digital voltage stabilisers - mainor · pdf filemini avr single-phase voltage stabilisers from...

34
AVR DIGITAL VOLTAGE STABILISERS 2009 2009 2009

Upload: leminh

Post on 15-Mar-2018

249 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 1

AVR DIGITAL VOLTAGE STABILISERS

200920092009

Page 2: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 2

Founded in 1950, ITALFARAD SpA is specialised in manufacturing electrical

capacitors for A.C. general applications, such as lighting, motor run, Power Factor

Correction.

ITALFARAD also produces L.V. fixed and automatic P.F.C. equipment and voltage

stabilisers .

In 1993, ITALFARAD was awarded a Quality System Certificate according to UNI EN

ISO 9001 Standards, this certificate has been updated to UNI EN ISO 9001:2000.

ITALFARAD have succeeded in obtaining an important share of the world market and

exports to more than 70 Countries all over the world.

Page 3: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 3

VOLTAGE STABILISERS

Index Page

INTRODUCTION AND TECHNOLOGY 4

ELECTRODYNAMIC VOLTAGE STABILISERS WITH DIGITAL CONTROL 8

MINI AVR Single-phase voltage stabilisers from 0.3kVA up to 150kVA 10

MIDI AVR Three-phase voltage stabilisers from 2kVA up to 450kVA 14

MAXI AVR Three-phase voltage stabilisers from 50kVA up to 3150kVA 22

DIMENSIONS 27

DIAGRAMS 28

ACCESSORIES 32

This document is property of ITALFARAD SpA: it is compulsory to notify the Company Head Office and ask for authorisation before any release or reproduction. ITALFARAD SpA shall not be held liable or responsible in any way whatsoever for unauthorised copies, alterations or additions made to the text or to the illustrations of this document. Any modification concerning the Company logo, symbols of the certifications, nomenclature and official data is strictly prohibited. For improvement purposes, the Company reserves the right to modify the products described in this catalogue at any moment without prior notice.

Page 4: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 4

INTRODUCTION & TECHNOLOGY

The increase of voltage sensitive equipment has determined a continuous request for means able to guarantee the

supply of steady voltage independently from mains variation.

Loss of data, defective products, security failure, machinery faults and inaccurate information are only a few examples of

possible problems due to unstable supply.

The voltage stabiliser has proved to be an efficient answer in order to prevent from potential damages due to input

voltage fluctuation.

Installing a voltage stabiliser is often the solution to ensure continuity and quality of production.

A typical voltage stabiliser is able to respond to changes in voltage level called sags (voltage drops) and surges

(voltage peaks) on the input line.

Sags might be due to undersized distribution lines, connection of large loads to the network, ground faults.

Surges might be generated by disconnection of large loads, increased voltage at the generating plant, atmospheric

events.

The duration of such phenomena depends on the cause and is not easily predictable.

Sags are generally more common, especially where the distribution is not wide and efficient.

Other disturbances like spikes, transients, high frequency noise and harmonic distortion have to be treated with the

addition of specific filtering systems.

The good functioning of the majority of electrical and electronic equipment depends on the supply voltage correctness

and steadiness. Nowadays, many industrial and private users are subject to long-lasting fluctuations that can be

inconvenient or even dangerous.

Office machines

Broadcasting systems

Food, Beverage and

Packaging

Private Houses with

High Installed

Industrial Plants

Test equipment

Electronically Driven

Machines

Computers

Laser cutting machines

VOLTAGEVOLTAGE

STABILISERSSTABILISERS

IMPORTANCE OF VOLTAGE STABILISERSIMPORTANCE OF VOLTAGE STABILISERS

USE OF A VOLTAGE STABILISERUSE OF A VOLTAGE STABILISER

Page 5: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 5

The kind of utilisation described above pushes towards the choice of a voltage stabiliser instead of a UPS in order to

have:

Lower costs

High power availability

Wider input variation ranges

Overload capacity up to 2In

Inrush current capacity up to 10In

Higher reliability and ruggedness

Absence of batteries and consequent easy storage and handling

Negligible harmonic distortion because of the use of electronic components only in auxiliary circuits

Service continuity

Generally speaking, a stabiliser can be chosen on the basis of a few elements:

1. NUMBER OF PHASES

2. RATED VOLTAGE

3. INPUT VARIATION RANGE

4. TYPE OF REGULATION

5. RATED POWER

6. INSTALLATION

Once these six points are established, any other optional request can be dealt with separately.

1. Number of phases

The stabiliser number of phases depends on the type of load:

1-phase load: 1-phase stabiliser

Combination of several 1-phase loads or 3-phase loads: 3-phase stabiliser or a 1-phase stabiliser on each load.

3-phase load: 3-phase stabiliser

2. Rated voltage

Always detect the nominal voltages that are supposed to be present at the input and at the output of the stabiliser. In

case of 3-phase systems, provide with the line-to-line voltage value.

Since there are different nominal voltages around the world, do not assume that YOUR nominal voltage is

automatically known.

The standard voltage stabiliser can operate with the following rated voltage:

COMPARISON WITH A UPS SYSTEMCOMPARISON WITH A UPS SYSTEM

CHOICE OF A VOLTAGE STABILISERSCHOICE OF A VOLTAGE STABILISERS

by adjusting the control card

VOLTAGE STABILISER

415 V ±15%

(353-415-477)

415 V ± 0.5%

by adjusting the control card

380 V ± 0.5%

standard setting

400 V ± 0.5%

VOLTAGE STABILISER

380 V ±15%

(323-380-437)

RATED VOLTAGE

400V ±15%

(340-400-460)

VOLTAGE STABILISER

INTRODUCTION & TECHNOLOGY

Page 6: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 6

3. Input variation range

It‟s a key information for the choice and the design of the stabiliser.

Establish the nature of the oscillation of the input voltage and always keep a safety margin on such percentage. The

standard production can include stabilisers for symmetrical and asymmetrical input variation range. If the input voltage

variation goes beyond the rated range, the difference between real and rated variation is transferred onto the output.

OUTPUT VOLTAGE WAVEFORM

INPUT VOLTAGE WAVEFORM

4. Type of regulation

Three-phase voltage regulation can be performed in two different ways:

independently on each phase. Used for 3-phase loads and 1-phase loads with up to 100% unbalance and

unbalanced input voltage. In this configuration the voltage stabiliser requires the neutral wire.

averaged on the three phases. Used for 3-phase loads and 2-phase loads with maximum 50% unbalance and

balanced input voltage. In this configuration the voltage stabiliser does not require the neutral wire.

1-ph. load

1-ph. load

1-ph. load

2-ph. load

3-ph. load

W2

OUTPUT

U2 V2 N

W1

STABILISER

INPUT

U1 V1 N

OUTPUT

V2U2 W2

3-ph. load

2-ph. load

STABILISER

INPUT

V1U1 W1

5. Rated power

Establish the power required to supply your load system and allow for an extra safety margin for possible future

extensions.

A voltage stabiliser power is expressed in kVA (kilovoltamperes), whilst load power is often given in kW (kilowatts). The

link between these two measuring units is provided by the power factor (cosØ):

Remember that: kVA = load voltage x load current (single-phase) kVA = x phase to phase load voltage x load current (three-phase) If the power factor or the load power in kW cannot be easily established, measure the absorbed currents in

order to allow for a correct design of the stabiliser.

All the stabilisers are designed for the maximum input current.

cos

kW kVA

INTRODUCTION & TECHNOLOGY

Page 7: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 7

In order to provide with the best machine, it is recommended to inform about the installation condition. It is necessary to

know:

IP protection degree

Indoor or outdoor installation

Installation site altitude and climatic properties

Ambient temperature

Possible environmental hazards such aggressive atmosphere, exposure to chemical components and so on.

The production covers an extensive range of standard types:

Single-phase electrodynamic line from 0.3 kVA up to 150kVA (MINI AVR)

Three-phase electrodynamic line from 2 kVA up to 450kVA (MIDI AVR Y, MIDI AVR A)

Three-phase electrodynamic line from 50 kVA up to 4000kVA (MAXI AVR)

Choosing an electromechanical voltage stabiliser means:

Smooth and reliable regulation

Up to ±0.5% output accuracy (electrodynamic stabilisers), up to ±0.3% output accuracy (static stabilisers)

Admitted inrush current up to 10In

Negligible introduction of harmonic distortion

High efficiency

High ratings

Access to the equipment can only be obtained by opening or dismantling the metal enclosure using appropriate tools:

the protection against direct contact is inherently obtained and complies with IP21 degree.

Inside the equipment there are dangerous voltages.

Access to the components for installation, setting, inspection and maintenance must be granted only to

qualified personnel in charge of it.

The stabiliser must not function without the earth connection.

