general notes - va vendor portal

12
E F H I J K L 17 18 E F H I J K L N O M N P Q R S P Q R S 19 20 21 22 17 18 19 20 21 22 E.3 H.1 H.7 E.3 F.3 H.1 H.7 NORTH 0" 8'-0" 4'-0" 16'-0" 1 8 " = 1'-0" 1/8" = 1'-0" SECOND POWER FLOOR PLAN - NORTH 16 15 15 GENERAL NOTES 1. REFER TO SPECIFICATIONS FOR ADDITIONAL ELECTRICAL REQUIREMENTS. 2. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS AND REFLECTED CEILING PLANS FOR COORDINATION OF ELECTRICAL DEVICES. 3. REFER TO CODE COMPLIANCE PLANS FOR FIRE BARRIERS, EGRESS PATHS AND TRAVEL DISTANCES ON SHEET GI002 THROUGH GI006. 4. REFER TO PHASING PLANS AND CONSTRUCTION ACCESS PLAN FOR COORDINATION OF ELECTRICAL DEVICES, EQUIPMENT, TEMPORARY PARTITION LOCATIONS, DEMOLITION AND INSTALLATION TIMING OF WORK ON SHEET NOS. GC100 AND IN SPECIFICATIONS. 5. REFER TO ARCHITECTURAL SHEETS FOR RATED WALL LOCATIONS, FLOOR SAW CUTTING AND REPAIR INFORMATION. 6. REFER TO MECHANICAL/ELECTRICAL SCHEDULES AND NOTES ON SHEETS ME601 FOR ADDITIONAL INFORMATION. 7. THE FOLLOWING SHADING INDICATES: SHADING INDICATES AREA OF EXISTING DEVICES, EQUIPMENT, AND FEEDERS TO REMAIN UNLESS NOTED OTHERWISE. AREAS FEATURING NO SHADING INDICATE WORK TO BE DEMOLISHED, FURNISHED AND INSTALLED UNDER THIS CONTRACT UNLESS NOTED OTHERWISE. ALL CIRCUITS/HOME RUNS OVERLAPPING WORK SCOPE AREA IS INCLUDED UNDER THIS CONTRACT. 8. THE FOLLOWING LINEWEIGHTS INDICATE: LIGHT SOLID LINES INDICATE EXISTING EQUIPMENT, DEVICES, BRANCH CIRCUITS, AND FEEDERS TO REMAIN AND ARE SHOWN FOR REFERENCE ONLY. EXISTING LOCATIONS AND LAYOUT MAY DIFFER FROM LAYOUT SHOWN. FIELD VERIFY EXACT LOCATIONS AND LAYOUT. DARK (BOLD) DASHED LINES INDICATE EXISTING EQUIPMENT, DEVICES, BRANCH CIRCUITS, AND FEEDERS TO BE REMOVED OR RELOCATED UNDER THIS CONTRACT. RELOCATED ITEMS WILL BE DESIGNATED WITH AN "(R)" NEXT TO THE EQUIPMENT OR FEEDER. DARK (BOLD) SOLID LINES INDICATE EQUIPMENT, DEVICES, BRANCH CIRCUITS, AND FEEDERS TO BE FURNISHED AND INSTALLED UNDER THIS CONTRACT. POWER NOTES 1. FURNISH AND INSTALL AN EQUIPMENT GROUNDING CONDUCTOR WITHIN THE RACEWAY(S) ALONG WITH PHASE CONDUCTORS FOR ALL FEEDERS AND BRANCH CIRCUITS. CONDUIT IS NOT PERMITTED TO ACT AS AN EQUIPMENT GROUNDING CONDUCTOR UNLESS NOTED OTHERWISE. 2. FURNISH AND INSTALL A 4 INCH SQUARE BY 2-1/2 INCH DEEP OUTLET BOX WITH GFCI RECEPTACLE AT 24 INCHES ABOVE FINISHED FLOOR AND LOCATED UNDER SINK(S) FOR 24-VOLT WIRING OF EACH FAUCET INFRARED OPERATOR. LOCATE OUTLET BOX PER PLUMBING FIXTURE MANUFACTURER'S INSTRUCTIONS. CONNECT INFRARED FAUCETS FOR SINKS TO 120/24V TRANSFORMER SERVING URINAL AND WATER CLOSET FLUSH VALVES. DO NOT EXCEED TEN (10) FLUSH VALVES OR FAUCETS. COORDINATE LOCATION AND ROUTING WITH SENSOR SYSTEM INSTALLER. 3. ALL 120V RECEPTACLES WITHIN 6 FEET OF SINKS SHALL BE GFCI TYPE. ALL MULTI-OUTLET STRIPS MOUNTED WITHIN 6 FEET OF SINKS SHALL BE CONNECTED TO GFCI BREAKERS. 4. LETTERS AND NUMBERS IN PARENTHESIS, LOCATED NEXT TO ELECTRICAL DEVICES, FOLLOWING ROOM NAMES AND NUMBERS, REPRESENT PANEL DESIGNATIONS AND CORRESPONDING CIRCUIT NUMBERS. CIRCUIT NUMBERS INDICATED FOR EXISTING PANELS ARE SCHEMATIC ONLY. FIELD VERIFY EXACT CIRCUIT NUMBERS. 5. HCF/MC CABLE IS NOT ACCEPTABLE EXCEPT FOR LIGHT FIXTURE WHIPS FROM JUNCTION BOX TO FIXTURES ONLY. MAXIMUM OF 6'-0" IN LENGTH 6. FURNISH AND INSTALL PLUGSTRIP WITH DUPLEX RECEPTACLES. USE WIREMOLD “5200” SERIES RACEWAY OR EQUAL WITH THE SALIENT CHARACTERISTICS OF THE SPECIFIED PRODUCT BY HUBBELL, PANDUIT, OR MONO-SYSTEMS. REFER TO DETAIL ON SHEET EP501. 7. CONNECT POWERED PROTECTION SCREENS CONTROL TO CONFERENCE LIGHTING CONTROL SYSTEM. REFER TO SHEET EL503. 8. CONVERT SINGLE DUPLEX RECEPTACLE TO DOUBLE DUPLEX RECEPTACLE. 9. FURNISH AND INSTALL NEMA 14-5OR, 4-WIRE RANGE RECEPTACLE. COORDINATE WITH ARCHITECTURAL TRADES FOR ACTUAL RANGE AND PLUG PROVIDED. 10. RECIRCUIT EXISTING RECEPTACLE(S) TO CIRCUIT INDICATED. 11. FURNISH AND INSTALL 70A-3P-480V CIRCUIT BREAKER WITH 120V SHUNT TRIP IN NEMA 1 RECESSED ENCLOSURE. INTERCONNECTING CONDUIT AND WIRING BY X-RAY MANUFACTURER/VENDOR/INSTALLER. COORDINATE LOCATION OF MAIN CIRCUIT BREAKER AND CONDUIT STUB-OUTS FOR POWER TO GENERATOR CABINET AND EMERGENCY STOP PUSH BUTTONS. REFER TO SHEET EP607. 12. REFER TO THIS SHEET FOR TYPICAL DETAIL OF POWER CONNECTIONS TO ENERGIZED FURNITURE. 13. CONFERENCE ROOM TABLE HAS DUAL OUTLETS FOR POWER, TELEPHONE, AND DATA WITH TABLE TOP JUNCTION BOX. 14. ALL ELECTRICAL DEVICES SHOWN WITHIN OFFICE FURNITURE LAYOUT ARE COORDINATED WITH OPEN BACK FURNITURE STYLE. COORDINATE WITH FURNITURE VENDOR FOR FINAL CONNECTION REQUIREMENTS. 15. FURNISH AND INSTALL 3/4" CONDUIT FOR POWER AND 1 1/4" CONDUIT FOR AV CABLING FROM CEILING PROJECTOR BOX TO FLOOR BOX. REFER TO IN-SLAB FLOOR BOX DETAIL ON SHEET EP501. 16. REFER TO ARCHITECTURAL SHEETS FOR FLOOR SAW CUTTING AND REPAIR. +90 B228B OFFICE DIRECTOR B228A PSA B233 AREA WORK NURSE B235 DERM TELE B236 DERM TELE B227 ROOM CONFERENCE B226 BREAK KITCHEN/ B225 LAB FUTURE B224 THERAPY PHOTO B222 WAITING DERMATOLOGY C207 CORRIDOR C205 CORRIDOR B250 WAITING AREA CLINICS B250A RECEPTION CLINICS C208 CORRIDOR B238 EXAM B239A EXAM 249 MEDS CLEAN SUPPLY/ B247 PROCEDURE B240 EXAM C209 CORRIDOR B246 ROOM MENTOR B248 WORK AREA NURSE B241 ROOM PROCEDURE B243 ROOM PROCEDURE B244 TOILET B245 ROOM PROCEDURE C205A LINEN +90 +90 +42" +90 R2B-2#33 R2B-2#33 R2B-2#31 R2B-2#33 R2B-2#36 R2B-2#28 R2B-2#36 R2B-2#28 R2B-2#38 R2B-2#28 R2B-2#32 R2B-2#34 R2B-2#34 R2B-2#32 R2B-2#30 R2B-2#30 R2B-2#22 R2B-2#26 R2B-2#22 R2B-2#26 R2B-2#20 R2B-2#28 R2B-2#28 R2B-2#20 R2B-2#24 R2B-2#24 R2B-2#18 R2B-2#18 R2B-2#31 SHEET NOTES 12, 13, AND 14 SHEET NOTES 12, 13, AND 14 R2B-2#33 SHEET NOTES 15, AND 16 R2B-2#33 R2B-2#29 R2B-2#25 R2B-2#25 R2B-2#29 R2B-2#25 R2B-2#25 R2B-2#15 J R2B-2#15 J R2B-2#25 R2B-2#25 R2B-2#27 R2B-2#3 R2B-2#3 R2B-2#21,23 R2B-2#17,19 R2B-2#13 FULL BODY MACHINE R2B-2#5,7 R2B-2#1 R2B-2#1 LASER R2B-2#9 FOOT MACHINE R2B-2#11 R2B-2#3 R2B-2#3 R2B-2#3 R2B-2#1 R2B-2#1 R2B-2#1 R2B-2#1 TV MONITOR R2B-2#16 R2B-2#2 R2B-2#2 R2B-2#4 R2B-2#4 R2B-2#6 R2B-2#6 R2B-2#10 R2B-2#10 R2B-2#10 R2B-2#10 R2B-2#10 R2B-2#10 R2B-2#8 R2B-2#12 R2B-2#12 R2B-2#12 R2B-2#12 R2B-2#12 R2B-2#12 KIOSK R2B-2#8 TV MONITOR R2B-2#16 KIOSK R2B-2#8 TV MONITOR R2B-2#14 R2B-1#1 R2B-1#1 J R2B-1#3 FCU-227 FCU-238 FCU-239 FCU-241 FCU-240 FCU-243 FCU-245 FCU-248 FCU-247 R2B-1#1 R2B-1#5 R2B-1#7 J R2B-1#3 R2B-1#5 R2B-1#7 R2B-1#1 R2B-1#3 R2B-1#5 R2B-1#7 R2B-1#1 J R2B-1#11 PATIENT LIFT R2B-1#9 +90" R2B-1#9 R2B-1#9 J R2B-1#15 R2B-1#13 R2B-1#13 J R2B-1#15 R2B-1#9 R2B-1#9 R2B-1#9 R2B-1#11 PATIENT LIFT +90" R2B-1#17 R2B-1#17 R2B-1#17 R2B-1#17 R2B-1#17 R2B-1#19 R2B-1#21 PATIENT LIFT +90" R2B-1#19 R2B-1#19 J R2B-1#25 R2B-1#23 R2B-1#19 R2B-1#23 R2B-1#27 R2B-1#27 R2B-1#31 R2B-1#31 R2B-1#35 R2B-1#19 R2B-1#33 R2B-1#33 J R2B-1#25 R2B-1#21 PATIENT LIFT +90" R2B-1#37 R2B-1#37 R2B-1#35 R2B-1#37 R2B-1#37 OMNICELL CR2B-1#7 ICE MAKER R2B-1#8 R2B-1#39 R2B-1#39 R2B-1#39 +90 DIGITAL DIRECTORY MONITOR +42 +42 R2B-2#35 R2B-2#42 R2B-2#35 R2B-2#40 R2B-1#17 R2B-1#1 16 2L2#16 2L2#16 2L2#16 2L1#7 2L2#16 2L2#12 2L2#10 2L2#8 2L2#14 2L2#4 2L2#6 2L2#2 2L2#15 +90" 2L2#17 2L2#13 PATIENT LIFT 2L1#1 2L1#1 2L1#7 2L1#3 2L2#15 2L2#11 2L2#17 2L2#17 +90" +90" 2L2#13 2L2#5 2L2#9 PATIENT LIFT +90" 2L2#5 2L2#17 2L2#11 2L2#7 2L2#7 2L2#3 2L2#9 2L2#9 2L2#9 2L2#3 2L2#1 2L2#1 2L1#5 2L1#5 2L1 2L1#23 2L1#23 2L1#23 2L1#23 2L1#6 2 2L1#10 2L1#19 2L1#19 2L1#17 2L1#11 2L1#21 2L1#21 2L1#15 2L1#7 2L1#17 2L1#7 2L1#9 2L1#9 2L1#7 2L1#5 2L1#7 2L1#23 2L1#23 2L1#17 COFFEE MAKER 2L1#16 2L1#19 ELEC B232 B230 COMM SPACE C2-1 STAIR B269 ELEC B229 SPACE C200 SPACE C201 EXIST SPACE C2-5 SPACE C2-2 EXIST SPACE C2-3 EXIST SPACE C202 EXIST SPACE C203 EXIST SPACE C2-6 EXIST SPACE C204 WAITING B252A OFFICE B251 EXIST EXIST EXIST EXIST OFFICE B253 OFFICE B254 CLASSROOM C B257A CLASSROOM D B257B CORRIDOR B270 EXAM B258 STOR B2 CLASSROOM E B260 CONFERENCE B261 CONFERENCE B262 CONFERENCE B263 CONFERENCE B264 CONFERENCE B265 EXIST EXIST r Albert Kahn Associates, Inc. is a member of the Albert Kahn Family of Companies. Albert Kahn Building 7430 Second Ave. Detroit, Michigan 48202-2798 ©2007 1W 22 1E ISSUE 002 - DD OWNER REVIEW 05/30/14 ISSUE 003 - CD OWNER REVIEW 10/21/14 ISSUE 004 - BID 02/05/15 P. GARLAND

