Transcript
Page 1: Grounding Bonding for Substation Communications

PRESENTATION TO IEEE PES, ORLANDO CHAPTER:

“GROUNDING & BONDING CONSIDERATIONS FOR SUBSTATION COMMUNICATIONS AND “SMART GRID””

Developed and Presented By:Adrian G Zvarych, PEPrincipal EngineerTRC EngineeringMember, IEEE24 September [email protected]

Additional Contributions & Peer Review By: Michael Cunningham, Senior Engineer - TRC

Page 2: Grounding Bonding for Substation Communications

Class Objectives

1. Understand Substation Grounding/Bonding Design Goals to Satisfy Communications Requirements

2. Review of Typical Substation Control House Grounding/Bonding Practices

3. Review Typical Telecom Room Grounding/Bonding Practices

4. Necessary Grounding & Bonding Elements for a Smart Grid Friendly and Communications – Ready Substation Control House

5. Look-Ahead for other opportunities

6. Review

40Years of Service

19692009

Page 3: Grounding Bonding for Substation Communications

Change Has Been Happening

40Years of Service

19692009

Page 4: Grounding Bonding for Substation Communications

Part 1: Substation Communications Evolution

Communications migration path:– Analog to digital– Discrete to multiplexed– Local Information decision needs to remote and diverse needs– Lower Reliability to High Reliability (design and need)– Minimal regulation (self- on inter-industry regulation to increased scrutiny and

regulation by others)

40Years of Service

19692009

Page 5: Grounding Bonding for Substation Communications

Pilot Wire Interface& Isolation Transformers

Page 6: Grounding Bonding for Substation Communications

Circa 1900’s Distribution Breakers

1912 – Manufactured GE Oil Break Switch…

STILL IN SERVICE!!!!

Page 7: Grounding Bonding for Substation Communications

Legacy Substation Communications Systems

PEOPLE/OPERATIONS Station Operators with all local indication Communications to Control Center via Power Line Carrier or Telephone Company Copper

Circuits (SCADA) Radio Dispatch for Crews

RELAY PROTECTION Power Line Carrier (first digital form of substation communications “ON-OFF”) Copper Based Pilot Wire All analog meters and electromechanical relays Needs driven by electric utility operations & reliability

40Years of Service

19692009

Page 8: Grounding Bonding for Substation Communications

Advancements in Legacy Substation Relaying and Communications

Driven by build out of high voltage and EHV transmission grid– Need for high speed and reliable/secure relaying– Need for remote and central monitoring and control of station equipment– First discrete component “solid state” relaying deployed in substations in the 1970s

Single Side-Band Power Line Carrier – more channels, more functionality Analog Point-To-Point Microwave Optical Networks

40Years of Service

19692009

Page 9: Grounding Bonding for Substation Communications

Development of “Non-Copper” Substation Communications Systems

Analog Microwave (circa 1960’s) Digital Microwave (circa 1980’s) Spread Spectrum – 900MHz (circa 1980’s) Fiber (circa 1990’s)

40Years of Service

19692009

Page 10: Grounding Bonding for Substation Communications

Advancements of Components/Technology

Protective Relaying Electromechanical Relays – Solid State Relays Solid State Relays – Microprocessor Relays

Communications Copper Analog Microwave Digital Microwave 900MHz – Licensed & Spread Spectrum/Unlicensed Fiber Discrete Analog Digital Multiplexed IP

40Years of Service

19692009

Page 11: Grounding Bonding for Substation Communications

TELECOMMUNICATIONS CIRCUIT HIERARCHY

DS0-1

DS0-2

DS0-3

DS0-4

DS0-24

.

.

.

DS1-1

DS1-2

DS1-4

DS1-3

DS1-28

.

.

.

OC1-1

OC1-2

OC1-3

OC3-1

OC3-2

OC3-3

OC3-4

OC12-1

OC12-2

OC12-3

OC12-4

OC48-1

OC48-2

OC48-3

OC48-4

OC192

IMUX

JMUX

JUNGLEMUX EXPANDABLETO OC48 BANDWIDTH

BROADBAND CARRIER CLASS NETWORKS

DWDM

11 2424 672672 2,0162,016 8,0648,064 32,25632,256 129,024129,024 oooo

Phone linesper circuit type

Page 12: Grounding Bonding for Substation Communications

And Now… Smart Grid!

