriority Array BACnetPriorityArra NULL RDefault Release BACnetBinaryPV inactive RNotify Type BACnetNotifyType Alarm O

NOTE - Refer to the Lennox VRF Mobile App for error code descriptions.NOTE - Inactive means indoor unit turned off, active means indoor unit turned on.

Page 37: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

37

Indoor Unit Table 13. Turn All Indoor Units ON/OFF

Attribute Identifi er Data Mode Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er Binary-output 5 R/WObject Name CharacterString ALL_AC_OnOff RObject Type BACnetObjectType Binary-output RCurrent Value BACnetBinaryPV inactive W

Description CharacterString turn on/turn off ac all the bus O

Status Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RPolarity BACnetPolarity Normal RInactive text CharacterString OActive text CharacterString turn off ac all the bus OTime Delay Unsigned 1 OStatus Change Time BACnetDateTime OStatus Change Times Unsigned OChange Time To 0 BACnetDateTime OPublicly Type Unsigned 1701 OFeedback Value BACnetBinaryPV inactive OEvent Enable BACnetEventTransitionBits T T T RAffi rm Transform BACnetEventTransitionBits T T T OPriority Array BACnetPriorityArra NULL RDefault Release BACnetBinaryPV inactive RNotify Type BACnetNotifyType Alarm O

NOTE - Refer to the Lennox VRF Mobile App for error code descriptions.NOTE - Active means turn off all indoor units.

Page 38: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

38

Outdoor Unit Table 1. Operation Mode

Attribute Identifi er Data Mode Attribute value Meaning Read/Write

Object Identifi er BACnetObjectIdentifi er MultiState-input 1 RObject Name CharacterString AC_IOperationMode RObject Type BACnetObjectType MultiState-input RDescription CharacterString Operation mode OCurrent Value REAL 0 RStatus Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RStatus Number Unsigned 3 R

Status TextBACnet ARRAY [N]CharacterString

123

HeatCoolStop

O

Time Delay Unsigned 1 OPublicly Type Unsigned 1701 OEvent Enable BACnetEventTransitionBits T T T OAffi rm Transform BACnetEventTransitionBits T T T ONotify Type BACnetNotifyType Alarm O

Appendix C. Outdoor Unit Detailed Points

NOTE - Outdoor unit control & monitoring points are not available for Mini-Split systems. -1P Mini-VRF systems require the Mini-VRF Control Interface V0CTRL00P-1.

Page 39: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

39

Outdoor Unit Table 2. Condenser Fan SpeedAttribute Identifi er Data Mode Attribute value Meaning Read/WriteObject Identifi er BACnetObjectIdentifi er MultiState-input 2 RObject Name CharacterString AC_IFanSpeed RObject Type BACnetObjectType MultiState-input RDescription CharacterString Fan Speed OCurrent Value Unsigned 0 RStatus Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RTake Off Service serviceBOOLEAN F RStatus Number Unsigned 4 ROptions Integer 1

23

HighMediumLow

O

Time Delay Unsigned 1 OPublicly Type Unsigned 1701 OEvent Enable BACnetEventTransitionBits T T T OAffi rm Transform BACnetEventTransitionBits T T T ONotify Type BACnetNotifyType event O

Page 40: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

40

Outdoor Unit Table 3. Ambient Temperature

Attribute Identifi er Data type Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er Analog-input 1 RObject Name CharacterString AC_ITempOutoor RObject Type BACnetObjectType Analog-input RCurrent Value REAL 0 RDescription CharacterString Outdoor Temperature OStatus Flags BACnetStatusFlags F F F REvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RUnit BACnetEngineering Units Degree-Fahrenheit RMinimum REAL 0°F (-18°C) OMaximum REAL 200°F (93°C) OTime Delay Unsigned 1 OPublicly Type Unsigned 1701 OLow Valve Value REAL 0°F (-18°C) OHigh Valve Value REAL 200°F (93°C) OWidth Valve Value REAL 1 OEnable Valve Value BACnetLimitEnable F T OEvent Enable BACnetEventTransitionBits T T T ONotify Type BACnetNotifyType event O

NOTE - The received value is degrees Fahrenheit (°F).

Page 41: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

41

Outdoor Unit Table 4. Indoor QuantityAttribute Identifi er Data Mode Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Analog-input 2 RObject Name CharacterString AC_ITotalACs RObject Type BACnetObjectType Analog-input RCurrent Value REAL 0 RDescription CharacterString Indoor unit qty OStatus Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RUnit BACnetEngineering Units RMinimum REAL 0 OMaximum REAL 250 OTime Delay Unsigned 1 OPublicly Type Unsigned 1701 OLow Valve Value REAL 0 OHigh Valve Value REAL 250 OWidth Valve Value REAL 1 OEnable Valve Value BACnetLimitEnable F T OEvent Enable BACnetEventTransitionBits T T T ONotify Type BACnetNotifyType Alarm O

Operation Instruction The CURRENT VALUE attribute of the selected object refl ects the current INDOOR UNIT QUANTITY (it’s read only).