A circuit breaker should be installed upstream the equipment in accordance with the requirements of IEC364 (CEI 64-

8) “Electrical installations”.

The stabiliser must be used exclusively on the purpose for which it has been designed and built.

Any other utilisation has to be considered as inappropriate and therefore dangerous.

The Company will not to be held liable for possible damages to people, animals and belongings due to incorrect use or

installation.

InstallationInstallation

Available RangeAvailable Range

AdvantagesAdvantages

Personal SafetyPersonal Safety

INTRODUCTION & TECHNOLOGY

Page 8: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 8

ELECTRODYNAMIC STABILIZERS

WITH DIGITAL CONTROL

The stabilising system is designed to operate with rated voltage in accordance with IEC 38 and is expected to be

connected between main power supply and load.

The purpose is to supply the loads a stabilised voltage having an input voltage variable with respect to the rated value.

The highest input current is obtained with the minimum rated voltage; as the output voltage is stabilised within a close

range, the output current is considered to be constant.

Stabilisation takes place on the „rms‟ value of the voltage and is not affected by harmonic distortion in the mains.

The stabiliser can operate with a load variation range from 0 to 100%; the response time depends on the input voltage

percentage variation and on the type of design (indicatively, it can vary between 8 and 80msec/V).

The voltage stabiliser is not affected by the load power factor and since regulation is performed without chopping the

voltage sine wave, neither appreciable harmonic distortion nor phase displacement is introduced on the downstream

line.

The equipment is housed in a metal enclosure with RAL7035 finish and IP21 protection class. Depending on the type,

the stabilisers can be air-cooled (natural or aided convection) or oil-cooled.

When the input variation percentage is –25%, -30% or –45% the unit is provided with a special component (super

capacitor) able to adjust automatically the output voltage to the minimum value after a failure in the mains.

Such device prevents from possible damages to the user due to the potentially high voltages that might occur when the

rated supply is re-established.

The main components of the stabiliser are:

1. Buck/boost transformer

The buck/boost transformer is a standard dry-type transformer; the secondary winding is connected in series to the

mains while the primary winding is supplied by the voltage regulator.

2. Voltage regulator

The voltage regulator consists of an autotransformer with continuously variable transformer ratio. The voltage intake

varies depending on the contact position; therefore the voltage supplied to the transformer primary winding also

varies. The voltage across the regulator contacts (and consequently that on the secondary winding of the buck/boost

transformer) is either in phase or in opposition to the supply voltage, and it is therefore added or subtracted to the

supply voltage, thus compensating its variations.

3. Auxiliary circuit with microprocessor

The DSP microprocessor-based control circuit (specific for fully digital drives) compares the output voltage value to

the adjusted one. When the percentage variation is too high, the control drives the voltage regulator gear motor. By

doing so the regulator rollers change their position thus varying the voltage drawn and supplied to the buck/boost

transformer primary winding.

All the described activities are performed automatically.

The voltage stabiliser can operate with input and output voltages different from the rated voltage. Such setting can be

performed at the factory or at the Customer's premises by adjusting the dip-switch mounted on the electronic control

card within the allowed range and according to the instructions described in the handbook. In the MAXI AVR stabilisers,

such setting can be performed by communicating directly with the microprocessor from a PC (through an RS232

interface). If the rated output voltage differs from the input voltage, a suitable step-up or step-down autotransformer

should be installed in the equipment. However the voltage stabiliser can work just as well after accepting that the range

of input voltage variation is not symmetric.

Description of the unitDescription of the unit

Main ComponentsMain Components

Page 9: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 9

Output ±0.5%

Input

Voltage regulator

Buck-boost Transformer

N

Standard models: ±15%, ±20%, ±25%, ±30% +15%/-25%, +15%/-35%, +15%/-45%

A “buck-boost” transformer is connected between input and output. The voltage on the primary side is determined by the position of the rollers on the regulator

With rollers and no sliding (consuming) parts!

Toroidal and Column RegulatorToroidal and Column Regulator

OPERATING PRINCIPLE

Page 10: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 10

The MINI AVR voltage stabiliser covers the power rating range between 0.3kVA and 150kVA and allows for the choice

of several input voltage variation percentages within a broad range (from +30% up to -45%).

For ±15%, ±20%, ±25 and ±30% range the change of stabilisation is obtained through different internal connections.

Fuses or automatic circuit breakers are provided on the regulation circuit to protect against overload and short circuit on

the voltage regulator. The auxiliary circuit is protected by fuses.

Where provided, a buzzer is activated whenever an overload condition occurs.

In the lower rating types, a pilot light that indicates when the stabiliser is connected to the mains in mounted on the front.

For higher ratings, the stabiliser is provided with a multi-task digital network analyser. Such instrument is able to

provide with information regarding the status of the line downstream the voltage stabiliser such as phase and linked

voltages, current, power factor, active power, apparent power, reactive power, etc.

The logic control is based on a microprocessor.

FREQUENCY 47/65Hz

ADMITTED LOAD VARIATION from 0 to 100%

MAINS WAVEFORM DISTORTION INCREMENT < 0.2%

COOLING Natural Air – Aided Air

AMBIENT TEMPERATURE -15/+45 °C

STORAGE TEMPERATURE -25/+60°C

RELATIVE HUMIDITY 95%

ADMITTED OVERLOAD 200% 2min

COLOUR RAL 7035

PROTECTION IP 21

INSTALLATION Indoor

Any other variation range not mentioned in the table above can be dealt with on request

±15% ±20% ±25% ±30% -25/+15% -35/+15% -45/+15%

1 0.7 0.5 0.3 0.7 0.5 0.3

2.5 2 1.5 1 2 1.5 1

5 4 3 2 4 3 2

7 5 4 3 5 4 3

10 7 5 4 7 5 4

15 10 7 5 10 7 5

20 15 10 7 15 10 7

25 20 15 10 20 15 10

35 25 20 15 25 20 15

45 35 25 20 35 25 20

60 45 35 25 45 35 25

75 60 45 35 60 45 35

100 75 60 45 75 60 45

150 100 75 60 100 75 60

Mini AVR Standard FeaturesMini AVR Standard Features

Rating in Relation to the Input Variation PercentageRating in Relation to the Input Variation Percentage

MINIMINI

AVRAVR MINI AVR

Page 11: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 11

MINIMINI

AVRAVR MINI AVR

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±15% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MINI AVR 111-15 1 230 5 230 4 >94 16 12 16

MINI AVR 113-15 2.5 230 12.5 230 11 >96 16 12 23

MINI AVR 115-15 5 230 25 230 22 >97 16 12 28

MINI AVR 117-15 7 230 35 230 31 >98 16 13 41

MINI AVR 119-15 10 230 50 230 44 >98 16 13 47

MINI AVR 121-15 15 230 75 230 65 >98 16 13 55

MINI AVR 123-15 20 230 102 230 87 >98 18 23 130

MINI AVR 125-15 25 230 128 230 109 >98 18 23 140

MINI AVR 127-15 35 230 179 230 152 >98 18 23 150

MINI AVR 129-15 45 230 230 230 196 >98 18 23 200

MINI AVR 128-15 60 230 307 230 261 >98 18 24 320

MINI AVR 131-15 75 230 384 230 326 >98 18 24 390

MINI AVR 133-15 100 230 511 230 435 >98 18 25 550

MINI AVR 135-15 150 230 767 230 652 >98 18 25 650

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±20% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MINI AVR 111-20 0.7 230 3.8 230 3 >94 12 12 16

MINI AVR 113-20 2 230 11 230 9 >96 12 12 23

MINI AVR 115-20 4 230 22 230 17.5 >97 12 12 28

MINI AVR 117-20 5 230 28 230 22 >98 12 13 41

MINI AVR 119-20 7 230 39 230 31 >98 12 13 47

MINI AVR 121-20 10 230 54 230 44 >98 12 13 55

MINI AVR 123-20 15 230 81 230 65 >98 14 23 130

MINI AVR 125-20 20 230 109 230 87 >98 14 23 140

MINI AVR 127-20 25 230 136 230 109 >98 14 23 150

MINI AVR 129-20 35 230 190 230 152 >98 14 23 200

MINI AVR 128-20 45 230 244 230 196 >98 14 24 320

MINI AVR 131-20 60 230 326 230 261 >98 14 24 390

MINI AVR 133-20 75 230 407 230 326 >98 14 25 550

MINI AVR 135-20 100 230 544 230 435 >98 14 25 650

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±25% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MINI AVR 111-25 0.5 230 3 230 2.2 >96 10 12 16

