THDPM-1

By-EMBUILT TECHNOLOGIES

www.embuilt.comwww.energylogger.blogspot.com

[email protected]

(THD MEASUREMENT WITH EXAMPLES AND FIGURES)

Date-01/09/2014

Page 2: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

THDPM-1

Auxiliary Supply : 180 – 240 VoltsInput Voltage : 0 – 240 VoltsCurrent : 0 – 2.0 A*(200mA,500mA range are also available)

Measures upto 51st HarmonicAccuracy Class : 1%Voltage HarmonicsCurrent Harmonics

Page 3: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

INTRODUCTION

THDPM-1 is THD analyzer which measures upto 51st harmonic.

It provides Voltage and Current THD. It shows the net effect on THD due to load. It also shows following parameters-

VoltageCurrentWattFrequencyPower Factor

It is useful for testing of LED Drivers, SMPS, CFL, CHOKES etc.

Page 4: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

MAIN PAGE

VOLTAGE

CURRENTWATT

PF

VOLTAGE THD

CURRENT THD

NET THD

(Frequency and PF shows alternately )

Press to see Voltage Harmonics

Page 5: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

VOLTAGE THD PAGE

3rdHarmonicVoltage

5th Harmonic

7th Harmonic

Voltage rms Value

1st Harmonic

THD %

Press to see more Harmonics (Upto 51st harmonic can be seen)

Press to see Current Harmonics

Press to see Previous Harmonic

Page 6: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

CURRENT THD PAGE

3rd Harmonic

Current

5th Harmonic7th Harmonic

Current rms Value

1st Harmonic

Current THD %

Press

to see more Harmonics

Press to see Previous Harmonic

Page 7: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

TEST BENCH SETUP

Page 8: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

THD ANALYSIS

Page 9: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

Experiment 1

Lets start testing with only bulb load.

We take a 100 Watt bulb load and connect it to load side.

Voltage THD is 2.90% and Current THD is 4.85%.

So bulb cause a small Distortion in current.

WITH BULB LOAD

Page 10: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

EXPERIMENT 1 PART AVOLTAGE THD

Page 11: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

EXPERIMENT 1 PART BCURRENT THD

Page 12: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

WITH CFL LOAD

Experiment with only CFL load.

We take a normal 14 Watt CFL and connect it to load side.

Voltage THD is 3.56% and Current THD is 26.99%.

A CFL distorts the current more.

Experiment 2

Page 13: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

EXPERIMENT 2 PART AVOLTAGE THD

Page 14: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

EXPERIMENT 2 PART BCURRENT THD

Page 15: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

WITH BULB AND CFL LOAD

Experiment with BULB and CFL load.

BULB specification is 100 Watt . CFL specification is 14W. Voltage THD is 3.23% and Current THD is

5.99% . BULB has more power than CFL and also

linear in nature so it tends to decrease the current distortion.

Experiment 3

Page 16: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

EXPERIMENT 3 PART AVOLTAGE THD

Page 17: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

EXPERIMENT 3 PART BCURRENT THD

Page 18: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

WITH BULB AND CAPACITOR LOAD

Experiment with BULB and CAPACITOR.

We take a capacitor of 3.15µF and connect to load side with a normal BULB load.

Voltage THD is 3.12% and Current THD is 15.34%.

A capacitor also distorts the current.

Experiment 4

Page 19: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

EXPERIMENT 4 PART AVOLTAGE THD

Page 20: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

EXPERIMENT 4 PART BCURRENT THD

Page 21: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

WITH LAPTOP LOAD

Experiment with Laptop load.

We take a laptop and connect it to supply with charger of 65watt.

Voltage THD is 7.92% and Current THD is 113.1%.

AC to DC Converters provides high distortion in current.

Experiment 5

Page 22: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

EXPERIMENT 5 PART AVOLTAGE THD

Page 23: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

EXPERIMENT 5 PART BCURRENT THD

Page 24: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

WITH BULB AND LAPTOP LOAD

Experiment with Laptop and Bulb load.

We Connect Bulb and Laptop at load side. Voltage THD is 8.83% and Current THD is

69.59% . A linear load reduces the current distortion. BULB has more power than Laptop Charger and also

linear in nature so it tends to decrease the current distortion.

Experiment 6

Page 25: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

EXPERIMENT 6 PART AVOLTAGE THD

Page 26: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

EXPERIMENT 6 PART BCURRENT THD

Page 27: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

WITH LED DRIVER LOAD

Experiment with LED and LED Driver Load.

We Connect LEDs at load side through LED Driver.

Voltage THD is 1.68% and Current THD is 133.9% .

LED Driver produces high distortion in current.

Experiment 7

Page 28: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

EXPERIMENT 7 PART AVOLTAGE THD

Page 29: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

EXPERIMENT 7 PART BCURRENT THD

Page 30: TOTAL HARMONIC DISTORTION POWER METER BY EMBUILT TECHNOLOGIES

WITH LED BULB LOAD

Experiment with LED BULB.

We Connect LED at at load side. Voltage THD is 2.55% and Current THD is

63.40% . LED Driver produces distortion in current.