Page 42: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

42

Outdoor Unit Table 5. Error Code Compressor 1Attribute Identifi er Data type Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Analog-input 3 RObject Name CharacterString AC_ICom1Current RObject Type BACnetObjectType Analog-input RCurrent Value REAL 0 RDescription CharacterString Compressor 1 current OStatus Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RUnit BACnetEngineering Units Amperes RMinimum REAL 0 OMaximum REAL 200 OTime Delay Unsigned 1 OPublicly Type Unsigned 1701 OLow Valve Value REAL 0 OHigh Valve Value REAL 200 OWidth Valve Value REAL 1 OEnable Valve Value BACnetLimitEnable F T ONotify Type BACnetNotifyType Alarm O

Operation InstructionThe CURRENT VALUE attribute of the selected object refl ects theCOMPRESSOR 1 ELECTRIC CURRENT (Read only).

Page 43: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

43

Outdoor Unit Table 6. Error Code Compressor 2Attribute Identifi er Data type Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Analog-input 4 RObject Name CharacterString AC_ICom2Current RObject Type BACnetObjectType Analog-input RCurrent Value REAL 0 RDescription CharacterString Compressor 2 current OStatus Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RUnit BACnetEngineering Units Amperes RMinimum REAL 0 OMaximum REAL 200 OTime Delay Unsigned 1 OPublicly Type Unsigned 1701 OLow Valve Value REAL 0 OHigh Valve Value REAL 200 OWidth Valve Value REAL 1 OEnable Valve Value BACnetLimitEnable F T OEvent Enable BACnetEventTransitionBits T T T ONotify Type BACnetNotifyType Alarm O

Operation InstructionThe CURRENT VALUE attribute of the selected object refl ects theCOMPRESSOR 2 ELECTRIC CURRENT (Read only).

Page 44: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

44

Outdoor Unit Table 7. Error Code Compressor 3Attribute Identifi er Data type Attribute value Read/WriteObject Identifi er BACnetObjectIdentifi er Analog-input 5 RObject Name CharacterString AC_ICom3Current RObject Type BACnetObjectType Analog-input RDescription CharacterString Compressor 3 current OCurrent Value REAL 0 RStatus Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RUnit BACnetEngineering Units Amperes RMinimum REAL 0 OMaximum REAL 200 OTime Delay Unsigned 1 OPublicly Type Unsigned 1701 OLow Valve Value REAL 0 OHigh Valve Value REAL 200 OWidth Valve Value REAL 1 OEnable Valve Value BACnetLimitEnable F T OEvent Enable BACnetEventTransitionBits T T T ONotify Type BACnetNotifyType Alarm O

Operation InstructionThe CURRENT VALUE attribute of the selected object refl ects theCOMPRESSOR 3 ELECTRIC CURRENT (Read only).

Page 45: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

45

Outdoor Unit Table 8. Error Code

Attribute Identifi er Data type Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er MultiState-input 3 RObject Name CharacterString AC_IMalfunction RObject Type BACnetObjectType MultiState-input RDescription CharacterString Malfunction Status OCurrent Value Unsigned 0 RStatus Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal RTake Off Service BOOLEAN F RStatus Number Unsigned 17 R

Status TextBACnet ARRAY[N]CharacterString

E0

O

E1 E2E3 E4 E5 E6 E7 E8 E9 EA EB ECEDEEEFNo

Time Delay Unsigned 1 OPublicly Type Unsigned 1701 OEvent Enable BACnetEventTransitionBits T T T OAffi rm Transform BACnetEventTransitionBits T T T ONotify Type BACnetNotifyType Alarm O

NOTE - Refer to the Lennox VRF Mobile App for error code descriptions.

Page 46: V0CTRL86P Lennox VRF, Mini-VRF and Mini-Split

46

Outdoor Unit Table 9. Protection Code

Attribute Identifi er Data Mode Attribute value Read/Write

Object Identifi er BACnetObjectIdentifi er MultiState-input 4 RObject Name CharacterString AC_IProtect RObject Type BACnetObjectType MultiState-input RDescription CharacterString Protect Status OCurrent value Unsigned 0 RStatus Flags BACnetStatusFlags F F F F REvent Status BACnet EventStatus Normal R

Take Off Service BOOLEAN F RStatus Number Unsigned 17 R

Status TextBACnet ARRAY[N]CharacterString

P0

O

P1 P2 P3 P4 P5 P6 P7 P8 P9 PA PB PC PD PE PF No

Time Delay Unsigned 1 OPublicly Type Unsigned 1701 OEvent Enable BACnetEventTransitionBits T T T OAffi rm transform BACnetEventTransitionBits T T T ONotify Type BACnetNotifyType Alarm O

NOTE - Refer to the Lennox VRF Mobile App for error code descriptions.