Page 1: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Commercial Geothermal Commercial Geothermal Heat PumpsHeat Pumps

Operation and Maintenance

How Reliable Are They?

Page 2: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

First gained moderate popularity as early as the late 1940s and early 1950s.

Page 3: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Most of these early systems are still providing a high level of service to building owners, and include systems in

•Tacoma (Tacoma City Light Building, 1954)

•Vancouver (Clark County PUD, 1956)

•Walla Walla (Whitman College 1964)

•Ephrata (Grant County PUD, 1955)

Page 4: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Present StudySystems were first identified through conversations with equipment sales representatives, architectural and engineering firms, well drillers, ground loop installers, HVAC contractors, and utilities.

Page 5: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Once the systems had been selected, detailed interviews were conducted with the owner/operator, maintenance staff, and, when possible, the system designer.

Page 6: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Heat Pump Selection CriteriaA number of the GSHP systems that date back to the 1950s were installed as a result of the building owners’ wish to adopt a unique, quality design that would create a positive impression in the community.

•Tacoma City Light Building

•Clark County PUD Building.

Page 7: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

A time when air conditioning was becoming more and more of an issue, and in the case of Whitman College, a driving force in selection of the geothermal systems.

Page 8: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

In the mid to late 1970s and early 1980s, a number of systems were built as a direct result of the oil crises of the early 1970s.

Grant County Courthouse, the Yakima County Correctional Facility, and several systems that were built in and around Eugene, Oregon.

Page 9: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Other reasons given included:environmental considerationscompatibility with building design or retrofit requirementsutility incentivesreputation of engineering design firmneed for individual temperature controlreduced space for mechanical equipment life cycle cost savings.

Page 10: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Development TrendsSeveral distinct designs, including pumped wells with central or distributed heat pumps and loop systems, horizontal or vertical, relying primarily on a distributed heat pump system layout.

Page 11: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Unfortunately, the industry has not yet matured to the point where all engineering design teams feel comfortable with all available technical alternatives, and thus design is often as much a factor of prior experience as it is a conscious decision to select the most appropriate technology for a given application.

Page 12: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Most early systems were based on pumped wells with either injection or disposal to nearby surface water. Other systems used surface water sources such as lakes, but were of essentially the same design.

Page 13: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

The heat pumps were water-to-water and two- or four-pipe systems were used to circulate water to fan coil units situated throughout the building. Examples of such systems include the Tacoma City Light Building, Whitman College, Parkview Apartments, the LDS Office Building, and the St. Paul Energy Park.

Page 14: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

By the early 1970s, pumped systems were still dominating the geothermal heat pump scene, but distributed systems were becoming a major player. Systems such as those serving The Exchange Building, the Tower Building, and more recently, the Sundown M Ranch.

Page 15: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

By the late 1970s, the trend seems to have moved more and more toward horizontal or vertical closed loop systems

Page 16: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

For many large commercial applications, the open loop water source system does seem to provide some economic advantage and continues to capture a significant market share where constraints on ground or surface water use have not been adopted.

Page 17: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Relatively unique water sources are now beginning to play an increasing role, including sewage effluent, secondary or re-use water systems, industrial or power generation heat rejection systems, sea water, lake water, river water, etc.

Page 18: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

On the building side, decentralized or distributed heat pump systems seem to increasingly dominate the field primarily because of the ease of operation and localized temperature control that they provide.

Page 19: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Large, centralized systems, however, continue to play a major role and are ideally suited to many retrofit situations, especially where, because of the historical nature of buildings, major changes are very difficult or impossible.

This was the case with the Grant County Courthouse, built in 1912 and retrofit in 1982.

Page 20: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Centralized systems are an extremely attractive choice for office parks or where low-temperature hydronic heating can be provided. The day care center at Squaw Valley is an interesting example of a modern hydronic system. Four 10-ton, horizontal ground loop-based commercial heat pumps supply over 22,000 feet of hydronic heating coils arranged to provide zone comfort within the building and provide over 8,000 feet of snow melt in the outside concrete playground area.

Page 21: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Building and GSHP System Characteristics22 systems were covered, the installed heat pump capacity varies from a low of 1.36-tons per 1,000 square feet to a high of 6.00-tons* per 1,000 square feet.

Page 22: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Water source systems, flows range from 1.30 gpm per ton of installed capacity to 7.50 gpm per ton of installed capacity with an average of 3.43 gpm per ton.

Page 23: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

For closed loop systems, the heat exchanger circuit pipe length ranged from 236 feet per ton to 600 feet per ton, with an average of 454 feet per ton.

Page 24: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Of those with vertical bores, the range is 166 feet of bore per ton to 204 feet.