MINI AVR 113-25 1.5 230 9 230 6.5 >97 10 12 23

MINI AVR 115-25 3 230 18 230 13 >98 10 12 28

MINI AVR 117-25 4 230 23 230 17.5 >98 10 13 41

MINI AVR 119-25 5 230 29 230 22 >98 10 13 47

MINI AVR 121-25 7 230 41 230 31 >98 10 13 55

MINI AVR 123-25 10 230 57 230 43 >98 11 23 130

MINI AVR 125-25 15 230 87 230 65 >98 11 23 140

MINI AVR 127-25 20 230 116 230 87 >98 11 23 150

MINI AVR 128-25 25 230 144 230 108 >98 11 23 200

MINI AVR 129-25 35 230 203 230 152 >98 11 24 320

MINI AVR 131-25 45 230 261 230 196 >98 11 24 390

MINI AVR 133-25 60 230 347 230 261 >98 11 25 550

MINI AVR 135-25 75 230 435 230 326 >98 11 25 650

Mini AVR ±15% Automatic SingleMini AVR ±15% Automatic Single--Phase Voltage StabiliserPhase Voltage Stabiliser

Mini AVR ±20% Automatic SingleMini AVR ±20% Automatic Single--Phase Voltage StabiliserPhase Voltage Stabiliser

Mini AVR ±25% Automatic SingleMini AVR ±25% Automatic Single--Phase Voltage StabiliserPhase Voltage Stabiliser

Page 12: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 12

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±30% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MINI AVR 111-30 0.3 230 2 230 1.3 >96 8 12 16

MINI AVR 113-30 1 230 6.2 230 4 >97 8 12 23

MINI AVR 115-30 2 230 12.4 230 9 >98 8 12 28

MINI AVR 117-30 3 230 18.6 230 13.5 >98 8 13 41

MINI AVR 119-30 4 230 24.8 230 18 >98 8 13 47

MINI AVR 121-30 5 230 31 230 22 >98 8 13 55

MINI AVR 123-30 7 230 43 230 30 >98 9 23 130

MINI AVR 125-30 10 230 61 230 43 >98 9 23 140

MINI AVR 127-30 15 230 93 230 65 >98 9 23 150

MINI AVR 128-30 20 230 124 230 87 >98 9 23 200

MINI AVR 129-30 25 230 156 230 109 >98 9 24 320

MINI AVR 131-30 35 230 217 230 152 >98 9 24 390

MINI AVR 133-30 45 230 279 230 195 >98 9 25 550

MINI AVR 135-30 60 230 372 230 261 >98 9 25 650

TYPE RATED POWER [kVA]

INPUT VOLTAGE

+15%

-25% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MINI AVR 111-25/15 0.7 230 4 230 3 >95 12 12 17

MINI AVR 113-25/15 2 230 11 230 8 >96 12 12 24

MINI AVR 115-25/15 4 230 23

230 17 >97 12 12 29

MINI AVR 117-25/15 5 230 29 230 22 >97 12 13 42

MINI AVR 119-25/15 7 230 40 230 30 >97 12 13 48

MINI AVR 121-25/15 10 230 58 230 43 >97

12 13 56

MINI AVR 123-25/15 15 230 87 230 65 >97 14 23 140

MINI AVR 125-25/15 20 230 116 230 87 >97 14 23 150

MINI AVR 127-25/15 25 230 145 230 108 >97 14 23 160

MINI AVR 128-25/15 35 230 203 230 152 >97 14 24 210

MINI AVR 129-25/15 45 230 261 230 195 >97 14 24 330

MINI AVR 131-25/15 60 230 348 230 261 >97 14 24 400

MINI AVR 133-25/15 75 230 435 230 326 >97 14 25 500

MINI AVR 135-25/15 100 230 580 230 435 >97 14 25 660

TYPE RATED POWER [kVA]

INPUT VOLTAGE

+15%

-35% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MINI AVR 111-35/15 0.5 230 3 230 2 >95 10 12 17

MINI AVR 113-35/15 1.5 230 10 230 6 >96 10 12 24

MINI AVR 115-35/15 3 230 20 230 13 >97 10 12 29

MINI AVR 117-35/15 4 230 27 230 17 >97 10 13 42

MINI AVR 119-35/15 5 230 33 230 22 >97 10 13 48

MINI AVR 121-35/15 7 230 47 230 30 >97 11 13 56

MINI AVR 123-35/15 10 230 67 230 43 >97 11 23 140

MINI AVR 125-35/15 15 230 100 230 65 >97 11 23 150

MINI AVR 127-35/15 20 230 134 230 87 >97 11 23 160

MINI AVR 128-35/15 25 230 167 230 108 >97 11 24 210

MINI AVR 129-35/15 35 230 234 230 152 >97 11 24 330

MINI AVR 131-35/15 45 230 301 230 195 >97 11 24 400

MINI AVR 133-35/15 60 230

401 230 261 >97 11 25 500

MINI AVR 135-35/15 75 230 501 230 326 >97 11 25 660

Mini AVR ±30% Automatic SingleMini AVR ±30% Automatic Single--Phase Voltage StabiliserPhase Voltage Stabiliser

Mini AVR Mini AVR --25%/+15% Automatic Single25%/+15% Automatic Single--Phase Voltage StabiliserPhase Voltage Stabiliser

Mini AVR Mini AVR ––35%/+15% Automatic Single35%/+15% Automatic Single--Phase Voltage StabiliserPhase Voltage Stabiliser

MINIMINI

AVRAVR MINI AVR

Page 13: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 13

TYPE RATED POWER [kVA]

INPUT VOLTAGE

+15%

-45% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MINI AVR 111-45/15 0.3 230 2.3 230 1.3 >95 8 12 17

MINI AVR 113-45/15 1 230 8 230 4 >96 8 12 24

MINI AVR 115-45/15 2 230 16 230 8 >97 8 12 29

MINI AVR 117-45/15 3 230 24 230 13 >97 8 13 42

MINI AVR 119-45/15 4 230 31 230 17 >97 8 13 48

MINI AVR 121-45/15 5 230 39 230 22 >97 9 13 56

MINI AVR 123-45/15 7 230 55 230 30 >97 9 23 140

MINI AVR 125-45/15 10 230 79 230 43 >97 9 23 150

MINI AVR 127-45/15 15 230 118 230 65 >97 9 23 160

MINI AVR 128-45/15 20 230 158 230 87 >97 9 24 210

MINI AVR 129-45/15 25 230 197 230 108 >97 9 24 330

MINI AVR 131-45/15 35 230 276 230 152 >97 9 24 400

MINI AVR 133-45/15 45 230 355 230 195 >97 9 25 500

MINI AVR 135-45/15 60 230 474 230 261 >97 9 25 660

The technical data in the above tables are subject to change by the Company either for internal reasons or because of a specific request from the Customer

Input output voltage 50Hz: 220/240V - Input output voltage 60Hz: 208/240V

Mini AVR Mini AVR ––45%/+15% Automatic Single45%/+15% Automatic Single--Phase Voltage StabiliserPhase Voltage Stabiliser

MINIMINI

AVRAVR MINI AVR

Page 14: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 14

The MIDI AVR voltage stabiliser covers the power rating range between 2kVA and 450kVA and allows for the choice of

several input voltage variation percentages within a broad range (from +30% up to -45%).

For ±15% and ±20% range, the change of stabilisation is obtained through different internal connections.

The regulation in the MIDI AVR Y stabilisers is independent on each phase. These stabilisers are used with three-phase

loads and single-phase loads with 100% unbalance and unbalanced input rated voltages. In this configuration the

voltage stabiliser requires the neutral wire.

The regulation in the MIDI AVR A stabilisers is performed on the average three-phase voltage. These stabilisers are

used with three-phase loads and two-phase loads with 50% maximum unbalance and balanced input rated voltages. In

this configuration the voltage stabiliser does not require the neutral wire.

Fuses or automatic circuit breakers are provided on the regulation circuit to protect against overload and short circuit on

the voltage regulator.

The auxiliary circuit is protected by fuses.

Where provided, a buzzer is activated whenever an overload condition occurs.

The measuring instrumentation for the MIDI AVR stabilisers mounted on the cabinet door and consists of a multi-task

digital network analyser. Such instrument is able to provide with information regarding the status of the line

downstream the voltage stabiliser such as phase and linked voltages, current, power factor, active power, apparent

power, reactive power, etc.

The logic control is based on a microprocessor.

MIDIMIDI

AVRAVR MIDI AVR A & Y

Page 15: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 15

FREQUENCY 47/65Hz

ADMITTED LOAD VARIATION from 0 to 100%

ADMITTED LOAD UNBALANCE up to 50%

MAINS WAVEFORM DISTORTION INCREMENT < 0.2%

COOLING Aided air

AMBIENT TEMPERATURE -15/+45 °C

STORAGE TEMPERATURE -25/+60°C

RELATIVE HUMIDITY 95%

ADMITTED OVERLOAD 200% 2min

COLOUR RAL 7035

PROTECTION IP 21

INSTALLATION Indoor

Any other variation range not mentioned in the table above can be dealt with on request.

