Transcript
Page 1: SMA plant management solutions for seamless power integration · The SMA Hybrid Controller intelligently controls energy flows and enables seamless integration of renewable energies

SMA LARGE SCALE SOLUTIONS

Optimal control of large scale PV projects

SMA HYBRID

SMA plant management solutions for seamless power integration

Page 2: SMA plant management solutions for seamless power integration · The SMA Hybrid Controller intelligently controls energy flows and enables seamless integration of renewable energies

Cost-effective

• Increases yields• Easy installation• Fast commissioning• Remote monitoring and system

setting with SCADA

Scalable

• Modular design for customiza-tion and system expansion

• A wealth of functions for various penetration levels

Benefit from clean solar power:

• Meet grid operator requirements including primary control reserve and frequency response• Stable utility grid operation without generators or electricity• Microgrid frequency and voltage control• High-precision frequency and voltage measurement• Control utility grid storage systems and generators • Support for cloud cameras

Robust

• Designed for harsh environ-ments

• Fully tested industrial grade components

SMA plant control

The SMA Hybrid Controller intelligently controls energy flows and enables seamless integration of renewable energies into power grids. With the new diesel-off function, it operates micro grids based entirely on renewable energies and keeps the utility grid stable even if strong fluctuations occur. The device automatically regulates all generators and storage systems according to the required load profile, and takes on comprehensive grid management functions up to the provision of control reserve in large utility grids. Thanks to its intuitive user interface, the SMA Hybrid Controller offers clearly structured configuration wizards and full transparency on energy flows.

Flexible

• The right configuration for every system size

• Storage systems can be integrated

NEW: 100% SOLAR POWER

FOR DIESEL-OFF MODE

Page 3: SMA plant management solutions for seamless power integration · The SMA Hybrid Controller intelligently controls energy flows and enables seamless integration of renewable energies

More flexibility for new opportunities

• Peak load shaving• Energy shifting• Time of use management

• Frequency & voltage control• Genset spinning reserve• Diesel off mode• Optimized genset operation

• Renewable ramp rate control• Frequency control• Energy shifting

• Feed-in management• Grid services

• Dispatch of PV power to match load demands

• Increase in self-consumption• Active & reactive power control

Page 4: SMA plant management solutions for seamless power integration · The SMA Hybrid Controller intelligently controls energy flows and enables seamless integration of renewable energies

www.SMA.de

TECHNICAL DATASMA Hybrid Controller

Hybrid Controller Small

Hybrid Controller Medium

Hybrid Controller Large

Hybrid Controller X-Large

General System DesignSystem size (PV system size) up to 750 kW up to 2000 kW unlimited unlimitedMaximum number of devices1) totalPV invertersGensetsBattery inverterExternal measurement (DAQ / Janitza / more upon request)Irradiation sensors

max. 40max. 32max. 8 − −max. 2

max. 1208)

max. 120max. 16max. 32max. 10max. 2

max. 1208)

max. 120max. 16max. 32max. 10max. 2

max. 1608)

max. 120max. 16max. 64max. 20max. 2

General DataDimensions (W x H x D) in mm (approx.) 760 x 760 x 210 760 x 760 x 210 760 x 760 x 210 upon requestWeight (approx.) 48 kg Degree of protection in accordance with DIN EN 60529 IP 65Ambient ConditionsOperating temperature range –20°C to +50°CMaximum operating altitude 2000 m above mean sea level2)

Humidity 5% to 95% (non-condensing)Power supplyVoltage supply (nominal value) 110 Vac to 240 Vac, 50 Hz / 60 Hz Power consumption (max. / average) 200 W / 120 WCommunicationSystem communication for system monitoring, SCADA and remote monitoring

Modbus / TCP, HTTP, FTP over Ethernet 10 BASE-T and 100 BASE-T(X)

Communication between the devices Ethernet 100BASE-FX and TX2)

Supported communication protocols IEC 60870-5-104; IEC 60870-5-1017); IEC 60870-5-1037); IEC 618507); IEEE1815 (DNP3)7)

Communication to inverters / maximum cable length Sunny Central: Ethernet 100BASE-TX or 100BASE-FX (optional) /Sunny Tripower: 100BASE-TX

Communication protocol to genset controllers Modbus / TCP Master via Ethernet 100BASE-FX and TX or CAN / CANOpen3)

Communication devices Unmanaged switch Routing switch, supporting a remote access and VPNOther InterfacesMulti-functional digital inputs for potential-free contacts 10 10 10 upon requestPower measurement Integrated current measurements: 1 A4) at the sensor input5)

Integrated voltage measurement: 480 V voltage input42

42

63

upon requestupon request

Compatible external power measurement No SMA FSC-11-DAQ, UMG 604 JANITZA6),ION PowerLogic 7650/7750/8600/8800 upon request

Visualization & data recordingVisualization and confi guration interface Web interface for local and remote monitoringData / event recording 10 second values for 30 days (changeable) / by eventsCompatible invertersInverters Sunny Tripower (STP TL-30, STP US-10, STP

60-10, STP50-40), Sunny Tripower Storage7), Sunny Highpower Peak1

Sunny Tripower (STP TL-30, STP US-10, STP 60-10, STP50-40), Sunny Tripower Storage,

Sunny Highpower Peak1, Sunny Central CP-XT, Sunny Central,

Sunny Central Storage1) Different distribution via customer-specifi c software is an option 2) Individual altitude, cable length upon request3) Protocol implementation upon request4) 5A sensor available upon request5) Up to 100 m cable length6) Not included in the scope of delivery of SMA7) Upon request8) Die maximale Anzahl der Geräte ist von den projektspezifi schen Anforderungen an die Regelungsfunktionen und den erwarteten Zykluszeiten abhängig.Type designation HYBRID CONTROLLER