detail waterproofing

11
1 lat Roof with Vent Pipe Sonol.Ultra Polyurethane joint sealant Pipe abraided and primed with Conc.2525 Primer Conipur Tc 458 RC Roof Slab Conc.2525 Existing Cement::Sand screed laid to fall Fall

Upload: ratnapudji6933

Post on 27-Oct-2015

141 views

Category:

Documents


8 download

TRANSCRIPT

Page 1: Detail Waterproofing

1

Flat Roof with Vent Pipe

Sonol.Ultra Polyurethane joint sealant

Pipe abraided and primedwith Conc.2525 Primer

Conipur Tc 458

RC Roof Slab

Conc.2525

Existing Cement::Sand screedlaid to fall

Fall

Page 2: Detail Waterproofing

2

Gutter/Parapet wall detail on Flat Roof

3mmx3mm regletfor membrane terminationfilled with S.Ultrasealant

Conipur M865Zdetailing to downpipe

Mortar fillet made fromConc.2525+filler

Conideck system

Existing Cement:Sand screed to fall

Conipur terminate300mm high upturntucked into reglet

Page 3: Detail Waterproofing

3

150

Discharge Pipe

Construction grout-shrinkagecompensated grout to fill recess

R.C. Slab

1:3 cement/sand screedlaid to fall

Sonoshield HLM 6000

20mm thick cement.sandprotective screed

Air-con discharge pipe

Levelling screed byothers

Tile finishes by others

FALL FALLFloor trap cover

Discharge Pipe Detail at Podium/Balcony/Terrace

Page 4: Detail Waterproofing

4

500CAR PARK BELOW

Angle fillet constructed fromnon-shrink mortar

Masterflex 610

Sonoshield HLM 6000

1:3 cement/sand protective screed

Sonoshield HLM 6000

Finemesh extended to 500mm onhorizontal surface

Sonoshield HLM 6000 on 1:3 cement/sandscreed laid to fall

Non-slip ceramic tiles and adhesivesby others

Finemesh reinforcement fixed spindleat 450mm contres glued to concretewith Concresive 1438

Non slip ceramic tiles andadhesives by others

WATER LEVEL POOL DECK LEVEL

Swimming Pool Detail

Page 5: Detail Waterproofing

5

Downpipe

Sonoshield HLM 6000Detailing around pipe

R.C. Roof Slab

Mortar Fillet

Masterpren 2003

10mm x 10mm regletfor membrane terminationfilled with SonolasticNP1 sealant

Protective screedreinforced with finemesh

FALL

25mm minimum thick castin-situ 1:3 cement/sand screed laid to fall

Masterpren 2003

50mm thick extrudedinsulation board

Separation layer

Drainage cell

50mm thick in-situ1:3 cement/sand screedreinforced with finemesh,panels of 750mm x 750mmwith 10mm wide jointfilled with Sonolastic PS2Polysulphide sealant

Gutter Detail at Roof

Page 6: Detail Waterproofing

6

DETAIL FOR PIPE PENETRATION CREATED THROUGH EXISTING FLOOR

Masterflex 610 + 611 swellable paste wrapped in helical profile

Bathroom Floor Slab

Masterflow 98

Barralastic

HLM6000

Page 7: Detail Waterproofing

7

Plan View of Penthouse Unit at Pantip Shores

Penthouse Unit

Bathroom area

Bathroom area

Page 8: Detail Waterproofing

8

Wall tiles by others

Floor tiles by others

Tile beddingby others

10mm x 10mm mortar fillet

For shower area, upturn of 1.8m.For non-showerarea 0.15m to prevent backsplashing ofwater

Bathroom Area with brick infill wallFor brick wall the brick surface must beplastered to receive Barralastic

SlabSlab

Barralastic(2 applications)on 3:1 sand:cement screedlaid to fall (optional )

Page 9: Detail Waterproofing

9

Wall tiles

Floor tiles

Tile bedding

10mm x 10mm mortar fillet

Bathroom Area with Stud & Frame

For brick wall the brick surface must beplastered to receive Barralastic

SlabSlab

Barralastic(2 applications)Reinforced with SonoshieldReinforcement at upturn

Drywall infill fixed to Stud & FrameTo be primed with Acryl 60 to receive Barralastic

Page 10: Detail Waterproofing

10

Barralastic50mm into downpipe

Barralastic2 coats

TilesFinishes installedUsing Nano-Light

Down Pipe Detail Floor trap cover

Masterflow 98 non shrinkgrout to fill box-outopening

Fall

Discharge pipe

Air-conwater dischargepipe

Page 11: Detail Waterproofing

11

Fall

Wet Area Vent Pipe Detail

Floor tiles

Tile bedding

Barralastic(2 coats)

Masterflow 98to fill box-out opening in the floor

pipe abraded to provide a mechanical key

Mortar Fillet

R.C Floor slab

NP-1joint sealant

Barralastic100mm

3:1 sand:cementscreed laid to fall(optional)

2 mm of protection layer