diesel generator set mtu 16v2000 ds1100...iso 8528-1, iso 3046-1, bs 5514 and as 2789. average load...
TRANSCRIPT
MTU 16V2000 DS1100Diesel Generator Set
Product highlights
380V-415V/50Hz/prime/fuelconsumptionoptimized16V2000G26F/air charge air cooling
Bene� ts— Lowfuelconsumption— Optimizedsystemintegrationability— Highreliabilityandavailabilityofpower— Longmaintenanceintervals— Optimizedratiobetweensizeandpower— Wideoperatingrangewithoutderating
Support— Globalproductsupportoffered
Standards— Engine-generatorsetisdesignedandmanufacturedinfacilitiescertifiedtostandardsISO2008:9001andISO2004:14001
— GeneratorsetcompliestoG3accordingtoISO8528— GeneratormeetsNEMAMG1,BS5000,ISO,DINENandIECstandards
— NFPA110
Power rating— Systemrating:1000kVA— AcceptsratedloadinonestepperNFPA110— GeneratorsetcompliestoG3accordingtoISO8528-5— GeneratorsetexceedsloadstepsaccordingtoISO8528-5
Performance assurance certi� cation (PAC)— Engine-generatorsettestedtoISO8528-5fortransientresponse— 75%loadfactorforprimepowerapplications— Verifiedproductdesign,qualityandperformanceintegrity— Allenginesystemsareprototypeandfactorytested
Complete range of accessories available— Controlpanel— Power panel— Fuelsystem— Fuelconnectionswithshut-offvalvemountedtobaseframe— Starting/chargingsystem— Exhaustsystem— Mechanicalradiator— Oversizedvoltagealternators
Emissions— Fuelconsumptionoptimized— TA-Luft,Tier2compliantandNEA(ORDE)optimizationoptionallyavailable
Certi� cations— CEcertificationoption— VDE4110Certification
Optionalequipmentandfinishingshown.Standardmayvary.
Application data 1)
Engine Fuel consump. opt. Emission opt. 2)
Manufacturer MTU MTU Model 16V2000G26F 16V2000G26F Type 4-cycle 4-cycle Arrangement 16V 16V Displacement: l 35.7 35.7 Bore: mm 135 135 Stroke: mm 156 156 Compression ratio 17.5 17.5 Rated speed: rpm 1500 1500 Engine governor ADEC (ECU 9) ADEC (ECU 9) Speed regulation ± 0.25% ± 0.25% Max power: kWm 890 890 Mean effective pressure: bar 19.1 19.1 Air cleaner dry dry
Fuel systemMaximum fuel lift: m 5 5 Total fuel flow: l/min 30 30
Fuel consumption 2)
At 100% of power rating: l/hr g/kWh 205/191 216/201 At 75% of power rating l/hr g/kWh 156/194 165/205 At 50% of power rating: l/hr g/kWh 108/202 115/214
Lube oil systemTotal oil system capacity: l 102 102 Max. lube oil temp. (alarm): °C 103 103 Max. lube oil temp. (shutdown): °C 105 105 Min. lube oil pressure (alarm): bar 4.5 4.5 Min. lube oil pressure (shutdown): bar 4 4
Combustion air requirementsCombustion air volume: m3/s 1.03 1.19 Max. air intake restriction: mbar 40 40
Cooling/radiator system Fuel consump. opt. Emission opt. 2)
Coolant flow rate (HT circuit): m3/hr 41.6 41.6 Heat rejection to coolant: kW 370 350 Heat radiated to charge air cooling: kW 145 205 Heat radiated to ambient: kW 40 40 Fan power for mech. radiator (40°C): 43.4 43.4 Fan power for mech. radiator (50°C): 43.4 43.4 Air flow required for mech. radiator (40°C) cooled unit: m3/min 1462 1462 Air flow required for mech. radiator (50°C) cooled unit: m3/min 1462 1462 Engine coolant capacity (without cooling equipment): l 70 70 Radiator coolant capacity (40°C): l 74 74 Radiator coolant capacity (50°C): l 106 106 Max. coolant temperature (warning): °C 102 102 Max. coolant temperature (shutdown): °C 105 105
Exhaust systemExhaust gas temp. (after turbocharger): °C 530 515 Exhaust gas volume: m³/s 2.78 3.07 Maximum allowable back pressure: mbar 50 50 Minimum allowable back pressure: mbar 30 30
GeneratorProtection class IP23 IP23 Insulation class H H Voltage regulation (steady state) ± 0.25% ± 0.25% Rado interference class N N