Upload: khangminh22

Post on 20-Mar-2023

1 views

Category:

Documents


0 download

TRANSCRIPT

E F H I J K L

17

18

E F H I J K L N O

M N P Q R S

P Q R S

19

20

21

22

17

18

19

20

21

22

E.3 H.1 H.7

E.3 F.3 H.1 H.7

NORTH0" 8'-0"4'-0" 16'-0"

18" = 1'-0"1/8" = 1'-0"

SECOND POWER FLOOR PLAN - NORTH

16

15 15

GENERAL NOTES1. REFER TO SPECIFICATIONS FOR ADDITIONAL ELECTRICAL REQUIREMENTS.

2. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS AND REFLECTED CEILINGPLANS FOR COORDINATION OF ELECTRICAL DEVICES.

3. REFER TO CODE COMPLIANCE PLANS FOR FIRE BARRIERS, EGRESS PATHS ANDTRAVEL DISTANCES ON SHEET GI002 THROUGH GI006.

4. REFER TO PHASING PLANS AND CONSTRUCTION ACCESS PLAN FORCOORDINATION OF ELECTRICAL DEVICES, EQUIPMENT, TEMPORARYPARTITION LOCATIONS, DEMOLITION AND INSTALLATION TIMING OF WORKON SHEET NOS. GC100 AND IN SPECIFICATIONS.

5. REFER TO ARCHITECTURAL SHEETS FOR RATED WALL LOCATIONS, FLOOR SAWCUTTING AND REPAIR INFORMATION.

6. REFER TO MECHANICAL/ELECTRICAL SCHEDULES AND NOTES ON SHEETSME601 FOR ADDITIONAL INFORMATION.

7. THE FOLLOWING SHADING INDICATES:

SHADING INDICATES AREA OF EXISTING DEVICES,EQUIPMENT, AND FEEDERS TO REMAIN UNLESSNOTED OTHERWISE. AREAS FEATURING NOSHADING INDICATE WORK TO BE DEMOLISHED,FURNISHED AND INSTALLED UNDER THISCONTRACT UNLESS NOTED OTHERWISE. ALLCIRCUITS/HOME RUNS OVERLAPPING WORKSCOPE AREA IS INCLUDED UNDER THISCONTRACT.

8. THE FOLLOWING LINEWEIGHTS INDICATE:

LIGHT SOLID LINES INDICATE EXISTINGEQUIPMENT, DEVICES, BRANCH CIRCUITS, ANDFEEDERS TO REMAIN AND ARE SHOWN FORREFERENCE ONLY. EXISTING LOCATIONS ANDLAYOUT MAY DIFFER FROM LAYOUT SHOWN.FIELD VERIFY EXACT LOCATIONS AND LAYOUT.

DARK (BOLD) DASHED LINES INDICATE EXISTINGEQUIPMENT, DEVICES, BRANCH CIRCUITS, ANDFEEDERS TO BE REMOVED OR RELOCATED UNDERTHIS CONTRACT. RELOCATED ITEMS WILL BEDESIGNATED WITH AN "(R)" NEXT TO THEEQUIPMENT OR FEEDER.

DARK (BOLD) SOLID LINES INDICATE EQUIPMENT,DEVICES, BRANCH CIRCUITS, AND FEEDERS TO BEFURNISHED AND INSTALLED UNDER THISCONTRACT.

POWER NOTES1. FURNISH AND INSTALL AN EQUIPMENT GROUNDING CONDUCTOR WITHIN THE

RACEWAY(S) ALONG WITH PHASE CONDUCTORS FOR ALL FEEDERS ANDBRANCH CIRCUITS. CONDUIT IS NOT PERMITTED TO ACT AS AN EQUIPMENTGROUNDING CONDUCTOR UNLESS NOTED OTHERWISE.

2. FURNISH AND INSTALL A 4 INCH SQUARE BY 2-1/2 INCH DEEP OUTLET BOXWITH GFCI RECEPTACLE AT 24 INCHES ABOVE FINISHED FLOOR ANDLOCATED UNDER SINK(S) FOR 24-VOLT WIRING OF EACH FAUCET INFRAREDOPERATOR. LOCATE OUTLET BOX PER PLUMBING FIXTURE MANUFACTURER'SINSTRUCTIONS. CONNECT INFRARED FAUCETS FOR SINKS TO 120/24VTRANSFORMER SERVING URINAL AND WATER CLOSET FLUSH VALVES. DONOT EXCEED TEN (10) FLUSH VALVES OR FAUCETS. COORDINATE LOCATIONAND ROUTING WITH SENSOR SYSTEM INSTALLER.

3. ALL 120V RECEPTACLES WITHIN 6 FEET OF SINKS SHALL BE GFCI TYPE. ALLMULTI-OUTLET STRIPS MOUNTED WITHIN 6 FEET OF SINKS SHALL BE CONNECTEDTO GFCI BREAKERS.

4. LETTERS AND NUMBERS IN PARENTHESIS, LOCATED NEXT TO ELECTRICALDEVICES, FOLLOWING ROOM NAMES AND NUMBERS, REPRESENT PANELDESIGNATIONS AND CORRESPONDING CIRCUIT NUMBERS. CIRCUITNUMBERS INDICATED FOR EXISTING PANELS ARE SCHEMATIC ONLY. FIELDVERIFY EXACT CIRCUIT NUMBERS.

5. HCF/MC CABLE IS NOT ACCEPTABLE EXCEPT FOR LIGHT FIXTURE WHIPS FROMJUNCTION BOX TO FIXTURES ONLY. MAXIMUM OF 6'-0" IN LENGTH

6. FURNISH AND INSTALL PLUGSTRIP WITH DUPLEX RECEPTACLES.USE WIREMOLD “5200” SERIES RACEWAY OR EQUAL WITH THE SALIENTCHARACTERISTICS OF THE SPECIFIED PRODUCT BY HUBBELL, PANDUIT, ORMONO-SYSTEMS. REFER TO DETAIL ON SHEET EP501.

7. CONNECT POWERED PROTECTION SCREENS CONTROL TO CONFERENCELIGHTING CONTROL SYSTEM. REFER TO SHEET EL503.

8. CONVERT SINGLE DUPLEX RECEPTACLE TO DOUBLE DUPLEX RECEPTACLE.

9. FURNISH AND INSTALL NEMA 14-5OR, 4-WIRE RANGE RECEPTACLE.COORDINATE WITH ARCHITECTURAL TRADES FOR ACTUAL RANGE AND PLUGPROVIDED.

10. RECIRCUIT EXISTING RECEPTACLE(S) TO CIRCUIT INDICATED.

11. FURNISH AND INSTALL 70A-3P-480V CIRCUIT BREAKER WITH 120V SHUNT TRIPIN NEMA 1 RECESSED ENCLOSURE. INTERCONNECTING CONDUIT ANDWIRING BY X-RAY MANUFACTURER/VENDOR/INSTALLER. COORDINATELOCATION OF MAIN CIRCUIT BREAKER AND CONDUIT STUB-OUTS FOR POWERTO GENERATOR CABINET AND EMERGENCY STOP PUSH BUTTONS. REFER TOSHEET EP607.

12. REFER TO THIS SHEET FOR TYPICAL DETAIL OF POWER CONNECTIONS TOENERGIZED FURNITURE.

13. CONFERENCE ROOM TABLE HAS DUAL OUTLETS FOR POWER, TELEPHONE,AND DATA WITH TABLE TOP JUNCTION BOX.

14. ALL ELECTRICAL DEVICES SHOWN WITHIN OFFICE FURNITURE LAYOUT ARECOORDINATED WITH OPEN BACK FURNITURE STYLE. COORDINATE WITHFURNITURE VENDOR FOR FINAL CONNECTION REQUIREMENTS.

15. FURNISH AND INSTALL 3/4" CONDUIT FOR POWER AND 1 1/4" CONDUIT FORAV CABLING FROM CEILING PROJECTOR BOX TO FLOOR BOX. REFER TOIN-SLAB FLOOR BOX DETAIL ON SHEET EP501.

16. REFER TO ARCHITECTURAL SHEETS FOR FLOOR SAW CUTTING AND REPAIR.

+90B228BOFFICE

DIRECTOR B228APSA

B233AREAWORKNURSE

B235DERMTELE

B236DERMTELE

B227ROOM

CONFERENCE

B226BREAK

KITCHEN/

B225LAB

FUTURE

B224THERAPY PHOTO

B222WAITING

DERMATOLOGY

C207CORRIDOR

C205CORRIDOR

B250WAITING AREA

CLINICS

B250ARECEPTION

CLINICS

C208CORRIDOR

B238EXAM

B239AEXAM

249MEDS

CLEAN SUPPLY/

B247PROCEDURE

B240EXAM

C209CORRIDOR

B246ROOM

MENTOR

B248WORK AREA

NURSE

B241ROOM

PROCEDURE

B243ROOM

PROCEDURE

B244TOILET

B245ROOM

PROCEDURE

C205ALINEN

+90

+90

+42"

+90

R2B-2#33

R2B-2#33 R2B-2#31

R2B-2#33

R2B-2#36

R2B-2#28

R2B-2#36

R2B-2#28

R2B-2#38

R2B-2#28R2B-2#32

R2B-2#34

R2B-2#34

R2B-2#32

R2B-2#30

R2B-2#30

R2B-2#22

R2B-2#26R2B-2#22

R2B-2#26R2B-2#20

R2B-2#28 R2B-2#28

R2B-2#20

R2B-2#24

R2B-2#24

R2B-2#18

R2B-2#18

R2B-2#31

SHEET NOTES12, 13, AND 14

SHEET NOTES12, 13, AND 14

R2B-2#33

SHEET NOTES15, AND 16

R2B-2#33

R2B-2#29

R2B-2#25

R2B-2#25

R2B-2#29R2B-2#25

R2B-2#25R2B-2#15

JR2B-2#15

J

R2B-2#25

R2B-2#25

R2B-2#27

R2B-2#3R2B-2#3

R2B-2#21,23

R2B-2#17,19

R2B-2#13

FULL BODYMACHINER2B-2#5,7

R2B-2#1

R2B-2#1LASERR2B-2#9

FOOTMACHINER2B-2#11

R2B-2#3

R2B-2#3

R2B-2#3

R2B-2#1R2B-2#1

R2B-2#1R2B-2#1

TV MONITORR2B-2#16

R2B-

2#2

R2B-

2#2

R2B-

2#4

R2B-

2#4

R2B-

2#6

R2B-

2#6 R2B-2#10

R2B-2#10

R2B-2#10 R2B-2#10

R2B-2#10

R2B-2#10R2B-2#8

R2B-2#12 R2B-2#12

R2B-2#12 R2B-2#12

R2B-2#12

R2B-2#12

KIOSKR2B-2#8

TV MONITORR2B-2#16 KIOSK

R2B-2#8TV MONITORR2B-2#14

R2B-1#1

R2B-1#1

JR2B-1#3

FCU-227

FCU-238

FCU-239

FCU-241

FCU-240

FCU-243 FCU-245

FCU-248

FCU-247

R2B-1#1

R2B-1#5

R2B-1#7

JR2B-1#3

R2B-1#5

R2B-1#7

R2B-1#1

R2B-1#3

R2B-1#5

R2B-1#7

R2B-1#1J

R2B-1#11PATIENT LIFT R2B-1#9+90"

