DIGIGATE SeriesBuilt to Last...
Online HF UPS 1KVA-10KVA
www.apec.sa.com
Applicaons
Centralized server center, network controlcenter, Informaon Center, Healthcare,
Telecommunicaon
Features:Adopt DSP digital control technology
- Adopt advanced DSP digital control technology, it imroves performance &
system reliability effecvely, and achieves higher level of power density
and miniaturizaon.
- Besides that, it can meet all customers individualized needs, DIGIGATE
Series 1-10KVA provide very rich extensible funcon, users can configure
the need flexibly.
Output Power factor 0.9
PF 0.9 is more suitable for the trend of electrical equipment and can take
more load. With new ECO(Economic) funcon, system efficiency canachieve 94%, it lower UPS power consumpon and save user ’s cost.
Input PFC
Adopt didgital control input PFC technology, Input Power Factor can be
more than 0.98, It avoids polluon to power grid, saves energy and also
reduce cost.
Digital Control at DC-DC Converter
DIGIGATE Series 1-3KVA UPS adopt digital control use Digital Control at
DC-DC converter part instead of Analog Control in the past and it is more
reliable.
Wide input voltage range
Extremely wide input voltage and frequency range, even in very poor
power environment of the remote areas can normally supply the power. Itreduced the frequency of baery discharge so that the baery life can be
prolonged.
Perfect protecon
- The UPS contain I/P and O/P over-protecon, short voltage protecon,
overload protecon, short-circuit protecon, inverter over-heat
protecon, baery low voltage warning protecon and baery overcharge
protecon, etc. Which is the above greatly ensure the stability of running
the system.
- With bypass funcon, when the output overload or UPS failure, can turn
to bypass without interrupon and supply power to load by mains supply,
accordingly provide alarm informaon.
- With input I and N lines detecve funcon can prevent the danger caused
by the inversion of L and N lines.
Cold start and mains power start funcon
- For emergency status, UPS can start with baery directly when the mains
power anomalies.
- UPS can start directly without baery can be used for high precision
stabilizer
Compable with generatorsnt
Wide range of input voltage and frequency that can affecvely isolate the
adverse power from generator can provide clean, safe and stable power
supply the lead.
Intelligent Baery Management
- It adopts intelligent management technology to charge by three steps, toeffecvely extend baery life and reduce the number of baery
maintenance. The baery can be self tesng to find baery problem
mely.
- With baery voltage, overcharge protecon, etc. to maximize the
protecon of the baery is not damaged.
8/14/2019 Diji 1kva-10kva
http://slidepdf.com/reader/full/diji-1kva-10kva 2/2
Rated Capacity 1KVA 2KVA 3KVA 6KVA 10KVA
Rated Input voltage
Rated Input frequency
Input voltage range
Input frequency rangeInput current 8A max 15A max 23A max 46A max 76A max
Power factorTHDIBypass Voltage Range
Output voltage
Output PF
Output power(VA/Wa) 900 1800 2700 5400 9000
Inverter overload capability (Transfer to
bypass)
Voltage accuracyLoad crest
Transfer Time
Under Mains Mode
Under Baery Mode
Phase-Locked Rate
Total Voltage Harmonic Distorton
Baery TypeQuantty 2 4 6DC voltage 24V 48V 72V
Input Baery 9AH/12V 9AH/12V 9AH/12VCharging Voltage 27.1 ± 0.4V 54.2 ± 0.6VBack up TimeCharging Method
Functon
Protecton
Communicaton Port
Sofware Functon
Display
Noise
6/7.5 12/13.5 13/14.5
440x468x88(with internal baery)
580x590x200(with internal baery)
12/13.5 28/29.5 33/34.50
Specificatons
Charging Current: Standard Model
Long tme model
Efficiency: Mains Mode
BAT Mode
ECO Mode
Operatng Envirnoment: Operaton temp
Store temp
Humidity
Alttude
From AC mode to BAT mode:0ms ; From BAT mode to AC Mode: 0ms
From Main mode to bypass mode:4ms ; From bypass mode to mains mode:4msFrom normal mode to ECO mode:10ms
≥90% (full load) ≥92% (full load)
87% 90%
98% 98%
OUTPUT FREQUENCY
Long back tme model: Dimensions
(WxDxH) mm
Packing Dimension
(WxDxH) mm
Net/Gross Weight(Kg)
220VAC
50Hz/60Hz Auto Adapton
(115-295) ±5VAC(half load);(145-295)±5VAC(full load)
45-55Hz ±0.5% 50Hz type : 55-65Hz ±5% 60Hz type
≥0.98 ≥0.99<6% <5%
Rated output voltage-34V - Rated output Voltage +34V
OUTPUT
0.9
105%-150%:30s ; ˃150%:300ms
105%-125%:3min;125%-
150%:30s
±0.23:01
Same as Input Frequency
(50/60 ±0.2)Hz
≤1Hz/s
Full linear load <3% ; Full nonl inear load <5%
BATTERYSealed lead acid maintainance free baery
16192V
9AH/12V216.8 ± 1V
1A
6A 1A/3A/5A/8A
SYSTEM CONTROL AND COMMUNICATION
Silence ; cold start ; AC restart ; Auto restart
20-90% (non-condensing)
0m<alttude<1500m,over 1500m,used with power derated
50dB 55dB
Over-temp protecton ; Fan testng protecton ; AC L and N reversely connectng
protecton; Output short circuit protecton
RS232(standard) : USB and SNMP card (opton)Graphic analyze: Switch On/Off UPS system : Montor UPS working status:
History record and event log
LCD+LED
SYSTEM OPERATING ENVIRNOMENT
208VAC/210VAC/220VAC/230VAC/240VAC Seng Available
Based On baery CapacityThree-Stage Charging
Standard model: Dimensions
(WxDxH) mm
Packing Dimension
(WxDxH) mm
Net/Gross Weight(Kg)
440x640x88(with internal baery)
440x565x132 (UPS)
440x565x132 (BAT)
530x710x170(with internal baery)
535x660x215(UPS)
546x676x266(BAT)
19/21.5(UPS) 52/54.5(BAT)
440 x 468 x 88 440 x 565 x 132
580x590x200 535x660x215
19/21.5
0-40 °C
25%°C - 55°C
www.apec.sa.com
P.O. Box 3411, Al Khobar 31952 - Saudi Arabia
Tel: +966 13 890 1261 Fax: +966 13 865 0066
E-mail: [email protected]
ARABIAN POWER ELECTRONICS COMPANY
D G C
a t . 0
8 . 1
3
Note: i) All specificaons subject to change without noce
ii) Custom-made specificaons are acceptable
Overcurrent Protecon
AC Input
Modem/Tel/Fax
DC Input
Outlet
FAN
RS232
SNMP/USB/AS400(Oponal)
1
1
2
3
4
5
6
7
8
Rear Panel