digigatei 10kva-120kva 3pin3pout

2

Click here to load reader

Upload: santhu-meprathu

Post on 04-Jun-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Digigatei 10kva-120kva 3pin3pout

8/14/2019 Digigatei 10kva-120kva 3pin3pout

http://slidepdf.com/reader/full/digigatei-10kva-120kva-3pin3pout 1/2

DIGIGATE SeriesBuilt to Last...

Online UPS 10KVA-120KVA(3P In/3P Out)

www.apec.sa.com

DIGIGATE Series 3Phase large power UPS(10KVA-120KVA), offer advanced DSP control, high speed 16bits digital IC, DDC control

technology also use advanced high power IGBT and SCR. It is a digital, Informaon, Networking, Online Intelligent Pure Sine-wave

Uninterrupble Power Supply, which is based on reliable, advanced, high efficiency digital/analog hybrid technology. DIGIGATE

Series can supply strong per guard for you.

ApplicaonsCentralized server center, network control center, Informaon Center, Healthcare,

Telecommunicaon

Page 2: Digigatei 10kva-120kva 3pin3pout

8/14/2019 Digigatei 10kva-120kva 3pin3pout

http://slidepdf.com/reader/full/digigatei-10kva-120kva-3pin3pout 2/2www.apec.sa.com

P.O. Box 3411, Al Khobar 31952 - Saudi Arabia

Tel: +966 (3) 890 1261 Fax: +966 (3) 865 0066

E-mail: [email protected]

ARABIAN POWER ELECTRONICS COMPANY

   D   G    C

   a   t .   0

   7 .   1

   3

Features (3P In/3P Out)

Intelligent Digital Control

High speed MCU control, it can do parameter seng, running

progress management, self-test, self-detecve, and so on. Also can

detect all the independent circuits, and do faults protecon.

Advanced DDC Direct Digital Control technology) using a DSP and

special IC used helps to keep UPS with perfect performance.

Advanced IGBT with high speed switch, high voltage, large current,

makes efficiency higher, driver circuit smaller, and improve the

system efficiency and reliability.

100% Unbalance load capability

3phase independent modulaon, full bridge Inverter designed, it

can be 100% unbalance load in 3phase.

Funconal LCD display

Large LCD display, it can show UPS running status, running progress,

UPS parameter data, fault events, etc.

Intelligent Baery Management

Recfier/Charger Integrated design, charging capacity is configured

according with baery, user can set up parameters with operaon

plaorm, and charging current can be configured by soware

automacally, also can configure baery self-test, charging/discharging

interval me, and keep baery long life.

Oponal communicaon interface

RS232/RS485, and several dry contacts, can be used for communicaons

and remote control.

Perfect protecon

With various system protecon. As over voltage, low voltage, over

current, over load, short circuit, etc can be detected, and supply reliable

protecon.

Parallel (Opon)

Up to two units work in parallel 1+1 parallel

Specificaons

D33010 D33015 DG20K/3/1D33020 D33030 D31040 D33050 D33060 D33080 D33100 D33120

Note: i) All specificaons subject to change without noce

  ii) Custom-made specificaons are acceptable

MODEL

AC Input

Bypass Input

DC System

AC Output

System

Outlooking

Cabinet color

Dimension(WxDxH)mm

Parallel cabinet

Packing(WxDxH)mm

Parallel cabinet

Gross weight(kg)   232 248   300 380 480 580 840650 950   1100

Rang

Operang Mode On line, stac bypass switch(zero transfer me), Double switch technology, output power to totally isolate

10KVA 15KVA   20KVA 30KVA 40KVA 50KVA 60KVA 80KVA   1 00KVA 120KVA

Phase

Voltage

Frequency

P.F

Phase

Voltage

Frequency

Transfer Time

VoltageCharge Current

Phase

Voltage

Frequency

P.F

Waveform

Distoron

Dynamic load voltage

instant distoron

Dynamic response recover me

Unbalance Voltage

Overload capacity

Efficiency

Interface

Temperature

Altude

Cooling

Noise (dB)

3phase +N+G

380V/400V/415V 25% or 200/208/220VAC 25%±   ±

0.85(input filter oponal)

3Phases+N+G

50/60Hz 5%±

0ms, Inverter/Bybass (overload)

50/60Hz 5%± 40 65Hz

    ≤

380V/400V/415V 25% or 200/208/220VAC 25%±   ± 380V/400V/415V + 15%/-25%

or 200/208/220VAC +15%/- 25%

DC360V(AC380V), DC192V(AC208V) 360V1A 30A(can be set according baery capacity)~ 5A 40A(can be set according baery capacity)~

3Phases+N+G

380V/400V/415V 2% or 200/208/220VAC 2%±   ±

50/60Hz 0.5%(Baery Mode)± 50/60Hz 0.2%(Baery Mode)±

0.8

True Sine Wave

Total Harmonic Distoron: 3%(Linear Load), 5%(Non-Linear Load)≤ ≤

≤ 2%

< 5%(from 0 to 100% abrupt change)±

<10ms

< 1%; < 3%(unbalance load voltage)± ±

105% 125% 10min; 125% 150% 1min; >150% 1s~ ~

91%    ≤

RS232 (SNMP, dry contact for oponal) RS232 (SNMP, dry contact for oponal)

0 40 (Operang)℃~

<100m (per100m, power decline 1%, Max 400m)

Forced Air cooling (can be adjusted in different load)

Black

48 60~ 53 65~ 55 65~

450x725x1140

600x700x1350450x850x1230

710x720x1450710x850x1500 900x800x1800

970x870x1960810x950x1662

565x945x1395

820x830x1610

556x828x1310

700x800x1520