R2B-1#9

R2B-1#9

JR2B-1#15

R2B-1#13

R2B-1#13

JR2B-1#15

R2B-1#9

R2B-1#9

R2B-1#9R2B-1#11PATIENT LIFT +90"

R2B-1#17

R2B-1#17

R2B-1#17

R2B-1#17

R2B-1#17

R2B-1#19 R2B-1#21PATIENT LIFT

+90"

R2B-1#19

R2B-1#19J

R2B-1#25

R2B-1#23

R2B-1#19

R2B-1#23

R2B-1#27

R2B-1#27

R2B-1#31R2B-1#31R2B-1#35

R2B-1#19

R2B-1#33 R2B-1#33

JR2B-1#25

R2B-1#21PATIENT LIFT

+90"

R2B-1#37

R2B-1#37

R2B-1#35

R2B-1#37

R2B-1#37

OMNICELLCR2B-1#7

ICE MAKERR2B-1#8

R2B-1#39

R2B-1#39

R2B-1#39

+90

DIGITALDIRECTORYMONITOR

+42 +42

R2B-2#35 R2B-2#42 R2B-2#35

R2B-2#40

R2B-1#17

R2B-1#1

16

2L2#16

2L2#16

2L2#16

2L1#7

2L2#16

2L2#12 2L2#102L2#82L2#14

2L2#4

2L2#6

2L2#22L2#15

+90"2L2#17

2L2#13

PATIENT LIFT

2L1#1

2L1#1

2L1#7

2L1#3

2L2#152L2#11

2L2#17

2L2#17 +90"+90"2L2#13 2L2#5

2L2#9

PATIENT LIFT

+90"2L2#5

2L2#17

2L2#112L2#7

2L2#72L2#3

2L2#9 2L2#9

2L2#9

2L2#3

2L2#1

2L2#1

2L1#5

2L1#5

2L1

2L1#23

2L1#23

2L1#23

2L1#23

2L1#62

2L1#10

2L1#192L1#192L1#17

2L1#11

2L1#21

2L1#212L1#15

2L1#72L1#17

2L1#7

2L1#92L1#9

2L1#7

2L1#5

2L1#7

2L1#23

2L1#23

2L1#17 COFFEE MAKER2L1#16

2L1#19

ELECB232

B230COMM

SPACEC2-1

STAIRB269

ELECB229

SPACEC200

SPACEC201

EXISTSPACEC2-5

SPACEC2-2

EXISTSPACEC2-3

EXISTSPACEC202

EXISTSPACEC203

EXISTSPACEC2-6

EXISTSPACEC204

WAITINGB252A

OFFICEB251

EXIST

EXISTEXIST

EXIST

OFFICEB253

OFFICEB254

CLASSROOM CB257A

CLASSROOM DB257B

CORRIDORB270

EXAMB258

STORB2

CLASSROOM EB260

CONFERENCEB261

CONFERENCEB262

CONFERENCEB263

CONFERENCEB264

CONFERENCEB265

EXIST

EXIST

r

Albert Kahn Associates, Inc. is a member ofthe Albert Kahn Family of Companies.

Albert Kahn Building7430 Second Ave.Detroit, Michigan 48202-2798

© 20071W

22 1E

ISSUE 002 - DD OWNER REVIEW 05/30/14

ISSUE 003 - CD OWNER REVIEW 10/21/14

ISSUE 004 - BID 02/05/15

P. GARLAND

EXISTCOMM

A339

EXISTCOMM

A370EXIST

COMMA335

EXISTCORRIDOR

C303

EXISTCORRIDOR

C3-305

EXISTTOILETA372

EXISTTOILETA372

EXISTELECA373

EXISTCORRIDOR

C3-305

EXISTSHARED OFFICE

A313

EXISTELECA311

EXISTSTORAGE

A309

EXISTTOILETA307

EXISTSHAREDOFFICEA300

STAIR #2

STAIR #1

EXISTCLOSET

B315

T

T

13

13.2

15

14

13.9

12

11

10

9.8

9.3

9

8

7.9A

7

6

5

E E.2 E.3 F F.3 H H.1 H.7 I J K L

15

14

13

17

17

10

9

7

6

5

8

13.9

A B C D E F G H I J K L

E.3E.2

F.3 H.7

H.1

M N

M N

1/8" = 1'-0"

THIRD FLOOR AND ROOF POWER PLAN - WEST 0" 8'-0"4'-0" 16'-0"

18" = 1'-0"

NORTH

EF-3

FURNISH AND INSTALL LIGHTINGPROTECTION MASTER LABEL SYSTEM.EXISTING LIGHTING PROTECTIONSYSTEM TO ACCOMMODATEBUILDING ADDITION AND ROOF TOPEQUIPMENT

EXISTING DOWN CONDUCTOR TOBE MODIFIED AND TIED INTOBUILDING ADDITION LIGHTINGPROTECTION SYSTEM EXTENSION(TYP.)

MWP

MWP

EF-1

1W-AH-21

r

Albert Kahn Associates, Inc. is a member ofthe Albert Kahn Family of Companies.

Albert Kahn Building7430 Second Ave.Detroit, Michigan 48202-2798

© 2007

T2

1W

22 1E

AREA OFPROJECT

ISSUE 004 - BID 02/05/15P. GARLAND

NORTH

1/8" = 1'-0"

FOURTH FLOOR POWER PLAN - WEST

10

11

12

13

14

15

13.9

7.9A

9.3

9.8

13.2

EXIS

T EL

EC P

AN

ELS

X1,419 SF

21'-0" 72'-0"ANA01

MECH ROOM

12

11

10

7

6

5

4

8

9

ELECTRICAL EQUIPMENTINDICATED ON THIS SHEET ISEXISTING TO REMAIN ANDFOR REFERENCE ONLYUNLESS OTHERWISE NOTED

54.0

9.0 35.0

EXISTINGUSS#6

PRIMARYSWITCH

PRIMARYSWITCH

EF-10

EF-3

EF-1

EF-2

EF-5EF-6

WPWP WP

WP

WP

WP

EF-8WP

COMPRESSORRACK FOR KITCHENREFRIGERATORS ANDFREEZER.

WP

EF-9

E78

E77

E96A

WP

TO SPARE 120VCIRCUIT FROMNEAREST FOURTH FLOOR208Y/120V PANEL

TO PANEL 4EPP1VIA VFD IN MECHANICALPENTHOUSE.

WP

WP

WPM

M

M M

MMM

M

M

E96BWP

TO PANEL 3K1CIRCUIT 43

REFER TO ME601AND ME602

WP

EXIS

TING

SUB

STA

TION

#5

EXISTINGPANEL 4EPP1

EF-12

PANEL L3A-1CIRCUIT 13,15,17IN ROOM A311.

TO PANEL 4EPP1VIA VFD IN MECHANICALPENTHOUSE.

TO PANEL 4EPP1

TO PANEL 4EPP1VIA VFD INMECHANICALPENTHOUSE.

TO PANEL 4EPP1VIA VFD IN MECHANICALPENTHOUSE.

TO PANEL 4EPP1VIA VFD IN MECHANICALPENTHOUSE.

TO PANEL 4EPP1VIA VFD IN MECHANICALPENTHOUSE.

EXISTINGMCC4-C1

ATS4-C3

ATS4-A1 ATS4-A2

ATS4-C2ATS4-C1

MCC4-D1

USS #4

ATS4-D1 ATS4-D2

CL4D-1-1

EXISTINGEMCC4-C1

ATS4-B2

ATS4-B1

ATS4-C4

ATS4-A3 ATS4-D3

ELEV #1

ATS4-C5

ELEV #2

EXISTINGEMCC4-A1

EXISTINGMCC4-A1

C D E F

G H

IJ K L

E.3

H.7

H.1

M N O P

Q R S

T U

GENERAL NOTES1. REFER TO SPECIFICATIONS FOR ADDITIONAL ELECTRICAL REQUIREMENTS.

2. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS AND REFLECTED CEILINGPLANS FOR COORDINATION OF ELECTRICAL DEVICES.

3. REFER TO CODE COMPLIANCE PLANS FOR FIRE BARRIERS, EGRESS PATHS ANDTRAVEL DISTANCES ON SHEET GI002 THROUGH GI006.

4. REFER TO PHASING PLANS AND CONSTRUCTION ACCESS PLAN FORCOORDINATION OF ELECTRICAL DEVICES, EQUIPMENT, TEMPORARYPARTITION LOCATIONS, DEMOLITION AND INSTALLATION TIMING OF WORKON SHEET NOS. GC100 AND IN SPECIFICATIONS.

5. REFER TO ARCHITECTURAL SHEETS FOR RATED WALL LOCATIONS, FLOOR SAWCUTTING AND REPAIR INFORMATION.

6. REFER TO MECHANICAL/ELECTRICAL SCHEDULES AND NOTES ON SHEETSME601 FOR ADDITIONAL INFORMATION.

7. THE FOLLOWING SHADING INDICATES:

SHADING INDICATES AREA OF EXISTING DEVICES,EQUIPMENT, AND FEEDERS TO REMAIN UNLESSNOTED OTHERWISE. AREAS FEATURING NOSHADING INDICATE WORK TO BE DEMOLISHED,FURNISHED AND INSTALLED UNDER THISCONTRACT UNLESS NOTED OTHERWISE. ALLCIRCUITS/HOME RUNS OVERLAPPING WORKSCOPE AREA IS INCLUDED UNDER THISCONTRACT.

8. THE FOLLOWING LINEWEIGHTS INDICATE:

LIGHT SOLID LINES INDICATE EXISTINGEQUIPMENT, DEVICES, BRANCH CIRCUITS, ANDFEEDERS TO REMAIN AND ARE SHOWN FORREFERENCE ONLY. EXISTING LOCATIONS ANDLAYOUT MAY DIFFER FROM LAYOUT SHOWN.FIELD VERIFY EXACT LOCATIONS AND LAYOUT.

DARK (BOLD) DASHED LINES INDICATE EXISTINGEQUIPMENT, DEVICES, BRANCH CIRCUITS, ANDFEEDERS TO BE REMOVED OR RELOCATED UNDERTHIS CONTRACT. RELOCATED ITEMS WILL BEDESIGNATED WITH AN "(R)" NEXT TO THEEQUIPMENT OR FEEDER.

DARK (BOLD) SOLID LINES INDICATE EQUIPMENT,DEVICES, BRANCH CIRCUITS, AND FEEDERS TO BEFURNISHED AND INSTALLED UNDER THISCONTRACT.

13

r

Albert Kahn Associates, Inc. is a member ofthe Albert Kahn Family of Companies.

Albert Kahn Building7430 Second Ave.Detroit, Michigan 48202-2798

© 2007

T2

1W

22 1E

AREA OFPROJECT

ISSUE 003 - CD OWNER REVIEW 10/21/14

ISSUE 004 - BID 02/05/15 P. GARLAND

GENERAL NOTES1. REFER TO SPECIFICATIONS FOR ADDITIONAL ELECTRICAL REQUIREMENTS.

2. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS AND REFLECTED CEILINGPLANS FOR COORDINATION OF ELECTRICAL DEVICES.

3. REFER TO CODE COMPLIANCE PLANS FOR FIRE BARRIERS, EGRESS PATHS ANDTRAVEL DISTANCES ON SHEET GI002 THROUGH GI006.

4. REFER TO PHASING PLANS AND CONSTRUCTION ACCESS PLAN FORCOORDINATION OF ELECTRICAL DEVICES, EQUIPMENT, TEMPORARYPARTITION LOCATIONS, DEMOLITION AND INSTALLATION TIMING OF WORKON SHEET NOS. GC100 AND IN SPECIFICATIONS.

5. REFER TO ARCHITECTURAL SHEETS FOR RATED WALL LOCATIONS, FLOOR SAWCUTTING AND REPAIR INFORMATION.

6. REFER TO MECHANICAL/ELECTRICAL SCHEDULES AND NOTES ON SHEETSME601 FOR ADDITIONAL INFORMATION.

7. THE FOLLOWING SHADING INDICATES:

SHADING INDICATES AREA OF EXISTING DEVICES,EQUIPMENT, AND FEEDERS TO REMAIN UNLESSNOTED OTHERWISE. AREAS FEATURING NOSHADING INDICATE WORK TO BE DEMOLISHED,FURNISHED AND INSTALLED UNDER THISCONTRACT UNLESS NOTED OTHERWISE. ALLCIRCUITS/HOME RUNS OVERLAPPING WORKSCOPE AREA IS INCLUDED UNDER THISCONTRACT.