Page 13: Grounding Bonding for Substation Communications

Effects of Smart Grid and Communications Technology

Higher density of low-signal voltage circuits (RS-232, RS-485) over copper in the control house

More fiber in the control house More non-substation hardened devices entering the control house IT-Telecom teams becoming more involved in substation control houses Organizational awareness of substation environment vs data center/telecom room

requirements

40Years of Service

19692009

Page 14: Grounding Bonding for Substation Communications

Users of Substation Information

System Operators P&C Engineering Asset Management Customer Service Center Field Maintenance Personnel (line trucks, P&C, substation, etc.) Electric System Customers (indirectly) Personnel Managers Corporate Security (access management, surveillance) IT-Security Cyber-Security Teams Utility Interchange (Where Transmission Tammy draws the line…) Others…

40Years of Service

19692009

Page 15: Grounding Bonding for Substation Communications

Substation Communications: Change Is Here

Traditional Telemetry Watts, Vars, Volts, Amps Status Open, Closed, Major, Minor Control Open, Close, Raise, Lower Voice SCADA – Analog/4 Wire AC Data

Present Day All of the above, plus Temperature Outdoor Ambient, Control House Transformer Telemetry Winding Temps, Dissolved Gas, Tap Position Battery Voltage IP Services

– Security Surveillance, Door Access Control– High Speed Remote Access for IEDs– Syncrophasors– Local Employee LAN Access– SCADA

40Years of Service

19692009

Page 16: Grounding Bonding for Substation Communications

“Change Is Here”

Increased data flow (to 27 TB/day or higher in larger utility systems) from substations Not just SCADA Non-Traditional organizations using or managing substation systems and information Increased deployment of non-station hardened equipment, despite efforts by IEEE to

develop standards such as IEEE-1613

40Years of Service

19692009

Page 17: Grounding Bonding for Substation Communications

PART 2: NAVIGATING THE TRANSITION

GOALS OF GROUNDING/BONDING – SUBSTATION AND TELECOM BASICS AND DEFINITIONS REAL WORLD CASE STUDY

Page 18: Grounding Bonding for Substation Communications

Substation GoalsSafety

– Step and Touch– Ground Potential Rise

Reliability– Lightning Mast/Shielding– Minimize Electrical System Damage and Outages– Lightning/Transient Suppression Equipment– Equalize potential differences across the station grid & in the control

building– Systems redundancy emphasized on Bulk Power and system-significant

generation

Grounding and Bonding Basics

40Years of Service

19692009

Page 19: Grounding Bonding for Substation Communications

Telecommunications GoalsSafety

– Bonding of metallic components

Reliability– Lightning protection and mitigation – outdoor– Single Point Ground Location for all attachments (Main Ground Bus)– Minimize equipment damage– Minimize telecom circuit outage time– Equipment and systems redundancy emphasized on Broadband– Reduce electrical noise– Reference for DC voltage

Grounding and Bonding Basics

40Years of Service

19692009

Page 20: Grounding Bonding for Substation Communications

Substation Grounding – A Great Start!

All outdoor metallic components are bonded to earth ground– Breakers– Transformers– Structures– Static Wires/OPGW– Distribution Neutrals– Station Service– Lightning Shielding (masts, overhead shield wires, etc.)

Control House– 4/0 copper grounding conductors brought in from grid (multiple places typically) CAUTION!!!– 4/0 conductors snaked through cable trench/cable tray system, reduced to AWG #6 as

needed for rack/panel connection– Relay/Metering/Control Panels tied to bond ‘snake’ running through the trench or tray cable

management system

40Years of Service

19692009

Page 21: Grounding Bonding for Substation Communications

ANSI/IEEE Substation Grounding Standards

IEEE 80: Guide for Safety in AC Substation Grounding

Technical Target: Outdoor AC substationsPurpose:

Establish safe limits of potential differences – human body interface Substation grounding practices review for safety/safe design practices Provide a procedure for the design of practical grounding systems based on

the above Develop analytical methods to aid in the understanding of gradient problems

