DIGIGATE SeriesBuilt to Last...
Online UPS 10KVA-120KVA(3P In/3P Out)
www.apec.sa.com
DIGIGATE Series 3Phase large power UPS(10KVA-120KVA), offer advanced DSP control, high speed 16bits digital IC, DDC control
technology also use advanced high power IGBT and SCR. It is a digital, Informaon, Networking, Online Intelligent Pure Sine-wave
Uninterrupble Power Supply, which is based on reliable, advanced, high efficiency digital/analog hybrid technology. DIGIGATE
Series can supply strong per guard for you.
ApplicaonsCentralized server center, network control center, Informaon Center, Healthcare,
Telecommunicaon
8/14/2019 Digigatei 10kva-120kva 3pin3pout
http://slidepdf.com/reader/full/digigatei-10kva-120kva-3pin3pout 2/2www.apec.sa.com
P.O. Box 3411, Al Khobar 31952 - Saudi Arabia
Tel: +966 (3) 890 1261 Fax: +966 (3) 865 0066
E-mail: [email protected]
ARABIAN POWER ELECTRONICS COMPANY
D G C
a t . 0
7 . 1
3
Features (3P In/3P Out)
Intelligent Digital Control
High speed MCU control, it can do parameter seng, running
progress management, self-test, self-detecve, and so on. Also can
detect all the independent circuits, and do faults protecon.
Advanced DDC Direct Digital Control technology) using a DSP and
special IC used helps to keep UPS with perfect performance.
Advanced IGBT with high speed switch, high voltage, large current,
makes efficiency higher, driver circuit smaller, and improve the
system efficiency and reliability.
100% Unbalance load capability
3phase independent modulaon, full bridge Inverter designed, it
can be 100% unbalance load in 3phase.
Funconal LCD display
Large LCD display, it can show UPS running status, running progress,
UPS parameter data, fault events, etc.
Intelligent Baery Management
Recfier/Charger Integrated design, charging capacity is configured
according with baery, user can set up parameters with operaon
plaorm, and charging current can be configured by soware
automacally, also can configure baery self-test, charging/discharging
interval me, and keep baery long life.
Oponal communicaon interface
RS232/RS485, and several dry contacts, can be used for communicaons
and remote control.
Perfect protecon
With various system protecon. As over voltage, low voltage, over
current, over load, short circuit, etc can be detected, and supply reliable
protecon.
Parallel (Opon)
Up to two units work in parallel 1+1 parallel
Specificaons
D33010 D33015 DG20K/3/1D33020 D33030 D31040 D33050 D33060 D33080 D33100 D33120
Note: i) All specificaons subject to change without noce
ii) Custom-made specificaons are acceptable
MODEL
AC Input
Bypass Input
DC System
AC Output
System
Outlooking
Cabinet color
Dimension(WxDxH)mm
Parallel cabinet
Packing(WxDxH)mm
Parallel cabinet
Gross weight(kg) 232 248 300 380 480 580 840650 950 1100
Rang
Operang Mode On line, stac bypass switch(zero transfer me), Double switch technology, output power to totally isolate
10KVA 15KVA 20KVA 30KVA 40KVA 50KVA 60KVA 80KVA 1 00KVA 120KVA
Phase
Voltage
Frequency
P.F
Phase
Voltage
Frequency
Transfer Time
VoltageCharge Current
Phase
Voltage
Frequency
P.F
Waveform
Distoron
Dynamic load voltage
instant distoron
Dynamic response recover me
Unbalance Voltage
Overload capacity
Efficiency
Interface
Temperature
Altude
Cooling
Noise (dB)
3phase +N+G
380V/400V/415V 25% or 200/208/220VAC 25%± ±
0.85(input filter oponal)
3Phases+N+G
50/60Hz 5%±
0ms, Inverter/Bybass (overload)
50/60Hz 5%± 40 65Hz
≤
~
380V/400V/415V 25% or 200/208/220VAC 25%± ± 380V/400V/415V + 15%/-25%
or 200/208/220VAC +15%/- 25%
DC360V(AC380V), DC192V(AC208V) 360V1A 30A(can be set according baery capacity)~ 5A 40A(can be set according baery capacity)~
3Phases+N+G
380V/400V/415V 2% or 200/208/220VAC 2%± ±
50/60Hz 0.5%(Baery Mode)± 50/60Hz 0.2%(Baery Mode)±
0.8
True Sine Wave
Total Harmonic Distoron: 3%(Linear Load), 5%(Non-Linear Load)≤ ≤
≤ 2%
< 5%(from 0 to 100% abrupt change)±
<10ms
< 1%; < 3%(unbalance load voltage)± ±
105% 125% 10min; 125% 150% 1min; >150% 1s~ ~
91% ≤
RS232 (SNMP, dry contact for oponal) RS232 (SNMP, dry contact for oponal)
0 40 (Operang)℃~
<100m (per100m, power decline 1%, Max 400m)
Forced Air cooling (can be adjusted in different load)
Black
48 60~ 53 65~ 55 65~
450x725x1140
600x700x1350450x850x1230
710x720x1450710x850x1500 900x800x1800
970x870x1960810x950x1662
565x945x1395
820x830x1610
556x828x1310
700x800x1520