OMICRON TEST METHOD FOR DTP

1. From relay software Press measure & counter

2. This screen will appeared

1 /17

Page 2: Omicron Test Method for Dtp

3. For pickup value (sensitivity) Double click on omicron icon

2 /17

Page 3: Omicron Test Method for Dtp

4. This screen will appear OMICRON MAIN SCREEN click QUICKCMC

3 /17

Page 4: Omicron Test Method for Dtp

5. There are two methods to test sensitivity 5/1 by applying value in ph R =0.2 A if no trip stop the test and increase the value to 0.3 Ato get the min pickup value

4 /17

Page 5: Omicron Test Method for Dtp

5/2 by applying value in ph R =0.2 A and make auto test by adjust the increasing value and take stop contact from the diff. relay to stop test at the pickup value So adjust step like as fellow:Triple = CMC156-EPI size = 0.01 AQuantity = I1 time = 0.5 SAnd select auto step and select stop contact then press test

5 /17

Page 6: Omicron Test Method for Dtp

6. For test harmonic in the main screen press testing tools then press harmonic

6 /17

Page 7: Omicron Test Method for Dtp

7. This screen will appearput Ia = 5 A time = 1 S select Ia from here and harmonic value = 22 % then file - export

7 /17

Page 8: Omicron Test Method for Dtp

8. this screen will appear enter the name of your harmonic (any name) for ex. 2 hr 22

8 /17

Page 9: Omicron Test Method for Dtp

9. this screen will appear then press OK then file - Exit or press here

9 /17

Page 10: Omicron Test Method for Dtp

10. this screen will appear then press NO

10 /17

Page 11: Omicron Test Method for Dtp

11. The main screen will appear againPress testing tools then transplay

11 /17

Page 12: Omicron Test Method for Dtp

12. This screen will appear press add to list

12 /17

Page 13: Omicron Test Method for Dtp

13. This screen will appear then select your test name and press open

13 /17

Page 14: Omicron Test Method for Dtp

14. This screen will appear then press ok

14 /17

Page 15: Omicron Test Method for Dtp

15. This screen will appear then press play (means the tester start to inject if you want to change the harmonic value repeat again from point 7 and adjust according your requirements

15 /17

Page 16: Omicron Test Method for Dtp

16. For RESTRAIN testOpen screen QUICKCMCThen inject ph R = 2.5 A angle 0 and connect it to ph R HV side, Inject ph S = 1.443 A angle 180, ph T= 1.443 A angle 0 and connect it to ph R ,ph T LV side consequently Then start test and read the measurements from TDP software and take Id , It

16 /17

Page 17: Omicron Test Method for Dtp

17. Instantaneous function 87B

Disable the harmonic & diff. functions Enable Instantaneous function 87B

Then open QUICKCMC and make auto test for this function to bring the tripping value Like as point Start from 9 A and size 0.1 ALike this screen

Eng. Mohammed Deraz