DOES NOT PROVIDE GUIDANCE FOR TELECOM RELIABILITY!!!40Years of Service

19692009

Page 22: Grounding Bonding for Substation Communications

Telecom – Friendly Aspects of IEEE 80

Core benefits of an IEEE 80 ground grid design for Telecommunications Excellent low net ground grid resistance, ½ ohm is possible, depending on final

design Site – specific ground grid design Human – safe design, from a step-and-touch perspective Ground Potential Rise voltage is typically limited and affected by step-and-touch

design criteria

40Years of Service

19692009

Page 23: Grounding Bonding for Substation Communications

Safety – minimize potential differences between metallic paths Reliability – ensure proper comm circuit operation despite transient conditions Eliminate ground loops Establish single point ground reference point in any one defined area (such as

a control building room) Provide an engineered design for grounding and bonding in an area with

telecom equipment

Grounding and Bonding Goals For Telecom

40Years of Service

19692009

Page 24: Grounding Bonding for Substation Communications

Fundamental Differences Between Substation & Telecom Grounding (Control House)

SUBSTATION1. Not engineered by site,

considered a ‘standard’ practice.2. Grounding conductors can enter

the control house in multiple locations and are tied to the station ground grid at different points

3. Racks bolted directly to the floor and to each other

4. Floating DC5. Floor materials vary6. No minimum ground/bond

conductor radius typically specified

TELECOM SITE

1. Engineered on a site basis (can be templatized)

2. Single point connection to ground field

3. Racks are isolated from the floor and from each other

4. DC (+) is grounded

5. Floor materials are conductive/anti-static

6. Minimum Bend Radius Specified for transient flow40

Years of Service

19692009

Page 25: Grounding Bonding for Substation Communications

Telecom Grounding & Bonding

Definitions “Grounding” – providing an engineered, low impedance path to earth “Bonding” – the permanent joining of metallic parts to form an electrically

conductive path which will assure electrical continuity and the capacity to safely conduct any current likely to be imposed, including 60Hz and transients

Grounded Conductor – a system or circuit conductor that is intentionally grounded (these normally carry current)

– Example: Electrical neutral wire, the DC (+) cable in 48 V DC Telecom supplies Grounding Conductor – a conductor used to connect equipment or the

grounded circuit of a wiring system to a grounding electrode or electrodes (these do not normally carry current)

– Example: AC Circuit electrical ground wire (the green wire), grounding wires used to interconnect racks, equipment bonding jumpers40

Years of Service

19692009

Page 26: Grounding Bonding for Substation Communications

Telecom Grounding & Bonding

Definitions (cont’d)

Solid Ground – an intentional connection to a grounding system, using a grounding wire in which there is no additional impedance imposed

Incidental Ground – an unplanned grounding connection. Example – a conductive cabinet attached to a concrete surface via Tapcon screws can be said to be ‘Incidentally Grounded’

Earthing Electrode – a copper or copper-clad steel rod driven into the earth to provide a lower impedance path to true earth ground. Other types of earthing electrodes are steel well casings, structural steel ground grids, metallic piping for water, sewer, etc.

True Earth Ground – a virtual location beneath the earth’s surface, where electrical resistance and impedance is zero, and ‘ground’ currents run freely, whether man-made or natural

Skin Depth – a frequency and materials dependent calculation which determines the penetration of current flow density into the surface of a conductor. http://www.microwaves101.com/encyclopedia/calsdepth.cfm

40Years of Service

19692009

Page 27: Grounding Bonding for Substation Communications

Telecom Grounding & Bonding

Components of a Telecom Grounding & Bonding System at a SubstationCHPGP: Control House Principal Ground Point

A ground bus bar located near the cable connection to the substation ground grid. It serves as the central connection point for all main grounding conductors and earthing electrode

Horizontal EqualizerAn insulated grounding conductor which has it’s origination point at the CHPGP, with the

function of connecting conductive equipment in a home run fashion to the principal grounding point in the room

Halo GroundA grounding conductor, supported on insulated stand-offs around the perimeter of the room,

typically installed at seven feet or higher elevation, to which all peripheral equipment are bonded (HVAC, Heaters, Junction Boxes, etc.). The Halo is a radial connection, and not a complete electrical loop.

Mechanical and Exothermic ConnectionsCable-to-device or cable-cable connections. Outdoor connections are typically exothermic,

in-building connections are typically mechanical compression, with two-hole lugs.Hardware & Miscellaneous

Insulated stand offs, cable management, plexiglas or Lexan shields, stainless steel nuts & bolts, no-oxide grease, exothermic weld molds, mechanical connectors, etc.

