Hitec Power Protection
Diesel Rotary UPS systems
Ride through systems Diesel UPS systems
www.hitec-ups.com
The problems The solution
7. Continuous Quality Power
1. Spikes
2. Frequency Variations
3. Voltage Sags
4. Outages
5. Harmonic Distortions
6. Transients
The result
Hitec Power ProtectionWhat we do
-
7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT
2/10
Major components
Generator
Chokecoil
Diesel engine
Inductioncoupling
Freewheelclutch
Switchgear
Dicon
Control panel
Free inner rotor principle
AC machine
Induction coupling
Freewheel clutch
Diesel engine
-
7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT
3/10
Four basic principles (1)
Simple, sure and reliable Rotary UPS/CPS concept invented and patented by Hitec
Power Protection in 1969
Rotary UPS/CPS = static UPS + standby generator
Fewer components than static UPS
Smaller footprint than static UPS
Easy installation & operation
Long lifespan (>25 years)
Line-interactive system
Rotary UPS/CPS run in parallel with utility power
Life-guarding mission critical processes
No power conversion
Four basic principles (2) Active filter (choke coil + generator)
Compensation utility voltage deviations
Filtering of utility borne harmonic voltages
Filtering of load borne harmonic currents
Power factor improvement (>0.98)
Environmental friendly system
Most energy efficient UPS/CPS system
Use of stored kinetic energy
No batteries required, no chemical waste No conditioned battery room required, saving space and energy
for ventilation and cooling
Lowest Total Cost of Ownership (TCO)
-
7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT
4/10
Diesel Rotary UPS systemSpecifications
Diesel, UPS and energy storage combined
Lowest TCO, 25+ years productive lifetime
No power conversion
High end-to-end efficiency (>96%)
High output values
Single unit rating Up to 2,5 MVA
Parallel configuration rating Up to 40 MVA
Output voltage
LV 380 .. 480 V, 50/60 Hz
MV Up to 24 kV, 50/60 HZ
Voltage deviation +/- 1% Frequency deviation +/- 1%
Options (e.g. remote monitoring, containerized designs,
vibration monitoring, .)
UPS Inverters
Air Conditioning
PFC
Standby Batteries
Spark-proof Lighting
Busduct & CablingFire Protection
& Security
All in one
Static UPS
Hitec DRUPS
Standby Diesel
-
7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT
5/10
Hitec Rotary UPS
Total losses 96%
Total losses >8%
100%
25 years)
Fire Protection
& Security
Air Conditioning
Standby Batteries
UPS Inverters PFC
Spark-proof Lighting
Busduct & Cabling
It is in the windings
Outer Rotor
2 pole AC windings
2 pole DC windings
50 Hz 60Hz
1500 RPM 1800 RPM
Inner Rotor
Stored Energy
50 Hz 60Hz
1500 1800
3000 + 3600 +
4500 RPM 5400 RPM
-
7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT
6/10
System operation
Dependent system load
Speed(rpm)
0
n
3n
Time
Utility mode
Speed(rpm)
0
n
3n
Time
Reactor and generator function as
active filter. The induction
coupling stores kinetic energy.
Q1 Q2
Q3
-
7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT
7/10
Change-over to diesel mode
Speed(rpm)
0
n
3n
Time
Power problem - Q1 opens, energy
from the inner rotor goes via the
generator to the load. The diesel
engine starts up and takes over
the power supply.
Q1 Q2
Q3
Diesel mode
Speed(rpm)
0
n
3n
Time
The outer rotor of the induction
coupling is re-energized. The
speed of the diesel engine is
digitally controlled ensuring a
constant output
Q1 Q2
Q3
-
7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT
8/10
Back to utility mode
Speed(rpm)
0
n
3n
Time
Utility power is back and after it
has stabilized the UPS/CPS
synchronizes and closes Q1. The
diesel engine ramps down and
the free-wheel clutch disengages.
Q1 Q2
Q3
Recording mains failure
Mainsvoltage
Outputvoltage
50.5 Hz
50 Hz
49.5 Hz
1 sec.
1500 rpm
Dynamic UPS at 100% load
MainsVoltage
Diesel engine RPM
50 Hz Line
Outputfrequency [Hz]
Free wheel clutchengaging
Moment ofmains failure
Dieselstart
-
7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT
9/10
Technical features D-UPS
Uses stored kinetic energy 50/60 Hz technology
Integrated power factor correction
Effective filter for spikes & harmonic distortion
High non-linear load capacity
High peak current capability (typical 15 In)
Very efficient with low operational costs
Easily paralleled MV applications up to 40 MVA
Hitec D-UPS configurations
Unit configurations System configurations
Single output
Dual output
Medium Voltage
Parallel redundant
Master slave
Cross link
Isolated redundant
Distributed redundant
-