diesel generator set mtu 12v4000 ds1750 · vde 0530, din en 12601, as1359 and iso 8528 requirements...
TRANSCRIPT
-
Optionalequipmentandfinishingshown.Standardmayvary.Optionalequipmentandfinishingshown.Standardmayvary.
MTU 12V4000 DS1750DieselGeneratorSet
Producthighlights
380V–11kV/50Hz/gridstabilitypower/fuelconsumptionoptimized/12V4000G14F/waterchargeaircooling
Bene� ts— Lowfuelconsumption— Optimizedsystemintegrationability— Highreliability— Highavailabilityofpower— Longmaintenanceintervals
Support— Globalproductsupportoffered
Standards— Engine-generatorsetisdesignedandmanufacturedinfacilitiescertifiedtostandardsISO2008:9001andISO2004:14001
— GeneratorsetcompliestoISO8528— GeneratormeetsNEMAMG1,BS5000,ISO,DINENandIECstandards
— NFPA110
Power rating— Systemratings:1590kVA-1700kVA— AcceptsratedloadinonestepperNFPA110— GeneratorsetcompliestoG3accordingtoISO8528-5— GeneratorsetexceedsloadstepsaccordingtoISO8528-5
Performance assurance certi� cation (PAC)— Engine-generatorsettestedtoISO8528-5fortransientresponse— 100%loadfactor— Verifiedproductdesign,qualityandperformanceintegrity— Allenginesystemsareprototypeandfactorytested
Complete range of accessories available— Controlpanel— Powerpanel— Circuitbreaker/powerdistribution— Fuelsystem— Fuelconnectionswithshut-offvalvemountedtobaseframe— Starting/chargingsystem— Exhaustsystem— Mechanicalandelectricaldrivenradiators— Mediumandoversizedvoltagealternators
Emissions— Fuelconsumptionoptimized
Certi� cations— CEcertificationoption— Unitcertificateacc.toBDEW(GermanGrid-Code)
-
Application data 1)
1 AlldatarefersonlytotheengineandisbasedonISOstandardconditions(25°Cand100mabovesealevel).2 ValuesreferencedareinaccordancewithISO3046-1.Conversioncalculatedwithfueldensityof0.83g/ml.Allfuelconsumptionvaluesrefertoratedenginepower.
Standardandoptionalfeatures
System ratings (kW/kVA)
Generator model Voltage fuel consumption optimized
without radiator with mechanical radiator
kWel kVA* AMPS kWel kVA* AMPS
LeroySomerLSA52.3S5(LowvoltageLeroySomerstandard)
380V 1360 1700 2583 1320 1650 2507
400V 1360 1700 2454 1320 1650 2382
415V 1360 1700 2365 1320 1650 2295
Marathon743RSL7090(LowvoltageMarathon)
380V 1352 1690 2568 1312 1640 2492
400V 1344 1680 2425 1312 1640 2367
415V 1272 1590 2212 1272 1590 2212
Marathon744RSL7091(LowvoltageMarathonoversized)
380V 1352 1690 2568 1312 1640 2492
400V 1344 1680 2425 1312 1640 2367
415V 1272 1590 2212 1272 1590 2212
Marathon1020FDH7095(Mediumvolt.marathon)
11kV 1352 1690 89 1312 1640 86
LeroySomerLSA53.2VL6(Mediumvolt.LeroySomer)
11kV 1352 1690 89 1320 1650 87
*cosphi=0.8
EngineManufacturer MTUModel 12V4000G14FType 4-cycleArrangement 12VDisplacement:l 57.2Bore:mm 170Stroke:mm 210Compressionratio 16.4Ratedspeed:rpm 1500Enginegovernor ECU9Maxpower:kWm 1420Aircleaner dry
Fuel systemMaximumfuellift:m 5Totalfuelflow:l/min 16
Fuel consumption 2) l/hr g/kwhAt100%ofpowerrating: 323.3 189At75%ofpowerrating: 250.2 195At50%ofpowerrating: 173.7 203
Liquid capacity (lubrication)Totaloilsystemcapacity:l 260Enginejacketwatercapacity:l 160Intercoolercoolantcapacity:l 40
Combustion air requirementsCombustionairvolume:m3/s 1.6Max.airintakerestriction:mbar 50
Cooling/radiator systemCoolantflowrate(HTcircuit):m3/hr 56Coolantflowrate(LTcircuit):m3/hr 30Heatrejectiontocoolant:kW 540Heatradiatedtochargeaircooling:kW 200Heatradiatedtoambient:kW 75Fanpowerforelectr.radiator(40°C):kW 38
Exhaust systemExhaustgastemp.(afterturbocharger):°C 430Exhaustgasvolume:m3/s 4.0Maximumallowablebackpressure:mbar 85Minimumallowablebackpressure:mbar 30
-
Standard and optional features
Representsstandardfeatures
Representsoptionalfeatures
Engine
4-cycle Standardsinglestageairfilter Oildrainextension&shut-offvalve
Closedcrankcaseventilationwithimprovedoilseperator Governor-electronicisochronous
Commonrailfuelinjection Fuelconsumptionoptimizedengine Centrifugaloilfilter
Generator
