Electrical scheme with 2 level sensors linking in a contactor controlling a pump for an automatic level control.

L1 L2 L3

T1 T2 T3

13

14

A1

A2

L1 L2

Upper level sensor

Lower level sensor

Pump

Working 1 - Empty tank: The switches are opened and do not permit the coil energization (A1/A2) from contactor keeping the pump off.

2 - The tanks level rises: The lower sensor close the contacts but the coil keeps not energyzed until the upper sensor be reached, then the contactor remain energyzed by the contacts 13/14, starting the pump.

3 - Lowering the tank: When the upper sensor opens the coil keep energyzed by the contacts 13/14 and the pump keep on. When the level get the lower sensor it will open the contact, turning the pump off.

IMPORTANT Automatic drain control