8. THE FOLLOWING LINEWEIGHTS INDICATE:

LIGHT SOLID LINES INDICATE EXISTINGEQUIPMENT, DEVICES, BRANCH CIRCUITS, ANDFEEDERS TO REMAIN AND ARE SHOWN FORREFERENCE ONLY. EXISTING LOCATIONS ANDLAYOUT MAY DIFFER FROM LAYOUT SHOWN.FIELD VERIFY EXACT LOCATIONS AND LAYOUT.

DARK (BOLD) DASHED LINES INDICATE EXISTINGEQUIPMENT, DEVICES, BRANCH CIRCUITS, ANDFEEDERS TO BE REMOVED OR RELOCATED UNDERTHIS CONTRACT. RELOCATED ITEMS WILL BEDESIGNATED WITH AN "(R)" NEXT TO THEEQUIPMENT OR FEEDER.

DARK (BOLD) SOLID LINES INDICATE EQUIPMENT,DEVICES, BRANCH CIRCUITS, AND FEEDERS TO BEFURNISHED AND INSTALLED UNDER THISCONTRACT.

1" CONDUITAND FITTING(NOTE 2)

1" FLEXIBLECONDUIT(NOTE 2)

3/4" CONDUITAND FITTING

FIRE-RATED POKE THRUS

NOTES:

1. WHEN FURNITURE IS AGAINST WALL, REPLACE FIRE-RATED POKE THRUS WITH RECESSED WALL MOUNTEDJUNCTION BOXES AND COVERPLATES. REFER TO DETAIL ON THIS SHEET.

2. PROVIDE 1" CONDUIT FOR TWO PHONE/DATA AND 1 1/4"C FOR THREE PHONE/DATA OUTLETS SHOWN FORFURNITURE.

3/4" FLEXIBLE CONDUITFOR EACH SERVICE

FURNITURE BASECOMMUNICATION BOX

FURNITURE

CL

FURNITURE BASEPOWER BOX

FLOOR SLAB

NOT TO SCALE1

DETAIL OF FURNITURE BASE CONNECTIONSFOR POWER-IN AND COMMUNICATIONS

FURNITURE BASE POWER BOX

3/4" FLEXIBLE CONDUITFOR EACH SERVICE(NOTE 2)

FURNITURE BASECOMMUNICATION BOX

4 11/16 " SQUARE BOX WITHSINGLE GANG PLASTER RINGFOR POWER (BEYOND)

4 11/16 " SQUARE BOX WITHSINGLE GANG PLASTER RINGFOR TELEPHONE AND 2-GANGPLASTER RING FOR COMPUTER

DRYWALL

STUD

NOTES:

1. WHEN FURNITURE IS NOT AGAINST WALL, REPLACE RECESSED WALL MOUNTED JUNCTION BOXES ANDCOVERPLATES WITH FIRE-RATED POKE THRUS OR FLOOR BOXES. REFER TO DETAIL ON THIS SHEET.

2. PROVIDE 1" CONDUIT FOR TWO PHONE/DATA AND 1 1/4"C FOR THREE PHONE/DATA OUTLETS SHOWN FORFURNITURE.

1" FLEXIBLECONDUIT(NOTE 2)

1" CONDUIT AND FITTING FORTELEPHONE AND COMPUTER

3/4" CONDUIT AND FITTING(BEYOND) FOR POWER (NOTE 2)FURNITURE

FLOOR SLAB

NOT TO SCALE3

DETAIL OF FURNITURE CONNECTIONSFOR POWER-IN AND COMMUNICATIONS

NOTES:

1. TERMINATE 2-1" FLEXIBLE CONDUITS INTO 4" SQUARE MONITOR OUTLET BOX. INSTALL OUTLETBOX AT +36"AFF.

2. PROVIDE 1" CONDUIT FOR TWO PHONE/DATA AND 1-1/4"C FOR THREE PHONE/DATA OUTLETSSHOWN FOR FURNITURE.

3. FURNISH SEPARATE CONDUIT AND BOX FOR PATIENT MONITOR OUTLET. INSTALL OUTLET BOXABOVE FURNITURE BASE. (DESIGNER: THIS NOTE AND REFERENCE ABOVE IS FOR HEALTH CAREPROJECTS ONLY. ELIMINATE NOTE AND REFERENCE FOR NON-HEALTH CARE PROJECTS.)

114" FLEXIBLE CONDUIT

(MINIMUM) TO POWER DEVICEFOR EACH TYPE OF SERVICE

114" FLEXIBLE CONDUIT

(MINIMUM) TOCOMMUNICATION DEVICEFOR EACH TYPE OF SERVICE

FURNITURE BASEPOWER BOX FURNITURE BASE

COMMUNICATION BOX

FURNISH AND INSTALL4" SQUARE JUNCTIONBOX W/BARRIER (NOTE 3)

CORE AND FIRE STOP(AS REQUIRED)

NOTE 1

CL

1" CONDUITAND FITTING(NOTE 2)

114" CONDUIT

AND FITTING(MINIMUM)

FLOOR SLAB

FURNITURE

NOT TO SCALE2

DETAIL OF FURNITURE BASE CONNECTIONSFOR POWER-IN AND COMMUNICATIONS

1" CONDUITAND FITTING(NOTE 2)

3/4" CONDUITAND FITTING

NOTES:

1. WHEN FURNITURE IS AGAINST WALL, REPLACE FLOOR BOXES WITH RECESSED WALL MOUNTED JUNCTIONBOXES AND COVERPLATES. REFER TO DETAIL ON THIS SHEET.

2. PROVIDE 1" CONDUIT FOR TWO PHONE/DATA OUTLETS AND 1 1/4"C FOR THREE PHONE/DATA OUTLETSSHOWN FOR FURNITURE.

1" FLEXIBLECONDUIT(NOTE 2)

CL CL

3/4" FLEXIBLE CONDUITFOR EACH SERVICE

FURNITURE BASECOMMUNICATION BOX

FURNITURE BASEPOWER BOX

FURNITURE

FLOOR SLAB

NOT TO SCALE4

DETAIL OF FURNITURE BASE CONNECTIONSFOR POWER-IN AND COMMUNICATIONS

FIRE-RATED POKE-THRUWIREMOLD RC4ARTTCAL OREQUAL BY HUBBELL

CL

FLOOR SLAB

3/4" CONDUIT TO PANEL ORTO NEXT POKE-THRU DEVICE

4" OUTLET BOX

3/4" CONDUIT TO NEXTPOKE-THRU DEVICE

COMMUNICATIONS WIRINGCONDUIT. SEE NOTE #2.

NOT TO SCALE5

DETAIL OF POKE-THRU DEVICEFOR POWER AND COMMUNICATIONS

POKE THROUGH DEVICE RC4ATCWIREMOLD, BLACK COLOR. USED INCONFERENCE/MEETING ROOMS ANDAREAS NOT FOR FEEDS TO FURNITURE.4 POWER OUTLETS, 4 COMM OUTLETS.OBTAIN BLANK FILLERS FROMMANUFACTURER

8 1/4"

16 9/16"

16 15/16"

- -

r

Albert Kahn Associates, Inc. is a member ofthe Albert Kahn Family of Companies.

Albert Kahn Building7430 Second Ave.Detroit, Michigan 48202-2798

© 2007

T2

1W

22 1E

AREA OFPROJECT

ISSUE 002 - DD OWNER REVIEW 05/30/14

ISSUE 003 - CD OWNER REVIEW 10/21/14

ISSUE 004 - BID 02/05/15

P. GARLAND

6"

5"

EQUAL (NOTE 3) 12" MAXIMUM

6"

EQUAL (NOTE 3) 12" MAXIMUM

AS SHOWN ON COMMUNICATION PLANS. REFER TO SHEET EC105.

DUAL CHANNEL ALUMINUM RACEWAY -WIREMOLD “5200” SERIES RACEWAY OREQUAL WITH THE SALIENT CHARACTERISTICSOF THE SPECIFIED PRODUCT BY HUBBELL,PANDUIT, OR MONO-SYSTEMS.

BARRIER WITHIN RACEWAY

ELEVATION

AS SHOWN ON POWER PLANS. REFER TO THIS SHEET EP105.

2"

SECTION A-A

6"

EQUAL (NOTE 3) 24" MAXIMUM

A

A

END OF RACEWAYOR WALL EDGE

ISOMETRIC

6"

NOTES:

1. PLACE RECEPTACLES AND DATA OUTLETS A MINIMUM OF 6" FROM EDGE OF SINK.

2. PLACE RECEPTACLES AND DATA OUTLETS A MINIMUM OF 12" FROM WALL CORNERS.

3. FOR LENGTHS THAT DO NOT EXACTLY MATCH 6" INCREMENTS, CENTER MIDDLERECEPTACLES AND DATA OUTLETS EQUALLY ON CENTER (12" MAXIMUM FOR RECEPTACLES,24" MAXIMUM FOR DATA OUTLETS).

4. ALL 120V RECEPTACLES WITHIN 6'-0" OF SINKS SHALL BE GFCI TYPE.

5. MOUNT RACEWAY AS FOLLOWS:

a. COUNTERS WITH BACKSPLASH - BOTTOM OF RACEWAY TO TOP OF BACKSPLASH

b. COUNTERS WITHOUT BACKSPLASH - BOTTOM OF RACEWAY 6" ABOVE COUNTER

c. NO CABINETS OR COUNTERS - TOP OF RACEWAY AT 48" ABOVE FINISHED FLOOR

6. CIRCUIT PLUGSTRIP SO THAT EVERY OTHER DUPLEX RECEPTACLE IS ON A DIFFERENT CIRCUITWITH A MAXIMUM OF FOUR DUPLEX RECEPTACLES ON A CIRCUIT.

7. FURNISH AND INSTALL TWO 20A CIRCUITS TO FEED INTO EACH GROUP OF 1 OR 2WORKSTATIONS WITH ONE CIRCUIT DESIGNATED FOR COMPUTER POWER AND ONE CIRCUITDESIGNATED FOR TASK LIGHTS AND CONVENIENCE RECEPTACLES.

8. USE WIREMOLD “5200” SERIES RACEWAY OR EQUAL WITH THE SALIENT CHARACTERISTICS OFTHE SPECIFIED PRODUCT BY HUBBELL, PANDUIT, OR MONO-SYSTEMS. REFER TO DETAIL ONSHEET EP501.

NOT TO SCALE2 ALUMINUM RACEWAY DETAIL

6"

WALL CORNER

6"

EQUAL (NOTE 3)

24" MAXIMUM

12" (NOTE 2)

EQUAL (NOTE 3)

12" MAXIMUM

EQUAL (NOTE 3)

12" MAXIMUM

12" (NOTE 2)

6"

6"

EQUAL (NOTE 3)

12" MAXIMUM

12" (NOTE 2)

3'-6

"

SEE

INTE

RIO

R EL

EVA

TION

S

SEE

INTE

RIO

R EL

EVA

TION

S

SEE

INTE

RIO

R EL

EVA

TION

S (4

" MIN

IMUM

)

SEE

INTE

RIO

R EL

EVA

TION

S (4

" MIN

IMUM

)

WIREWAY MOUNTINGWITH BACKSPLASH

WIREWAY MOUNTINGWITHOUT BACKSPLASH

WIREWAY MOUNTINGWITHOUT BASE CABINET

WALL CORNER

EQUAL (NOTE 3)

12" MAXIMUM

EQUAL (NOTE 3)

24" MAXIMUM

UPPER CABINET(OPTIONAL)

UPPER CABINET(OPTIONAL)

UPPER CABINET(OPTIONAL)

3'-6

"

WIREWAY MOUNTINGWITHOUT CABINETS

GENERAL NOTES1. REFER TO SPECIFICATIONS FOR ADDITIONAL ELECTRICAL REQUIREMENTS.

2. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS AND REFLECTED CEILINGPLANS FOR COORDINATION OF ELECTRICAL DEVICES.

3. REFER TO CODE COMPLIANCE PLANS FOR FIRE BARRIERS, EGRESS PATHS ANDTRAVEL DISTANCES ON SHEET GI002 THROUGH GI006.

4. REFER TO PHASING PLANS AND CONSTRUCTION ACCESS PLAN FORCOORDINATION OF ELECTRICAL DEVICES, EQUIPMENT, TEMPORARYPARTITION LOCATIONS, DEMOLITION AND INSTALLATION TIMING OF WORKON SHEET NOS. GC100 AND IN SPECIFICATIONS.

5. REFER TO ARCHITECTURAL SHEETS FOR RATED WALL LOCATIONS, FLOOR SAWCUTTING AND REPAIR INFORMATION.

6. REFER TO MECHANICAL/ELECTRICAL SCHEDULES AND NOTES ON SHEETSME601 FOR ADDITIONAL INFORMATION.

7. THE FOLLOWING SHADING INDICATES:

SHADING INDICATES AREA OF EXISTING DEVICES,EQUIPMENT, AND FEEDERS TO REMAIN UNLESSNOTED OTHERWISE. AREAS FEATURING NOSHADING INDICATE WORK TO BE DEMOLISHED,FURNISHED AND INSTALLED UNDER THISCONTRACT UNLESS NOTED OTHERWISE. ALLCIRCUITS/HOME RUNS OVERLAPPING WORKSCOPE AREA IS INCLUDED UNDER THISCONTRACT.

