discover the mircom flex-net system
TRANSCRIPT
FleX-Net Network Series Overview
The FleX-Net system is designed to establish
Mircom as major player against key competitive
fire alarm manufacturers with networking
capabilities;
Notifier
EST
Siemens
Simplex
FleX-Net Network Series Overview
Based on the proven and reliable FX-2000 Series platform
Most of the existing functionality of the FX-2000 is maintained or enhanced
QX-5000 Series audio system is integrated into the FleX-Net system
Network system provides a fully distributed audio system
Firefighter’s telephone are integrated into the FleX-Net to form a networked telephone system
FleX-Net Network Series Overview
Unites multiple FleX-Net intelligent
fire alarm control panels as one
system
Supports copper and/or fiber optic
network cable
All control panels operate
independently, but as a cohesive
system for unified response
Enhanced survivability –
communications loss will not
compromise the system
Easily accommodates future growth
FleX-Net Network Series Overview
FleX-Net main board is equipped with one Signaling Line Circuit, two conventional non-addressable loops, and 4 Notification Appliance Circuits
The FleX-Net system has the look and feel of the FX-2000
Each node supports up to 28 SLCs and up to 7 remote annunciators
Each node supports a maximum of 5000 addressable points
The FleX-Net system has a faster processor with more memory to allow for future enhancements
FleX-Net Series Network Features
Up to 63 nodes
A node can be;
Building
Command Center
A group of floors within a building
Multiple Control Centers
Peer-to-Peer Network Communications
Proprietary ARCnet Communication Protocol
Long track record as industrial networking technology
Redundant Class B or Class A Wiring Configuration
FleX-Net Series Network Features
Built-in BACnet Compatibility
Built-in Computer Graphics software
Built-in Web Server
RS-232 port for event printer or hyperterminal
FleX-Net Series Configuration Features
FXConfig software supports network wide
configuration
DACT and Audio system are integrated into the
Configuration software
Simple easy-to-use interface and one-click
downloading of job to panels
Ability to export to XML
Generate reports for maintenance
FleX-Net Network Applications
Airports
Hotels & Resorts
Colleges & Universities
Office Buildings
Hospitals
High Rise Buildings
Target Customers Medium to large-scale facilities
Hospitality Hotels
Resorts
Retail/Shopping Malls
Department Stores
High Rise Buildings
Banks
Education Schools (Elementary, High and Middle Schools),
Universities/Colleges Dormitories, Campus Buildings, Administration Buildings
Manufacturing Facilities
Corporate Headquarters
Airports
Healthcare Hospitals
Long Term Care Facilities
FleX-Net Network
Supports all FleX-Net
intelligent systems
FX-2003-12NDS
FX-2017-12NDS
FX-2009-12NDS
FX-MNS
FleX-Net Series Network Main Chassis
The FleX-Net Network Main Chassis:
Support the FNC-2000 Fire Network Controller
Module
Support conventional, non-addressable adder
modules
Have the same design as the existing FX-2000 main
chassis
FX-2003-12NDS Compact Network Main Chassis
One SLC, Class C or Class A.
Four NACs, Class B or Class A, rated for
1.7A each.
Includes a 4 line by 20 character back-lit
LCD display.
12A Power Supply.
Will accommodate three internal adder
modules (e.g. network card, DACT, quad
loop adder).
Will accommodate two display adders
(e.g. IPS-2424, RAX-1048, FDX-008).
FX-2003-12NDS Compact Network Main Chassis
FX-2000 Main BoardMain Board
Left-most slot is reserved for a DACT or PR-100 adder module. If neither is required, this slot can be used for other adder modules.
It is recommended to locate the
network card at position #2
FX-2017-12NDS Mid Size Network Main Chassis
One SLC, Class C or Class A.
Four NACs, Class B or Class
A, rated for 1.7A each.
Includes a 4 line by 20
character back-lit LCD
display.
12A Power Supply.
Will accommodate 17
internal adder modules (e.g.
network card, DACT, quad
loop adder).
Will accommodate three
display adders (e.g. IPS-
2424, RAX-1048, FDX-008).
FX-2017-12NDS Mid Size Network Main Chassis
It is recommended to locate the
FNC-2000 network card at position #2
FX-2009-12NDS Large Network Main Chassis
One SLC, Class C or Class A.
Four NACs, Class B or Class A,
rated for 1.7A each.
A 4 line by 20 character back-lit
LCD display.
12A Power Supply.
Will accommodate 9 internal
adder modules (e.g. network card,
DACT, quad loop adder).
The BB-5008 box will
accommodate 7 display adders,
using expansion chassis’.
The BB-5014 box will
accommodate 13 display adders
using expansion chassis’.
