•Fiber-free,non-particulating,formaldehyde-free,freeofPDBEflameretardants,lowVOC,andmanufacturedwithbuilt-inMicroban®antimicrobialprotectiontoimproveIndoorAirQuality
•AttenuatesairbornenoisetoreducebackgroundnoisefromHVACsystems
•MeetsASHRAE90.1-2010,ASHRAEStandard189.1,
•IECC2012andCaliforniaTitle24forincreasedenergyefficiency
•Designedtolasttheusefullifeofmechanicalequipment
•Pressuresensitiveadhesivesystemsavesinstallationlaborcosts
Theoriginal,fiber-free,closed-cellthermalandacousticalductinsulation–withalabor-savingpressuresensitivesystem–engineeredtosafeguardIAQ,attenuateHVACnoiseandreduceenergywaste
a d v a n c e d i n s u l a t i o n
Self-AdhesiveDuctLiner/Wrap
Fiber Free
Technical Data: AP Armaflex® SA and AP Armaflex® FS SA Black Duct Liner and Wrap – Self Adhesive
Description:Blackflexibleclosed-cellelastomericthermalandacousticalductinsulationinsheetandrollformwithaself-adheringbacking
Specifications Compliance:
ASTMC534,TypeII—SheetGrade1ASTMC1534ASTMD1056,2B1
ASTME84,NFPA255,UL723ASTMG21/C1338ASTMG22CAN/ULCS1021
MEA107-89MMIL-P-15280J,FORMS2
MIL-C-3133C(MILSTD670B)GradeSBE32
NFPA90A,90BUL181UL945V-A,V-0,FileE55798CityofLA–RR7642
Approvals, Certifications, Compliances:•KeyphysicalpropertiesareapprovedbyFactoryMutual.
•GREENGUARD®Children&SchoolsIndoorAirQualitycertified.
•ManufacturedwithoutCFCs,HFCs,HCFCs,PBDEs,orFormaldehyde.
•MadewithEPAregisteredMicroban®antimicrobialproductprotection.
•AllArmacellfacilitiesinNorthAmericaareISO9001:2008certified.
Typical Properties
Specifications: Values Test Method:
AP Armaflex SA Through 1” Duct Liner and Wrap
AP Armaflex FS SA 1-1/2 and 2” Duct Liner
AP Armaflex SA 1-1/2 and 2” Duct Wrap
Thermal Conductivity:Btu•in./h•ft2•°F(W/mK)
75°FMeanTemperature(24°C)90°FMeanTemperature(32°C)
0.25(0.036)0.256(0.037)
0.28(0.040)0.28(0.040)
0.25(0.036)0.256(0.037)
ASTMC177orC518
Water Vapor Permeability:Perm-in.[Kg/(s•m•Pa)]
0.05(0.725x10–13) 0.08(1.16x10–13) 0.05(0.725x10–13) ASTME96,ProcedureA
Flame Spread and Smoke Developed Index:
25/50rated 25/50rated Doesnotpass ASTME84CAN/ULCS1021-APthrough1”
Water Absorption, %byVolume: 0.2% 0.2% 0.2% ASTMC209
Mold Growth:Fungi Resistance :Bacterial Resistance:
Passed Passed Passed UL181ASTMG21/C1338ASTMG22
Upper Use Limit: 2 180°F(82°C) 180°F(82°C) 180°F(82°C)
Lower Use Limit: 3 -297°F(-183°C)4 -297°F(-183°C)4 -297°F(-183°C)4
Ozone Resistance: GOOD GOOD GOOD
Erosion Resistance: Doesnotbreakaway,flakeofforshowevidenceordelaminationatvelocitiesof10,000ft/min
ASTMC1071
R-Value R-1.4 R-2.1 R-3.1 R-4.2 R-6 R-8Thickness: 3/8" 1/2" 3/4" 1" 1-1/2" 2"
Sound Absorption Coefficients Frequency 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz NRC SAAThicknessNom.1"(25mm) 0.01 0.13 0.39 0.69 0.29 0.26 0.40 0.38
Sizes:Sheet:WidthxLength 36”x48”
Roll:Width 48”(allthicknesses)and60”(1”only)
Thickness APArmaflexSADuctLinerandWrap:1/2”,3/4”,and1”APArmaflexFSSADuctLiner:1-1/2”and2”APArmaflexSADuctWrap:1-1/2”and2”
1APArmaflexmeetsCAN/ULCS102through1”thickness.2APArmaflexandAPArmaflexFSBlackDuctLiner/Wrapswithstandtemperatureof250°F(121°C)whentestedaccordingtoASTMC411.“TestMethodforSurfacePerformanceofHigh-TemperatureInsulations”.Atthistemperature,AP/ArmaflexDuctLiner/Wrapinsulationshowsnoevidenceofflaming,glowing,smoldering,delamination,meltingorinsulationcollapse.Althoughthisinsulationwillwithstandhightemperatures,continuoususetemperatureshouldbelimitedto180°F(82°C).
3Attemperaturesbelow-20°F(-29°C),elastomericinsulationstartstobecomelessflexible.However,thischaracteristicdoesnotaffectthermalefficiencyandresistancetowatervaporpermeabilityofArmaflexinsulation.
4Forapplicationsof-40°Fto-297°F(-40°Cto-183°C),contactArmacell.
APArmaflexandFS Self-AdhesiveDuctLinerandWrap Submittal 021B Eng/USA 1/2013
©2013ArmacellLLC.PrintedinUnitedStatesofAmerica
Armacellprovidesthisinformationasatechnicalservice.TotheextenttheinformationisderivedfromsourcesotherthanArmacell,Armacellissubstantially,ifnotwholly,relyingupontheothersource(s)toprovideaccurateinformation.InformationprovidedasaresultofArmacell’sowntechnicalanalysisandtestingisaccuratetotheextentofourknowledgeandability,asofdateofprinting,usingeffectivestandardizedmethodsandprocedures.Eachuseroftheseproducts,or information,shouldperformtheirownteststodeterminethesafety, fitnessandsuitabilityof theproducts,orcombinationofproducts, foranyforeseeablepurposes,applicationsandusesbytheuserandbyanythirdparty towhichtheusermayconveytheproducts.SinceArmacellcannotcontroltheenduseofthisproduct,Armacelldoesnotguaranteethattheuserwillobtainthesameresultsaspublishedinthis document. The data and information are provided as a technical service and are subject to change without notice. The GREENGUARD Children & Schools CertifiedMarkis a registered certification mark used under license through the GREENGUARD Environmental Institute. Microban is a registered trademark of Microban Products Company.
a d v a n c e d i n s u l a t i o n
ARMACELL LLC TEL:800.866.5638FAX:919.304.3847info.us@armacell.comwww.armacell.us7600OakwoodStreetExtension,Mebane,NC27302