8. THE FOLLOWING LINEWEIGHTS INDICATE:

LIGHT SOLID LINES INDICATE EXISTINGEQUIPMENT, DEVICES, BRANCH CIRCUITS, ANDFEEDERS TO REMAIN AND ARE SHOWN FORREFERENCE ONLY. EXISTING LOCATIONS ANDLAYOUT MAY DIFFER FROM LAYOUT SHOWN.FIELD VERIFY EXACT LOCATIONS AND LAYOUT.

DARK (BOLD) DASHED LINES INDICATE EXISTINGEQUIPMENT, DEVICES, BRANCH CIRCUITS, ANDFEEDERS TO BE REMOVED OR RELOCATED UNDERTHIS CONTRACT. RELOCATED ITEMS WILL BEDESIGNATED WITH AN "(R)" NEXT TO THEEQUIPMENT OR FEEDER.

DARK (BOLD) SOLID LINES INDICATE EQUIPMENT,DEVICES, BRANCH CIRCUITS, AND FEEDERS TO BEFURNISHED AND INSTALLED UNDER THISCONTRACT.

NOT TO SCALE1 DETAIL OF IN-SLAB FLOOR BOX FOR POWER AND COMMUNICATIONS

1 1/4" CONDUIT, KNOCKOUT,AND FITTING (NOTE 1)

LOW VOLTAGE COMPARTMENTOF FLOOR OUTLET BOX

POWER COMPARTMENT OFFLOOR BOX OUTLET

3/4" CONDUIT, KNOCKOUT,AND FITTING (NOTE 3)

1 1/4" CONDUIT, KNOCKOUT,AND FITTING (NOTE 2)

LOW VOLTAGE COMPARTMENTOF FLOOR OUTLET BOX

WIREMOLD FPBTCBK OR EQUALCOVER ASSEMBLY

WIRE MOLD RFB4-C1-1 OR EQUALFOUR COMPARTMENT COMBINATIONBOX FOR POWER ANDCOMMUNICATIONS

FLOOR SLAB

NOTES

1. FURNISH AND INSTALL 1 1/4" CONDUIT FOR TWO DATA AND ONE VOICE OUTLET ALONG WITHMULTISERVICE ACCESSORIES TO MATCH OWNER REQUIREMENTS. REFER TO SPECIFICATIONS FORADDITIONAL REQUIREMENTS.

2. FURNISH AND INSTALL 1 1/4" CONDUIT FOR FUTURE MULTIMEDIA OUTLET ALONG WITH BLANKMULTISERVICE ACCESSORIES.

3. FURNISH AND INSTALL 3/4" CONDUIT FOR TWO DUPLEX RECEPTACLES ALONG WITH MULTISERVICEACCESSORIES TO ACCOMMODATE OUTLETS.

4. FURNISH AND INSTALL ACCESSORIES TO ACCOMMODATE DUAL RECEPTACLES FOR POWER, DUALOUTLETS FOR TELEPHONE AND DATA.

5. THE MANUFACTURER PRODUCT IDENTIFIED ABOVE MEETS THE SALIENT CHARACTERISTICS OF THISSPECIFICATION. SUCH INFORMATION IS ONLY PROVIDED TO SHOW AN EXAMPLE OF PRODUCTSWHICH MEET THE SPECIFICATIONS AND DO NOT, IN ANY WAY, LIMIT THE OFFEROR FROM PROVIDINGPRODUCTS FROM OTHER MANUFACTURERS WHICH MEET THE SALIENT CHARACTERISTICS ASIDENTIFIED IN THE SPECIFICATION

r

Albert Kahn Associates, Inc. is a member ofthe Albert Kahn Family of Companies.

Albert Kahn Building7430 Second Ave.Detroit, Michigan 48202-2798

© 2007

T2

1W

22 1E

AREA OFPROJECT

ISSUE 003 - CD OWNER REVIEW 10/21/14

ISSUE 004 - BID 02/05/15 P. GARLAND

PRIMARY FEEDER #A-101

PRIMARY FEEDER #A-102

5252

FUTU

RE

FUTU

RE

5252

PRIMARY FEEDER #A-106

PRIMARY FEEDER #A-104

" "

PRIMARY FEEDER #A-105

PRIMARY FEEDER #A-103

1200A

ASAM

5051

" "

" "

" "

100E

" "

125E

K

KK

125E

" "

K

KK

100E

" "

K

KK

125E

" "

K

KK

125E

" "

K

KK

30E

" "

K

K

30E

" "

K

K

50E

" "

K

K

K

K

PS102

PS101

PS109PS100

K

K

PS103

" "

PS106

100E

" " " "

100E

" " " "

100E

100E

1200/5A

CS1

113

ELECTRONICMETERING

13.2KV-120V

13.2KV-120V

5051

86

CS

3

3PT13.2KV-120V

TRANSFORMER1000KVA

13.2KV-480Y/277V

TRANSFORMER500KVA

13.2KV-208Y/120V

TRANSFORMER225KVA

13.2KV-208Y/120V

TRANSFORMER1500/2000KVA OA, OF

13.2KV-480Y/277V

TRANSFORMER1500/2000KVA OA, OF

13.2KV-480Y/277V

" "

1200/5A3

" "

" "

TRANSFORMER1500KVA OA, OF

13.2KV-4160V

TRANSFORMER1500KVA OA, OF

13.2KV-4160V

N.O.

N.C.

N.C.

N.O.

N.O.

N.C.

N.O.

N.C.

N.C.

N.O.

N.O.

5051G3

AS

LA

5051G3

1200A 5252

ASAM

5051

1200/5A

CS1

113

5051G3

1200A 5252

ASAM

5051

1200/5A

CS1

113

5051G3

1200A 5252

ASAM

5051

1200/5A

CS1

113

5051G3

1200A 5252

ASAM

5051

1200/5A

CS1

113

5051G3

1200A 5252

ASAM

5051

1200/5A

CS1

113

5051G3

1200A

INCOMING 40KVFEEDER NO. PROVIDEDBY DETROIT EDISON

1200A, 15KV, 3ph, 3W + GRD.

N.O.

N.C.

600A3P

600A3P

600A3P

600A3P

N.C.

N.O.

600A3P

600A3P

N.C.

N.O.

600A3P

600A3P

N.C.

N.O.

600A3P

600A3P

N.O.

N.C.

N.O.

N.C.200/30E, 3P

200/15E, 3P

200/30E, 3P

600A3P

600A3P

TRANSFORMER 1000KVAWITH COOLING FAN

13.2KV-4800V, 3ı , 3W

600A3P

600A3P

" " " "

TRANSFORMER 1500KVAWITH COOLING FAN

13.2KV-4800V, 3ı , 3W

N.O.

N.C.

600A3P

600A3P

600A3P

600A3P

600A3P

600A3P

600A3P

600A3P

N.C.

600A3P

600A3P

N.C.

N.O.

600A3P

600A3P

600A3P

600A3P

N.C.

N.O.

N.O.

N.C.

600A3P

600A3P

EXISTING 3-1/C - 15KV 133% SHIELDEDINSULATION 500Kcmil EPR & 1-500KcmilXHHW GRD IN 5" PVC CONDUIT IN DUCTBANK

EXISTING 3-1/C-15KV 133% SHIELDEDINSULATION 500Kcmil EPR & 1-500KcmilXHHW GRD IN 5" PVC CONDUIT INDUCTBANK

PS108

PS107

EXISTING 5"C, WITH 3- 1/C -15KV 133%SHIELDED INSULATION 500Kcmil EPR& 1-500KcmilL XHHW GRD.

EXISTING 5"C, WITH 3- 1/C -15KV 133%SHIELDED INSULATION 500Kcmil EPR& 1-500Kcmil XHHW GRD.

EXISTING 5"C, WITH 3- 1/C -15KV 133%SHIELDED INSULATION 500Kcmil EPR& 1-500Kcmil XHHW GRD.

EXISITNG 3 -1/C -15KV 133% SHIELDEDINSULATION 500Kcmil EPR & 1-500KcmilXHHW GRD IN 5" PVC CONDUIT IN DUCTBANK

EXISTING 3- 1/C- 15KV 133% SHIELDEDINSULATON 500Kcmil EPR & 1-500KcmilXHHW GRD. IN DUCTBANK

EXISTING 3- 1/C -15KV 133% SHIELDEDINSULATION & 1-500Kcmil XHHW GRDIN 5" PVC CONDUIT IN DUCTBANK

EXISTING 3- 1/C -15KV 133% SHIELDEDINSULATION & 1-500Kcmil XHHW GRDIN 5" PVC CONDUIT IN DUCTBANK

FUTURE CLINICAL BUILDING SUBSTATION NO. 1-1-06

DETROIT EDISON SWITCH

TO BATTERY CHARGER

10EN.O.

N.C.

600A3P

600A3P

EXISTING CHILLER SUBSTATION NO. 2

EXISTING CHILLER SUBSTATION NO. 1

EXISTING ENERGY CENTER SUBSTATION NO. 2

EXISTING ENERGY CENTER SUBSTATION NO. 1

EXISTING MAIN PRIMARY SWITCHGEAR LINE-UP

EXISTING BUILDING 1 ISOLATION BANK "A"

EXISTING BUILDING 1 ISOLATION BANK "B"

EXISTING RESEARCH BUILDING 31 TRANSFORMER T-1

EXISTING RESEARCH BUILDING 31 TRANSFORMER T-2

EXISTING WEST SITE TRANSFORMER T-3

K

K

" "

K

K

K

K

DETROIT EDISON 310MVA OIL FILLEDTRANSFORMER40KV-13.2KV

RECALIBRATE RELAYS. SETTING TO BE MAXIMUM ALLOWEDBASED UPON COORDINATI0N/SHORT CIRCUIT STUDY

LA

LA

LA

LA

LA

LA

TRANSFORMER1500/1725KVA

13.2KV-480Y/277V,3ı ,4W

125E

TRANSFORMER2000/2300KVA

13.2KV-480Y/277V,3ı ,4W

TRANSFORMER 150KVA

13.2KV-480Y/277V,3ı ,4W

TRANSFORMER2000/2300 KVA

13.2KV-480Y/277V,3ı ,4W

TRANSFORMER2000/2300 KVA

13.2KV-480Y/277V,3ı ,4W

TRANSFORMER2000/2300 KVA

13.2KV-480Y/277V,3ı ,4W

EXISTING CLINICAL BUILDING FIRE PUMPSUBSTATION NO. 1-B-01

EXISTING CLINICAL BUILDING LIGHTING\RECEPTACLESUBSTATION NO. 1-1-05

EXISTING CLINICAL BUILDING HVAC SUBSTATION NO. 1-1-04

EXISTING CLINICAL BUILDING X-RAY SUBSTATION NO. 1-1-03

EXISTING CLINICAL BUILDING HVAC SUBSTATION NO. 1-1-02

EXISTING 3-1/C-15KV 133%SHIELDED INSULATION500Kcmil EPR & 1-500Kcmil XHHWGRD IN 5" PVC CONDUIT INDUCTBANK

PS1091

NEW 3-1/C-15KV 133%SHIELDED INSULATION500Kcmil EPR & 1-500KcmilXHHW GRD IN 5" PVCCONDUIT IN DUCTBANK

EXISTING CLINICAL BUILDING LIGHTING\RECEPTACLESUBSTATION NO. 1-1-01

TO ISOLATION BANK A MOTORIZEDAUTOMATIC TRANSFER SWITCH

TO ISOLATION BANK B MOTORIZEDAUTOMATIC TRANSFER SWITCH

FUTURE CONNECTION

K

K

K

NEW LIGHTING UNIT SUBSTATION 6

NEW MECHANICAL UNIT SUBSTATION 4

NEW MECHANICAL UNIT SUBSTATION 5

FOR CONTINUATIONSEE E7.11

NEW 3-1/C-15KV 133%SHIELDED INSULATION500Kcmil EPR & 1-500Kcmil XHHWGRD IN 5" GALVANIZED RIGIDSTEEL CONDUIT

EXISTING 3-1/C-15KV 133% SHIELDED INSULATION 500KcmilEPR & 1-500Kcmil XHHW GRD IN 5" PVC CONDUIT IN DUCTBANK

EXISTING 3-1/C-15KV 133% SHIELDED INSULATION 500KcmilEPR & 1-500Kcmil XHHW GRD IN 5" CONDUIT TYPICAL

EXISTING 5"C, WITH 3 -1/C- 15KV133% SHIELDED INSULATION 500KcmilEPR & 1-500Kcmil XHHW GRD

EXISTING 3- 1/C -15KV133% SHIELDED INSULATION500Kcmil EPR &1-500Kcmil XHHW GRD

FOR CONTINUATIONSEE E7.10

FOR CONTINUATIONSEE E7.9

600A/3P65,000AIC

600A/3P65,000AIC

TRANSFORMER 500/575KVA

13.2KV-480Y/277V

TRANSFORMER750/1000KVA

13.2KV-480Y/277V

TRANSFORMER 500/575KVA

13.2KV-480Y/277V

V.A.UTILITY

1200/5A

M

NOT TO SCALE

ONE LINE DIAGRAM - 13.2 KILOVOLT PRIMARY

ELECTRICAL EQUIPMENTINDICATED ON THIS SHEET ISEXISTING TO REMAIN ANDFOR REFERENCE ONLYUNLESS OTHERWISE NOTED

r

Albert Kahn Associates, Inc. is a member ofthe Albert Kahn Family of Companies.