Page 25: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Equipment and Design ProblemsOpen-Loop System

There is little doubt that well problems dominate when it comes to open loop systems. The two most often encountered problems are inadequate flow in the production well and plugging that causes pressure build-up in the injection well.

Page 26: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Production problems are most often a result of excessive draw down of the acquifer due to over use or severe drought. It can also be a result of sedimentation in the bottom of the well.

Page 27: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

The vast majority of problems associated with open loop systems are caused by the injection well. For example, the Yakima County Correctional Facility, the Sundown M Ranch, Lane Community College's downtown campus, and the Lane County Public works Yard all have experienced some level of difficulty with the injection well.

Page 28: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

The principal cause appears to be iron bacteria and, where a mature colony is established, extremely difficult to eliminate. It is thought that the iron bacteria are often introduced into the system by the well driller, and are a result of using contaminated tools in the drilling operation.

Page 29: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

In some cases, the pressure build up problem is caused by scaling (often calcium carbonate, CaCO3).

Page 30: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

The next most common problem associated with open loop systems is pump failure. Both open shaft, vertical down-hole pumps; and submersible pumps are regularly employed and, at least for those cases where high volume is desired, the down-hole shaft system appears to dominate.

Page 31: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Principal problems seem to be with bearings and seals, often resulting in the need for major maintenance and, in a worse case scenario, resulting in a broken shaft.

Page 32: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Finally, the lack of a heat exchanger (shell and tube or plate and frame) to isolate the production flow from the in-building equipment can result in major system problems including excessive corrosion in the heat pump tube bundle.

Page 33: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

A majority of the systems visited had either installed plate and frame heat exchangers or commented on the desire to incorporate such equipment into their present systems or future design.

Example:

Yakima County Correctional Facility

Page 34: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Closed-Loop System

Correct sizing of the ground loop continues to be a cause for continued design problems and special attention should be placed on minimizing inference between loops, whether they be horizontal or vertical.

Page 35: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Estimating loop length is much more difficult to calculate and is highly dependent upon soil characteristics including temperature, moisture content, particle size and shape, and heat transfer coefficients.

Example:

Benton County PUD

Page 36: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Other problems associated with loop design and installation include improper header design, inadequate system purging, leaks associated with corrosion of fittings, or poor workmanship.

Page 37: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Central vs Distributed Heat Pump SystemsThere seems to be very few problems associated with either the choice to employ a centralized or decentralized heat pump arrangement. Both afford the capability to provide supplemental heating or cooling through the use of boilers or cooling towers.

Example:

The Exchange Building in Farmington, Connecticut

Page 38: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

The only major design problems that seem to be somewhat common in many centralized heat pump systems is the use of a two-pipe system to circulate hot or chilled water.

Examples:

•Grant County Courthouse

•Parkview Apartments

•Saint Paul Energy Park

Page 39: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Operation and MaintenanceMost maintenance problems associated with open-loop systems are well related. The problems include problems with pumps, including bearings and seals, and often as a result of bearing problems, severe shaft problems.

Page 40: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Other maintenance issues include the need to clean or even rework production and injection wells and the need for chemical treatment of injected water to control scaling or bacterial growth that plugs the injection wells.

Page 41: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Another potentially major maintenance issue is removal of sand from the heat exchanger(s) if adequate filters and/or sand traps are not used.

Page 42: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Central heat pump systems seem to require very limited maintenance, and because all major pieces of equipment are located in a central location, most maintenance chores can be carried out easily.

Page 43: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Decentralized systems do require considerably more routine maintenance.

For example, when the Tower Building in Yakima, Washington, was purchased by the present owner, approximately one compressor per week required replacement; however, once a routine preventative maintenance program was put into place, only one compressor failure occurred over the entire following year.

Page 44: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Despite the maintenance issues mentioned, maintenance costs are relatively low in all but a few cases, averaging $0.17 per square foot per year.

Page 45: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Anonymously high maintenance costs are a result of, in one case, a poorly structured maintenance contract; lack of local maintenance providers; and relatively high in-house personnel costs assigned to the HVAC system.

Page 46: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

ConclusionEarlier concerns over long-term reliability, operation, and maintenance costs were, to a large extent, unfounded.

Page 47: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

A majority of the systems have proven to be extremely reliable, with many having been in service over 25 years, and maintenance problems and costs have been acceptably low.

Page 48: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Advancements in equipment, installation techniques, and control systems as well as knowledge of heat transfer continues to reduce equipment and design problems.

Page 49: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Increasing knowledge and use of a wide variety of water sources as well as ground loop designs and configurations, together with the number of in-building systems that are now possible allow that geothermal heat pump technology can be tailored to fit almost any possible building need.