±15% ±20% ±25% ±30% -25/+15% -35/+15% -45/+15%

5 4 3 2 4 3 2

10 7 4 3 7 4 3

15 10 7 4 10 7 4

20 15 10 7 15 10 7

30 20 15 10 20 15 10

45 30 20 15 30 20 15

60 45 30 20 45 30 20

75 60 45 30 60 45 30

105 75 60 45 75 60 45

135 105 75 60 105 75 60

175 135 105 75 135 105 75

230 175 135 105 175 135 105

300 230 175 135 230 175 135

450 300 230 175 300 230 175

Midi AVR A Standard FeaturesMidi AVR A Standard Features

Rating in Relation the Input Variation PercentageRating in Relation the Input Variation Percentage

MIDIMIDI

AVRAVR MIDI AVR A & Y

Page 16: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 16

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±15% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MIDI AVR 333-15 5 400 8 400 7 >95 16 22 82

MIDI AVR 335-15 10 400 16 400 14 >96 16 22 82

MIDI AVR 337-15 15 400 25 400 21 >97 16 22 109

MIDI AVR 339-15 20 400 33 400 28 >98 16 23 145

MIDI AVR 341-15 30 400 50 400 43 >98 16 23 170

MIDI AVR 343-15 45 400 76 400 65 >98 16 23 190

MIDI AVR 345-15 60 400 102 400 87 >98 18 24 320

MIDI AVR 347-15 75 400 126 400 108 >98 18 24 380

MIDI AVR 349-15 105 400 176 400 152 >98 18 25 460

MIDI AVR 351-15 135 400 229 400 195 >98 18 25 507

MIDI AVR 353-15 175 400 297 400 253 >98 18 25 850

MIDI AVR 355-15 230 400 390 400 332 >98 18 26 930

MIDI AVR 357-15 300 400 509 400 433 >98 18 26 760

MIDI AVR 359-15 450 400 765 400 650 >98 18 50 1200

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±20% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MIDI AVR 333-20 4 400 7 400 6 >95 12 22 82

MIDI AVR 335-20 7 400 13 400 10 >96 12 22 82

MIDI AVR 337-20 10 400 17 400 14 >97 12 22 109

MIDI AVR 339-20 15 400 26 400 21 >98 12 23 145

MIDI AVR 341-20 20 400 36 400 29 >98 12 23 170

MIDI AVR 343-20 30 400 54 400 43 >98 12 23 190

MIDI AVR 345-20 45 400 81 400 65 >98 14 24 320

MIDI AVR 347-20 60 400 107 400 86 >98 14 24 380

MIDI AVR 349-20 75 400 135 400 108 >98 14 25 460

MIDI AVR 351-20 105 400 187 400 150 >98 14 25 507

MIDI AVR 353-20 135 400 244 400 195 >98 14 25 850

MIDI AVR 355-20 175 400 316 400 253 >98 14 26 930

MIDI AVR 357-20 230 400 415 400 332 >98 14 26 760

MIDI AVR 359-20 300 400 542 400 433 >98 14 50 1200

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±25% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MIDI AVR 333-25 3 400 6 400 4 >96 10 22 82

MIDI AVR 335-25 4 400 8 400 6 >97 10 22 82

MIDI AVR 337-25 7 400 13 400 10 >98 10 22 109

MIDI AVR 339-25 10 400 19 400 14 >98 10 23 145

MIDI AVR 341-25 15 400 29 400 22 >98 10 23 170

MIDI AVR 343-25 20 400 38 400 29 >98 10 23 190

MIDI AVR 345-25 30 400 57 400 43 >98 11 24 320

MIDI AVR 347-25 45 400 86 400 65 >98 11 24 380

MIDI AVR 349-25 60 400 115 400 86 >98 11 25 460

MIDI AVR 351-25 75 400 144 400 108 >98 11 25 507

MIDI AVR 353-25 105 400 203 400 152 >98 11 25 850

MIDI AVR 355-25 135 400 260 400 195 >98 11 26 930

MIDI AVR 357-25 175 400 337 400 253 >98 11 26 760

MIDI AVR 359-25 230 400 443 400 332 >98 14 50 1200

Midi AVR A ±15% Digital ThreeMidi AVR A ±15% Digital Three--Phase Voltage StabiliserPhase Voltage Stabiliser

Midi AVR A ±20% Digital ThreeMidi AVR A ±20% Digital Three--Phase Voltage StabiliserPhase Voltage Stabiliser

Midi AVR A ±25% Digital ThreeMidi AVR A ±25% Digital Three--Phase Voltage StabiliserPhase Voltage Stabiliser

MIDIMIDI

AVRAVR MIDI AVR A & Y

Page 17: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 17

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±30% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MIDI AVR 333-30 2 400 4 400 3 >96 8 22 82

MIDI AVR 335-30 3 400 6 400 4 >96 8 22 82

MIDI AVR 337-30 4 400 8 400 6 >97 8 22 109

MIDI AVR 339-30 7 400 14 400 10 >98 8 23 145

MIDI AVR 341-30 10 400 20 400 14 >98 8 23 170

MIDI AVR 343-30 15 400 31 400 22 >98 8 23 190

MIDI AVR 345-30 20 400 41 400 29 >98 9 24 320

MIDI AVR 347-30 30 400 61 400 43 >98 9 24 380

MIDI AVR 349-30 45 400 93 400 65 >98 9 25 460

MIDI AVR 351-30 60 400 123 400 87 >98 9 25 507

MIDI AVR 353-30 75 400 154 400 108 >98 9 25 850

MIDI AVR 355-30 105 400 217 400 152 >98 9 26 930

MIDI AVR 357-30 135 400 278 400 195 >98 9 26 760

MIDI AVR 359-30 175 400 361 400 253 >98 9 50 1200

TYPE RATED POWER [kVA]

INPUT VOLTAGE

+15%

-25% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MIDI AVR 333-25/15 4 400 8 400 6 >94 12 22 92

MIDI AVR 335-25/15 7 400 13 400 10 >95 12 22 92

MIDI AVR 337-25/15 10 400 19 400 14 >96 12 22 119

MIDI AVR 339-25/15 15 400 27 400 22 >97 12 23 155

MIDI AVR 341-25/15 20 400 39 400 29 >97 12 23 180

MIDI AVR 343-25/15 30 400 57 400 43 >97 12 23 210

MIDI AVR 345-25/15 45 400 87 400 65 >97 14 24 340

MIDI AVR 347-25/15 60 400 116 400 87 >97 14 24 400

MIDI AVR 349-25/15 75 400 144 400 108 >97 14 25 480

MIDI AVR 351-25/15 105 400 202 400 152 >97 14 25 527

MIDI AVR 353-25/15 135 400 260 400 195 >97 14 25 850

MIDI AVR 355-25/15 175 400 337 400 253 >97 14 26 930

MIDI AVR 357-25/15 230 400 443 400 332 >97 14 26 1100

MIDI AVR 359-25/15 300 400 578 400 433 >97 14 50 1400

TYPE RATED POWER [kVA]

INPUT VOLTAGE

+15%

-35% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MIDI AVR 333-35/15 3 400 7 400 4 >94 10 22 92

MIDI AVR 335-35/15 4 400 9 400 6 >95 10 22 92

MIDI AVR 337-35/15 7 400 15 400 10 >96 10 22 119

MIDI AVR 339-35/15 10 400 21 400 14 >97 10 23 155

MIDI AVR 341-35/15 15 400 33 400 22 >97 10 23 180

MIDI AVR 343-35/15 20 400 44 400 29 >97 10 23 210

MIDI AVR 345-35/15 30 400 66 400 43 >97 11 24 340

MIDI AVR 347-35/15 45 400 100 400 65 >97 11 24 400

MIDI AVR 349-35/15 60 400 133 400 87 >97 11 25 480

MIDI AVR 351-35/15 75 400 166 400 108 >97 11 25 527

MIDI AVR 353-35/15 105 400 234 400 152 >97 11 25 850

MIDI AVR 355-35/15 135 400 300 400 195 >97 11 26 930

MIDI AVR 357-35/15 175 400 389 400 253 >97 11 26 1100

MIDI AVR 359-35/15 230 400 511 400 332 >97 11 50 1400

Midi AVR A ±30% Digital ThreeMidi AVR A ±30% Digital Three--Phase Voltage StabiliserPhase Voltage Stabiliser

Midi AVR A Midi AVR A ––25%/+15% Digital Three25%/+15% Digital Three--Phase Voltage StabiliserPhase Voltage Stabiliser

Midi AVR A Midi AVR A ––35%/+15% Digital Three35%/+15% Digital Three--Phase Voltage StabiliserPhase Voltage Stabiliser