or
FX-2009-12NDS Large Network Main Chassis
It is recommended to locate the
network card at position #2
FleX-Net Applications
Size of
Application
FX-2003-12NDS FX-2017-12NDS FX-2009-12NDS
Small X
Medium X X
Large X
With Voice
Evacuation and
Fire Fighter
Telephones
X
FNC-2000 Fire Network Controller Module
Provides network capability to
the FleX-Net Series
Interface for connecting the
optional FOM-2000-SP Fiber
Optic Network Adder Module
Mounts in any of the FleX-Net
fire alarm main chassis
FOM-2000-SP Fiber Optic Network Adder Module
Allows for the use of fiber
optic cabling on the FleX-
Net Series panels
Seamlessly connects to
the interface on the FNC-
2000 Fire Alarm Network
Controller Module
FleX-Net Adder Modules
FleX-Net supports the following adder modules;
Loop Controller
ALC-792M Quad Loop Adder
Conventional Adder Modules
DM-1008A Initiating Device Ckt
SGM-1004A Supervised Output
RM-1008A Relay Module
Auxiliary Adder Modules
UDACT-300A
PR-300 Polarity Reversal Module
RAXN-LCD Network Remote LCD Annunciator
4 lines x 24 character LCD Annunciator
Connects to any node via RS-485 to annunciate the network system
Does not take up a node address
3 ribbon headers support display adders
Mounts in a BB-1000 or BB-5000 Series enclosure
Mircom FleX-Net Fire Alarm Control Panel
Normal Condition
June 18, 2014
24 lines x 40 character LCD Annunciator
Connects to any node via RS-485 to annunciate the network system
Does not take up a node address
3 ribbon headers support display adders
Mounts in a BB-1000 or BB-5000 Series enclosure
RAXN-LCDG Remote Graphic Annunciator
FleX-Net Annunciators and Programmable Modules
FleX-Net supports the
following display adders;
LED Annunciator
RAX-1048TZ
Graphic Driver Modules
MDG-32
AGD-048
Programmable Switches
FDX-008
IPS-2424
Intelligent network panel that supports:
Main fire alarm chassis
Network Controller Modules ▪ Fire, Audio, & Telephone modules
Audio card cage ▪ Supports up to four 60-watt QAA style
amplifiers
30 Amp power supply
Room for up to a 40AH battery-set
Requires BBX-FXMNS enclosure
FleX-Net Integrated Fire and Audio Network Panel
FX-MNS Integrated Fire Alarm Network Main Chassis
One SLC, Class C or Class A.
Four NACs, Class B or Class A,
rated for 1.7A each.
A 4 line by 20 character back-lit
LCD display.
12A Power Supply.
Will accommodate 17 internal
adder modules (e.g. network card,
DACT, quad loop adder).
Will accommodate three display
adders (e.g. IPS-2424, RAX-1048,
FDX-008).
QMB-5000N Main Audio Network Card Cage
Audio and Telephone Control
Multi-channel operation
Distributed audio
5 telephone channels (with TNC-5000)
Multiple amplifier sizes
Uses existing QAA style amplifiers Maximum of 4 QAA style amplifiers
Maximum of 180 watts per enclosure
Amplifiers mount in audio card cage
Maximum of 3 QBB-5001 audio cabinets can be connected to the FX-MNS
Maximum of 3 X 360 Watts
Up to 540W per node
FleX-Net Audio Features
Multi-Channel Operation
Alarm tone can be different per node
Alert tone can be different per node
Paging is common per system
Five Telephone Handset Circuits on the node
Conventional or;
Addressable
Each node will support a master telephone
ANC-5000 Audio Network Controller Module
Provides audio microphone
control on the network
system
Provides space for an Alert
and Evacuation digital
voice message
Mounts on a plate in the
QMB-5000N audio card
cage or in the FX-MNS
main chassis
TNC-5000 Telephone Network Controller Module
Provides 5 hardwired
telephone circuits for the local
floor panel with circuit #1
configurable for the master
telephone handset
Provides network
communication path
Mounts with the ANC-5000 on
a plate in the QMB-5000N
main chassis or in the FX-MNS
QMB-5000N Audio Card Cage
TNC-5000
Telephone
Network
Controller
Module
ANC-5000
Audio
Network
Controller
Module
The black plate mounts
in the first slot
of the QMB-5000N
audio card cage
Space for
4 QAA
style
amplifiers
Both the ANC-5000 and TNC-5000
mount on a black plate
QAA Style Amplifiers
System uses existing QX-5000 Series audio amplifiers
25/70 volt models QAA-5415-25
QAA-5415-70
QAA-5230
QAA-5160
Amplifiers mount in the QMB-5000N audio card cage
Audio Expansion
Ribbon Cable
Maximum of 3 QBB-5001 cabinets FleX-NetTM
Integrated Fire & Voice Panel
Max. 180 watts
QBB-5001
Max. 360 watts
QBB-5001
Max. 360 watts
QBB-5001
Max. 360 watts
QMB-5000 card rack in a
QBB-5001 Box yields 360W
Audio Expansion
Up to 7 Remote LOCs per Node FleX-NetTM
Integrated Fire & Voice Panel
ACU – Autonomous Control Unit
Remote LOCs
QMP-5101N Network Master Microphone Paging Module
Network capable
Includes master paging
microphone and common
control functions
Used with the QAZT-
5302 selector panel
Mounts in a BB-5008 or
BB-5014 enclosure
QMT-5302N Network Master Telephone Control Module
Network capable
Includes master telephone handset and common control functions
Used with the QAZT-5302 selector panel
Mounts in a BB-5008 or BB-5014 enclosure
QAZT-5302
Paging and Telephone Selector Module
Provides zoned
paging and telephone
selection
Connects to:
QMP-5101N Master
Paging Module
QMT-5302N Master
Telephone Control
Module
OpenGN Graphics Software
An aesthetically pleasing high quality
customizable graphical interface between
administrators and monitored buildings
Building ready monitoring control system
with full software management in a user
friendly graphical enabled interface
Easy configuration and customization of
alarm devices
Remote desktop programming from any
location
Upload/download configuration files
without taking the whole system off-line
Customizable fire annunciation graphical
icons to provide customer specific site
representation