4polethree-phasesynchronousgenerator Brushless,self-excited,self-regulating,self-ventilated Digitalvoltageregulator Anticondensationheater StatorwindingY-connected,accessibleneutral(broughtout) ProtectionIP23
InsulationclassH,utilizationacc.toH RadiosuppressionEN55011,group1,cl.B Shortcircuitcapability3xInfor10sec WindingandbearingRTDs(withoutmonitoring) ExcitationbyAREP MountingofCT´s:2coreCT´s Windingpitch:2/3winding Voltagesetpointadjustment±10%
MeetsNEMAMG-1,BS5000,IEC60034-1,VDE0530,DINEN12601,AS1359andISO8528requirements LeroySomerlowvoltagegenerator Marathonlowvoltagegenerator Oversizedgenerator Mediumvoltagegenerator
Cooling system
Jacketwaterpump Thermostat(s) Waterchargeaircooling
Mechanicalradiator Electricaldrivenfront-endcooler Jacketwaterheater
Control panel
Pre-wiredcontrolcabinetforeasyapplicationofcustomizedcontroller(V1+) Islandoperation(V2) AutomaticmainsfailureoperationwithATS(V3a) Automaticmainsfailureoperationincl.controlofgeneratorandmainsbreaker(V3b) Islandparalleloperationofmultiplegensets(V4) Automaticmainsfailureoperationwithshort(<10s)mainsparalleloverlapsynchronization(V5) Mainsparalleloperationofasinglegenset(V6)
Mainsparalleloperationofmultiplegensets(V7) Baslercontroller Deifcontroller Completesystemmetering Digitalmetering Engineparameters Generatorprotectionfunctions Engineprotection SAEJ1939engineECUcommunications Parametrizationsoftware Multilingualcapability Multipleprogrammablecontactinputs Multiplecontactoutputs Eventrecording
IP54frontpanelratingwithintegratedgasket Differentexpansionmodules Remoteannunciator Daytankcontrol Generatorwindingtemperaturemonitoring Generatorbearingtemperaturemonitoring ModbusTCP-IP
Power panel
Availablein600x600and600x1000 Phasemonitoringrelay230V/400V Supplyforbatterycharger Supplyforjacketwaterheater
Supplyforanticondensationheating Plugsocketcabinetfor230VcompatibleEuro/USA
Supplyforelectricaldrivenradiatorfrom45kW–75kW(PP600x1000)
-
Standard and optional features
Circuit breaker/power distribution
3-polecircuitbreaker 4-polecircuitbreaker
Manual-actuatedcircuitbreaker Electrical-actuatedcircuitbreaker
Stand-alonesolutioninseperatecabinet
Fuel system
Flexiblefuelconnectorsmountedtobaseframe Fuelfilterwithwaterseparator Fuelfilterwithwaterseparatorheavy-duty
Switchablefuelfilterwithwaterseparator Switchablefuelfilterwithwaterseparatorheavy-duty Seperatefuelcooler
Fuelcoolerintegratedintocoolingequipment
Starting/charging system
24Vstarter Starterbatteries,cables,rack,disconnectswitch
Batterycharger
Mounting system
Weldedbaseframe Resilientengineandgeneratormounting Modularbaseframedesign
Representsstandardfeatures
Representsoptionalfeatures
Exhaust system
Exhaustbellowswithconnectionflange Exhaustsilencerwith10dB(A)soundattenuation
Exhaustsilencerwith30dB(A)soundattenuation
Exhaustsilencerwith40dB(A)soundattenuation Y-connection-pipe
-
Rolls-Royce Groupwww.mtu-solutions.com/powergen
Weights and dimensions
Sound data
— Consult your local MTU distributor for sound data.
Emissions data
— Consult your local MTU distributor for emissions data.
Rating definitions and conditions
— Grid Stability Power ratings apply to installations serving electric utility programs. At constant or varying load, the number of generator set operating hours is limited to 1000 hours per year with no more than 500 hours per year at 100% load without interruption. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO 8528-1, ISO 3046-1, BS 5514 and AS 2789. Average load factor: ≤ 100%.
— Consult your local MTU distributor for derating information.
Drawing above for illustration purposes only, based on a standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design. See website for unit specific template drawings.
Sub
ject
to
chan
ge.
| 32
3847
1 | E
diti
on 0
1/20
| ES
M 2
020
-03.
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific engine-generator set.
System Dimensions (L x W x H) Weight (dry/less tank)
Open power unit (OPU) 4059 x 1810 x 2330 mm 10654 kg