MIDIMIDI

AVRAVR MIDI AVR A & Y

Page 18: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 18

TYPE RATED POWER [kVA]

INPUT VOLTAGE

+15%

-45% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MIDI AVR 333-45/15 2 400 5 400 3 >94 8 22 92

MIDI AVR 335-45/15 3 400 8 400 4 >95 8 22 92

MIDI AVR 337-45/15 4 400 10 400 6 >95 8 22 119

MIDI AVR 339-45/15 7 400 18 400 10 >96 8 23 155

MIDI AVR 341-45/15 10 400 25 400 14 >97 8 23 180

MIDI AVR 343-45/15 15 400 39 400 22 >97 8 23 210

MIDI AVR 345-45/15 20 400 52 400 29 >97 9 24 340

MIDI AVR 347-45/15 30 400 79 400 43 >97 9 24 400

MIDI AVR 349-45/15 45 400 118 400 65 >97 9 25 480

MIDI AVR 351-45/15 60 400 158 400 87 >97 9 25 527

MIDI AVR 353-45/15 75 400 196 400 108 >97 9 25 850

MIDI AVR 355-45/15 105 400 276 400 152 >97 9 26 930

MIDI AVR 357-45/15 135 400 354 400 195 >97 9 26 1100

MIDI AVR 359-45/15 175 400 460 400 253 >97 9 50 1400

FREQUENCY 47/65Hz

ADMITTED LOAD VARIATION from 0 to 100%

ADMITTED LOAD UNBALANCE up to 100%

MAINS WAVEFORM DISTORTION INCREMENT < 0.2%

COOLING Aided Air

AMBIENT TEMPERATURE -15/+45 °C

STORAGE TEMPERATURE -25/+60°C

RELATIVE HUMIDITY 95%

ADMITTED OVERLOAD 200% 2min

COLOUR RAL 7035

PROTECTION IP 21

INSTALLATION Indoor

Any other variation range not mentioned in the table above can be dealt with on request.

±15% ±20% ±25% ±30% -25/+15% -35/+15% -45/+15%

5 4 3 2 4 3 2

10 7 4 3 7 4 3

15 10 7 4 10 7 4

20 15 10 7 15 10 7

30 20 15 10 20 15 10

45 30 20 15 30 20 15

60 45 30 20 45 30 20

75 60 45 30 60 45 30

105 75 60 45 75 60 45

135 105 75 60 105 75 60

175 135 105 75 135 105 75

230 175 135 105 175 135 105

300 230 175 135 230 175 135

450 300 230 175 300 230 175

Midi AVR A Midi AVR A ––45%/+15% Digital Three45%/+15% Digital Three--Phase Voltage StabiliserPhase Voltage Stabiliser

Midi AVR Y Standards FeaturesMidi AVR Y Standards Features

Rating in Relation to the Input Variation PercentageRating in Relation to the Input Variation Percentage

MIDIMIDI

AVRAVR MIDI AVR A & Y

Page 19: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 19

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±15% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MIDI AVR 444-15 5 400 8 400 7 >95 16 22 90

MIDI AVR 446-15 10 400 16 400 14 >96 16 22 90

MIDI AVR 448-15 15 400 25 400 21 >97 16 22 110

MIDI AVR 450-15 20 400 33 400 28 >98 16 23 155

MIDI AVR 452-15 30 400 50 400 43 >98 16 23 180

MIDI AVR 454-15 45 400 76 400 65 >98 16 23 200

MIDI AVR 456-15 60 400 102 400 87 >98 18 24 380

MIDI AVR 458-15 75 400 126 400 108 >98 18 24 430

MIDI AVR 460-15 105 400 176 400 152 >98 18 25 490

MIDI AVR 462-15 135 400 229 400 195 >98 18 25 580

MIDI AVR 464-15 175 400 297 400 253 >98 18 26 950

MIDI AVR 466-15 230 400 390 400 332 >98 18 26 1030

MIDI AVR 468-15 300 400 509 400 433 >98 18 26 860

MIDI AVR 470-15 450 400 765 400 650 >98 18 50 1300

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±20% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MIDI AVR 444-20 4 400 7 400 6 >95 12 22 90

MIDI AVR 446-20 7 400 13 400 10 >96 12 22 90

MIDI AVR 448-20 10 400 17 400 14 >97 12 22 110

MIDI AVR 450-20 15 400 26 400 21 >98 12 23 155

MIDI AVR 452-20 20 400 36 400 29 >98 12 23 180

MIDI AVR 454-20 30 400 54 400 43 >98 12 23 200

MIDI AVR 456-20 45 400 81 400 65 >98 14 24 380

MIDI AVR 458-20 60 400 107 400 86 >98 14 24 430

MIDI AVR 460-20 75 400 135 400 108 >98 14 25 490

MIDI AVR 462-20 105 400 187 400 150 >98 14 25 580

MIDI AVR 464-20 135 400 244 400 195 >98 14 26 950

MIDI AVR 466-20 175 400 316 400 253 >98 14 26 1030

MIDI AVR 468-20 230 400 415 400 332 >98 14 26 860

MIDI AVR 470-20 300 400 542 400 433 >98 14 50 1300

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±25% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MIDI AVR 444-25 3 400 6 400 4 >96 10 22 90

MIDI AVR 446-25 4 400 8 400 6 >97 10 22 90

MIDI AVR 448-25 7 400 13 400 10 >98 10 22 110

MIDI AVR 450-25 10 400 19 400 14 >98 10 23 155

MIDI AVR 452-25 15 400 29 400 22 >98 10 23 180

MIDI AVR 454-25 20 400 38 400 29 >98 10 23 200

MIDI AVR 456-25 30 400 57 400 43 >98 11 24 380

MIDI AVR 458-25 45 400 86 400 65 >98 11 24 430

MIDI AVR 460-25 60 400 115 400 86 >98 11 25 490

MIDI AVR 462-25 75 400 144 400 108 >98 11 25 580

MIDI AVR 464-25 105 400 203 400 152 >98 11 26 950

MIDI AVR 466-25 135 400 260 400 195 >98 11 26 1030

MIDI AVR 468-25 175 400 337 400 253 >98 11 26 860

MIDI AVR 470-25 230 400 443 400 332 >98 11 50 1300

Midi AVR Y ±15% Digital ThreeMidi AVR Y ±15% Digital Three--Phase Voltage StabilisersPhase Voltage Stabilisers

Midi AVR Y ±20% Digital ThreeMidi AVR Y ±20% Digital Three--Phase Voltage StabilisersPhase Voltage Stabilisers

Midi AVR Y ±25% Digital ThreeMidi AVR Y ±25% Digital Three--Phase Voltage StabilisersPhase Voltage Stabilisers

MIDIMIDI

AVRAVR MIDI AVR A & Y

Page 20: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 20

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±30% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MIDI AVR 444-30 2 400 4 400 3 >96 8 22 90

MIDI AVR 446-30 3 400 6 400 4 >96 8 22 90

MIDI AVR 448-30 4 400 8 400 6 >97 8 22 110

MIDI AVR 450-30 7 400 14 400 10 >98 8 23 155

MIDI AVR 452-30 10 400 20 400 14 >98 8 23 180

MIDI AVR 454-30 15 400 31 400 22 >98 8 23 200

MIDI AVR 456-30 20 400 41 400 29 >98 9 24 380

MIDI AVR 458-30 30 400 61 400 43 >98 9 24 430

MIDI AVR 460-30 45 400 93 400 65 >98 9 25 490

MIDI AVR 462-30 60 400 123 400 87 >98 9 25 580

MIDI AVR 464-30 75 400 154 400 108 >98 9 26 950

MIDI AVR 466-30 105 400 217 400 152 >98 9 26 1030

MIDI AVR 468-30 135 400 278 400 195 >98 9 26 860

MIDI AVR 470-30 175 400 361 400 253 >98 9 50 1300

TYPE RATED POWER [kVA]

INPUT VOLTAGE

+15%

-25% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MIDI AVR 333-25/15 4 400 8 400 6 >94 12 22 100

MIDI AVR 335-25/15 7 400 13 400 10 >95 12 22 100

MIDI AVR 337-25/15 10 400 19 400 14 >96 12 22 120

MIDI AVR 339-25/15 15 400 27 400 22 >97 12 23 165

MIDI AVR 341-25/15 20 400 39 400 29 >97 12 23 190

MIDI AVR 343-25/15 30 400 57 400 43 >97 12 23 220

MIDI AVR 345-25/15 45 400 87 400 65 >97 14 24 400

MIDI AVR 347-25/15 60 400 116 400 87 >97 14 24 450

MIDI AVR 349-25/15 75 400 144 400 108 >97 14 25 510

MIDI AVR 351-25/15 105 400 202 400 152 >97 14 25 600

MIDI AVR 353-25/15 135 400 260 400 195 >97 14 26 950

MIDI AVR 355-25/15 175 400 337 400 253 >97 14 26 1030

MIDI AVR 357-25/15 230 400 443 400 332 >97 14 26 1200

MIDI AVR 359-25/15 300 400 578 400 433 >97 14 50 1500

TYPE RATED POWER [kVA]