Page 50: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Walla Walla Corps of EngineersHeadquarters BuildingLocation: Walla Walla, WashingtonKey Contact: Brian Miller, Walla Walla District, Corps of EngineersGeothermal Source: Municipal water from both ground and surface

water sourcesSystem Type: Multiple heat pump (129 heat pumps) loop system

with a double walled heat exchangerAge of System: 2 yearsBuilding Type: 91,432 ft2 office and printingEnergy Use: 21.5 kWh/ft2

Estimated Maintenance Cost: ?System Designer: Corps of Engineers internal design

Page 51: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Inn of the Seventh Mountain

Location: Bend, OregonBuilding Type: 248,800 sq.ft. condominium complex and

convention center plus 2 swimming pools and

2 spa poolsSystem Type: Open loop, central water source heat pump

systemAge: 6 yearsEstimated Energy Use: 24.47 kWh/sq.ft./yr. Total complex, 10.14 kWh/sq.ft./yr. Heat pump systemEstimated Maintenance Cost: $0.18/sq.ft./yr.

Page 52: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Parkview ApartmentsLocation: Winchester, MassachusettsBuilding Type: 207,400 sq.ft. apartment/

condominium complexSystem Type: Open loop, central and water source

heat pump systemAge: 34 yearsEnergy Use: 15.35 kWh/sq.ft./year – Total 8.43

kWh/sq.ft./yr for the mechanicalsystem

Estimated Maintenance Cost: Approximately

$0.12 to $0.15/ sq.ft./yr.

Page 53: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

System Economics

When the system was first built (1965), the owner, Edward Brendt, calculated that heating and cooling was costing an average of only $6.10 per apartment per month, or approximately $0.11 per square foot per year.

Parkview ApartmentsParkview Apartments

Page 54: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

At this time (1998), heating and cooling requires 8.43 kWh/square foot/year, while total electrical consumption is 15.35 kWh/square foot/year (1997).

Parkview ApartmentsParkview Apartments

Page 55: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Maintenance costs are calculated to run approximately $0.12 to $0.15/square foot/year.

Parkview ApartmentsParkview Apartments

Page 56: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Havenhill Public LibraryLocation: Havenhill, MassachusettsBuilding Type: Public library, total 44,000 sq.ft.System Type: Open loop, standing column wells,

water source heat pumpsAge: 5 yearsEnergy Use: 16.3 kW/sq.ft/yr.Estimated Maintenance Cost: $0.135/sq.ft./yr.

Page 57: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

System EconomicsIn the first full year of operation, the system saved a total of $11,586, showing a reduction in total electric bills of 23 percent and a 65 percent reduction in cost for space conditioning.

Havenhill LibraryHavenhill Library

Page 58: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Of significant importance to both the library and the utility was an approximately 50 percent reduction in demand.

Havenhill LibraryHavenhill Library

Page 59: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

For 1998, the entire electric load for the library was 709,800 kWh for a total of 16.13 kWh per square foot per year. Maintenance is running approximately $0.135 per square foot per year.

Havenhill LibraryHavenhill Library

Page 60: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

Bryant CollegeLocation: Smithfield, Rhode IslandBuilding Type: Two college resident halls,

total 41,390 sq.ft.System Type: Closed loop vertical bores

ground source heat pumpsAge: 3 yearsEstimated Energy Use: NAEstimated Maintenance Cost: $0.01/sq.ft./yr.

Page 61: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

The ExchangeLocation: Farmington, ConnecticutBuilding Type: 265,000 sq.ft. commercial and office

complexSystem Type: Open loop, distributed water source

heat pump systemAge: 28 yearsEnergy Use: 17.18 kWh/sq.ft./year total: 6.2 kWh

for the heating and cooling systemEstimated Maintenance Cost: approximately

$0.16/sq.ft./year

Page 62: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

System Economics

James Minges, of The Minges Associates, performed an energy analysis on the building in 1997 and calculated that over the 26-year operating history, the building had saved approximately $5,200,000 as compared to a conventional system made up of hot water boilers and conventional chillers and cooling towers.

The ExchangeThe Exchange

Page 63: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

In 1997, maintenance cost was $0.16 per square foot/year, operating costs amounted to $0.60 per square foot/year, and replacement costs $0.05 per square foot/year for a total of $0.81 per square foot per year.

The ExchangeThe Exchange

Page 64: Commercial Geothermal Heat Pumps Operation and Maintenance How Reliable Are They?

The total electrical load for the building in 1997 was 4,552,560 kWh. This amounts to 17.18 kWh per square foot/year. Based on the numbers presented by Mr. Minges, the heat pump system uses ca 6.2 kWh per square foot/year.

The ExchangeThe Exchange