District Heating and Cooling in Kansai International Airport
KANSAI INTERNATIONAL AIRPORT Heating & Cooling Supply Co., Ltd.
■District Heating and Cooling System in Kansai International Airport
In supplying heat to facilities on the airport island extending more than 4km from north to south, plants have been set up in three districts with a high concentration of demand-Central, South, and North-with the aim of reducing construction costs and heat loss from pipes, while chillers have been distributed throughout the island. The Central Plant supplies heat to the management and passenger districts, which make up more than 85% of heat demand on the island. Electric centrifugal chillers, ice thermal storage systems, steam absorption chillers, and fire-tube boilers have been set up, and the facility configuration allows for a variety of operations to meet the needs of the situation on hand. The North and South Plants supply heat to their respective surroundings. The South Plant supplies heat to the international cargo, development, and supplies processing (fuel, wastewater and waste treatment) districts, while the North Plant focuses on the supply of heat to the domestic cargo district. The heat source for the north and south districts comes in the form of steam, provided through pipes leading from boilers located in the Central Plant. The steam powers the steam absorption chillers in each plant to provide chilled water, and at the same time, serves as steam for heating purposes.
Customer Steam Cold water
・Passenger terminal district
・Management district
Customer Steam Cold water
・Domestic cargo district
・Observation hall
Customer Steam Cold water
・International cargo district
・Supplies processing district
・Development district
Central Plant
South Plant
Fire-tube boiler
High efficiency electric centrifugal chiller Inverter centrifugal chiller
Steam absorption chiller
Steam absorption chiller
North Plant
Steam
Steam absorption chiller
Brine centrifugal chiller
Ice thermal storage system
Central Plant North Plant Kansai Electric Power South Plant
South Plant supply area
North Plant supply area
Central Plant supply area
Steam tubing
Second phase island
Connecting bridge
Development district
Supplies processing
International cargo district
Management district
Passenger terminal district
Domestic cargo district
Marine access district
Cold water
Type Standard temperature (℃) Pressure (Mpa)
Cold water (feed) 6.0 0.58~0.73 Cooling
Cold water (return) 13.0 0.29~0.49
Steam (feed) Saturated temperature 0.58~0.83 Heating
Condensation (return) 80 0.29
Type Total length
Cold water pipe (feed) Approx. 5km Cooling
Cold water pipe (return) Approx. 5km
Steam pipe (feed) Approx. 9km Heating
Condensate return pipe (return) Approx. 9km
Central Plant
Steam
generated 0.83MPa saturated steam
Steam flow 15t/h×4 units
Central Plant
High efficiency
centrifugal chiller 2,000Rt×2 units
Inverter centrifugal
chiller 1,200Rt×1 unit
Brine centrifugal
chiller
During ice-making 1,100Rt
During compressing 1,500Rt ×1 unit
Central Plant South Plant North Plant
2,000Rt×6 units 1,700Rt×4 units
350Rt×2 units
160Rt×2 units
125Rt×3 units
30Rt×2 units
Central Plant
Format Internal melt ice-on-coil
Capacity 5,000Rth×2 tanks
Electric centrifugal chiller
Fire-tube boiler
Steam absorption chiller
Ice thermal storage tank
■Overview of Heat Supply Facilities
■District piping ■Supply conditions
(Note) 1Rt = 3,024 kcal/h (1kcal=4.18605kJ)
(supply) Cold water(supply)
(supply) (supply)
KANSAI INTERNATIONAL AIRPORT Heating & Cooling Supply Co., Ltd.
Senshu-Kuko Naka 1-banchi, Tajiri-cho, Sennan-gun, Osaka 549-0011, Japan
as of October 2012