Albert Kahn Building7430 Second Ave.Detroit, Michigan 48202-2798

© 2007

T2

1W

22 1E

AREA OFPROJECT

ISSUE 002 - DD OWNER REVIEW 05/30/14

ISSUE 003 - CD OWNER REVIEW 10/21/14

ISSUE 004 - BID 02/05/15

P. GARLAND

125E 200E

600A3P

600A3PK K

ISOLATIONBANK ASECONDARYSELECTORSWITCHES

125E 200E

600A3P

600A3PK K

ISOLATIONBANK BSECONDARYSELECTORSWITCHES

MANHOLEP6

MANHOLEP5

MANHOLEP2

TO SOUTHMETER HOUSE

MANHOLEP3

MANHOLE P4

80E

500KVA

MANHOLE P10

BUILDING #22

125E

125E

125E

UNIT SUB 1

UNIT SUB 2

UNIT SUB 3

750KVA

NURSING HOME

SWITCHBOARD 3

SWITCHBOARD 2

SWITCHBOARD 1

100E

300E300E

600A3P

600A3P

BUILDING 1ISOLATION BANK "A"

1200A/300A

G

SITE GENERATOR600A

3P

600A3P

125E

BUILDING 1ISOLATION BANK "B"

1500KVAWITH FAN COOLING13,200-4800V, 3ɸ, 3W

250E

600A3P

600A3P

600A3P

600A3P

1000KVAWITH FAN COOLING13,200-4800V, 3ɸ, 3W

600A3P

600A3P

WESTERN ENGINE

250E

ISOLATION BANK BMOTORIZED OPERATEDAUTOMACTIC TRANSFER SWITCH

ISOLATION BANK AMOTORIZED OPERATEDAUTOMACTIC TRANSFER SWITCH

ISOLATION BANK APRIMARY SELECTORSWITCHES

ISOLATION BANK BPRIMARY SELECTORSWITCHES

PRIMARY FEEDER #A-10613200V, 3ɸ, 3W

PRIMARY FEEDER #A-10413200V, 3ɸ, 3W

GENERATOR DISTRIBUTIONSWITCHGEAR

DESTINATION ANDLOAD SHALL BEFIELD VERIFIED ANDREMOVED IF NOT USED

750KVA4800-208/120V3ɸ, 4W

FEEDER BUS DUCT

1500KW, 4800V, 3ɸ, 3W

750KVA4800-208/120V3ɸ, 4W

750KVA4800-208/120V3ɸ, 4W

NOT TO SCALE

ONE LINE DIAGRAM - 4800 VOLT PRIMARY

ELECTRICAL EQUIPMENTINDICATED ON THIS SHEET ISEXISTING TO REMAIN ANDFOR REFERENCE ONLYUNLESS OTHERWISE NOTED

r

Albert Kahn Associates, Inc. is a member ofthe Albert Kahn Family of Companies.

Albert Kahn Building7430 Second Ave.Detroit, Michigan 48202-2798

© 2007

T2

1W

22 1E

AREA OFPROJECT

ISSUE 002 - DD OWNER REVIEW 05/30/14

ISSUE 003 - CD OWNER REVIEW 10/21/14

ISSUE 004 - BID 02/05/15

P. GARLAND

P1B PE

PPA

LPA

TOSWBD #3

3000A, 208/120V, 3P, 3W

SWITCHBOARD #1

1 2 5 7 8 14 15 16 17 19 20 21 22 23 24

TO UNIT SUBSTATION #1 FEDFROM ISOLATION BANK B.SEE DWG. E7-2 FORCONTINUATION

ELEVATORS3 & 4

_

CR5A-1

RBA-1 RBA-2

R1A-1 R1A-2

R2A-1 R2A-2

R3A-1 R3A-2

FUTURERP

FUTURERP

FUTURERP

CR1A-1

CR2A-1

CR3A-1

CR4A-1

FUTURERP

FUTURERP

FUTURERP

FUTURERP

FUTURERP

CR6A-1 FUTURERP

CR7A-1

CR8A-1

FUTURERP

FUTURERP

INSTALL PANELSWITHIN 10'-0" OFJUNCTION BOX (TYP)

2B2 2B1

2B

BB

2BA 2BB

24

OUTPATIENTBLDG T2

3 4 6 10 1211 13 18

SPARE

ATS1-260A3P

ATSB-A1400A, 3P

TCRA, 150KVA, 3P480-208/120V, 4WK-4

TOPARALLELINGSWITCHBOARD

800AF300AT

800AF300AT 400A

800AF400AT

800AF300AT

800AF300AT

800AF300AT

800AF300AT

800AF300AT

800AF300AT

800AF300AT

800AF300AT

800AF500AT

800AF200AT

800AF400AT

800AF400AF

800AF400AT

800AF300AT

800AF150AT

800AF150ATGFIGFIGFIGFI

9

1B1 1B

1BA

GFIGFI GFI GFI GFI GFI GFI800AF150AT GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI

RECEPTACLECRITICAL POWER

A RISER

2 1/2"C., 3-#4/0,& 1#4 GRD

1 #1/0 IN 3/4" PVCCONDUIT TO ELECTRICALROOM GROUND BAR (TYP)

WIREWAY

WIREWAY

WIREWAY

WIREWAY

_ WIREWAY

_ WIREWAY

_ WIREWAY

_ WIREWAY

WIREWAY

WIREWAY

_ WIREWAY

_ WIREWAY

_ WIREWAY

10" X 10" WIREWAY(TYP)

1500 KW GENERATOR

200A, 3P CB

8AA 8AA2

ATS-2

FORSITELTG

KITCHENETTEPANEL

5BAB

6BAB

7BAB

KITCHENETTEPANEL

KITCHENETTEPANEL

CR9A-1

2 1/2"C., 3-#4/0, 2#4/0 NEUTRAL& 1#4 GRD (TYP FORALL RECEPTACLE PANELSUNLESS OTHERWISE NOTED

1BAB

2BAB

3BAB

3", 4 #350kcmil& 1 #3 GRD

R4A-1 FUTURERP

WIREWAY

FUTURERP

WIREWAY

FUTURERP

CONN LOAD79.06 KVARDEM LOAD65.86 KVAR

CONN LOAD25.20 KVARDEM LOAD23.60 KVAR

CONN LOAD25.20 KVARDEM LOAD23.60 KVAR

CONN LOAD25.20 KVARDEM LOAD23.60 KVAR

3 1/2"C., 3#500kcmil2#500kcmil NEUTRAL& 1#3 GRD (TYP FORALL RECEPTACLEPANELS UNLESSOHERWISE NOTED)

3 1/2"C., 3#500kcmil2#500kcmil NEUTRAL& 1#3 GRD (TYPUNLESS NOTEDOTHERWISE

1 1/2"C, 4#1/0 & 1#6 GRDWIRE LENGTH SHALL NOTEXCEED 10'-0" FROM SPLICETO LUG

NEW,3#500 kcmil,2#500kcmil

(NEUTRAL), &1#3 GRD

INTO EXISTING3 1/2"C

EXISTING3 1/2"C,

3#500kcmil,2#500kcmil

(NEUTRAL), &1#3 GRD

800AF300AT

400A3P

SPARE(OLD CHAPEL

AC UNIT)

SPARE SPARE

PHONEROOM

600A, 208/120V, 3PH, 4W + GRD COPPER BUS AND LUGS

60A3P

UV-2

40A,3P(HARC)

70 A3P(HARC)

60 A3P(HARC)

RH-1-1(5KW)

RH-1-2(5KW)

RH-1-3(10KW)

RH-2-1(10KW)

RH-2-2(10KW)

RH-2-3(10KW)

1"C,3#4& 1#8GRD

60A3P

100A3P

1"C,3#6& 1#8GRD

3/4"C,3#8& 1#10GRD

30A3P

30A3P

60A3P

60A3P

60A3P

60A3P

20A,3P(HARC)

20A,3P(HARC)

40A,3P(HARC)

40A,3P(HARC)

40A,3P(HARC)

RTU-1 RTU-2

3/4"C,3#8& 1#10GRD

60A,3PSPACE

60A,3PSPACE

200A,3P200A,

3P40A,3P(HARC)

PDP-8A

RH-1-4(5KW)

30A3P

1/2"C, 3#12 & 1#10 GRD

20A,3P(HARC)

SPARE SPARE

4BA1 4BA2

125A MCB CA

CONN LOAD112.34 KVARDEM LOAD86.88 KVAR

SPARE

R5A-1R5A-2

R6A-1R6A-2

R7A-1R7A-2

R8A-1R8A-2

RECEPTACLENORMAL POWER

A RISER

_WIREWAY

_WIREWAY

_WIREWAY _

WIREWAY

_

FUTURERP

FUTURERP

FUTURERP

FUTURERP

FUTURERP

R9A-1

9C

CBCB

8A

9A

IN 8TH FLOORCEILING SPACE

IN 8TH FLOORCEILING SPACE

WIREWAY

FUTURERP

CONN LOAD107.70 KVARDEM LOAD91.41 KVAR

200A3P

200A3P

400A800AF300AT

NEW

RELOCATED FROMPOSITION 22

CRBA-1

NEW

RELOCATED FROMPOSITION 4

J

NOT TO SCALE

ONE-LINE DIAGRAM - SUBSTATION 1

3BA 3BB

ELECTRICALROOMB312

ELECTRICALROOMA373

3K1 3K2 3K3

4 -500kcmil& 1 #3 GNDIN 3 1/2" C.

400A 3P 4W84-CCTS.

400A 3P 4W84-CCTS.

400A 3P 4W72-CCTS.

2L1 2L2

STORAGEB266

-

R1A-3

R2A-3

2 1/2"C., 3-#4/0,& 2#4/0NEUTRAL & 1#4 GRD

2 1/2"C., 3-#4/0,& 2#4/0NEUTRAL & 1#4 GRD

ELECTRICAL EQUIPMENTINDICATED ON THIS SHEET ISEXISTING TO REMAIN ANDFOR REFERENCE ONLYUNLESS OTHERWISE NOTED

REFER TO PANELSCHEDULES FORREQUIREMENTS

REFER TO PANELSCHEDULES FORREQUIREMENTS

r

Albert Kahn Associates, Inc. is a member ofthe Albert Kahn Family of Companies.