1 All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level).
2 Emission optimized data refer to TA-Luft optimized and NEA (ORDE) optimized/Tier 2 compliant engines.
Representsstandardfeatures
Representsoptionalfeatures
Engine
4-Cycle Standardsinglestageairfilter Oildrainextension&shut-offvalve Fullflowoilfilters Closedcrankcaseventilation
ADECelectronicisochronousenginegovernor Commonrailfuelinjection Dryexhaustmanifold Electricstartingmotor(24V)
Fuelconsumptionoptimizedengine TA-Luftoptimizedengine Tier2optimizedengine NEA(ORDE)optimizedengine
Generator
LeroySomerlowvoltagegenerator MeetsNEMAMG1,BS5000, IEC60034-1,VDE0530, DINEN12601,AS1359 andISO8528requirements Superiorvoltagewaveform Solidstate,volts-per-Hertzregulator 4polethree-phasesynchronous generator Brushless,self-excited,self-regulating,self-ventilated Digitalvoltageregulator Anticondensationheater StatorwindingY-connected, accessibleneutral(broughtout)
ProtectionIP23 lessthan5%harmonicdistorsion 2/3 pitch stator windings Noloadtofullloadregulation ±0.25%voltageregulationnoloadto fullload InsulationclassH,utilizationacc.toH RadiosuppressionEN55011, group1,cl.B Shortcircuitcapability3xInfor10sec Sustainedshortcircuitcurrentofupto300%oftheratedcurrentforupto10seconds(LeroySomergenerator) WindingandbearingRTDs (withoutmonitoring)
ExcitationbyAREP+PMI MountingofCT´s:3x2coreCT´s Voltagesetpointadjustment±10V Sustainedshortcircuitcurrentofupto250%oftheratedcurrentforupto10seconds(Marathongenerator) Marathonlowvoltagegenerator Oversizedgenerator
Standardandoptionalfeatures
System ratings (kW/kVA)
Generator model Voltage with mechanical radiator**
kWel kVA* AMPS
LeroySomerLSA50.2M6 (Lowvoltage LeroySomerstandard)
380 V 800 1000 1519
400 V 800 1000 1443
415 V 800 1000 1391
LeroySomerLSA50.2L7 (Lowvoltage LeroySomeroversized)
380 V 800 1000 1519
400 V 800 1000 1443
415 V 800 1000 1391
Marathon740RSL7183 (Lowvoltage Marathonstandard)
380 V 800 1000 1519
400 V 800 1000 1443
415 V 800 1000 1391
Marathon742RSL7185 (Lowvoltage Marathonoversized)
380 V 800 1000 1519
400 V 800 1000 1443
415 V 800 1000 1391 *cosphi=0.8 **BE,fueloptimized:max.poweravailableupto:openpowerunit40°C/400m;TAL,EPATier2compl.,NEA:standardoperatingconditions/openpowerunit25°C/100m Electricaloutputsmayvarydependingongeneratorvoltageandambientconditions.ForpoweroutputsconsultyourMTUdealer. Intakeairdepression/mbar:15mbar Exhaustbackpressure/mbar:30mbar
Standard and optional features
Representsstandardfeatures
Representsoptionalfeatures
Cooling system
Jacketwaterpump Thermostat(s)
Airchargeaircooling Mechanicalradiator
Jacketwaterheater
Exhaust system
Exhaustbellowswithconnectionflange Exhaustsilencerwith10dB(A)soundattenuation
Exhaustsilencerwith30dB(A)soundattenuation Exhaustsilencerwith40dB(A)soundattenuation
Y-connection-pipe
Fuel system
Flexiblefuelconnectorsmountedto baseframe
Fuelfilterwithwaterseparator Switchablefuelfilterwithwaterseparator
Fuel cooler
Starting/charging system
24Vstarter Starterbatteries,cables,rack, disconnect switch
Batterycharger Redundantstarter2x7.5KW
Mounting system
Weldedbaseframe Resilientengineandgeneratormounting Modularbaseframedesign
Power Panel
Availablein600x600 Phasemonitoringrelay230V/400V
Supplyforbatterycharger Supplyforjacketwaterheater
Plugsocketcabinetfor230V compatibleEuro
Control Panel
Pre-wiredcontrolcabinetforeasy applicationofcustomizedcontroller(V1+) Islandoperation(V2) AutomaticmainsfailureoperationwithATS(V3a) Automaticmainsfailureoperation incl.controlofgeneratorandmainsbreaker(V3b) Islandparalleloperationofmultiplegensets(V4) Automaticmainsfailureoperationwithshort(<10s)mainsparallel overlapsynchronization(V5) Mainsparalleloperationofasinglegenset(V6)
Mainsparalleloperationofmultiplegensets(V7) Baslercontroller Deifcontroller Completesystemmetering Digitalmetering Engineparameters Generatorprotectionfunctions Engineprotection SAEJ1939engineECU communications Parametrizationsoftware Multilingualcapability Multipleprogrammablecontactinputs Multiplecontactoutputs
Eventrecording IP54frontpanelratingwith integratedgasket Differentexpansionmodules Remoteannunciator Daytankcontrol Generatorwindingtemperature monitoring Generatorbearingtemperature monitoring Differentialprotectionwith multi-functionprotectionrelay ModbusRTU-TCPgateway
Weights and dimensions
Sound data
— ConsultyourlocalMTUdistributorforsounddata.
Emissionsdata
— ConsultyourlocalMTUdistributorforemissionsdata.
Ratingdefinitionsandconditions
— Primepowerratingsapplytoinstallationswhereutilitypowerisunavailableorunreliable.Atvaryingload,thenumberofgeneratorsetoperatinghoursisunlimited.A10%overloadcapacityisavailableforonehourintwelve.RatingsareinaccordancewithISO8528-1,ISO3046-1,BS5514andAS2789. Averageloadfactor:≤75%.Operatinghours/year:unlimited
— ConsultyourlocalMTUdistributorforderatinginformation
Drawingaboveforillustrationpurposesonly,basedonastandardopenpower400Voltengine-generatorset.Lengthsmayvarywithothervoltages.Donotuseforinstallationdesign.Seewebsiteforunitspecifictemplatedrawings.
Subjecttochange.|3239551|Edition01/19|ESM2019-12.
Weightsanddimensionsarebasedonopenpowerunitsandareestimatesonly.Consultthefactoryforaccurateweightsanddimensionsforyourspecificengine-generatorset.
System Dimensions (L x W x H) Weight (dry/less tank)
Openpowerunit(OPU) 4440x1990x2200mm 6550kg
Rolls-Royce Groupwww.mtu-solutions.com/powergen