INPUT VOLTAGE

+15%

-35% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MIDI AVR 444-35/15 3 400 7 400 4 >94 10 22 100

MIDI AVR 446-35/15 4 400 9 400 6 >95 10 22 100

MIDI AVR 448-35/15 7 400 15 400 10 >96 10 22 120

MIDI AVR 450-35/15 10 400 21 400 14 >97 10 23 165

MIDI AVR 452-35/15 15 400 33 400 22 >97 10 23 190

MIDI AVR 454-35/15 20 400 44 400 29 >97 10 23 220

MIDI AVR 456-35/15 30 400 66 400 43 >97 11 24 400

MIDI AVR 458-35/15 45 400 100 400 65 >97 11 24 450

MIDI AVR 460-35/15 60 400 133 400 87 >97 11 25 510

MIDI AVR 462-35/15 75 400 166 400 108 >97 11 25 600

MIDI AVR 464-35/15 105 400 234 400 152 >97 11 26 950

MIDI AVR 466-35/15 135 400 300 400 195 >97 11 26 1030

MIDI AVR 468-35/15 175 400 389 400 253 >97 11 26 1200

MIDI AVR 470-35/15 230 400 511 400 332 >97 11 50 1500

Midi AVR Y ±30% Digital ThreeMidi AVR Y ±30% Digital Three--Phase Voltage StabilisersPhase Voltage Stabilisers

Midi AVR Y Midi AVR Y --25%/+15% Digital Three25%/+15% Digital Three--Phase Voltage StabilisersPhase Voltage Stabilisers

Midi AVR Y Midi AVR Y ––35%/+15% Digital Three35%/+15% Digital Three--Phase Voltage StabilisersPhase Voltage Stabilisers

MIDIMIDI

AVRAVR MIDI AVR A & Y

Page 21: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 21

TYPE RATED POWER [kVA]

INPUT VOLTAGE

+15%

-45% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MIDI AVR 444-45/15 2 400 5 400 3 >94 8 22 100

MIDI AVR 446-45/15 3 400 8 400 4 >95 8 22 100

MIDI AVR 448-45/15 4 400 10 400 6 >95 8 22 120

MIDI AVR 450-45/15 7 400 18 400 10 >96 8 23 165

MIDI AVR 452-45/15 10 400 25 400 14 >97 8 23 190

MIDI AVR 454-45/15 15 400 39 400 22 >97 8 23 220

MIDI AVR 456-45/15 20 400 52 400 29 >97 9 24 400

MIDI AVR 458-45/15 30 400 79 400 43 >97 9 24 450

MIDI AVR 460-45/15 45 400 118 400 65 >97 9 25 510

MIDI AVR 462-45/15 60 400 158 400 87 >97 9 25 600

MIDI AVR 464-45/15 75 400 196 400 108 >97 9 26 950

MIDI AVR 466-45/15 105 400 276 400 152 >97 9 26 1030

MIDI AVR 468-45/15 135 400 354 400 195 >97 9 26 1200

MIDI AVR 470-45/15 175 400 460 400 253 >97 9 50 1500

MAXI AVR Digital Control

The technical data in the above tables are subject to change by the Company either for internal reasons or because of a specific request from the Customer

Input output voltage 50Hz: 380/415V - Input output voltage 60Hz: 460/480V

Midi AVR Y Midi AVR Y ––45%/+15% Digital Three45%/+15% Digital Three--Phase Voltage StabilisersPhase Voltage Stabilisers

MIDIMIDI

AVRAVR MIDI AVR A & Y

Page 22: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 22

The MAXI AVR line covers the range from 50kVA to 3150kVA and allows for the choice of several input voltage variation

percentages within a broad range (from +30% up to -45%).

The MAXI AVR voltage stabilisers are built with independent regulation on each phase.

The MAXI AVR type is used when the grid is unbalanced and when unbalanced three-phase loads and/or single-phase

loads need to be supplied. In this situation, the presence of the neutral wire is required.

The stabilisers are air cooled (natural convection with cabinet internal temperature lower than 40°C).

The measuring instrumentation for the SIRIUS stabilisers is incorporated in a control panel on the cabinet door and

consists of two multi-task digital network analysers. Such instruments are able to provide with information regarding

the status of the lines upstream and downstream the voltage stabiliser, such as phase and linked voltages, current,

power factor, active power, apparent power, reactive power, etc. Said information can also be monitored on a remote

PC via an RS485 output, an RS485/RS232 converter and a special software package supplied with the unit. Pilot lights

are provided for each phase signalling „power on‟, reaching of voltage regulation limits and direction of voltage regulation

(increase/decrease). Alarms for minimum and maximum voltages, maximum current, over-temperature and ventilation

failure are also indicated. The alarm indicators are accompanied by an acoustic alarm.

All these signals (consisting of several LEDs) are located on the control panel mounted on the cabinet door. The

stabiliser is provided with a voltage regulator protection circuit controlled by thermal probes. The circuit works in case of

temporary overload: it opens the connection between the voltage regulator and the buck/boost transformer and short-

circuits the transformer primary winding at the same time.

By doing so, the transformer voltage drop is cancelled and the user can be supplied the mains voltage (although not

stabilised) without interruption.

The auxiliary circuit is protected by fuses.

The logic control, performed on the true rms voltage, is based on a 2-way microprocessor. By using this device,

monitoring the system and setting the stabiliser parameters via a PC connection are made possible.

MAXIMAXI

AVRAVR MAXI AVR

Page 23: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 23

FREQUENCY 47/65Hz

ADMITTED LOAD VARIATION from 0 up to 100%

ADMITTED LOAD UNBALANCE up to 100%

MAINS WAVEFORM DISTORTION INCREMENT < 0.2%

COOLING Natural Air (aided over 40°C)

AMBIENT TEMPERATURE -15/+45 °C

STORAGE TEMPERATURE -25/+60°C

RELATIVE HUMIDITY 95%

ADMITTED OVERLOAD 200% 2min

COLOUR RAL 7035

PROTECTION IP 21

INSTALLATION Indoor

Any other variation range not mentioned in the table above can be dealt with on request.

±15% ±20% ±25% ±30% -25/+15% -35/+15% -45/+15%

125 100 75 50 100 75 50

160 125 100 75 125 100 75

200 160 125 100 160 125 100

250 200 160 125 200 160 125

315 250 200 160 250 200 160

400 315 250 200 315 250 200

500 400 315 250 400 315 250

630 500 400 315 500 400 315

800 630 500 400 630 500 400

1000 800 630 500 800 630 500

1250 1000 800 630 1000 800 630

1600 1250 1000 800 1250 1000 800

2000 1600 1250 1000 1600 1250 1000

2500 2000 1600 1250 2000 1600 1250

3150 2500 2000 1600 2500 2000 1600

4000 3150 2500 2000 3150 2500 2000

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±15% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MAXI AVR 664-15 125 400 212 400 181 >98 20 40 650

MAXI AVR 666-15 160 400 272 400 231 >98 20 40 670

MAXI AVR 668-15 200 400 340 400 289 >98 20 41 900

MAXI AVR 670-15 250 400 425 400 361 >98 20 41 950

MAXI AVR 672-15 315 400 535 400 455 >98 20 41 1050

MAXI AVR 674-15 400 400 680 400 578 >98 20 51 1300

MAXI AVR 676-15 500 400 850 400 723 >98 20 51 1400

MAXI AVR 678-15 630 400 1071 400 910 >98 20 42 1700

MAXI AVR 680-15 800 400 1361 400 1156 >98 24 52 2400

MAXI AVR 682-15 1000 400 1700 400 1445 >98 24 52 2600

MAXI AVR 684-15 1250 400 2125 400 1806 >98 24 44 4400

MAXI AVR 686-15 1600 400 2720 400 2312 >98 24 44 4800

MAXI AVR 688-15 2000 400 3400 400 2890 >98 24 44 5200

MAXI AVR 690-15 2500 400 4250 400 3613 >98 24 49 6900

MAXI AVR 692-15 3150 400 5355 400 4552 >98 24 49 7300

MAXI AVR 694-15 4000 400 6800 400 5780 >98 24 60 9000

Maxi AVR Standard FeaturesMaxi AVR Standard Features

Rating in Relation to the Input Variation PercentageRating in Relation to the Input Variation Percentage

Maxi AVR ±15% Digital ThreeMaxi AVR ±15% Digital Three--Phase Voltage StabilisersPhase Voltage Stabilisers