Albert Kahn Building7430 Second Ave.Detroit, Michigan 48202-2798

© 2007

T2

1W

22 1E

AREA OFPROJECT

ISSUE 002 - DD OWNER REVIEW 05/30/14

ISSUE 003 - CD OWNER REVIEW 10/21/14

ISSUE 004 - BID 02/05/15

P. GARLAND

CC-B

3000A, 208/120V, 3P, 3W

SWITCHBOARD #2

CC-1B P2 10D

SPACE

10A 10AA

10B

10C

1 2 3 4 6 12 13 14 15 16 17 18 19 20 21 22 23 24

TO UNIT SUBSTATION #2 FEDFROM ISOLATION BANK B.SEE DWG. E7-2 FORCONTINUATION

ELEVATORS5 & 6

ATSB-D1400A-3P

R5D-1 R5D-2

R6D-1 R6D-2

R7D-1 R7D-2

R8D-1 R8D-2

FUTURERP

FUTURERP

FUTURERP

FUTURERP

CRBD-1 FUTURERP

CR1D-1

CR2D-1

CR3D-1 FUTURERP

CR4D-1 FUTURERP

FUTURERP

CR5D-1

FUTURERP

CR6D-1

FUTURERP

CR7D-1

CR8D-1 FUTURERP

FUTURERP

INSTALL PANELS WITHIN 10'-0"OF JUNCTION BOX (TYP)

5V

PULLBOX(OLD5VV)

5

SPARE

8BL

6B6BL

8BR

WIREWAY

SPARE

SR-R SR-L

WIREWAY

200A3P

100A3P

60A3P

100A3P

S2200A3P200A3P

60A3P

100A3P

AHU 20 HPCOMP

10 HPCOMP

1110

SPARE

400A3P

TCRD150KVA, 3P,4W480V-208/120VK-4

BA1 BA2

BA3

800AF300AT

7B

5BA

5BB

5B

TO PARALLELINGSWITCHBOARD

7 8 9

400AGFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI800AF600AT

800AF150AT

800AF300AT

800AF300AT

800AF500AT

800AF150AT

800AF400AT

800AF400AT

800AF400AT

800AF600AT

800AF600AT

800AF300AT

800AF300AT

800AT300AF

800AF300AT

800AF300AT

800AF300AT

800AF300AT

800AF300AT

800AF300AT

SPARESPARESPARE

2 1/2"C., 3-#4/0,& 1#4 GRD (TYP)

RECEPTACLENORMAL POWER

D RISER

RECEPTACLECRITICAL POWER

D RISER

WIREWAY

WIREWAY

_ WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

TO BLDG.No. 26 (185 KWGENERATORBUILDING)

PANEL

TO 185 KW GENERATORSYSTEM THRU ATS#1(SEE SWBRD#3 POS#3)

30 TON A/CUNIT-5th FLOORROOF

TRANSF S230 KVA,208/120V,3P, 4WPULL

BOX

ATSB-C1400A-3P

CRBC-1 FUTURERP

CR1C-1 FUTURERP

CR2C-1 FUTURERP

CR3C-1 FUTURERP

CR4C-1 FUTURERP

FUTURERP

CR5C-1

FUTURERP

CR6C-1

FUTURERP

CR7C-1

CR8C-1 FUTURERP

RECEPTACLECRITICAL POWER

C RISER

_ WIREWAY

_ WIREWAY

_ WIREWAY

WIREWAY

_ WIREWAY

_ WIREWAY

_ WIREWAY

WIREWAY

WIREWAY

GFI 800AF300AT

TO PARALLELINGSWITCHBOARD

400A3P

8K8D

200A3PCB200A

3PCB

2 1/2"C., 4#4/0& 1#4 GRD

9AA

R9D-1 CR9D-1 CR9C-1

3 1/2"C., 3#500kcmil,& 1#3 GRD

WIREWAY

FUTURERP

WIREWAY

FUTURERP

WIREWAY

FUTURERP

CONN LOAD109.03 KVADEM LOAD94.08 KVA

CONN LOAD122.14 KVADEM LOAD105.99 KVA

CONN LOAD131.61 KVADEM LOAD108.14 KVA

CONN LOAD33.71 KVADEM LOAD31.67 KVA

NOTE 1

NOTE 2

NOTES:

1. 3 1/2"C., 3#500kcmil, 2#500kcmil NEUTRAL, AND 1#3 GROUND (TYPICAL UNLESS NOTED OTHERWISE)

2. 1#1/0 IN 3/4" PVC CONDUIT TO ELECTRICAL ROOM GROUND BAR (TYPICAL)

3. 3 1/2"C., 3#350kcmil, 2#350kcmil NEUTRAL, AND 1#4 GROUND

2 1/2"C., 3-#4/0, 2#4/0NEUTRAL & 1#4 GRD(TYP FOR ALL RECEPTACLEPANELS UNLESS OTHERWISE NOTED)

RELOCATEDDISCONNECTSWITCH

2"C, 3#4/O & #4 GRD1 1/4"C, 3#1 & 1#6 GRD

1"C, 3#4 & 1#8 GRD

R1D-1 R1D-2

FUTURERP

R2D-1 R2D-2

R3D-1 R3D-2

R4D-1

R1D-3

R2D-3

FUTURERP

FUTURERP

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

10" X 10" WIREWAY(TYP)

RBD-1 RBD-2

FUTURERPFUTURERP

3 1/2"C., 3#500kcmil2#500kcmil NEUTRAL& 1#3 GRD (TYP FORALL RECEPTACLEPANELS UNLESSOHERWISE NOTED)

TB-CRB2150KVA,3P,4W480V-208/120VK-4

SPARE

NEWRELOCATED FROMPOSITION 9

RELOCATED FROMPOSITION 10

RELOCATED FROMPOSITION 17

RELOCATED FROMPOSITION 8

NOTE 1

NOT TO SCALE

ONE-LINE DIAGRAM - SUBSTATION 2

EXISTINGSPARE

EXISTINGSPARE

FUTURERP

FUTURERP

2 1/2"C,3#4/0,2#4/0NEUTRAL& 1#4GRD

2 1/2"C,3#4/0,2#4/0NEUTRAL& 1#4GRD

ELECTRICAL EQUIPMENTINDICATED ON THIS SHEET ISEXISTING TO REMAIN ANDFOR REFERENCE ONLYUNLESS OTHERWISE NOTED

r

Albert Kahn Associates, Inc. is a member ofthe Albert Kahn Family of Companies.

Albert Kahn Building7430 Second Ave.Detroit, Michigan 48202-2798

© 2007

T2

1W

22 1E

AREA OFPROJECT

ISSUE 002 - DD OWNER REVIEW 05/30/14

ISSUE 003 - CD OWNER REVIEW 10/21/14

ISSUE 004 - BID 02/05/15

P. GARLAND

P1A

SWITCHBOARD #3

3BBC

KITCHENTRAYVEYOR

4XR

2 9 10 11 12 15 16 17 18 19 20 21 22 23 24

TO UNIT SUBSTATION #3 FEDFROM ISOLATION BANK A.SEE DWG. E7-2 FORCONTINUATION

3000A, 208/120V, 3PH, 3W

ELEVATORS1 & 2

R1B-1

R4B-1

FUTURERP

FUTURERP

FUTURERP

FUTURERP

FUTURERP

FUTURERP

FUTURERP

FUTURERP

FUTURERP

RBC-1

R1C-1

RBC-2

R1C-2

R2C-1 R2C-2

R3C-1 R3C-2

R4C-1

RP-L

1

RP-R RS

3

MAINO.R.CHILLER

ACP-1

ADP-2 ADP-3 ADP-4

ADP-6

LP-A LP-B LP-BA

LINEAR ACCELERATORSUITE PANELS

SPARE

400A-3P

4 5 6800AF300AT

800AF300AT

800AF300AT

800AF300AT

800AF300AT

BBA

800AF300AT

7800AF300AT

BDD

8800AF500AT

800AF500AT

800AF300AT

800AF300AT

800AF300AT

800AF400AT

BC

800AF600AT

800AF200AT

800AF400AT

800AF400AT

800AF150ATGFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI GFI

800AF300AT

800AF600AT 400A

TOPARALLELINGSWITCHBOARD

PBA

BB2

BB1

BBP

BBP1

PBA-1

FUTURER2B-1

R5B-1

R6B-1

R7B-1

R8B-1

CRBB-1

CR1B-1

CR2B-1

CR3B-1

CR4B-1

CR5B-1

CR6B-1

CR7B-1

CR8B-1

R3B-1

RECEPTACLENORMAL POWER

B RISER

RECEPTACLECRITICAL POWER

B RISER

RECEPTACLENORMAL POWER

B RISER

TCRB150KVA480-208/120V3PH,4WK-4

RECEPTACLENORMAL POWER

C RISER

2 1/2"C., 3-#4/0,& 1#4 GRD (TYP)

10" X 10" WIREWAY(TYP)

_

_

_

_

__

_

_

_

_

_

_

_

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAYWIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

WIREWAY

_ WIREWAY

_ WIREWAY

_

TO BLDG.No. 26 (185 KWGENERATORBUILDING)

PANEL

FUSEBLOCK

TO SWBD.#2, CKT.#1ATS #1

225A-3P

PANELRE

TO 185 KWGENERATORSYSTEM

AHU-5THFLOORPENTHOUSE

8DD

PPA

LPA

13 14800AF400AT

800AF200ATGFI GFI

260A3P

FORSITELTG

ATS-2

R5C-1R5C-2

R6C-1R6C-2

R7C-1R7C-2

R8C-1R8C-2

_WIREWAY

_WIREWAY

_WIREWAY

_WIREWAY

_

FUTURERP

FUTURERP

FUTURERP

FUTURERP

800AF400AT

FUTURERP

FUTURERP

FUTURERP

DP-1(RB)

"1A"

BLDG. #3

9B A/C

3 1/2"C., 3#500kcmil2#500kcmil NEUTRAL& 1#3 GRD (TYPUNLESS NOTEDOTHERWISE

ATSB-B1400A-3P

150A3PCB

2"C., 4#2/0& 1#6 GRD

3 1/2"C., 4#500kcmil,& 1#3 GRD

100A 3P

1 1/4"C., 4#2 &1#6 GRD

R9C-1

RBB-1

R9C-2FUTURERP

WIREWAY

WIREWAY

WIREWAY

FUTURERP

FUTURERP

FUTURERP

FUTURERP

FUTURERP

FUTURERP

FUTURERP

FUTURERP

FUTURERP

FUTURERP FUTURE

RP

PANELE

2 1/2"C., 3-#4/0, 2#4/0NEUTRAL & 1#4 GRD(TYP FOR ALL RECEPT.PANELS UNLESSOTHERWISE NOTED)

1 #1/0 IN 3/4" PVCCONDUIT TOELECTRICAL ROOMGROUND BAR (TYP)

3 1/2"C., 3#500kcmil2#500kcmil NEUTRAL& 1#3 GRD (TYP FORALL RECEPT. PANELSUNLESS OHERWISENOTED)

FLUSHMOUNTEDIN CLAYTILE WALL

CONN LOAD16.20 KVADEM LOAD15.80 KVA

CONN LOAD0.00 KVADEM LOAD0.00 KVA

CONN LOAD33.09 KVADEM LOAD31.31 KVA CONN LOAD

18.87 KVADEM LOAD18.38 KVA

CONN LOAD127.06 KVADEM LOAD103.44 KVA

CONN LOAD87.5 KVADEM LOAD63.84 KVA

NOTE 2

NOTE 1

NOTES:

2. CONCEAL CONDUIT IN EXISTING WALL. PATCH WALL AS REQUIRED TO MATCH THE EXISTING ADJACENT WALL.

TOSWBD#1

50A3P

1200A, 208V, 3PH, 3W

20A2P

30A3P

1000A3P

300A3P

1W-AH-15

30A2P

35A3P

NEMASIZE 1

COMPR.,FAN

7.5HP

20A3P

20A3P

3/4"C, 2#12 & 1#12GRDVFD VFD

1W-AH-15

3/4"C, 3#10 & 1#10GRD1"C, 3#6 & 1#8GRD

3/4"C, 3#8 & 1#10GRD

60A3P

30A3P

30A3P

30A2P

3/4"C, 2#12 & 1#12 GRD30A2P

30A2P

30A2P

30A2P

30A2P

1W-AC-110.6 KVA

200A3P

200AF 20A2P

20A2P

20A2P

20A2P

3/4"C, 3#12& 1#12GRD

30A2P

30A2P

30A2P

30A2P

TU-15-5ELECTRIC

RE-HEAT COIL1.5 KW, 208 V, 1 PHALTERNATE PHASE

CONNECTIONS

UNITHEATER

5KW,3PH

UNITHEATER

5KW,3PH

RH-1-11.5 KW

RH-1-23.0 KW

RH-1-31.0 KW

RH-1-42.4 KW

RH-1-51.6 KW

RH-1-62.5 KW

ELECTRICRE-HEAT COIL

208 V, 1 PHALTERNATE PHASE

CONNECTIONS

TU-15-11.2KW

TU-15-21.5KW

ELECTRIC RE-HEAT COIL208 V, 1 PHALTERNATE PHASECONNECTIONS

TU-15-31.2KW

TU-15-41.4KW

1"C, 3#6 & 1#8 GRD

60A2P

TU-15-63.2 KW

SPARE

2" C, 3#4/0 & 1#4 GRD

NEW PANEL RP- MCC A 200A MAIN CIRCUITBREAKER, 3 PHASE, 3 WIRE WITH 6-20A, 2P, 1-50A, 3P &1 - 40A, 2P BRANCH CIRCUIT BREAKERS, 13 SPACES(FOURTH FLOOR)

3/4"C, 3#8 &1#10 GRD

1. EXISTING CONDUIT AND WIRE TO REMAIN IN PIPE BASEMENT. INSTALL A NEW J BOX AT A CONVIENT LOCATION FOR SPLICING IN THE NEW CIRCUIT.

4BA4B

RELOCATED FROMPOSITION 23

RELOCATED FROMPOSITION 22 NEW

ELECTRIC RE-HEAT COIL208 V, 1 PHALTERNATE PHASECONNECTIONS

3/4"C, 2#12 & 1#12 GRD

NOT TO SCALE

ONE-LINE DIAGRAM - SUBSTATION 3

R2D-3

2 1/2"C,3#4/0,2#4/0NEUTRAL& 1#4GRD

ELECTRICAL EQUIPMENTINDICATED ON THIS SHEET ISEXISTING TO REMAIN ANDFOR REFERENCE ONLYUNLESS OTHERWISE NOTED

r

Albert Kahn Associates, Inc. is a member ofthe Albert Kahn Family of Companies.

