dimplex si 130 tur+

Upload: aisfm

Post on 03-Apr-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Dimplex Si 130 Tur+

    1/2

    Data sheet SI 130TUR+

    Reversible brine-to-water heat pump

    Order reference: SI 130TUR+

    Max. flow temperature for heating: 58 CCasing colour: white

    Heat pump for heating and cooling with integrated regulation installed indoors.Variable connection options for brine and heating connections on the rear wall ofthe casing. Access for servicing from the front, no minimum clearance required onthe sides, accessible from underneath with a lift truck. A sound-optimised insulated

    metal casing and integrated solid-borne sound insulation with free-swingingcompressor base plate, make direct connection with the heating system possible.High coefficients of performance due to compliance with EN 14511 for largervolume flows on the heat consumption side. Optimised heating and coolingoperation via an external four-way reversing valve which is activated by thecontroller (special accessory). Reversible refrigerating circuit with additional heatexchanger for higher DHW temperatures in heating operation and waste heatrecovery in cooling operation. Sensor monitoring of the refrigerating circuit for highdegree of operational safety; integrated thermal energy metering (display of thecalculated thermal energy volume for heating and domestic hot water preparationon the WPM EconPlus heat pump manager). The control panel is integrated into abrown-red design screen and can also be used as wired remote control using thewall mounting set (special accessories MS PGD). Universal design with the optionof flexible expansion for:

    -Bivalent or bivalent-renewable operating mode

    - combined distribution systems for heating and cooling

    - unmixed and mixed heating and cooling circuits

    Silent cooling via panel heating/cooling systems requires the use of the roomclimate control station (special accessory) to regulate the flow temperature on thebasis of the air temperature and humidity of a reference room. Soft starter, loadcontactor for brine circulating pump, integrated flow and return flow sensor; externalsensor (standard NTC-2) and dirt filter for brine circuit included in the scope ofsupply.

    Technical data SI 130TUR+

    Dimplex Reversible brine-to-water heat pump (Low temperature)

    Order reference SI 130TUR+

    Casing colour white

    Max. flow temperature for heating 58 C

    Temperature operating limits for brine -5 C to 25 C

    Temperature operating limits for cooling 5 C to 30 C

    Heat output / COP at B0/W35 kW/- 1 compr.: 57,60 / 4,50

    2 compr.: 108,50 / 4,30

    Sound pressure level at a distance of 1 m dB (A) 60

    Sound power level dB (A) 76

    Minimum heating water flow at internal pressure differential m/h / Pa 9,00 / 2900

    Refrigerant R410A kg 16,90

    Flow rate (heat source) at int. pressure differential m/h / Pa 24,50 / 21500

    Dimensions (W x D x H) mm 1350 x 775 x 1890

    Weight (incl. packing) kg 830Connection voltage 3/N/PE ~400 V, 50 Hz

    Starting current with soft starter A 108

    Fuse protection A 80

    Connection heating 3

    Heat source connection 3

    Heat output and COP according to EN255 (EN 14511) at B0/W35 (B0 = brine inlet temperature 0 C, W35 = heating water outlet temperature +35 C)

    Please note that additional space is required for pipe connections, operation and maintenance.

    Internet: 16.06.201050294420

    Phone: +49 (0)9221 709-201Fax: +49 (0)9221 709-339

    Glen Dimplex Deutschland GmbHDimplex DivisionAm Goldenen Feld 1895326 Kulmbach

    Page 1/2Subject to change and errors!E-mail: [email protected]

    Internet: www.dimplex.de

    mailto:[email protected]://www.dimplex.de/http://www.dimplex.de/mailto:[email protected]://www.dimplex.de/
  • 7/28/2019 Dimplex Si 130 Tur+

    2/2

    System accessories SI 130TUR+

    Description Order ref. Article

    number

    Sample

    item

    Item Price

    Heat pumps

    Reversible brine-to-water heat pump SI 130TUR+ 361770 1

    Elasticated sound insulation underlay strips SYL 250 352260

    DN 65 dirt trap SMF 65 362170

    Heat source accessories

    Brine circuit antifreeze (200 l) AFN 824 324610

    Brine circuit antifreeze (20l) AFN 825 328610Plate heat exchanger for SI 75 WTE 75 358450

    Titanium plate heat exchanger for SI 75 WTT 75 358500

    Hydraulic accessories

    Universal buffer tank (500 l)* PSW 500 339210

    Heating accessories

    Fan convector for heating 800 W SRX 080M 359080

    Fan convector for heating 1200 W SRX 120M 359090

    Fan convector for heating 1400 W SRX 140M 359100

    Fan convector for heating 1800 W SRX 180M 359110

    Heating and cooling accessories

    Fan convector for heating/cooling HL 11C 351730

    Fan convector for heating/cooling HL 16C 351740

    Fan convector for heating/cooling HL 26C 351750Fan convector for heating/cooling HL 36C 351760

    DHW preparation accessories

    Hot water cylinder (500 l) with temperature sensor WWSP 900 339220 3

    Flange heater for domestic hot water FLH 60 338060

    Flange heater for domestic hot water FLHU 70 338070 3

    FLH 25M flange heater FLH 25M 349430

    Safety valve combination SVK 852 326660

    Solar station for hot water SST 25 348430

    Control accessories

    Extension for an Ethernet network connection NWPM 356960

    Extension for a KNX/EIB bus connection EWPM 356970

    Extension for a Modbus connection LWPM 410 339410

    Swimming pool / remote fault indicator relay module RBG WPM 339700Wall mounting set MS PGD MS PGD 353810

    Remote control for WPM 2006/2007/EconPlus/R* AP PGD 356570

    External temperature sensor with casing FG 3115 336620

    Temperature sensor NTC-10 NTC-10 353390

    Thermostat for heating and domestic hot water KRRV 003 322070

    Control accessories (cooling)

    Room climate control system for temperature and humidity

    measurement

    RKS WPM 342220

    Passive cooling controller* WPM Econ PK 360000

    Room temperature controller heating/cooling* RTK 601U 355610

    Room temperature controller heating/cooling RTK 602U 355620

    Dew point monitor* TPW WPM 350970

    Solar thermal systems accessories

    Solar station SOLPU 1 356230

    * Other specific accessories available / required

    Important information:The combination of the components and the quantities indicated represent a non-binding sample system, which needs to be tested and individuallyadapted as required. Pump dimensioning must be reviewed according to the pressure loss of the system and the minimum heating water flow rate ofthe heat pump.

    Internet: 16.06.201050294420

    Phone: +49 (0)9221 709-201Fax: +49 (0)9221 709-339

    Glen Dimplex Deutschland GmbHDimplex DivisionAm Goldenen Feld 1895326 Kulmbach

    Page 2/2Subject to change and errors!E-mail: [email protected]

    Internet: www.dimplex.de

    mailto:[email protected]://www.dimplex.de/http://www.dimplex.de/mailto:[email protected]://www.dimplex.de/