MAXIMAXI

AVRAVR MAXI AVR

Page 24: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 24

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±20% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MAXI AVR 664-20 100 400 180 400 144 >98 15 40 650

MAXI AVR 666-20 125 400 226 400 181 >98 15 40 670

MAXI AVR 668-20 160 400 289 400 231 >98 15 41 900

MAXI AVR 670-20 200 400 361 400 289 >98 15 41 950

MAXI AVR 672-20 250 400 452 400 361 >98 15 41 1050

MAXI AVR 674-20 315 400 569 400 455 >98 15 51 1300

MAXI AVR 676-20 400 400 722 400 578 >98 15 51 1400

MAXI AVR 678-20 500 400 903 400 723 >98 15 42 2000

MAXI AVR 680-20 630 400 1138 400 910 >98 18 52 2400

MAXI AVR 682-20 800 400 1445 400 1156 >98 18 52 2600

MAXI AVR 684-20 1000 400 1806 400 1445 >98 18 44 4400

MAXI AVR 686-20 1250 400 2258 400 1806 >98 18 44 4800

MAXI AVR 688-20 1600 400 2890 400 2312 >98 18 44 5200

MAXI AVR 690-20 2000 400 3613 400 2890 >98 18 49 6900

MAXI AVR 692-20 2500 400 4516 400 3613 >98 18 49 7300

MAXI AVR 694-20 3150 400 5690 400 4552 >98 18 60 9000

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±25% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MAXI AVR 664-25 75 400 144 400 108 >98 12 40 650

MAXI AVR 666-25 100 400 193 400 144 >98 12 40 670

MAXI AVR 668-25 125 400 241 400 181 >98 12 41 900

MAXI AVR 670-25 160 400 308 400 231 >98 12 41 950

MAXI AVR 672-25 200 400 385 400 289 >98 12 41 1050

MAXI AVR 674-25 250 400 482 400 361 >98 12 51 1300

MAXI AVR 676-25 315 400 607 400 455 >98 12 51 1400

MAXI AVR 678-25 400 400 770 400 578 >98 12 42 1700

MAXI AVR 680-25 500 400 963 400 723 >98 15 52 2400

MAXI AVR 682-25 630 400 1214 400 910 >98 15 52 2600

MAXI AVR 684-25 800 400 1541 400 1156 >98 15 44 4400

MAXI AVR 686-25 1000 400 1927 400 1445 >98 15 44 4800

MAXI AVR 688-25 1250 400 2408 400 1806 >98 15 44 5200

MAXI AVR 690-25 1600 400 3083 400 2312 >98 15 49 6900

MAXI AVR 692-25 2000 400 3853 400 2890 >98 15 49 7300

MAXI AVR 694-25 2500 400 4817 400 3613 >98 15 60 9000

Maxi AVR ±20% Digital ThreeMaxi AVR ±20% Digital Three--Phase Voltage StabilisersPhase Voltage Stabilisers

Maxi AVR ±25% Digital ThreeMaxi AVR ±25% Digital Three--Phase Voltage StabilisersPhase Voltage Stabilisers

MAXIMAXI

AVRAVR MAXI AVR

Page 25: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 25

TYPE RATED POWER [kVA]

INPUT VOLTAGE

±30% [V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MAXI AVR 664-30 50 400 103 400 72 >98 10 40 650

MAXI AVR 666-30 75 400 155 400 108 >98 10 40 670

MAXI AVR 668-30 100 400 206 400 144 >98 10 41 900

MAXI AVR 670-30 125 400 258 400 181 >98 10 41 950

MAXI AVR 672-30 160 400 330 400 231 >98 10 41 1050

MAXI AVR 674-30 200 400 413 400 289 >98 10 51 1300

MAXI AVR 676-30 250 400 516 400 361 >98 10 51 1400

MAXI AVR 678-30 315 400 650 400 455 >98 10 42 1700

MAXI AVR 680-30 400 400 826 400 578 >98 12 52 2400

MAXI AVR 682-30 500 400 1032 400 723 >98 12 52 2600

MAXI AVR 684-30 630 400 1300 400 910 >98 12 44 4400

MAXI AVR 686-30 800 400 1651 400 1156 >98 12 44 4800

MAXI AVR 688-30 1000 400 2064 400 1445 >98 12 44 5200

MAXI AVR 690-30 1250 400 2580 400 1806 >98 12 49 6900

MAXI AVR 692-30 1600 400 3303 400 2312 >98 12 49 7300

MAXI AVR 694-30 2000 400 4128 400 2892 >98 12 60 9000

TYPE RATED POWER [kVA]

INPUT VOLTAGE

+15%

-25%

[V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MAXI AVR 664-25/15 100 400 192 400 144 >97 15 40 715

MAXI AVR 666-25/15 125 400 241 400 180 >97 15 40 740

MAXI AVR 668-25/15 160 400 308 400 231 >97 15 41 1100

MAXI AVR 670-25/15 200 400 385 400 289 >97 15 41 1210

MAXI AVR 672-25/15 250 400 481 400 361 >97 15 41 1320

MAXI AVR 674-25/15 315 400 607 400 455 >97 15 51 1650

MAXI AVR 676-25/15 400 400 770 400 578 >97 15 51 1760

MAXI AVR 678-25/15 500 400 963 400 722 >97 15 42 1900

MAXI AVR 680-25/15 630 400 1213 400 910 >97 18 52 2780

MAXI AVR 682-25/15 800 400 1541 400 1156 >97 18 52 3020

MAXI AVR 684-25/15 1000 400 1926 400 1445 >97 18 44 4840

MAXI AVR 686-25/15 1250 400 2408 400 1806 >97 18 44 5280

MAXI AVR 688-25/15 1600 400 3082 400 2312 >97 18 44 5720

MAXI AVR 690-25/15 2000 400 3853 400 2890 >97 18 49 7590

MAXI AVR 692-25/15 2500 400 4817 400 3612 >97 18 49 8030

MAXI AVR 694-25/15 3150 400 6069 400 4552 >97 18 60 9000

Maxi AVR ±30% Digital ThreeMaxi AVR ±30% Digital Three--Phase Voltage StabilisersPhase Voltage Stabilisers

Maxi AVR Maxi AVR --25%/+15% Digital Three25%/+15% Digital Three--Phase Voltage StabilisersPhase Voltage Stabilisers

MAXIMAXI

AVRAVR MAXI AVR

Page 26: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 26

TYPE RATED POWER [kVA]

INPUT VOLTAGE

+15%

-35%

[V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MAXI AVR 664-35/15 75 400 166 400 108 >97 12 40 715

MAXI AVR 666-35/15 100 400 222 400 144 >97 12 40 740

MAXI AVR 668-35/15 125 400 278 400 180 >97 12 41 1100

MAXI AVR 670-35/15 160 400 356 400 231 >97 12 41 1210

MAXI AVR 672-35/15 200 400 444 400 289 >97 12 41 1320

MAXI AVR 674-35/15 250 400 556 400 361 >97 12 51 1650

MAXI AVR 676-35/15 315 400 700 400 455 >97 12 51 1760

MAXI AVR 678-35/15 400 400 889 400 578 >97 12 42 1900

MAXI AVR 680-35/15 500 400 1111 400 722 >97 15 52 2780

MAXI AVR 682-35/15 630 400 1400 400 910 >97 15 52 3020

MAXI AVR 684-35/15 800 400 1778 400 1156 >97 15 44 4840

MAXI AVR 686-35/15 1000 400 2223 400 1445 >97 15 44 5280

MAXI AVR 688-35/15 1250 400 2779 400 1806 >97 15 44 5720

MAXI AVR 690-35/15 1600 400 3557 400 2312 >97 15 49 7590

MAXI AVR 692-35/15 2000 400 4446 400 2890 >97 15 49 8030

MAXI AVR 694-35/15 2500 400 5558 400 3613 >97 15 60 9000

The technical data in the above tables are subject to change by the Company either for internal reasons or because of a specific request from the Customer

Input output voltage 50Hz: 380/415V - Input output voltage 60Hz: 460/480V

Maxi AVR Maxi AVR ––35%/+15% Digital Three35%/+15% Digital Three--Phase Voltage StabilisersPhase Voltage Stabilisers

TYPE RATED POWER [kVA]

INPUT VOLTAGE

+15%

-45%

[V]

MAX INPUT

CURRENT [A]

OUTPUT VOLTAGE ±0.5%

[V]

RATED OUTPUT

CURRENT [A]

EFFICIENCY [%]

RESPONSE TIME

[ms/V] CABINET

WEIGHT [kg]