Albert Kahn Building7430 Second Ave.Detroit, Michigan 48202-2798

© 2007

T2

1W

22 1E

AREA OFPROJECT

ISSUE 002 - DD OWNER REVIEW 05/30/14

ISSUE 003 - CD OWNER REVIEW 10/21/14

ISSUE 004 - BID 02/05/15

P. GARLAND

SEE DWG. E7-1FOR CONTINUATION

400A-3P

1#4/0 TO SUBSTATIONROOM GRD (TYP)

ELECTRONIC METERING

GFI30E

LA

N.C. N.O.

600A3P

600A3P

PRIMARY FEEDERNO A-105

PRIMARY FEEDERNO A-103

EMCC4-A1

GFIGFI GFIGFI

TOPARALLELINGSWITCHBOARD

TOPARALLELINGSWITCHBOARD

EMCC4-C1

400A-3P

400A-3P

UNIT SUBSTATION #4 (MECHANICAL)

400A-3P

MCC4-A1

250A-3P

EM8C-1

GFI250A-3P

GFI

TOPARALLELINGSWITCHBOARD

EM1C-1

EM2C-1

EM3C-1

EM4C-1

EM5C-1

EM6C-1

EM7C-1

1

VFD

EMBC-1

VFD

15A-3P15A-3P20A-3P80A-3P90A-3P

3

9 KV

AR

7 KV

AR

P-5H3 HP

AH-1SF-1

40 HP

AH-1EEF-1

30 HP

3#8

& 1

#10

GRD

, 3/4

"C

3#12

& 1

#12

GRD

, 3/4

"C

3#6

& 1

#8

GRD

, 3/4

"C

EM9C-1

3

7 KV

AR

AH-2EEF-2

30 HP

3#8

& 1

#10

GRD

, 3/4

"C

1

P-6H3 HP

3#12

& 1

#12

GRD

, 3/4

"C

80A-3P 15A-3P

3"C 4-250 KCMIL & 1#4 GRD

AH-7SF-7

7 1/2 HP

3#12

& 1

#12

GRD

, 3/4

"C

CONN LOAD 94.67 KVADEM LOAD 75.75 KVA CONN LOAD 35.70 KVA

DEM LOAD 28.56 KVA

CONN LOAD 0.00 KVADEM LOAD 0.00 KVACONN LOAD 0.00 KVA

DEM LOAD 0.00 KVA

MCC4-D1

500/575 KVAEQUIPPED WITHPROVISIONS FOR FANS13.2KV-480Y/277V, 3P, 4W

800 AF700 AT

3 1/2"C WITH 4-600 KCMIL & 1#1/0 GRD 3 1/2"C WITH 4-600 KCMIL& 1 #1/0 GRD IN EACH

CONN LOAD 59.07 KVADEM LOAD 47.26 KVA

CONN LOAD 62.70 KVADEM LOAD 50.16 KVA

CONN LOAD 252.14 KVADEM LOAD 201.73 KVA

3#12

& 1

#12

GRD

, 3/4

"C

RF-71 1/2 HP

30A/NF 30A/NF60A/NF 60A/NF 60A/NF

400A, 480/277V, 3P, 4W - 42,000 A1C

400A, 480/277V, 3P, 4W - 42,000 A1C

ATS4-A3400A-3PWITH OVER-LAPPINGNEUTRAL42,000 AIC

ATS4-C5260A-3PWITHOVER-LAPPINGNEUTRAL42,000 AIC

ATS4-C4260A-3PWITHOVER-LAPPINGNEUTRAL42,000 AIC

ATS4-D3400A-3PWITHOVER-LAPPINGNEUTRAL42,000 AIC

400A, 480/277V, 3P, 4W - 42,000 A1C

400A, 480/277V, 3P, 4W - 42,000 A1C

SWITCHBOARD #4 - 800A, 480/277V, 3P, 4W - 42,000 AIC

LEGEND:

"A" SPACE FOR A 20A -3P CIRCUIT BREAKER ANDNEMA SIZE 1 FULL VOLTAGE NON REVERSINGMOTOR STARTER. PROVIDE A SEPARATECAPACITOR COMPARTMENT FOR A 4 KVARCAPACITOR.

"B" SPACE FOR A 60A -3P CIRCUIT BREAKER ANDNEMA SIZE 2 FULL VOLTAGE NON REVERSINGMOTOR STARTER. PROVIDE A SEPARATECAPACITOR COMPARTMENT FOR A 6 KVARCAPACITOR.

2#14

INTE

RLO

CK

2#14

INTE

RLO

CK

"A" "A" "A" "B" "A" "B""A" "A" "A" "B"

"B""A" "A" "A" "B""A""A""A""A" "B" "B"

3

9 KV

AR

AH-2SF-2

40 HP

90A-3P

60A/NF

3#6

& 1

#8

GRD

, 3/4

"C

1/2"C , 3 #12 & 1 #12 GRD30 A,3 P

15 A,3 P

COMPRESSORFOR 8 TH FLOORWALK-IN COOLER

30 A,3 P

15 A,3 P

CONTROL AIRCOMPRESSOR2 MOTORS AT2 HP EACN

3

1/2"C , 3 #12 & 1 #12 GRD

NOT TO SCALE

ONE-LINE DIAGRAM - SUBSTATION 4

ELECTRICAL EQUIPMENTINDICATED ON THIS SHEET ISEXISTING TO REMAIN ANDFOR REFERENCE ONLYUNLESS OTHERWISE NOTED

r

Albert Kahn Associates, Inc. is a member ofthe Albert Kahn Family of Companies.

Albert Kahn Building7430 Second Ave.Detroit, Michigan 48202-2798

© 2007

T2

1W

22 1E

AREA OFPROJECT

ISSUE 002 - DD OWNER REVIEW 05/30/14

ISSUE 003 - CD OWNER REVIEW 10/21/14

ISSUE 004 - BID 02/05/15

P. GARLAND

EMCC4-C1

MCC4-C1

20A-3P70A-3P

12

6 KV

AR

AH-6SF-6

25 HP

3#8

& 1

#10

GRD

, 3/4

"C

30A/NF

EMCC4-B1

MCC4-B1

3

90A-3P 40A-3P

1 1 1 1 1

30A/NF 30A/NF 30A/NF 30A/NF30A/NF

20A-3P 30A-3P 30A-3P 15A-3P 15A-3P 15A-3P15A-3P

P-3H5 HP

P-4H5 HP

3

3#8

& 1

#10

GRD

, 3/4

"C

1 1

P-7H3 HP

3#12

& 1

#12

GRD

, 3/4

"C

2

4 KV

AR

3#10

& 1

#10

GRD

, 3/4

"C

1

15A-3P 80A-3P 15A-3P 15A-3P

3#6

& 1

#8

GRD

, 3/4

"C

AH-3SF-3

40 HP

AH-5SF-5

15 HP

AH-3EEF-3

30 HP

SEE DWG. E7-1FOR CONTINUATION

400A-3P

1#4/0 TO SUBSTATIONROOM GRD (TYP)

ELECTRONIC METERING

GFI30E

LA

N.C. N.O.

PRIMARY FEEDERNO A-103

PRIMARY FEEDERNO A-105

GFIGFI GFIGFI

TOPARALLELINGSWITCHBOARD

TOPARALLELINGSWITCHBOARD

400A-3P

400A-3P

UNIT SUBSTATION #5 (MECHANICAL)

400A-3P

250A-3P

EM8B-1

GFI250A-3P

GFI

TOPARALLELINGSWITCHBOARD

EM1B-1

EM2B-1

EM3B-1

EM4B-1

EM5B-1

EM6B-1

EM7B-1

EMBB-1

3"C 4-250 KCMIL & 1#4 GRD

600A-3P

600A-3P

AH-16SF-16

7 1/2 HP

30A/NF

CONN LOAD 54.18 KVADEM LOAD 43.34 KVA

CONN LOAD 111.86 KVADEM LOAD 89.51 KVA

CONN LOAD 47.99 KVADEM LOAD 38.41 KVA

CONN LOAD 0.00 KVADEM LOAD 0.00 KVA

CP-1COND REC.PMP CTRL

PNL

LEAD1 1/2 HP

LAG1 1/2 HP

P-1H10 HP

P-2H10 HP

CONN LOAD 0.00 KVADEM LOAD 0.00 KVA CONN LOAD 0.00 KVA

DEM LOAD 0.00 KVA

CONN LOAD 214.03 KVADEM LOAD 171.26 KVA

500/575 KVAEQUIPPED WITHPROVISIONS FOR FANS13.2KV-480Y/277V, 3P, 4W

800 AF800 AT

3 1/2"C WITH4-600 KCMIL& 1 #1/0 GRDIN EACH3 1/2"C WITH 4-600 KCMIL &

1 #1/0 GRD IN EACH

3 KV

AR

3 KV

AR

3#12

& 1

#12

GRD

, 3/

4"C

RF-67 1/2 HP

3#12

& 1

#12

GRD

, 3/4

"C

3#12

& 1

#12

GRD

, 3/4

"C

3#12

& 1

#12

GRD

, 3/4

"C

3#12

& 1

#12

GRD

, 3/4

"C

3#12

& 1

#12

GRD

, 3/4

"C

3#12

& 1

#12

GRD

, 3/4

"C

3#12

& 1

#12

GRD

, 3/4

"C

RF-53 HP

60A/NF 30A/NF60A/NF60A/NF 60A/NF

30A/NF

ATS4-C3400A-3PWITHOVER-LAPPINGNEUTRAL42,000 AIC

400A, 480/277V, 3P, 4W - 42,000 AIC

ATS4-B5260A-3PWITHOVER-LAPPINGNEUTRAL42,000 AIC

ATS4-B4260A-3PWITHOVER-LAPPINGNEUTRAL42,000 AIC

ATS4-B3400A-3PWITHOVER-LAPPINGNEUTRAL42,000 AIC

400A, 480/277V, 3P, 4W - 42,000 AIC

400A, 480/277V, 3P, 4W - 42,000 AIC400A, 480/277V, 3P, 4W - 42,000 AIC

BP-1COND REC.PMP CTRL

PNL

3#1

& 1

#6

GRD

, 1 1

/4"C

15 HP 25 HP 25 HP

100A-3P

100A/3P

LOCATED INTHE SUBBASEMENT

CONTROLLER WITHPREWIRED PUMPS(ONLY TWO PUMPSCAN RUN AT ONETIME)

LEGEND:

"A" SPACE FOR A 20A -3P CIRCUIT BREAKER ANDNEMA SIZE 1 FULL VOLTAGE NON REVERSINGMOTOR STARTER. PROVIDE A SEPARATECAPACITOR COMPARTMENT FOR A 4 KVARCAPACITOR.

"B" SPACE FOR A 60A -3P CIRCUIT BREAKER ANDNEMA SIZE 2 FULL VOLTAGE NON REVERSINGMOTOR STARTER. PROVIDE A SEPARATECAPACITOR COMPARTMENT FOR A 6 KVARCAPACITOR.

9 KV

AR

7 KV

AR

"A" "B"

"B""A""A"

"A""A" "A" "A" "A" "B"

"A" "B""A" "A" "B"

SWITCHBOARD #5 - 800A, 480/277V, 3P, 4W - 42,000 AIC

SPARE

30A3P

CONTROL AIRCOMPRESSOR2 MOTORS AT

2 HP EACH

15A3P

1/2"C, 3 #12& 1 #12 GRD

PANEL 4EPP1100A 3P 3W42-CIRCUIT

SERVESEF-1,2,3,4,5,6,7

4 -#2 & 1#8 GND-1 1/4"C

PANEL4PP1

150A 3P 3W42-CIRCUIT

SERVESAHU-8,16,17,18

3 -#1/0 & 1#6 GND-1 1/2"C3-#3/0 & 1#6 GND-2"C

150A 3-P200A 3-P

100A 3-P

MECHANICALPENTHOUSEON ROOF

NOT TO SCALE

ONE-LINE DIAGRAM - SUBSTATION 5

GFI 100A-3P

GENERAL X-RAY MACHINE (A295)REFER TO SHEET EP102W FORADDITIONAL INFORMATION.

C100N

ELECTRICAL EQUIPMENTINDICATED ON THIS SHEET ISEXISTING TO REMAIN ANDFOR REFERENCE ONLYUNLESS OTHERWISE NOTED

r

Albert Kahn Associates, Inc. is a member ofthe Albert Kahn Family of Companies.

Albert Kahn Building7430 Second Ave.Detroit, Michigan 48202-2798

© 2007

T2

1W

22 1E

AREA OFPROJECT

ISSUE 002 - DD OWNER REVIEW 05/30/14

ISSUE 003 - CD OWNER REVIEW 10/21/14

ISSUE 004 - BID 02/05/15

P. GARLAND