40Years of Service

19692009

Page 28: Grounding Bonding for Substation Communications

Case Study: Wind Farm Control House Application

Attributes: Collector Station (34kV-230kV) yard adjacent to transmission switching station Transmission switching station has microwave tower for Primary relaying channel,

SCADA, and internal voice communications Copper leased entrance cable, with isolation, at Transmission control house Transmission control house has “PRIMARY” and “SECONDARY” rooms Communications racks and telco isolation equipment in PRIMARY room PA System in place to cover the switchyard (copper connections to yard corners)

40Years of Service

19692009

Page 29: Grounding Bonding for Substation Communications

Grounding-BondingCommunications Tower & Outside Facilities

Wireless communications for Smart Grid• Requires lightning protection @ top• Proper bonding along feedline route

• Bond @ antenna• Bond prior to horizontal transition• Bond prior to CH entry• Center conductor protection just inside CH

• Driven rods @ tower & feedline entrance

STATION GROUND GRID

40Years of Service

19692009

Page 30: Grounding Bonding for Substation Communications

Case Study Substation

Page 31: Grounding Bonding for Substation Communications

Overall Communications Elementary

Page 32: Grounding Bonding for Substation Communications

Control House Floor Plan

Page 33: Grounding Bonding for Substation Communications

40Years of Service

19692009

Ice Bridge Detail

Page 34: Grounding Bonding for Substation Communications

40Years of Service

19692009

Inside Wall Elevation

Page 35: Grounding Bonding for Substation Communications

40Years of Service

19692009

Cross Section Elevation

Page 36: Grounding Bonding for Substation Communications

Control House Bonding Connections

Page 37: Grounding Bonding for Substation Communications

Grounding-Bonding Inside The Control House

Key Design Features:• Single Point Ground Bus (no ground loops)• Discrete (insulated preferred) home-run bonding connections to all equipment

connections:• Cable tray & rack taps• AC System Neutral @ AC Panel• Telecom Reference Ground point• Substation ground grid connection• Building steel• Microwave feedlines

Departure From Telecom Practice• Racks directly bolted to floor and each other without isolation• Cable trays may not be bonded across joints• Grounding conductors not insulated40

Years of Service

19692009

Page 38: Grounding Bonding for Substation Communications

A Few Images…

Page 39: Grounding Bonding for Substation Communications

SCADA “Master” 900 MHz Transceiver 900 MHz SCADA “Remote” 900 MHz Transceiver – Indoor Mount

Page 40: Grounding Bonding for Substation Communications

“Smart” Recloser “Master” Tower

Page 41: Grounding Bonding for Substation Communications

Tower Leg Bonding

Page 42: Grounding Bonding for Substation Communications
Page 43: Grounding Bonding for Substation Communications

Halo Ground

Simple Feedline Entrance

Page 44: Grounding Bonding for Substation Communications

Outdoor Main Ground Bus Mounting

Insulated Stand-Off

Page 45: Grounding Bonding for Substation Communications

Feedline Entrance

Page 46: Grounding Bonding for Substation Communications

Ground Bus Bar Example

Page 47: Grounding Bonding for Substation Communications

1. Main Ground Bus…“Producers” and “Absorbers” SeparatedClear separation of power, grounding, and data cables

Page 48: Grounding Bonding for Substation Communications

DC (+) Ground Reference…

Page 49: Grounding Bonding for Substation Communications

“A” and “B”Battery Strings

SeparatelyGrounded

Page 50: Grounding Bonding for Substation Communications

Isolation pads under rackAnti-Static floor tiles

Page 51: Grounding Bonding for Substation Communications
Page 52: Grounding Bonding for Substation Communications

Look-Ahead – Other Opportunities

Cable Management– Low Voltage Serial Connections: RS-232/485, GPS– Ethernet– Fiber Optic Entrance and Patch Cables

Non-Substation Hardened Equipment Security (card access, surveillance, etc.) Working with teams outside “Transmission Engineering”

Page 53: Grounding Bonding for Substation Communications

Summary

Communications Grounding-Bonding practices require safety, but also reliability

Control House equipment connects to a single – point ground bus bar to which all metallic elements are bonded

Soft – radius bends for all grounding and bonding connections

Minimize or eliminate ground loops

Page 54: Grounding Bonding for Substation Communications

THE ROAD TO THE FUTURE IS BRIGHT FOR POWER AND SMART GRID COMMUNICATIONS…

Are you ready?


Top Related