MAXI AVR 664-45/15 50 400 131 400 72 >97 10 40 780

MAXI AVR 666-45/15 75 400 197 400 108 >97 10 40 805

MAXI AVR 668-45/15 100 400 263 400 144 >97 10 41 1200

MAXI AVR 670-45/15 125 400 328 400 180 >97 10 41 1320

MAXI AVR 672-45/15 160 400 420 400 231 >97 10 41 1440

MAXI AVR 674-45/15 200 400 525 400 289 >97 10 51 1800

MAXI AVR 676-45/15 250 400 656 400 361 >97 10 51 1920

MAXI AVR 678-45/15 315 400 827 400 455 >97 10 42 2100

MAXI AVR 680-45/15 400 400 1051 400 578 >97 12 52 3060

MAXI AVR 682-45/15 500 400 1313 400 722 >97 12 52 3340

MAXI AVR 684-45/15 630 400 1655

400 910 >97 12 44 5280

MAXI AVR 686-45/15 800 400 2102 400 1156 >97 12 44 5760

MAXI AVR 688-45/15 1000 400 2627 400 1445 >97 12 44 6240

MAXI AVR 690-45/15 1250 400 3284 400 1806 >97 15 49 8280

MAXI AVR 692-45/15 1600 400 4204 400 2312 >97 15 49 8760

MAXI AVR 694-45/15 2000 400 5254 400 2890 >97 15 60 9000

Maxi AVR Maxi AVR ––45%/+15% Digital Three45%/+15% Digital Three--Phase Voltage StabilisersPhase Voltage Stabilisers

MAXIMAXI

AVRAVR MAXI AVR

Page 27: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 27

CABINETS DIMENSIONS (w x d x h) mm

12 275X425X260

13 300X565X280

22 360x520x1000

23 405x670x1150

24 605x850x1450

25 605x850x1650

26 1210x850x1650

40 600x800x2000

41 1200x800x2000

42 2400x800x2000

44 3600x1000x2100

49 3600x1400x2200

50 1815x850x1650

51 1800x800x2000

52 2400x1000x2100

Any dimensions other than the ones in the above table can be dealt with on request.

DIMENSIONS

Page 28: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 28

DIAGRAMS

M

SURGE

ARRESTER

INPUT

NETWORK ANALYSER

V

Wh

WA

cos

SOFT START

CIRCUIT

OUTPUT NETWORK

ANALYSER

MICROPROCESSOR

DRIVE CARD

BY-PASS LINE

RS232

BUCK/BOOST

TRANSFORMER VOLTAGE

REGULATOR

CURRENT

TRANSFORMERWh cos

V A W

INPUT

OUTPUT

ISOLATING

TRANSFORMER

INPUT

INTERRUPTING

DEVICE

CURRENT

TRANSFORMER

OUTPUT

INTERRUPTING

DEVICE

EMI / RFI

FILTER

RED: POWER LINE

BLUE: ACCESSORIES ON REQUEST

1-PH. VOLTAGE

STABILISER (TYPE 'MINIAVR')

Page 29: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 29

M

SURGE

ARRESTER

INPUT

NETWORK ANALYSER

V

Wh

WA

cos

SOFT START

CIRCUIT

OUTPUT NETWORK

ANALYSER

MICROPROCESSOR

DRIVE CARD

BY-PASS LINE BUCK/BOOST

TRANSFORMER VOLTAGE

REGULATOR

CURRENT

TRANSFORMERWh cos

V A W

INPUT

OUTPUT

ISOLATING

TRANSFORMER

INPUT

INTERRUPTING

DEVICE

CURRENT

TRANSFORMER

OUTPUT

INTERRUPTING

DEVICE

EMI / RFI

FILTER

RED: POWER LINE

BLUE: ACCESSORIES ON REQUEST

RS232

3-PH. VOLTAGE

STABILISER

(TYPE 'MIDIAVR A')

DIAGRAMS

Page 30: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 30

M

SURGE

ARRESTER

INPUT

NETWORK ANALYSER

V

Wh

WA

cos

SOFT START

CIRCUIT

OUTPUT NETWORK

ANALYSER

MICROPROCESSOR

DRIVE CARDS

BY-PASS LINE BUCK/BOOST

TRANSFORMER

VOLTAGE

REGULATORS

CURRENT

TRANSFORMERSWh cos

V A W

INPUT

OUTPUT

ISOLATING

TRANSFORMER

INPUT

INTERRUPTING

DEVICE

CURRENT

TRANSFORMERS

OUTPUT

INTERRUPTING

DEVICE

EMI / RFI

FILTER

RED: POWER LINE

BLUE: ACCESSORIES ON REQUEST

M M

RS232

3-PH. VOLTAGE

STABILISER

(TYPE 'MIDIAVR Y')

DIAGRAMS

Page 31: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 31

M

SURGE

ARRESTER

INPUT

NETWORK ANALYSERV

Wh

WA

cos

SOFT START

CIRCUIT

OUTPUT NETWORK

ANALYSER

2-WAYS MICROPROCESSOR

DRIVE CARD WITH ALARMS

BY-PASS LINE

RS232

BUCK/BOOST

TRANSFORMER VOLTAGE

REGULATORS

CURRENT

TRANSFORMERSWh cos

V A W

INPUT

OUTPUT

ISOLATING

TRANSFORMER

INPUT

INTERRUPTING

DEVICE

CURRENT

TRANSFORMERS

OUTPUT

INTERRUPTING

DEVICE

EMI / RFI

FILTER

RED: POWER LINE

BLUE: ACCESSORIES ON REQUEST

M M

3-PH. VOLTAGE

STABILISER

(TYPE 'MAXIAVR')

DIAGRAMS

Page 32: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 32

The characteristics so far described are typical of the standard machine. Accessories performing other tasks can be

supplied on request. Combinations of one or more of the following accessories are usually installed in an additional

modular enclosure.

optionaloptional

STABILISERMAINS USER

MAINS STABILISER USER

MAINS STABILISER USER

MAINS STABILISER USER

ByBy--Pass SwitchPass Switch

Useful for working on the voltage stabiliser without switching off the power supply to the loads. For the operators' safety,

the by-pass operation should be manual. The by-pass device consists of three interlocked switches with three positions:

by-pass OFF/stabiliser ON

by-pass OFF/stabiliser OFF

by-pass ON/stabiliser OFF

Input Isolation TransformerInput Isolation Transformer

It provides for galvanic separation between the stabiliser (and its load) and the mains.

It also protects from possible overvoltages. It allows the connection with system without neutral cable, giving a fixed and stable star point for the system.

Interrupting DevicesInterrupting Devices

Fused disconnections or circuit breakers with thermal and magnetic release can be supplied whenever it is necessary to

isolate the input line, the output one or both.

ACCESSORIES

Page 33: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 33

Surge arresters (lightning arresters) and overvoltage suppressers can be provided to protect from overvoltage peaks

of atmospheric or operational origin by discharging them to ground. The installation depends on the system

configuration. For example, in case of high ratings the suggested sequence would be: spark-gap arresters followed by

an isolating device (ideally an isolating transformer) and varistor-based arresters on its output.

SPD

F2

SPD

F2

F1

STABILISER USERMAINS

The „Soft Start‟ circuit is a protection with a double purpose:

To delay the connection to the load each time the stabiliser switches on so that the users can undergo a smooth

start-up with an already stabilised voltage.

To protect the load from surges, sags and overload by disconnecting the load from the stabiliser.

STABILISER

TIMING CIRCUIT

MAINS USER

DELAYED

RESETTING RELAY

WITH 'LOAD-ON' SIGNAL

On request the stabiliser can be designed for outdoor installation and be housed in stainless steel or glass-fibre

cabinets.

Surge Arresters (SPD)Surge Arresters (SPD)

“Soft Start” Circuit“Soft Start” Circuit

Protection Degree (IP)Protection Degree (IP)

High protection degree (up to IP54) can be obtain by increasing the dimensions or by including heat exchangers and air

conditioning units.

Additional Instrumentation and Special CostructionAdditional Instrumentation and Special Costruction

For special requirements, the instrumentation can be expanded according to request, with provision for computerised

remote signalling. Due to our flexibility, it is possible to customise the design according to specific requests

Outdoor ConstructionsOutdoor Constructions

EMI FiltersEMI Filters

Protection against radio-frequencies disturbances (kHZ-MHZ range)

ACCESSORIES

Page 34: DIGITAL VOLTAGE STABILISERS - Mainor · PDF fileMINI AVR Single-phase voltage stabilisers from 0 ... to changes in voltage level called sags (voltage drops) ... the output voltage

Italfarad S.p.A. Via IV Novembre n.1 Minerbio Bologna Italy Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: [email protected] Web:www.italfarad.com 34 Edizione 07-2009

ITALFARAD S.p.A.

Via IV novembre n.1

40061 Minerbio Bo Italy

Tel. +39 051 6618311

Fax +39 051 6605594

E-mail: [email protected]

Web: www.italfarad.com